Aggregated Rooftop PV Sizing in Distribution Feeder Considering Harmonic Distortion Limit
|
|
- Lorin Hampton
- 6 years ago
- Views:
Transcription
1 Aggregated Rooftop PV Sizing in Distribution Feeder Considering Harmonic Distortion Limit Mrutyunjay Mohanty Power Research & Development Consultant Pvt. Ltd., Bangalore, India Student member, IEEE Shekhar Kelapure Power Research & Development Consultant Pvt. Ltd., Bangalore, India Senior member, IEEE Abstract With the global green initiatives, agencies dealing with the renewable energy are coming with lucrative schemes to promote consumers for opting solar photovoltaic (PV) source as an alternative source of energy. The aggregated impact of the growing number of dispersed rooftop PV source may originate many power system related problems, power quality problem being one of them. This paper presents the methodology to determine the maximum PV solar capacity that can be allocated in a distribution feeder keeping harmonic distortion within acceptable limit as per IEEE-519 standard. The proposed approach also gives additional aggregated PV solar size at any location for future PV penetration, provided the harmonic injection does not raise voltage distortion above specified limit. A case study is carried out on a distribution feeder consisting 5 distribution transformers (s) to validate the approach and results are published. Power system simulation tool MiPower TM is used for network modeling and for verifying the result. Keywords Dispersed PV solar source; PV penetration; aggregated PV source; PV sizing; harmonic analysis; voltage distortion. I. INTRODUCTION As power distribution companies are providing subsidies for rooftop solar panels, a large number of consumers are now opting for PV sources as a secondary source of energy. Though this is considered as clean energy source, many research areas are continuously evolving to identify and improve the impact on flexibility, reliability and power quality issues due to large penetration of these PV sources which use power electronics based DC-AC converters[1-2]. There are some constraints, which limits the net PV penetration capacity, such as, overvoltage in system, equipment overloading, harmonic distortion, etc. The practical problem area for sizing aggregated PV source in a distribution feeder with respect to harmonic distortion is discussed in detail in section II. The methodology is also explained as a strategic solution for the same. II. PROBLEM DESCRIPTION Multiple guidelines are followed by the power distribution companies for approving rooftop PV capacity based upon consumer category. Normally the consumers are allowed to install rooftop PV source in first come first serve basis, after feasibility study is done related to available transformer capacity, harmonic distortions, etc. For deciding maximum PV penetration without violating harmonic distortion limit violation, an approach has been analyzed [3], which is limited to few typical distribution patterns, such as, in case PV sources are allocated across feeder in equal distribution / uniformly increasing / uniformly decreasing manner. In [4] location based PV optimization using particle swarm optimization (PSO) technique gives the ideal size of PV without violating harmonic distortion limits. But in case of distribution system, location based optimization can t be used, as the location of the rooftop solar is fixed at consumer premise. Though with the guidelines for rooftop PV approval process, over voltage and transformer overloading issue can be avoided. But in case of heavily loaded and long feeder, harmonic distortion crosses the limit specified by IEEE-519 [5], because of aggregated harmonic injection from PV sources. Available power system simulation software can help in finding harmonic distortion level in a distribution feeder with specific PV injection points. But it would be a cumbersome process form network planning perspective, to determine the maximum aggregated rooftop solar capacity in a feeder with different PV penetration level for transformers. the feasible capacity of aggregated rooftop PV sources to be connected at specific location (under any ) for future PV penetration. Considering these above requirements, a methodology is explained in section III, to find out maximum capacity of aggregated PV sources can be allocated in a feeder or in other words, to find out penetration factor for each in any feeder without exceeding harmonic distortion limit. Thus a chart can be made available for network planners on total numbers of s with a range of penetration factors. penetration factor = Aggregate installed PV capacity under the rated capacity Also another practical challenge comes related to determining the available PV source capacity for future penetration, under any with respect to harmonic distortion limit. In such scenario, though network is having enough capacity to carter additional PV plant, but same can bring
2 harmonic distortion issues. Instead of repetitively checking the feasibility with different PV capacity, an approach is explored in section IV to compute feasible PV capacity directly. III. MATHEMATICAL FORMULATION FOR MAXIMUM PV PENETRAION A feeder can get PV penetration near to the substation or at tail end or at middle of the feeder or combination of all. Allowable PV source capacity diverges [6] based upon it s distance from substation along the feeder. Generally all distribution feeders are operated radially, hence current harmonics, injected from converters get accumulated in feeder and flows towards substation, unless feeder is equipped with mid-span filter banks. So using the mathematical logics of radial load flow solution, total maximum allowable harmonic current can be computed keeping the voltage distortion below limit. Then based upon the harmonic current magnitude, a meaningful estimation can be concluded for deciding aggregated wise PV penetration capacity. Of course due the phase cancellation, there would be reduction in net harmonic current[7-8], this deviation is not much to be worried about, at the planning level. A typical distribution system shown in fig.1 consisting number s connected to grid through a feeder is used for deriving nodal equations to calculate voltage distortion. Aggregated distribution loads as well as PV sources are connected at secondary side. Grid n Lumped Load Solar Panel Fig. 1. A typical distribution system with aggregated load and PV sources A. Penetration from tail end in feeder When PV penetration starts from feeder tail end, current harmonics accumulated at primary side sees maximum impedance. So when PV sources are installed from feeder tail end towards substation, voltage harmonic distortion at tail end gets the maximum impact and increases gradually. So PV sources can be added, till voltage distortion at tail end of main trunk line remains below acceptable limit. And to check the feasibility related to harmonic distortion, no need to compute distortion at other buses, as distortion at those areas will be always less than farthest bus from substation. The derivation for harmonic voltage at the farthest bus from grid using driving point impedance is explained here in a 3 bus radial system network, taken from the fig. 1. If harmonic current injections are considered from Bus 1, 2 and 3 are, and respectively, harmonic voltage at Bus 3 is as in (1): = _ + _ Where, = Grid impedance for h order, _ and _ are the branch impedance between Bus 1-2 and Bus 2-3 for h order. If bus wise h order driving point impedance at Bus 1, 2 and 3 are considered to be Z _, Z _ and Z _ respectively, ignoring load impedance, the difference between driving point impedance of two consecutive bus will be the line impedance, so, Z _ = (Z _ Z ), Z _ = (Z _ Z _ ) and Z _ = Z _. Because, if load impedance is ignored (generally taken as parallel combination of resistance and harmonic order times fundamental reactance), the driving point impedance at each bus sees the impedance in direction towards the substation[9-10]. This consists of branch line impedance and substation impedance. = (2) = ( )+ ( )+( )( ) (3) In (3) harmonic voltage is represented in terms of harmonic injections (, and ) and driving point impedance (, and ). Similarly voltage distortion at bus is computed using multiplication two matrices, these are: [1 ] matrix, filled with bus wise driving point impedance [ 1] matrix, filled with bus wise current injections at those buses. As PV penetration is initiated from tail end, impedance matrix gets filled from [1, ] to [1,1], whereas current injection matrix gets filled from [, 1] to [1,1] in arrow mark direction shown in (4). In case of no harmonic injection, corresponding fields gets filled with zeros. Harmonic voltage at tail end (at bus) is computed using below matrix: = _... (4) _, _, are the driving point impedance calculated at each buses and, _, are the harmonic currents injected at each bus. Harmonic voltage at bus is as in (5): = ( )+ + + ( ) (1) (5)
3 B. Penetration from substation end in feeder Unlike last matrix filling as explained in last sub-section A, as PV penetration is initiated from substation end, current matrix gets filled from [1,1] to [1, ] and impedance matrix gets filled from [1,1] to [, 1] in arrow mark direction shown in (6). = (6) Equation for computing harmonic voltage at bus remains same as in (5). C. Procedure to compute maximum feasible PV solar capacity To compute the total overall Solar capacity, step-by-step procedures are described as follows. Step 1) Model distribution network including elements, such as, feeder branches, s, aggregated lumped load (summated value of all consumer load) using any power system simulation tool. Step 2) Initialize IEEE specified voltage distortion limits and allowable PV penetration limit for s. Step 3) Compute driving point impedance at each bus for the interested harmonic order ignoring the load impedance. Step 4) Decide the PV penetration direction, such as: starting from feeder towards tail end of feeder or in a reverse manner. Step 5) Accordingly formulate the matrix as shown in (4) or (6) based upon penetration directions. Step 6) Based on the desired penetration factor, allocate the PV capacity. Assuming harmonic characteristics of all inverters are same irrespective of their size, a fixed percentage can be considered on a total PV capacity connected under. Step 7) Execute equations formulated in step-5. Find the individual and total voltage distortion at farthest bus from substation. Step 8) If computed voltage distortion is above IEEE specified limit, stop and total PV capacity in that feeder with the considered penetration factor is concluded as: penetration factor capacity Where n is the last included without violating distortion. Go to step 10. Step 9) If voltage distortion is below specified limit, go to step-7 to update matrices in (4) or (6) by including adding next for voltage distortion calculation. Step 10) Perform detailed analysis from various aspects with finalized PV capacity. All the steps explained above are shown in the flow chart in fig.2. Continue addition of next in selected PV installation direction Fig. 2. Flow chart for computing maximum PV penetration This approach is applied on a test system and result is published in sub-section A and B of section V. IV. Inputs: Network model( including lines, s and lumped load) Interested harmonic orders (h= i,, j) Fix PV penetration level for s Fix voltage distortion limits Compute driving point impedance at each bus Select PV penetration direction, from substation end / from feeder tail end Calculate harmonic voltage at farthest location where PV is installed using (4) or (6) No Does the computed individual and total voltage distortion is above IEEE specified limit? Stop further addition and compute total feasible PV solar penetration capacity as the summation of PVs till distortion limit is not crossed. Perform detail analysis from various aspects. END MATHEMATICAL FORMATION FOR ADDITIONAL PV SOURCE FOR FUTURE PENETRATION This section explains about the methodology for determining additional PV capacity at any bus without violating voltage distortion limit. Assume in the existing network (shown in fig.3) with PV penetration, harmonic voltage at Bus 1, 2, 3, 4, and 5 are,,, and due to current harmonic injections,,, and respectively.,,, and are driving point impedance respectively. Yes
4 Grid Bus 1 Bus 2 Bus 3 Bus 4 Bus 5 Fig. 3. A typical distribution system with proposed PV connection at Bus3 Maximum additional PV at 3 has to be designed ensuring does not exceeds harmonic voltage limit. Voltage harmonic at 5: = + + (7) + As harmonic injection remains same at 4 and 5, (7) can be written as follows: = + (8) Where constant = ( + )( - ) + ( - ). So if changes to _, with additional PV source, new harmonic voltage at 5 changes as (9): _ = _ + (9) With an additional harmonic current injection at 3, new harmonic voltage at Bus _ are derived as follows: New harmonic voltage _ at 1: _ = + (10) New harmonic voltage _ at 2: _ = _ ( (11) ) _ = (12) ( ) _ = ( (13) )+ + ( ) _ = + (14) As previous harmonic voltage at 2, = + ( )( ) New harmonic voltage _ at 3: _ = _ ( ) (15) => _ = (16) ( ) => _ = ( )+ (17) + ( ) => _ = + (18) Here previous harmonic voltage at 5, = ( ) Solving two equations (9) and (18) gives the _ in terms of as shown in (20) => _ =( + )+ (19) => _ = + (20) Where =( + ) Similar equation as in (20) can be formed for desired harmonic frequencies. While deciding the maximum allowed harmonic current injections, a boundary condition can be created, such that, the individual as well as total voltage harmonic distortion fall below IEEE specified limit. A case study analysis is presented in section V to validate this approach (see sub section C). V. CASE STUDY The proposed methodology is tested on a 11kV distribution feeder consisting of five 11/0.415 kv distribution transformers shown in fig. 4. Total distribution load connected under each 500kVA capacity is 350kW at 0.95 power factor. Constant PQ type loads are considered for the analysis with harmonic injections from PV sources. However, load side harmonic current injections also can be included, which would further decrease the PV capacity in order to keep the harmonic distortion below allowable limit. Weasel type conductor is considered for the analysis with 1.5 kms distance between buses, and total feeder length to be 7.5 kms. Feeder library data is provided in Table I. TABLE I. PV PV PV PV PV Fig. 4. Distribution system for case study 11KV FEEDER IMPEDANCE DATA Positive seq. R Positive seq. X Zero seq. R Zero seq. X ohm/km/phase ohm/km/phase ohm/km/phase ohm/km/phase Driving point impedance computed through MiPower TM software tabulated in Table II. Bus 33/11kV Bus 1 Bus 2 Bus 3 Bus 4 Bus 5 Bus 6 11/0.415 %X= p.u. TABLE II. HARMONIC DRIVING POINT IMPEDANCE 5 th Order 7 th Order 11 th Order Z in Angle Z in Angle Z in Angle ohm in deg. ohm in deg. ohm in deg. Bus Bus Bus Bus Bus Bus The current harmonic injections from PV solar inverters are assumed to be 30%, 12% and 10% for 5, 7 and 11 harmonic order respectively. Total allowable PV capacity is determined in sub-sections A and B. The 5 harmonic current injected form 200kW PV source kv side is calculated as follows: 0.30 ( (200/( )) (21)
5 And current transformation ratio (0.415/11) is multiplied to get the reflected current at primary side. Similiary 7 and 11 current harmonics injections to be calculated. A. Penetration from substation end in feeder Using the flow chart in section II, both individual and total voltage harmonic distiortion are calculated as shown in Tables III to V. Shaded portion in coloumn defines the feasible number of s, those can take the allocated PV capacity keeping THD below speified limit. For example, in Table III, 200 kw of aggreagted PV source can be installed under all 5 no.s s. Whereas, as per Table IV, 225 kw capacity off aggreagted PV source can be installed under only 3 no.s s. TABLE III. HARMONIC VOLTAGE DISTORTION AT BUS 6 WITH 200 KW PV CAPACITY PER TABLE IV. HARMONIC VOLTAGE DISTORTION AT BUS 6 WITH 225 KW PV CAPACITY PER TABLE V. HARMONIC VOLTAGE DISTORTION AT BUS 6 WITH 250 KW PV CAPACITY PER B. Penetration from substation end in feeder Tables VI to VII depict voltage distortion results in case of forward PV allocation starting from substation end. TABLE VI. HARMONIC VOLTAGE DISTORTION AT BUS 6 WITH 200 KW PV CAPACITY PER TABLE VII. HARMONIC VOLTAGE DISTORTION AT BUS 6 WITH 225 KW PV CAPACITY PER TABLE VIII. HARMONIC VOLTAGE DISTORTION AT BUS 6 WITH 250 KW PV CAPACITY PER From the test results as shown in Tables III to VIII, maximum aggregated PV capacity with different penetration factor is as shown in Table IX, as a comparison between backward and forward PV penetration. TABLE IX. BACKWARD VS FORWARD PV PENETRATION Aggregated PV Backward PV penetration Forward PV penetration capacity / Total feasible capacity In kw Total feasible capacity In kw 200 kw 200*5= 1000 kw 200*5= 1000 kw 225 kw 225*3 = 675 kw 225*4 = 900 kw 250 kw 250*3= 750 kw 250*4 = 1000 kw It can be observed, when PV penetration starts from tail end, total feasible PV capacity increases as compare to forward penetration. Because of harmonic currents from PV inverters sees more impedance as compared to those installed near to substation. C. Available PV source capacity at any specific location This test case is meant to determine additional PV capacity at specific location, using the methodology explained in Section IV. Distribution network shown in fig. 4 is taken as a sample network. Aggregated roof top solar PV source under each is considered as 200kW. Current harmonic distortions from PV solar inverters are taken as, 27%, 12% and 10% for 5, 7 and 11 harmonic order respectively. In order to find the maximum available aggregated PV capacity at 4, using (20) and driving point impedance from Table II, following equations are formed: = (11.60) + ( ), for 5 (22) = (15.58) + ( ), for 7 (23) = (23.814) + ( ), for 11 (24) These describe the individual voltage harmonic variation at feeder tail end (at 6 ), with respect to harmonic current.
6 Boundary conditions are formed considering individual as well as total harmonic distortion limits as in (25-26): 100 3%, h (25) + _ % (26) Both THD and individual distortion for 6 are plotted against harmonic current shown in fig.5. Voltage harmonic distortion Fig. 5. Voltage harmonic distortion for Bus 6 against harmonic current It is observed from voltage distortion plot, at 0.6A current, 5 order voltage distortion is reaching 2.998%. And at 0.62A it exceeds IEEE specified limit to 3.001% (marked in red color diamond shape). Whereas, other individual and total voltage distortions are still below IEEE specified limits 3% and 5% respectively. So maximum fundamental current is selected considering 5 harmonic current distortion level(27%), because 7 and 11 order current distortions are, 12% and 10% respectively, which are lower than 5 harmonic distortions. So the reflected fundamental current at secondary (0.415kV) side is as below: (0.62 (11/0.415))/ 0.27 = 60.86A (27) And the additional feasible PV capacity would be: 3 (0.415) = 3 (0.415) = (28) Harmonic analysis is performed on this network with existing PV sources and including additional PV source using MiPower TM and results are published in Table X. TABLE X. th th th HARMONIC VOLTAGE AFTER INSTALLING ADDITIONAL PV With exciting PV sources Current harmonic in Ampere With additional PV source at Bus 4 Bus VTHD VTHD Bus Bus From Table X, it is observed that, with the additional feasible PV source at 4 (computed as kw), 5 harmonic voltage at 6 is increased from 2.88% to 2.99%, which is below IEEE specified limit (3%) and voltage THD is also below IEEE specified limit (5%). So the additional PV solar capacity calculated through proposed methodology does not violate harmonic distortion limit. So without computing the feasible capacity in a repetitive manner, this methodology is able to determine the maximum future PV solar penetration at specific location. VI. CONCLUSION The proposed methodology computes maximum PV penetration capacity in a feeder with different transformer penetration level. Also in addition finds additional PV capacity at a specific location for future rooftop PV penetration without exceeding the IEEE voltage specified limit. The results demonstrate the strength of the approach and are verified using MiPower TM simulation software. The proposed methodology can be used for distribution system planning level as a preliminary approach to study the impact of rooftop solar source penetration in distribution feeder with respect to harmonic distortion. And accordingly necessary prevention measures can be taken to avoid high harmonic distortion improving the power quality. REFERENCES [1] J. H. R. Enslin and P. J. M. Heskes, "Harmonic interaction between a large number of distributed power inverters and the distribution network," in IEEE Transactions on Power Electronics, vol. 19, no. 6, pp , Nov [2] P. P. Barker and R. W. De Mello, "Determining the impact of distributed generation on power systems. I. Radial distribution systems," Power Engineering Society Summer Meeting, IEEE, Seattle, WA, 2000, pp vol. 3. [3] A. Bhowmik, A. Maitra, S. M. Halpin and J. E. Schatz, "Determination of allowable penetration levels of distributed generation resources based on harmonic limit considerations," in IEEE Transactions on Power Delivery, vol. 18, no. 2, pp , April 2003 [4] IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE Std , [5] V. R. Pandi, H. H. Zeineldin and W. Xiao, "Determining Optimal Location and Size of Distributed Generation Resources Considering Harmonic and Protection Coordination Limits," in IEEE Transactions on Power Systems, vol. 28, no. 2, pp , May 2013 [6] H. Anderson, B. Rebecca, H. Joshua and K.Benjamin, "Maximum Photovoltaic Penetration Levels on Typical Distribution Feeders", Journal Article, NREL/JA , July 2012 [7] Y. J. Wang, R. M. O'Connell and G. Brownfield, "Modeling and prediction of distribution system voltage distortion caused by nonlinear residential loads," in IEEE Transactions on Power Delivery, vol. 16, no. 4, pp , Oct [8] H. E. Mazin, W. Xu and B. Huang, "Determining the Harmonic Impacts of Multiple Harmonic-Producing Loads," in IEEE Transactions on Power Delivery, vol. 26, no. 2, pp , April [9] MiPower TM User Manual, [10] G. J. Wakileh, Power Systems Harmonics, First Ediition, Springer, J. Arillaga, N.R. Watson, Power System Harmonics, Second Edition, John Willy & Sons Ltd, 2003.
Maximum Allowable PV Penetration by Feeder Reconfiguration Considering Harmonic Distortion Limits
Maximum Allowable PV Penetration by Feeder Reconfiguration Considering Harmonic Distortion Limits Vemula Mahesh Veera Venkata Prasad #1, R. Madhusudhana Rao *, Mrutyunjay Mohanty #3 #1 M.Tech student,
More informationHarmonic impact of photovoltaic inverter systems on low and medium voltage distribution systems
University of Wollongong Research Online University of Wollongong Thesis Collection 1954-2016 University of Wollongong Thesis Collections 2006 Harmonic impact of photovoltaic inverter systems on low and
More informationDetermination of Smart Inverter Power Factor Control Settings for Distributed Energy Resources
21, rue d Artois, F-758 PARIS CIGRE US National Committee http : //www.cigre.org 216 Grid of the Future Symposium Determination of Smart Inverter Power Factor Control Settings for Distributed Energy Resources
More informationHarmonic Planning Levels for Australian Distribution Systems
Abstract Harmonic Planning Levels for Australian Distribution Systems V.J. Gosbell 1, V.W. Smith 1, D. Robinson 1 and W. Miller 2 1 Integral Energy Power Quality Centre, University of Wollongong 2 Standards
More informationHarmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits
WREF 01 Paper # 048 Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits Ketut Dartawan Ricardo Austria, Le Hui and Mark Suehiro* Pterra Consulting Maui Electric Company*
More informationOptimal placement of distribution transformers in radial distribution system
International Journal of Smart Grid and Clean Energy Optimal placement of distribution transformers in radial distribution system Vishwanath Hegde *, Raghavendra C. G., Prashanth Nayak Pradeep S., Themchan
More informationOptimal PMU Placement in Power System Considering the Measurement Redundancy
Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 4, Number 6 (2014), pp. 593-598 Research India Publications http://www.ripublication.com/aeee.htm Optimal PMU Placement in Power System
More informationOptimal Sizing and Placement of DG in a Radial Distribution Network using Sensitivity based Methods
Optimal Sizing and Placement of DG in a Radial Distribution Network using Sensitivity based Methods Nitin Singh 1, Smarajit Ghosh 2, Krishna Murari 3 EIED, Thapar university, Patiala-147004, India Email-
More informationPower Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2
IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 03, 2015 ISSN (online): 2321-0613 Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive
More informationSensitivity Analysis for 14 Bus Systems in a Distribution Network With Distributed Generators
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 3 Ver. I (May Jun. 2015), PP 21-27 www.iosrjournals.org Sensitivity Analysis for
More informationMinimization of Power Loss and Improvement of Voltage Profile in a Distribution System Using Harmony Search Algorithm
Minimization of Power Loss and Improvement of Voltage Profile in a Distribution System Using Harmony Search Algorithm M. Madhavi 1, Sh. A. S. R Sekhar 2 1 PG Scholar, Department of Electrical and Electronics
More informationHybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation
Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation Maher G. M. Abdolrasol maher_photo@yahoo.com Dept. of Electrical Engineering University of Malaya Lembah Pantai, 50603
More informationVoltage Level Management of Low Voltage Radial Distribution Networks with High Penetration of Rooftop PV Systems
Voltage Level Management of Low Voltage Radial Distribution Networks with High Penetration of Rooftop PV Systems Piyadanai Pachanapan and Surachet Kanprachar Abstract The increasing of rooftop photovoltaic
More informationMAINS SIGNAL PROPAGATION THROUGH DISTRIBUTION SYSTEMS. J. Stones*, S. Perera*, V. Gosbell* and N. Browne**
ABSTRACT MAINS SIGNAL PROPAGATION THROUGH DISTRIBUTION SYSTEMS J. Stones*, S. Perera*, V. Gosbell* and N. Browne** *School of Electrical, Computer and Telecommunications Engineering University of Wollongong
More informationAS the power distribution networks become more and more
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 21, NO. 1, FEBRUARY 2006 153 A Unified Three-Phase Transformer Model for Distribution Load Flow Calculations Peng Xiao, Student Member, IEEE, David C. Yu, Member,
More informationSELECTING THE BEST POINT OF CONNECTION FOR SHUNT ACTIVE FILTERS IN MULTI-BUS POWER DISTRIBUTION SYSTEMS
SELECTING TE BEST POINT OF CONNECTION FOR SUNT ACTIVE FILTERS IN MULTI-BUS POWER DISTRIBUTION SYSTEMS Luis Morán T. () José Mahomar J. () Juan Dixon R. (2) () Dept. of Electrical Engineering (2) Dept.
More informationTransient Stability Improvement Of Power System With Phase Shifting Transformer
INTERNATIONAL JOURNAL OF TECHNOLOGY ENHANCEMENTS AND EMERGING ENGINEERING RESEARCH, VOL 3, ISSUE 3 19 Transient Stability Improvement Of Power System With Phase Shifting Transformer Jyothi Varanasi, Aditya
More informationOptimal Positioning and Sizing of DG Units Using Differential Evolution Algorithm
Optimal Positioning and Sizing of DG Units Using Differential Evolution Algorithm Ravi 1, Himanshu Sangwan 2 Assistant Professor, Department of Electrical Engineering, D C R University of Science & Technology,
More informationINCREASING NETWORK CAPACITY BY OPTIMISING VOLTAGE REGULATION ON MEDIUM AND LOW VOLTAGE FEEDERS
INCREASING NETWORK CAPACITY BY OPTIMISING VOLTAGE REGULATION ON MEDIUM AND LOW VOLTAGE FEEDERS Carter-Brown Clinton Eskom Distribution - South Africa cartercg@eskom.co.za Gaunt CT University of Cape Town
More informationImpact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods
Proceedings of the th WSEAS International Conference on Power Systems, Beijing, China, September -, 200 Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing
More informationDiscussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation
Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation TSAI-HSIANG CHEN a NIEN-CHE YANG b Department of Electrical Engineering National Taiwan University
More informationOptimal Voltage Regulators Placement in Radial Distribution System Using Fuzzy Logic
Optimal Voltage Regulators Placement in Radial Distribution System Using Fuzzy Logic K.Sandhya 1, Dr.A.Jaya Laxmi 2, Dr.M.P.Soni 3 1 Research Scholar, Department of Electrical and Electronics Engineering,
More informationEMERGING distributed generation technologies make it
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 4, NOVEMBER 2005 1757 Fault Analysis on Distribution Feeders With Distributed Generators Mesut E. Baran, Member, IEEE, and Ismail El-Markaby, Student Member,
More informationAdaptive Relaying of Radial Distribution system with Distributed Generation
Adaptive Relaying of Radial Distribution system with Distributed Generation K.Vijetha M,Tech (Power Systems Engineering) National Institute of Technology-Warangal Warangal, INDIA. Email: vijetha258@gmail.com
More informationPerformance Evaluation for Different Levels Multilevel Inverters Application for Renewable Energy Resources
Performance Evaluation for Different Levels Multilevel Inverters Application for Renewable Energy Resources M.Charai 1, A.Raihani 1, O.Bouattan 1, H.Naanani 2 1 Laboratoire des Signaux, Systèmes Distribués
More informationVoltage Controller for Radial Distribution Networks with Distributed Generation
International Journal of Scientific and Research Publications, Volume 4, Issue 3, March 2014 1 Voltage Controller for Radial Distribution Networks with Distributed Generation Christopher Kigen *, Dr. Nicodemus
More informationIdentification of weak buses using Voltage Stability Indicator and its voltage profile improvement by using DSTATCOM in radial distribution systems
IOSR Journal of Electrical And Electronics Engineering (IOSRJEEE) ISSN : 2278-1676 Volume 2, Issue 4 (Sep.-Oct. 2012), PP 17-23 Identification of weak buses using Voltage Stability Indicator and its voltage
More informationPQ Audit - The right choice to ensure power system performance. Mr Lalit Kumar Wasan Tata Power- DDL
PQ Audit - The right choice to ensure power system performance Mr Lalit Kumar Wasan Tata Power- DDL Outline vpower Quality v Present Challenges v Harmonics & Its Impact on DISCOM v Future Challenges Roof-Top
More informationThe Analysis of Voltage Increase Phenomena in a Distribution Network with High Penetration of Distributed Generation
The Analysis of Voltage Increase Phenomena in a Distribution Network with High Penetration of Distributed Generation Insu Kim, Ronald G. Harley, and Raeey Regassa Georgia Institute of Technology Atlanta,
More informationHybrid Power Quality Compensator for Traction Power System with Photovoltaic Array
IJMTST Volume: 2 Issue: 07 July 2016 ISSN: 2455-3778 Hybrid Power Quality Compensator for Traction Power System with Photovoltaic Array M. Kalidas 1 B. Lavanya 2 1PG Scholar, Department of Electrical &
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationINVESTIGATING THE BENEFITS OF MESHING REAL UK LV NETWORKS
INVESTIGATING THE BENEFITS OF MESHING REAL UK LV NETWORKS Muhammed S. AYDIN Alejandro NAVARRO Espinosa Luis F. OCHOA The University of Manchester UK The University of Manchester UK The University of Manchester
More informationSIMULATION AND EVALUATION OF A PHASE SYNCHRONOUS INVERTER FOR MICRO-GRID SYSTEM
SIMULATION AND EVALUATION OF A PHASE SYNCHRONOUS INVERTER FOR MICRO-GRID SYSTEM Tawfikur Rahman, Muhammad I. Ibrahimy, Sheikh M. A. Motakabber and Mohammad G. Mostafa Department of Electrical and Computer
More informationImpact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation
Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation R. S. Al Abri, M. H. Albadi, M. H. Al Abri, U. K. Al Rasbi, M. H. Al Hasni, S. M. Al Shidi Abstract This paper presents an analysis
More informationA Practical Application of Low Voltage DC Distribution Network Within Buildings
A Practical Application of Low Voltage DC Distribution Network Within Buildings B Marah 1 Hoare Lea LLP. London, UK bmarah@theiet.org Y R Bhavanam 2, G A Taylor 2, M K Darwish 2 Brunel University London.
More informationHARMONIC distortion complicates the computation of. The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus
1592 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005 The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus Ahmed Faheem Zobaa, Senior Member, IEEE Abstract A
More informationA Novel Approach to Simultaneous Voltage Sag/Swell and Load Reactive Power Compensations Using UPQC
A Novel Approach to Simultaneous Voltage Sag/Swell and Load Reactive Power Compensations Using UPQC N. Uma Maheshwar, Assistant Professor, EEE, Nalla Narasimha Reddy Group of Institutions. T. Sreekanth,
More informationLOAD BALANCING IN PRIMARY DISTRIBUTION FEEDERS BY COMBINATION OF RENEWABLE ENERGY SOURCE AND VOLTAGE SOURCE INVERTER
Paper ID: EE14 LOAD BALANCING IN PRIMARY DISTRIBUTION FEEDERS BY COMBINATION OF RENEWABLE ENERGY SOURCE AND VOLTAGE SOURCE INVERTER Metkari Vishal T., Department of Electrical, Sanjeevan Engineering &
More informationImpact of Thyristor Controlled Series Capacitor on Voltage Profile of Transmission Lines using PSAT
Impact of Thyristor Controlled Series Capacitor on Voltage Profile of Transmission Lines using PSAT Babar Noor 1, Muhammad Aamir Aman 1, Murad Ali 1, Sanaullah Ahmad 1, Fazal Wahab Karam. 2 Electrical
More informationENHANCEMENT OF POWER FLOW USING SSSC CONTROLLER
ENHANCEMENT OF POWER FLOW USING SSSC CONTROLLER 1 PRATIK RAO, 2 OMKAR PAWAR, 3 C. L. BHATTAR, 4 RUSHIKESH KHAMBE, 5 PRITHVIRAJ PATIL, 6 KEDAR KULKARNI 1,2,4,5,6 B. Tech Electrical, 3 M. Tech Electrical
More informationSizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks
Sizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks André Braga Instituto Superior Técnico Av. Rovisco Pais, 1049-001 Lisbon, Portugal
More informationSHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP
SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP Kiran V. Natkar 1, Naveen Kumar 2 1 Student, M.E., Electrical Power System, MSS CET/ Dr. B.A.M. University, (India) 2 Electrical Power System,
More informationDelhi Technological University (formerly DCE) Delhi-42, India
American International Journal of Research in Science, Technology, Engineering & Mathematics Available online at http://www.iasir.net ISSN (Print): 2328-3491, ISSN (Online): 2328-358, ISSN (CD-ROM): 2328-3629
More informationApplication of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System
International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 9, Issue 8 (January 2014), PP. 25-33 Application of Fuzzy Logic Controller in UPFC
More informationDesign of Interline Dynamic Voltage Restorer for Voltage Sag Compensation
Design of Interline Dynamic Voltage Restorer for Voltage Sag Compensation Anandan.D 1, Karthick.B 2, Soniya.R 3, Vanthiyadevan.T 4, V.Karthivel, M.E., 5 U.G. Student, Department of EEE, Angel College of,
More informationThe Selective Harmonic Elimination Technique for Harmonic Reduction of Multilevel Inverter Using PSO Algorithm
The Selective Harmonic Elimination Technique for Harmonic Reduction of Multilevel Inverter Using PSO Algorithm Maruthupandiyan. R 1, Brindha. R 2 1,2. Student, M.E Power Electronics and Drives, Sri Shakthi
More informationParticle Swarm Based Optimization of Power Losses in Network Using STATCOM
International Conference on Renewable Energies and Power Quality (ICREPQ 14) Cordoba (Spain), 8 th to 10 th April, 2014 Renewable Energy and Power Quality Journal (RE&PQJ) ISSN 2172-038 X, No.12, April
More informationIMPLEMENTATION OF NETWORK RECONFIGURATION TECHNIQUE FOR LOSS MINIMIZATION ON A 11KV DISTRIBUTION SYSTEM OF MRS SHIMOGA-A CASE STUDY
IMPLEMENTATION OF NETWORK RECONFIGURATION TECHNIQUE FOR LOSS MINIMIZATION ON A 11KV DISTRIBUTION SYSTEM OF MRS SHIMOGA-A CASE STUDY PROJECT REFERENCE NO. : 37S0848 COLLEGE : PES INSTITUTE OF TECHNOLOGY
More informationCHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS
66 CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS INTRODUCTION The use of electronic controllers in the electric power supply system has become very common. These electronic
More informationRenewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA
Renewable Interconnection Standard & Experimental Tests Yahia Baghzouz UNLV Las Vegas, NV, USA Overview IEEE Std 1547 Voltage limitations Frequency limitations Harmonic limitations Expansion of IEEE Std
More informationDesign of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller
Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller M. Ajay Department of Electronics and Electrical Engineering, Avanthi institute
More informationThe Effect of PV on Transformer Ageing: University of Queensland s Experience
Australasian Universities Power Engineering Conference, AUPEC 214, Perth, WA, Australia, 28 September 1 October 214 1 The Effect of PV on Transformer Ageing: University of Queensland s Experience D. Martin,
More informationOPTIMAL PLACEMENT OF UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEMS USING PARTICLE SWARM OPTIMIZATION METHOD
OPTIMAL PLACEMENT OF UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEMS USING PARTICLE SWARM OPTIMIZATION METHOD M. Laxmidevi Ramanaiah and M. Damodar Reddy Department of E.E.E., S.V. University,
More informationProtecting Feeders With Distributed Resource Scott Elling HDR Inc HDR, all rights reserved.
Protecting Feeders With Distributed Resource Scott Elling HDR Inc. 2015 HDR, all rights reserved. Background Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection
More informationVolume 2, Number 4, 2016 Pages Jordan Journal of Electrical Engineering ISSN (Print): , ISSN (Online):
JJEE Volume, Number 4, 6 Pages - Jordan Journal of Electrical Engineering ISSN (Print): 49-96, ISSN (Online): 49-969 Enhancement of Voltage Stability and Line Loadability by Reconfiguration of Radial Electrical
More informationIdentifying Long Term Voltage Stability Caused by Distribution Systems vs Transmission Systems
Identifying Long Term Voltage Stability Caused by Distribution Systems vs Transmission Systems Amarsagar Reddy Ramapuram M. Ankit Singhal Venkataramana Ajjarapu amar@iastate.edu ankit@iastate.edu vajjarapu@iastate.edu
More informationI J C T A, 10(9), 2017, pp International Science Press
I J C T A, 10(9), 2017, pp. 533-539 International Science Press ISSN: 0974-5572 Substation Monitoring System (SMS) For Remote Power Quality Monitoring and Analysis of Power Distribution Network using Object
More informationDesign and Analysis of Resonant Harmonic Filter
Design and Analysis of Resonant Harmonic Filter M.Raja Vidya Bharathi, AP/EEE T.Arputhamary, AP/EEE J.Divineshia Sharon, AP/EEE K.B.P. Mahavishnu, AP/EEE DMI College of Engineering,Chennai-6000123 Abstract
More informationStudy of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants
4th International Conference on Machinery, Materials and Information Technology Applications (ICMMITA 2016) Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants Chen-Xin
More informationHarmonic Study in Low Voltage Distribution Network in a Real Time Foundry Industry
I J C T A, 9(37) 2016, pp. 769-781 International Science Press Harmonic Study in Low Voltage Distribution Network in a Real Time Foundry Industry D. Ravichandran * and Er. R. Panneerselvam ** Abstract:
More informationVoltage Unbalance Reduction in Low Voltage Feeders by Dynamic Switching of Residential Customers among Three Phases
Voltage Unbalance Reduction in Low Voltage Feeders by Dynamic Switching of Residential Customers among Three Phases Farhad Shahnia, Peter Wolfs and Arindam Ghosh 3 Centre of Smart Grid and Sustainable
More informationCHAPTER 3 DEVELOPMENT OF DISTRIBUTION SIMULATION PACKAGE FOR LOAD ANALYSIS OF LV NETWORK
78 CHAPTER 3 DEVELOPMENT OF DISTRIBUTION SIMULATION PACKAGE FOR LOAD ANALYSIS OF LV NETWORK 3.1 INTRODUCTION Distribution loads vary in response to temperature, time of the day, day of the week and other
More informationModeling and Validation of an Unbalanced LV Network Using Smart Meter and SCADA Inputs
Modeling and Validation of an Unbalanced LV Network Using Smart Meter and SCADA Inputs Derek C. Jayasuriya, Max Rankin, Terry Jones SP AusNet Melbourne, Australia Julian de Hoog, Doreen Thomas, Iven Mareels
More informationIslanding Detection Method Based On Impedance Measurement
Islanding Detection Method Based On Impedance Measurement Chandra Shekhar Chandrakar 1, Bharti Dewani 2 Department of Electrical and Electronics Engineering Chhattisgarh Swami Vivekananda Technical University
More informationDistributed Active Filter Systems (DAFS): A new approach to power system harmonics
Distributed Active Filter Systems (DAFS): A new approach to power system harmonics Po-Tai Cheng Zhung-Lin Lee CENTER FOR ADVANCED POWER TECHNOLOGIES (CAPT) Department of Electrical Engineering National
More informationCharge Pump Phase Locked Loop Synchronization Technique in Grid Connected Solar Photovoltaic Systems
IOSR Journal of Computer Engineering (IOSR-JCE) e-issn: 2278-0661, p- ISSN: 2278-8727Volume 16, Issue 1, Ver. VII (Feb. 2014), PP 91-98 Charge Pump Phase Locked Loop Synchronization Technique in Grid Connected
More informationUNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEM FOR ENHANCING POWER QUALITY
International Journal of Electrical Engineering & Technology (IJEET) Volume 7, Issue 6, Nov Dec, 2016, pp.55 63, Article ID: IJEET_07_06_005 Available online at http://www.iaeme.com/ijeet/issues.asp?jtype=ijeet&vtype=7&itype=6
More informationIslanding Detection Technique based on Simulation of IEEE16 Bus System
Islanding Detection Technique based on Simulation of IEEE16 Bus System 1 Mahesh M, 2 Kusuma Devi G.H. 1 PG Scholar, 2 Research Scholar Jain University Bengaluru. Dept. of Electrical and Electronics Engineering.
More informationDISTRIBUTION NETWORK RECONFIGURATION FOR LOSS MINIMISATION USING DIFFERENTIAL EVOLUTION ALGORITHM
DISTRIBUTION NETWORK RECONFIGURATION FOR LOSS MINIMISATION USING DIFFERENTIAL EVOLUTION ALGORITHM K. Sureshkumar 1 and P. Vijayakumar 2 1 Department of Electrical and Electronics Engineering, Velammal
More informationAn Ellipse Technique Based Relay For Extra High Voltage Transmission Lines Protection
Proceedings of the 14th International Middle East Power Systems Conference (MEPCON 10), Cairo University, Egypt, December 19-21, 2010, Paper ID 162. An Ellipse Technique Based Relay For Extra High Voltage
More informationImpact Assessment Generator Form
Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project
More informationGrounding Strategies for Solar PV Panels
Grounding Strategies for Solar PV Panels A. S. Ayub, W. H. Siew Department of Electronic & Electrical Engineering, University of Strathclyde, Glasgow, Scotland, United Kingdom ahmad.ayub@strath.ac.uk,
More informationOptimal sizing of battery energy storage system in microgrid system considering load shedding scheme
International Journal of Smart Grid and Clean Energy Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme Thongchart Kerdphol*, Yaser Qudaih, Yasunori Mitani,
More informationHARMONICS ANALYSIS USING SEQUENTIAL-TIME SIMULATION FOR ADDRESSING SMART GRID CHALLENGES
HARMONICS ANALYSIS USING SEQUENTIAL-TIME SIMULATION FOR ADDRESSING SMART GRID CHALLENGES Davis MONTENEGRO Roger DUGAN Gustavo RAMOS Universidad de los Andes Colombia EPRI U.S.A. Universidad de los Andes
More informationIDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)
IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone
More informationHarmonic Aggregation Techniques for Power Quality Assesment A review of different methods
Harmonic Aggregation Techniques for Power Quality Assesment A review of different methods M.M.Share Pasand Department of Electrical and Electronics Engineering Standard Research Institute- SRI Alborz,
More informationImproving the Power Factor Correction in the Presence of Harmonics by Reducing the Effect of Resonance and Harmonics
Indonesian Journal of Electrical Engineering and Computer Science Vol. 3, No. 2, August 2016, pp. 282 ~ 295 DOI: 10.11591/ijeecs.v3.i2.pp282-295 282 Improving the Power Factor Correction in the Presence
More informationNew Methods to Mitigate Distribution System Harmonics
Alberta Power Industry Consortium 214 Power & Energy Innovation Forum New Methods to Mitigate Distribution System Harmonics By Wilsun Xu Power Disturbance & Signaling Research Lab November 5, 214 Outline
More informationA Case Study of Resonance in 11kV Network in the Presence of Series Current Limiting Reactors, VSDs and Power Factor Improvement Capacitors
International Journal of Electrical Energy, Vol. 2, No., December 201 A Case Study of Resonance in 11kV Network in the Presence of Series Limiting s, VSDs and Power Factor Improvement s Yadavalli Venkata
More informationPower Quality in High Density Residential Distribution Grids
Power Quality in High Density Residential Distribution Grids Gustav R. Krüger, Raj M. Naidoo Abstract Research in the field of power quality challenges in distribution grids is gaining a strong foothold.
More informationPhasor-Based Interdependencies of Harmonic Sources in Distribution Networks
Phasor-Based Interdependencies of Harmonic Sources in Distribution Networks Reza Arghandeh a*, Ahmet Onen a, Jaesung Jung a, Danling Cheng b, Robert P. Broadwater a, Virgilio Centeno a a Department of
More informationEnhancement of Power Quality in Distribution System Using D-Statcom for Different Faults
Enhancement of Power Quality in Distribution System Using D-Statcom for Different s Dr. B. Sure Kumar 1, B. Shravanya 2 1 Assistant Professor, CBIT, HYD 2 M.E (P.S & P.E), CBIT, HYD Abstract: The main
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationSOLAR POWERED REACTIVE POWER COMPENSATION IN SINGLE-PHASE OPERATION OF MICROGRID
SOLAR POWERED REACTIVE POWER COMPENSATION IN SINGLE-PHASE OPERATION OF MICROGRID B.Praveena 1, S.Sravanthi 2 1PG Scholar, Department of EEE, JNTU Anantapur, Andhra Pradesh, India 2 PG Scholar, Department
More informationIEEE sion/1547revision_index.html
IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html
More informationSession Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages
Session Four: ractical Insulation Co-ordination Session Four: ractical Insulation Co-ordination for Lightning Induced Overvoltages Jason Mayer Technical Director, Energy Services, Aurecon Introduction
More informationR10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours
Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions
More informationACCURATE MODELING FOR LOSSES REDUCTION USING A REAL-TIME POWER FLOW AT ENELVEN
ACCURATE MODELING FOR LOSSES REDUCTION USING A REAL-TIME POWER FLOW AT ENELVEN Renato CESPEDES I. Roytelman, A.Ilo P.Parra,L.Rodriguez,H.Socorro,T. Romero KEMA Consulting Colombia SIEMENS USA,Austria ENELVEN
More informationADVANCEMENT IN STATE GRASPING METHOD OF MV DISTRIBUTION NETWORK FOR SHORT-TERM AND MID-TERM PLANNING
PV capacity [GW] ADVANCEMENT IN STATE GRASPING METHOD OF MV DISTRIBUTION NETWORK FOR SHORT-TERM AND MID-TERM PLANNING Hiroyuki ISHIKAWA Ishikawa.Hiroyuki@chuden.co.jp Takukan YAMADA Yamada.Takukan@chuden.co.jp
More informationPower System Stability Enhancement Using Static Synchronous Series Compensator (SSSC)
Vol. 3, Issue. 4, Jul - Aug. 2013 pp-2530-2536 ISSN: 2249-6645 Power System Stability Enhancement Using Static Synchronous Series Compensator (SSSC) B. M. Naveen Kumar Reddy 1, Mr. G. V. Rajashekar 2,
More informationAnalysis of Voltage Rise Effect on Distribution Network with Distributed Generation
Analysis of Voltage ise Effect on Distribution Network with Distributed Generation M. A. Mahmud, M. J. Hossain, H.. Pota The University of New South Wales at the Australian Defence Force Academy, Northcott
More informationAnnamacharya Institute of Technology and Sciences, Tirupathi, A.P, India
Active Power Loss Minimization Using Simultaneous Network Reconfiguration and DG Placement with AGPSO Algorithm K.Sandhya,Venkata Supura Vemulapati 2,2 Department of Electrical and Electronics Engineering
More informationISSN Vol.07,Issue.11, August-2015, Pages:
ISSN 2348 2370 Vol.07,Issue.11, August-2015, Pages:2063-2068 www.ijatir.org LCL Filter Design and Performance Analysis for Grid-Interconnected Systems T. BRAHMA CHARY 1, DR. J. BHAGWAN REDDY 2 1 PG Scholar,
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationElectromagnetic Harmonic Filters Technical Guide
Eliminator Series Electromagnetic Harmonic Filters Technical Guide Neutral Eliminator TM (NCE TM ) Parallel connected, 3-phase, 4-wire passive electromagnetic device that diverts 3rd and other triplen
More informationDESIGN AND ANALYSIS OF INTERLEAVED NON-INVERTING BUCK BOOST CONVERTER FOR PV MODULE
DESIGN AND ANALYSIS OF INTERLEAVED NON-INVERTING BUCK BOOST CONVERTER FOR PV MODULE P. Vijayapriya, A. Thamilmaran, Akshay Kumar Jain and Alakshyender Singh School of Electrical Engineering, Vellore Institute
More informationPublished in: Proceedings of the 37th Annual Conference of IEEE Industrial Electronics Society, IECON 2011
Aalborg Universitet A centralized control architecture for harmonic voltage suppression in islanded microgrids Wang, Xiongfei; Blaabjerg, Frede; Chen, Zhe; Guerrero, Josep M. Published in: Proceedings
More informationA Modified Single-Phase Quasi z source converter
International Journal of Engineering Trends and Technology (IJETT) Volume 27 Number 5 - September 205 A Modified Single-Phase Quasi z source converter N.Subhashini #, N.Praveen Kumar #2 # PG Student[PE],
More informationDESIGN OPTIMIZATION TECHNIQUES FOR IMPROVED POWER FACTOR AND ENERGY EFFICIENCY FOR INDUSTRIAL PROCESSES. Darren R. Rabosky
DESIGN OPTIMIZATION TECHNIQUES FOR IMPROVED POWER FACTOR AND ENERGY EFFICIENCY FOR INDUSTRIAL PROCESSES by Darren R. Rabosky Copyright by Darren R. Rabosky, 2012 All Rights Reserved A thesis submitted
More informationModeling and Evaluation of Geomagnetic Storms in the Electric Power System
21, rue d Artois, F-75008 PARIS C4-306 CIGRE 2014 http : //www.cigre.org Modeling and Evaluation of Geomagnetic Storms in the Electric Power System K. PATIL Siemens Power Technologies International, Siemens
More information