1 Operation Manual IR24 (Types MWG 2491 and MWG 2492) Transmitter for carbon dioxide GfG GESELLSCHAFT FÜR GERÄTEBAU MBH KLÖNNESTRASSE DORTMUND TELEPHONE / FAX / INFO@GFG-MBH.COM AMTSGERICHT DORTMUND HR B 2742 CERTIFIED TO DIN EN ISO 9001:2008 ATEX QM CERTIFICATION

2 Table of Contents Page For your safety 3 General Description 3 Operating instructions 4 Unit design 4 Measurement procedure 4 Installation location of the transmitter 5 Installation 5 Installing electrical connections 6 Commissioning 6 Control of the electrical zero point 7 Checking the display sensitivity 8 Servicing 10 Maintenance and inspection 10 Fault - cause - remedy 10 Connection plans for transmitters on gas measurement computer (GMA) 11 IR24 type MWG IR24 type MWG Terminal assignment plan 12 Technical specifications 12-2-

3 M E N U 1 0 C H A N N E L 8 0 o u t / N 6 0 A 3 i n / M A A 1 U 2 0 % O N F A U L T T U E S T Q U I T M E N U M E N U A 3 A 2 F A U L T For your safety According to Article 3 of the Technical Working Materials Act (Gesetz über technische Arbeitsmittel), this operating manual points out on the intended use of the product and serves to prevent risks. It must be read and followed by all persons that utilise this product or use, service, maintain, and control it. This product can only perform its duties for which it is intended, when it utilised, used, maintained, serviced and controlled according to the instructions given by the GfG company. The warranty provided by the GfG company becomes null and void if it is not used, maintained, controlled or serviced according to the instructions issued by the GfG company. The above does not alter the information on warranty and liability in the terms and conditions of the GfG company. General Description A fixed gas warning system consists of a transmitter (MWG) and a gas measurement computer (GMA). Transmitter and gas measurement computer are connected via a remote sensor cable. The transmitter converts the unit of "gas concentration" into an electrical signal for measuring and sends it via the remote sensor cable to the gas measurement computer for further processing. Fixed gas measurement and warning system 5 Vol% CO2 A 1 Evaluation Auswerten Alarmieren Warning Measurement Messen Figure 1 The transmitter IR24 is an "intelligent" measuring head. Its extensive electronic system takes over many tasks that facilitate the operation and maintenance and also significantly increase the reliability and accuracy. The transmitter IR24 is characterised by: Latest infrared measuring technique (IR) for high reliability and long service life Simple calibration on site Service lid for adjusting zero point and sensitivity Thermostatic control of the measuring cell for compensating temperature influences -3-

4 Operating instructions According to the national regulations, gas warning devices must be inspected for proper functioning by an expert after installation, but before any measuring operation is carried out (commissioning). In Germany the following applies: Regulation for the prevention of accidents, gases 56(2) "UVV Gase" (BGV B6 formerly VBG 61). The transmitter IR24 has been tested for correct operation and display prior to delivery. The calibration was carried out with appropriate testing gases. This does not absolve from a functional testing after installation. Unit design The unit design of the transmitter IR24 is shown in figure 2. Transmitter IR24 unit design Gehäuseoberteil Casing top (Deckel) Gehäuseunterteil Casing bottom 5 Vol % CO2 Messbereich Detection range Messgas Gas Befestigungsschraube Lock screw for für die service Serviceklappe lid Serviceklappe lid Cable Messkabeldurchführung gland PG PG-Verschraubung screwing Diffusionsfläche inlet Figure 2 The transmitter IR24 consists of a robust metal housing. The diffusion opening is located at the lower end of the housing. Potentiometers (controllers) for adjusting the electric zero point and the display sensitivity (adjustment) as well as test sockets for a display unit for checking the zero point and display sensitivity are located behind the service lid. The main circuit board and the calibrating board are in the housing. The electronic system of the main circuit board converts the measuring signal into the measured value output ma or ma. The operating elements are on the calibrating board. Measurement procedure The infrared measuring cell makes use of the property of gases to absorb light in certain spectral areas. The infrared light emitted through a lamp passes through the measurement -4-

5 section filled with sample gas. Thanks to the sample gas, the radiation energy is weakened through absorption. The absorption of infrared radiation within a certain wavelength area in the sample gas depends on the concentration of the gas to be measured. The energy decrease of the infrared radiation caused by absorption is measured with the help of detectors. Installation location of the transmitter In determining the place of installation, it is important to know the environmental conditions and to take them into account when selecting the location, e.g. the ventilation conditions the fact that the density of carbon dioxide (CO 2 ) is higher than the one of air. Thus, gas gathers at ground level. The transmitter IR24 must be installed in the room so that the gases reach the sensor even with unfavourable ventilation. If necessary, a measurement must be made for example with smoke tubes. Outside influences are also to be noted: Rain water, splash water, dripping water, condensation and the dust in the atmosphere. The transmitter IR24 is largely protected against the ingress of water and dust (IP 54). In very difficult conditions, special accessories can be used to protect the transmitter IR24 from damage. GfG will be happy to advise you on appropriate measures.! If the measuring chamber is exposed to environmental conditions which were not known to GfG during planning or delivery, the warranty may become invalid. In determining the place of installation ensure that the transmitter is accessible for service and calibration work. For reasons of easy servicing, the transmitter must be positioned vertically with the sensor pointing downward. Another installation position does not influence the measurement accuracy. Installation The transmitter IR24 is connected to the gas measurement computers according to the terminal assignment (page 12) and connection plans IR24 (page Fehler! Textmarke nicht definiert.). For mounting, unscrew the four special screws (pos. 9, figure 2) and remove the housing cover. The housing is fastened through two boreholes.! The transmitter IR24 is not approved for operation in potentially explosive atmospheres. -5-

6 Installing electrical connections The laying of cables and connection of the electrical installation may only be carried out by an expert taking into consideration the relevant provisions. Depending on the version or type of operation of the transmitter IR24, installation has to be done with a triple or multi-wired shielded cable (e.g. LIYCY 3 x 1.5mm 2 ). The cross-section depends on the length of the connection cable. For short distances (until 200 m), a wire cross-section of 0.75 mm 2 instead of 1.5 mm 2 is sufficient. The shielding is to be placed on the PG cable gland. If a power supply unit or another system is used for operating the transmitter, its operating voltage must not exceed 24 V. After installation, the cover must be closed and screwed again. The transmitter may only be installed and opened when it is free from any gas. Wiring scheme transmitter IR brown green white 24V Ground ma ma GMA Figure 3 Commissioning After mounting and installing the transmitter IR24, its commissioning can be done by an expert. The IR24 has been calibrated and checked in factory. Calibration work performed in factory is done after a run-in period of the new transmitter lasting several days. This measure results in an optimum basic setting. If the transmitter is switched on again, the infrared sensor required a certain run-in period which might last approx minutes until calibration check. -6-

7 Control of the electrical zero point Upon delivery, the transmitter IR24 is checked and calibrated. However, deviations can occur dependent on the transport, installation and environmental conditions. Caution: The electric zero point can only be set in 100 vol.% nitrogen or synthetic air which is free from CO 2. The transmitter requires a run-in period of 30 minutes. If the zero point calibration is done earlier, the sensor setting performed in factory will be falsified. After a run-in period of 30 min. the test sockets (U M ) behind the service lid of the IR24 (figure 4) and the gas measurement computer can be used to connect and read a voltmeter (please refer to the operating instructions of the GMA gas measurement computer). Transmitter IR24 circuit board Sicherung Fuse SI1 SI1 Service switch Serviceschalter SERVICE OPERATION BETRIEB Klemmleiste Terminal bar Potentiometer" ZEROPOINT NULLPUNKT" Test Prüfbuchse socket UM für for volt Voltmeter Potentiometer CALIBRATION "KALIBRIEREN" PG Verschraubung screwing IR - Sensor Figure 4 While setting the zero point, the service switch should be adjusted to "SERVICE" position. -7-

8 The following flowchart describes the procedure for checking the electric zero point: Open the service lid on IR24. Use a calibration adapter for feeding zero gas into the measuring chamber (100 vol% N 2 or synthetic air free from CO 2 ). The flow rate should amount to approx. 0.5 l/min. Service switch in "SERVICE" position Connect the voltmeter to the test socket U M (refer to figure 4) U M = 0.2 V? yes no Adjust the voltage on "ZERO POINT" potentiometer to 0.2 V. Service switch in "MEASURING MODE" position Close the service lid on IR24. Check U N at GMA gas measurement computer. U N should amount to 0 V. Deviations can be adjusted at the GMA gas measurement computer. Please refer to the operating instructions of the GMA gas measurement computer. Checking the display sensitivity For checking the display sensitivity, a test gas adapter has to be plugged in or screwed on the sensor holder. Afterwards, select a suitable test gas. You will need to check first which test gas has been used for setting the transmitter. For the gas type and the measurement range please refer to the test report and the information plate on the transmitter. The value of test gas concentration should amount to a value which is at least 20 % above the second alarm level. For the basic setting of the alarm level and the gas indicator, please refer to the test report of the transmitter. Caution: The display sensitivity can only be adjusted with a suitable test gas. The transmitter requires a run-in period of 30 minutes. If the display sensitivity is modified earlier, the sensor setting performed in factory will be falsified. While checking the display sensitivity, the service switch should be adjusted to "SERVICE" position. The following flowchart describes the procedure for checking the display sensitivity: -8-

9 Serviceklappe Open service am lid IR24 at IR24. entfernen. Kalibrieradapter Fix calibration am adapter IR24 befestigen. at IR24. Serviceschalter switch in in Position position "SERVICE" SERVICE. Prüfgas Supply drucklos test gas mit without einem Durchfluß pressure, von at etwa a flow 0,5 rate l/min of dem approx. IR24 zuführen. 0.5 l/min, Prüfgas to IR24. ist ein Test CO2-Luft- gas is oder a COCO2-Stickstoff-Gemisch 2 /air or 2 /nitrogen mit mixture einer CO2 with Konzentration a CO 2 concentration die dem Meßbereichendwert equivalent to full entspricht scale oder or at mindestens least 20 % 20 % above oberhalb the der 2. alarm 2 Alarmschwelle threshold. liegt. Die Within Anzeige approx. am Gasmesscomputer 1 minute the display muß sich at the innerhalb GMA controller von etwa 1 min must entsprechend show the test dem gas Wert concentration. der Prüfgaskonzentration Should you eingestellt operate haben. the MWG Wird without der MWGMA, G ohne you GMA can betrieben, see the so voltage können values die Spannungswerte from the calibration der Kalibrierkur curve and ve entnommen measure at und IR24 am output IR24-Ausgang U M. "UM" gemessen werden. Gemessener Is the measured W ert stimmt value equivalent mit dem Wert to der the Kalibrierkurve value in the überein? calibration curve? Yes ja nein No An Adjust dem IR24 calibration bzw. dem point Gasmesscomputer at IR24 or at den the Kalibrierpunkt controller. Please nachjustieren. refer to Beachten the operation Sie bitte die manual Betriebsanleitung of your GMA. des Gasmesscomputers. Serviceschalter switch in in Position position "MESSBETRIEB" OPERATION. Serviceklappe Close service am lid IR24 at IR24. schließen. Prüfgas Disconnect und Kalibrieradapter test gas and calibration entfernen. adapter. -9-

10 Servicing In the sense of the regulation for the prevention of accidents, gases "UVV Gase" and according to DIN 31051, servicing includes the maintenance, inspection and repair of gas warning devices. The data sheet T023 published by the German Association of the Chemical Industry (BG Chemie) describes adequate measures as e.g. the periodical performance of a functional testing. This functional testing includes: Checking with alarm gas Zero point and sensitivity (calibration) Time setting Gas sampling system, gas treatment (if applicable) Triggering of warning signals Signalling unit for malfunctions This check has to be performed by an expert. The result has to be confirmed in writing. The calibration intervals shall normally not exceed 16 weeks. The functional testing has to be performed prior to commissioning and at least once a year. Maintenance and inspection Maintenance and inspection include all measures for maintaining the nominal state of the gas warning system. The transmitter IR24 does not require any special maintenance. However, a few aspects should be taken into consideration. Depending on the environmental conditions, gas warning systems can behave differently. Thus, it is important to perform a visual inspection each day in particular within the first few days after commissioning (refer to T023). Checking the gas treatment, the filter units if applicable. Checking the gas supply for contamination. For assuring a correct measurement, the gas supply must be free from any debris. Measuring cells (sensors) get worse and wear out with increasing age. Depending on type and gas admission, there is more or less load on the sensors such that the sensitivity can only be checked with an appropriate test gas during a time period to be determined. The calibration of sensitivity is a professional calibration which is normally performed by the GfG Customer Service or an authorized person. Fault - cause - remedy Fault Cause Remedial action Zero point can no longer be set Sensor defective Replace sensor Final value can no longer be set Sensor defective Replace sensor Output current has dropped to 0 ma Defective fuse Line disconnected Replace fuse Re-connect -10-

11 Connection plans for transmitters on gas measurement computer (GMA) IR24 type MWG 2492 brown green white V GND 4 20 ma GMA GMA GMA GMA81 (A) IR24 type MWG 2491 brown green white V GND ma GMA GMA GMA with bus board from year of manufacture 97 (blue) GMA with bus board to year of manufacture 96 (colourless) GMA GMA GMA81 (A)

12 Terminal assignment plan U= 18,0 V - 24,0 V R1 I = 4-20 ma MWG 2492 MWG 2491 Max. load 150 Ohm Use shielded cable for distances of more than 5 m Technical specifications Transmitter IR24 Transmitter type: MWG 2491 and MWG 2492 Measurement principle: Infrared (IR) Measurement gas: Carbon dioxide (CO 2 ) Measurement range: 1, 2, 5, 10, 15, 20, 25, 50, 70 vol.% (partial pressure measurement) Gas supply: Diffusion No significant influence on measuring signal when using the calibration adapter with l/min. Response time t 90 : 25 s Expected service life of sensor: > 5 years Climatic conditions Storage temperature: C Operating temperature: C Humidity: %r.h. non condensing Air pressure: kpa (100 kpa = 1000 mbar) Electrical connections Supply voltage: V DC Power consumption : < 150 ma (temporarily 200 ma) Output signal in measuring 0,2..1 ma or ma mode: Output signal in service mode: 0..0,2 ma or 0..4 ma with 2Hz pulsating Max. load: ma or ma Technology for people and the environment _OM_IR24_CO2.doc State: December 15, 2015 Subject to change GfG Gesellschaft für Gerätebau mbh Klönnestraße 99 D Dortmund Telephone: Fax: info@gfg-mbh.com Internet:

13 -13-

Worldwide Manufacturer of Gas Detection Solutions. Transmitter EC 23. Operation Manual

Worldwide Manufacturer of Gas Detection Solutions. Transmitter EC 23. Operation Manual Worldwide Manufacturer of Gas Detection Solutions Transmitter EC 23 Operation Manual Table of Contents For Your Safety...4 General Description...4 Electrical Connections...5 Zero Point Adjustment...5

More information

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information *09005137* BA_EN_DE50 Rev.A 11/12 *09005137* d e v e l o p i n g s o l u t i o n s DE50 Operating Manual Differential pressure transmitter Table of Contents 1 Safety guidelines 2 Application purpose 3

More information

Operating Instructions

Operating Instructions Level and Pressure Operating Instructions VEGATOR 620, 621, 622 max. 0 10 min. 0 10 on VEGATOR 622! 6 7 8 9 10 11 12 13 14 in out Contents Contents Safety information... 2 Note Ex area... 2 1 Product description

More information

Instruction Manual T5140 T5141 T5145 T5240 T5241 T5245. Programmable transmitter of CO2 concentration with 4-20 ma output. with 0-10 V output

Instruction Manual T5140 T5141 T5145 T5240 T5241 T5245. Programmable transmitter of CO2 concentration with 4-20 ma output. with 0-10 V output www.cometsystem.com Instruction Manual T5140 T5141 T5145 Programmable transmitter of CO2 concentration with 4-20 ma output T5240 T5241 T5245 Programmable transmitter of CO2 concentration with 0-10 V output

More information

Humidity Temperature Sensor TFG80 Duct version with Polyga measuring element

Humidity Temperature Sensor TFG80 Duct version with Polyga measuring element Galltec Mess- und Regeltechnik GmbH MELA Sensortechnik GmbH D-71145 Bondorf. Germany D-07987 Mohlsdorf-Teichwolframsdorf. Germany Tel. +49 (0)7457-9453-0. Fax +49 (0)7457-3758 Tel. +49(0)3661-62704-0.

More information

Manual Dew point transmitter SP-ESH420 Version: 01/2011/EN

Manual Dew point transmitter SP-ESH420 Version: 01/2011/EN Manual Dew point transmitter SP-ESH420 Version: 01/2011/EN 1. General Information...3 1.1 Manufacturer...3 1.2 Warranty notes...3 1.3 About this operating manual...4 2. Description of application...5 2.1

More information

Precipitation Monitor ,

Precipitation Monitor , THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA Instruction for use 021197/11/09 Precipitation Monitor 5.4103.10.000, 5.4103.10.700 ADOLF THIES GmbH & Co. KG Hauptstraße

More information

Operator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique

Operator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique Operator Manual Transmitters Series KAT-... Analog transmitters in 2-wire technique Important Safety Notes! In the case of non-observance of the installation and safety notes or improper use of the transmitter

More information

Precipition Sensor with analogue Intensity Output ,

Precipition Sensor with analogue Intensity Output , THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA Instruction for use 021335/11/09 Precipition Sensor with analogue Intensity Output 5.4103.20.041, 5.4103.20.741 ADOLF THIES

More information

Overview of types. Technical data

Overview of types. Technical data echnical data sheet SHA-.. Multifunctional linear actuators for adjusting air dampers and slide valves in ventilation and air-conditioning systems for building services installations For air control dampers

More information

CDG. Carbon Dioxide - User Manual Gas Detector. 1 Intended Use. 2 Functional Description. 3 Installation. 4 Electrical Connection.

CDG. Carbon Dioxide - User Manual Gas Detector. 1 Intended Use. 2 Functional Description. 3 Installation. 4 Electrical Connection. Carbon Dioxide - User Manual 1 Intended Use 2 Functional Description 2.1 Control Mode 2.2 Sensor 3 Installation 3.1 Mounting instructions 3.2 Installation 4 Electrical Connection 4.1 Instruction 5 Commissioning

More information

RK PPM Hexane Transmitter Operator s Manual

RK PPM Hexane Transmitter Operator s Manual 65-2461RK PPM Hexane Transmitter Operator s Manual Part Number: 71-0144RK Revision: 0 Released: 2/16/11 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual

More information

User Manual. PolyGard ADTD Infrared Carbon Dioxide Transmitter Serial No. SM03_00X. October, 2011

User Manual. PolyGard ADTD Infrared Carbon Dioxide Transmitter Serial No. SM03_00X. October, 2011 PolyGard Infrared Carbon Dioxide Transmitter Serial No. SM0_00X User Manual October, 0 GAADTD6_E_0 Page Intended Use... Functional Description.... Control Mode.... Sensor... Installation.... Mounting Instructions....

More information

Endress Hauser. SmarTec M CLD 133 Conductivity Measurement

Endress Hauser. SmarTec M CLD 133 Conductivity Measurement Technical Information / Operating Instructions TI 281C/07/en/08.02 No. 51506567 SmarTec M Conductivity Measurement Compact conductivity transmitter with inductive sensor and integrated temperature compensation

More information

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions ELECTRONIC SPEED CONTROLLER Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING

More information

Technical Specification Temperature-Humidity-Pressure Sensor

Technical Specification Temperature-Humidity-Pressure Sensor Technical Specification ITEM CODE RELEASE DATE AUTHOR B80951-01 24 th October 2017 T. Thiesing REVISION REVISION DATE VERSION AUTHOR B-COMMAND GmbH Gruetzmuehlenweg 46 22339 Hamburg Germany FON: +49 40

More information

Technical Documentation

Technical Documentation Technical Documentation PROAM-21 Power amplifier for directional valves Grundlage der Funktionsbeschreibung und zur Prüfung der Module (keine Produktdokumentation). AMCA HYDRAULIC FLUID POWER B.V. P.O.BOX

More information

Radio receiver E17 2-channel, 27 MHz, 40MHz, or 433 MHz, 2 relay outputs. Operating voltage: 230 V/AC or 12 V or 24 V AC/DC available.

Radio receiver E17 2-channel, 27 MHz, 40MHz, or 433 MHz, 2 relay outputs. Operating voltage: 230 V/AC or 12 V or 24 V AC/DC available. Fig.: 230 V version Radio receiver E17 2-channel, 27 MHz, 40MHz, or 433 MHz, 2 relay outputs. Operating voltage: 230 V/AC or 12 V or 24 V AC/DC available. Installation, connection and programming instructions

More information

AHC-XP. Dewpoint-guided Power Controller for Glass and Handrail Heaters. Front view. Characteristics

AHC-XP. Dewpoint-guided Power Controller for Glass and Handrail Heaters. Front view. Characteristics Dewpoint-guided Power Controller for Glass and Handrail Heaters Front view Characteristics Dew point-guided power controller for cost-optimized operation of glass and handrail heaters Digital display of

More information

RK Hydrogen Transmitter Operator s Manual

RK Hydrogen Transmitter Operator s Manual 65-2451RK Hydrogen Transmitter Operator s Manual Part Number: 71-0133RK Revision: C Released: 5/17/11 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual before

More information

4/3 proportional directional valve direct operated, with integrated electronics

4/3 proportional directional valve direct operated, with integrated electronics 4/ proptional directional valve direct operated, with integrated electronics RE 2964/. Replaces: 2.2 /6 Type 4WREEM Sizes 6 and Component series 2X Maximum operating pressure 5 bar Maximum flow: 9 l/min

More information

CD-Pxx-00-0 Series Duct Mount CO 2 Transmitter

CD-Pxx-00-0 Series Duct Mount CO 2 Transmitter Installation Instructions CD-Pxx-00-0 Issue Date February 4, 006 CD-Pxx-00-0 Series Duct Mount CO Transmitter Application Requirements FCC Compliance Statement This equipment has been tested and found

More information

ENGLISH S-CO2 AMBIENT AIR SENSOR INSTALLATION AND OPERATING INSTRUCTIONS CO 2. TF5701_B_v1_web

ENGLISH S-CO2 AMBIENT AIR SENSOR INSTALLATION AND OPERATING INSTRUCTIONS CO 2. TF5701_B_v1_web S-CO2 CO 2 AMBIENT AIR SENSOR INSTALLATION AND OPERATING INSTRUCTIONS ENGLISH TF5701_B_v1_web 1 DESCRIPTION This module measures carbon dioxide (CO 2 ) in the range of 0 to 2 000 ppm and is equipped with

More information

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL Roline L1 Series Humidity - Temperature Transmitters INSTRUCTION MANUAL 20030314 CONTENTS Overview... 3 Operation... 5 Power supply... 5 Operating range and limits... 5 Temperature compensation of the

More information

Submersible pressure sensor For water and wastewater Model LW-1

Submersible pressure sensor For water and wastewater Model LW-1 Replacement product: Model LF-1 Level measurement Submersible pressure sensor For water and wastewater Model LW-1 WIKA data sheet LM 40.03 Applications Level measurement in rivers and lakes Deep well and

More information

Technical data. Parameterisable damper actuator in the

Technical data. Parameterisable damper actuator in the echnical data sheet Parameterisable damper actuator in the IP66 protective housing for or adjusting ad usting air dampers in industrial plants and in technical building installations For air dampers up

More information

M224. M C bis. TYPE CODE M K Y 45 / 18 x 60 - / / / - #

M224. M C bis. TYPE CODE M K Y 45 / 18 x 60 - / / / - # Solenoid coil MKY/18x60 For explosion-hazard zones Protection class IP65/66/67 Optional with integrated amplifier electronics Ex db IIC T6 / T4 Gb Ex tb IIIC IP65 T80 C/T130 C Db Ex db I Mb II 2 G Ex db

More information

WATERFLUX 3000 Quick Start

WATERFLUX 3000 Quick Start WATERFLUX 3000 Quick Start Electromagnetic flow sensor The documentation is only complete when used in combination with the relevant documentation for the signal converter. KROHNE CONTENTS WATERFLUX 3000

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet LH24A-00 Communicative linear actuator adjusting dampers and slide valves in technical building installations Air damper size up to approx. m² Actuating force 50 N Nominal voltage AC/DC

More information

Hygro-ThermoTransmitter-compact xxx

Hygro-ThermoTransmitter-compact xxx THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA Instruction for use 020891/08/07 Hygro-ThermoTransmitter-compact 1.1005.54.xxx 1.1005.54.000/150/161/461/173 1.1005.54.241/441

More information

Electromotoric actuators for stroke valves

Electromotoric actuators for stroke valves s ACVATIX Electromotoric actuators for stroke valves SAS.. Electromotoric actuators with 5.5 mm stroke and 400 N positioning force SAS31.. Operating voltage AC 230 V, 3-position control signal Operating

More information

Installation & Operating Manual. iwap202

Installation & Operating Manual. iwap202 Installation & Operating Manual iwap202 This page is intentionally left blank. Document Number 409345 (based on 407655) (See Last Page for Revision Details) For warranty information, refer to Terms and

More information

Transducer transmitter BILT 4 II 2(1) G. Technical Manual

Transducer transmitter BILT 4 II 2(1) G. Technical Manual GB Transducer transmitter BILT 4 II 2(1) G Technical Manual Transducer transmitter BILT 4 Contents Introduction General... 3 Ex.safety description... 4 Technical data... 5 Installation General... 6 Mechanical

More information

Radio System Strobe Wizard Plus Freemask

Radio System Strobe Wizard Plus Freemask Radio System Strobe Wizard Plus Freemask User manual Translation of the original German user manual Doc. No.: 900.0509.00 Version: 09/2017 Contents Information about this manual and about the manufacturer...

More information

RK-CH4-4 Methane Transmitter Operator s Manual

RK-CH4-4 Methane Transmitter Operator s Manual 65-2395RK-CH4-4 Methane Transmitter Operator s Manual Part Number: 71-0468 Revision: P1 Released: 10/17/18 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual

More information

FINAL. Hygro-ThermoTransmitter-compact xxx xxx MEETINSTRUMENTATIE. Instruction for use /06/ x4.0xx/1xx/4xx/8xx...

FINAL. Hygro-ThermoTransmitter-compact xxx xxx MEETINSTRUMENTATIE. Instruction for use /06/ x4.0xx/1xx/4xx/8xx... M E E T I N S T R U M E N T A T I E MEETINSTRUMENTATIE Turfschipper 114 2292 JB Wateringen Tel. 0174 272330 Fax. 0174 272340 info@catec.nl www.catec.nl Turfschipper 114 2292 JB Wateringen Tel. +31 (0)174

More information

Uniform surface Led series SFL-UV

Uniform surface Led series SFL-UV Uniform surface Led series SFL-UV New: digital remote controllable UV-LED SFL-UV-L UV-LED SFL-UV-M UV-LED SFL-UV-S High UV irradiance combined with a uniform irradiated area is the key feature of the surface

More information

Operating instructions

Operating instructions SITOP power flexi 6EP1353-2BA00 Betriebsanleitung Operating instructions Best. Nr.: C98130-A7518-A1-03-7419 Siemens AG Österreich, 03.2001 1/8 SITOP power flexi Maßbild Dimension drawings SITOP power flexi

More information

Engineering Guideline. pac-carriers Type for Yokogawa Centum VP

Engineering Guideline. pac-carriers Type for Yokogawa Centum VP Engineering Guideline pac-carriers Type 9195 for Yokogawa Centum VP pac-carrier Type 9195 2 Engineering Guideline / Yokogawa Centum VP 26.0.2018 pac-carrier Type 9195 Integrated solutions for Yokogawa

More information

WATERFLUX 3000 Quick Start

WATERFLUX 3000 Quick Start WATERFLUX 3000 Quick Start Electromagnetic flowmeter The documentation is only complete when used in combination with the relevant documentation for the signal converter. KROHNE CONTENTS WATERFLUX 3000

More information

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL M1 Series Humidity - Temperature Transmitter INSTRUCTION MANUAL 20031110 -2- CONTENTS Overview... 3 Operation... 4 Power supply... 4 Operating range and limits... 4 Temperature compensation of the humidity

More information

CashConcepts CCE 4000

CashConcepts CCE 4000 CashConcepts CCE 4000 Coin Counter and Sorting Machine User Manual Introduction Thank you for choosing the CCE 4000. This coin counting and coin sorting machine is designed to simplify the daily cash or

More information

User Manual. PolyGard AT-2000 V3. Infrared Refrigerant Gas Transmitter Serial No. AT March, 2009

User Manual. PolyGard AT-2000 V3. Infrared Refrigerant Gas Transmitter Serial No. AT March, 2009 PolyGard AT-2000 V3 Infrared Refrigerant Gas Transmitter Serial No. AT-2000 User Manual March, 2009 February 16, 2016 Revision Specifications subject to change without notice. USA 160216 Page 2 of 13 1

More information

Differential pressure sensors

Differential pressure sensors 1 912 1912P02 QBM64/ 1912P01 QBM63/ Differential pressure sensors for air and non-aggressive gases, with a diaphragm sensing element QBM63/ QBM64/ With choice of pressure-linear or extracting-the-root

More information

ProHead. User s Guide

ProHead. User s Guide ProHead User s Guide 2Profoto ProHead Profoto ProHead Thank you for choosing Profoto. Thanks for showing us your confidence by investing in a ProHead unit. For more than four decades we have sought the

More information

Room Sensors. for relative humidity and temperature

Room Sensors. for relative humidity and temperature 1 857 1857P01 Room Sensors for relative humidity and temperature QFA20 Operating voltage AC 24 V or DC 13535 V Signal output DC 010 V for relative humidity Signal output DC 010 V or LG-Ni 1000 or T1 for

More information

Room Sensors. In ventilating and air conditioning plants to acquire relative humidity and temperature in rooms. Humidity measuring range

Room Sensors. In ventilating and air conditioning plants to acquire relative humidity and temperature in rooms. Humidity measuring range 1 857 1857P01 Room Sensors for relative humidity and temperature QFA20 Use Operating voltage AC 24 V or DC 13535 V Signal output DC 010 V for relative humidity Signal output DC 010 V or LG-Ni 1000 or T1

More information

QPM Series Indoor Air Quality Duct Sensors

QPM Series Indoor Air Quality Duct Sensors Document No. CE1N1962 QPM Series Indoor Air Quality Duct Sensors Description The QPM Series Room Carbon Dioxide (CO 2 ) and Air Quality Duct Sensors are designed for applications where precise, stable

More information

RSMFX-2R MULTIFUNCTIONAL

RSMFX-2R MULTIFUNCTIONAL Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND

More information

SCHMIDT Flow Sensor SS 25.60

SCHMIDT Flow Sensor SS 25.60 Product description Product advantages Form 107/06/09/1000/3 Art. No. 511 047.02 A Data subject to change The flow sensor is a mass flow sensor (thermal anemometer), designed for use in oxygen. Due to

More information

QUINT-PS-24DC/24DC/10

QUINT-PS-24DC/24DC/10 QUINT-PS-24/24/10 QUINT - converter, primary switched mode, input: 24 V, output: 24 V /10 A INTERFACE Data Sheet PHOENIX CONTACT - 02/2006 Description The QUINT - converter 24 V/10 A converts the voltage

More information

Tube Facing Tool.

Tube Facing Tool. www.swagelok.com Tube Facing Tool This manual contains important information for the safe and effective operation of the Swagelok TF72 series tube facing tool. Users should read and understand its contents

More information

Global Water Instrumentation, Inc.

Global Water Instrumentation, Inc. Global Water Instrumentation, Inc. 151 Graham Road P.O. Box 9010 College Station, TX 77842-9010 T: 800-876-1172 Int l: (979) 690-5560, F: (979) 690-0440 Barometric Pressure: WE100 Solar Radiation: WE300

More information

Pressure Transmitter SIL

Pressure Transmitter SIL Pressure Transmitter SI Characteristics - TRANSDUCER - Pressure: Range: Output: Accuracy: Temperature of medium: Material enclosure: Pressure connection: Electrical connection: Protection: relative / absolute

More information

Installation guide 971 SmartRadar LTi

Installation guide 971 SmartRadar LTi Installation guide 971 SmartRadar LTi March 2009 Part no. 4416.715 Revision 3 Enraf B.V. P.O. Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100 Fax : +31 15 2701 111 E-mail : enraf-nl@honeywellenraf.nl

More information

Operating Instructions K-POWERgrip EWL Always on the safe site.

Operating Instructions K-POWERgrip EWL Always on the safe site. Operating Instructions K-POWERgrip EWL 4941. Always on the safe site. KaVo Elektrotechnisches Werk GmbH Wangener Straße 78 D-88299 Leutkirch A 1 User information...2 A 1.1 Meaning of the pictograms...2

More information

User guide ProHead Plus

User guide ProHead Plus User guide ProHead Plus For other languages visit: /support ProHead Plus 2 Congratulations on your new Profoto product! Thanks for showing us your confidence by investing in a ProHead unit. For more than

More information

Air Quality Sensor KNX AQS

Air Quality Sensor KNX AQS Air Quality Sensor KNX AQS Installation and Adjustment 1 Content 1. Description... 3 1.0.1. Measurement of carbon dioxide in the air... 3 1.1. Technical specifications... 4 2. Installation and commissioning...

More information

Installation and Operating Instructions Differential pressure transmitter for potentially explosive areas. MG-1000-EEx USAGE STRUCTURE AND DESIGN

Installation and Operating Instructions Differential pressure transmitter for potentially explosive areas. MG-1000-EEx USAGE STRUCTURE AND DESIGN Installation and Operating Instructions Differential pressure transmitter for potentially explosive areas Mimablad: 176GB/1999-10-25 Ersätter: MG-1000-EEx USAGE MG-1000-EEx is suitable for use in measurement

More information

Dawson DSM150. Digital Light Meter User s Manual

Dawson DSM150. Digital Light Meter User s Manual Dawson DSM150 Digital Light Meter User s Manual TABLE OF CONTENTS LIMITED WARRANTY AND LIMITATION OF LIABILITY... 3 Out of Box... Error! Bookmark not defined. Accessories... 4 Safety Information... 6 Certification...

More information

METRISO. Analog Insulation, Low Resistance and Voltage Measurement Instrument /9.14

METRISO. Analog Insulation, Low Resistance and Voltage Measurement Instrument /9.14 3-349-813-3 1/9.14 Insulation measurement per EN 61557-2/VDE 413, part 2 Test voltages: 5 V, 1 V, 25 V, 5 V and 1 V Analog display of measured values and limit values Intelligent filter precise and measurement-dependent

More information

USER'S GUIDE. Vaisala HUMICAP Humidity and Temperature Transmitters HMD70U/Y U303EN11

USER'S GUIDE. Vaisala HUMICAP Humidity and Temperature Transmitters HMD70U/Y U303EN11 USER'S GUIDE Vaisala HUMICAP Humidity and Temperature Transmitters HMD70U/Y U303EN11 PUBLISHED BY Vaisala Oyj Phone (int.): +358 9 8949 1 P.O. Box 26 Fax: +358 9 8949 2227 FIN-00421 Helsinki Finland Visit

More information

ED701 General Industry Pressure Transmitter

ED701 General Industry Pressure Transmitter ED701 General Industry Pressure Transmitter Standard industrial process connections Complete range of electrical connections 4... 20 ma and Voltage outputs Accuracy: 0.1%, 0.2% and 0.4% FS Quick response

More information

LF Conductivity Measuring Probe

LF Conductivity Measuring Probe LF Conductivity Measuring Probe Contents 1 General 1.1 Introduction 1.2 Application range 2 Safety 2.1 Warnings and symbols 3 Transport and storage 4 Application 5 Measuring principle 6 Assembly 7 Construction

More information

SCHMIDT Flow Sensor SS SS FB

SCHMIDT Flow Sensor SS SS FB Product description Flow sensor with integrated microcontroller transducer for the measurement of air-flow velocity and for the determination of the flow rate and flow volume. The aerodynamically styled

More information

SolidFlow 2.0. Solid mass flow measurement. Product Information. SWR engineering Messtechnik GmbH enveatm a trademark of Environnement S.

SolidFlow 2.0. Solid mass flow measurement. Product Information. SWR engineering Messtechnik GmbH enveatm a trademark of Environnement S. EN SolidFlow.0 Product Information Solid mass flow measurement SWR engineering Messtechnik GmbH enveatm a trademark of Environnement S.A Group Use SolidFlow.0 has been specially developed for measuring

More information

PolyGard Digital Transmitter DGC DT-02

PolyGard Digital Transmitter DGC DT-02 PolyGard Digital Transmitter DGC DT-02 Description LON interoperable digital gas transmitter to monitor toxic and combustible gases and vapors in the ambient air. The complete monitoring and alarm tripping

More information

Smart Power Relay E I...

Smart Power Relay E I... Smart Power Relay E-48-8I... Description The Smart Power Relay E-48-8I.- is a remotely controllable electronic load disconnecting relay with three functions in a single unit: l electronic relay l electronic

More information

Sarspec, Lda. - Rua Camilo Castelo Branco, 965 PQ Vila Nova de Gaia Phone:

Sarspec, Lda. - Rua Camilo Castelo Branco, 965 PQ Vila Nova de Gaia Phone: 2 3 IMPORTANT SAFETY NOTE: Before operating this device, please read carefully this User Manual and be familiar with its contents prior to using this equipment. To help avoid potential serious injury to

More information

SI-125 Power Amplifier Manual 6205 Kestrel Road; Mississauga, Ontario; Canada; L5T 2A1 November 2016, Rev 0.5

SI-125 Power Amplifier Manual 6205 Kestrel Road; Mississauga, Ontario; Canada; L5T 2A1 November 2016, Rev 0.5 SI-125 Power Amplifier Manual 6205 Kestrel Road; Mississauga, Ontario; Canada; L5T 2A1 November 2016, Rev 0.5 Phone: (905) 564-0801 Fax: (905) 564-0806 www.telecor.com E:\T2-108\T2-M108-ABC\T2-M108-B.doc/AD

More information

VIESMANN. Installation and service instructions VITOTROL 300 RF. for contractors. Vitotrol 300 RF

VIESMANN. Installation and service instructions VITOTROL 300 RF. for contractors. Vitotrol 300 RF Installation and service instructions for contractors VIESMANN Vitotrol 3 RF Wireless remote control for one, two or three heating circuits For applicability, see the last page VITOTROL 3 RF 4/212 Please

More information

INSTRUCTION MANUAL Vibration Meter

INSTRUCTION MANUAL Vibration Meter INSTRUCTION MANUAL Vibration Meter VM-63A 3-20-41 Higashimotomachi, Kokubunji, Tokyo 185-8533, Japan http://www.rion.co.jp/ Organization of This Manual This manual describes the features and operation

More information

LT3000 ULTRASONIC LEVEL TRANSMITTER

LT3000 ULTRASONIC LEVEL TRANSMITTER LT3000 ULTRASONIC LEVEL TRANSMITTER Owner s Manual Specifications Installation Calibration Troubleshooting Warranty Drawings Distributed By: iprocessmart.com 14262 Doolittle Drive San Leandro, CA 94577

More information

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO E

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO E OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO E Lievers Holland Postbus 103 3640 AC Mijdrecht Tel: +31 (0)297 231900 Fax: +31 (0)297 231909 E mail: info@lieversholland.nl www.lieversholland.nl Operation

More information

High-Voltage Isolation Amplifiers / Shunt Isolators. VariTrans P 29000

High-Voltage Isolation Amplifiers / Shunt Isolators. VariTrans P 29000 High-Voltage Isolation Amplifiers / Shunt Isolators VariTrans P 29000 Compact high-voltage isolators with safe galvanic isolation, VariPower broad-range power supply and genuine calibrated range selection.

More information

Outside Temperature Sensors

Outside Temperature Sensors 1 814 1814P01 Symaro Outside Temperature Sensors QAC31 Active sensors for acquiring the outside temperature Operating voltage AC 24 V or DC 13535 V Signal output DC 010 V or 420 ma Use The QAC31 outside

More information

English. Operating manual. Temperature measuring transducer MU125. Save for later reference. Company / brands of GHM

English. Operating manual. Temperature measuring transducer MU125.  Save for later reference. Company / brands of GHM English Operating manual Temperature measuring transducer MU125 Company / brands of GHM www.ghm-messtechnik.de Save for later reference. Table of contents Page 1. Intended use (areas of application)...

More information

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted Electrical temperature measurement Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted WIKA data sheet TE 60.34 Applications Machine building, plant and vessel construction

More information

Circuit Breaker Finder

Circuit Breaker Finder ECB50-FGIS Circuit Breaker Finder and AC Line Tracer User Manual ECB50-FGIS Circuit Breaker Finder and AC Cable Tracer Contents Safety Information...3 Symbols Used in this Manual...3 Introduction...4 Finding

More information

Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters

Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters ll 2G EEx ia llc T6 As our products are continuously improved, we reserve the right to make any change in the stated specifications

More information

Refer to manual. Failure to read message could result in personal injury or serious damage to the equipment or both.

Refer to manual. Failure to read message could result in personal injury or serious damage to the equipment or both. CERAVAC Transmitter CTR 100 N Short form manual 300544675_002_C0 Part numbers: 230 300V02 230 310V02 230 301V02 230 311V02 230 302V02 230 312V02 230 303V02 230 313V02 230 304V02 230 314V02 230 305V02 230

More information

Rudder or propeller angular position transmitter KINAX WT720

Rudder or propeller angular position transmitter KINAX WT720 Description The is a robust, absolute angular position transmitter, which is particularly suitable for use in marine applications such as the detection of rudder or propeller positions. In contrast to

More information

Room air quality sensors

Room air quality sensors 1 961 QPA10 / QPA20 1961P01 1961P02 QPA20 D Room air quality sensors QPA10.. QPA20.. Maintenance-free sensing element (depending on type) based on optical infrared absorption measurement (NDIR 1) ) Or

More information

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO-E

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO-E OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO-E Lievers Holland PO Box 103 3640 AC Mijdrecht Tel: +31 (0)297-231900 Fax: +31 (0)297-231909 E-mail: info@lieversholland.nl - www.lieversholland.nl CONTENT

More information

Wind Transmitter compact xx

Wind Transmitter compact xx THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA Instruction for Use 021075/08/11 Wind Transmitter compact 4.3519.xx.140... 961 ADOLF THIES GmbH & Co. KG Hauptstraße 76

More information

QFM21... Duct sensors. Symaro. for relative humidity and temperature

QFM21... Duct sensors. Symaro. for relative humidity and temperature 1 864 1864P01 Symaro Duct sensors for relative humidity and temperature QFM21... Operating voltage AC 24 V / DC 13.5...35 V Signal output DC 0...10 V / 4 20 ma for relative humidity Signal output DC 0...10

More information

MODEL AT-10 ANALOG TRANSMITTER

MODEL AT-10 ANALOG TRANSMITTER MODEL AT-10 ANALOG TRANSMITTER INSTALLATION & OPERATING MANUAL Industrial Weighing Systems 9 Richmond Street Picton, Ontario K0K 2T0 Phone: 613-921-0397 Fax: 613-476-5293 Web: www.iwsystems.ca info@iwsystems.ca

More information

Wind Transmitter compact xx

Wind Transmitter compact xx THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA Instruction for Use 021720/03/14 Wind Transmitter compact 4.3519.xx.140... 961 Contents 1 Models... 3 2 Application...

More information

HLV Instruction & Operations Manual

HLV Instruction & Operations Manual HLV-2000 Instruction & Operations Manual 1 Content Chapter page 1. Certificate of conformity 3 2. Introduction 4 3. Safety instructions 5 4. Electrical connections 6 5. Warranty 7 6. Front panel operation

More information

Operating Instructions TIC 251/252. Profibus DP-Gateway PG 0009 BE/E (0903)

Operating Instructions TIC 251/252. Profibus DP-Gateway PG 0009 BE/E (0903) Operating Instructions TIC 251/252 Profibus DP-Gateway PG 0009 BE/E (0903) Contents Page 1. Safety Precautions... 3 2. Understanding The TIC 251/252... 4 2.1. For Your Orientation... 4 Delivery Consignment...

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet GR24A--R Communicative Retrofit rotary actuator for rotary valves and butterfly valves Nominal torque 40 Nm Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Position

More information

Receiver Type /Version Factory No. Frequency. Transmitter Type /Version Factory No. Frequency

Receiver Type /Version Factory No. Frequency. Transmitter Type /Version Factory No. Frequency Receiver Type /Version Factory No. Frequency Transmitter Type /Version Factory No. Frequency 1. STANDARD SPECIFICATION Portable transmitter. Receiver with integrated mounting holes. Multi-pin connecting

More information

Technical data sheet TDS0037

Technical data sheet TDS0037 Technical data sheet TDS0037 PREMIER CARBON DIOXIDE SENSOR NON-CERTIFIED VERSION TYPE MSH-P-CO2/NC Patent Numbers Great Britain GB 2 401 432 & GB 2 403 291 Europe EP 1544603 & EP 1818667-Pending France

More information

PREMIER PLATINUM INFRARED GAS SENSOR

PREMIER PLATINUM INFRARED GAS SENSOR PREMIER PLATINUM INFRARED GAS SENSOR LOW POWER VERSION HIGH RANGE CARBON DIOXIDE SENSOR Non Exd Certified *** Available in EN50271 / SIL1 Certified versions *** Technical data sheet TDS0154 SIL1 Non -

More information

CO2 OR HYDROCARBONS INFRARED SENSOR WITH INTEGRATED TRANSMITTER

CO2 OR HYDROCARBONS INFRARED SENSOR WITH INTEGRATED TRANSMITTER 1. FEATURES Analogue (voltage or dynamic pellistor) standard output Incorporated signal linearisation and temperature compensation suited for manufacturers without any specialist knowledge in IR technology

More information

HLV Instruction & Operations Manual. Content

HLV Instruction & Operations Manual. Content HLV-800-3 Instruction & Operations Manual Content 1 Chapter page 1. Certificate of conformity 3 2. Introduction 4 3. Safety instructions 5 4. Electrical connections 6 5. Warranty 7 6. Front panel operation

More information

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5.

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5. Ex i Isolators Temperature Transmitter with Output 0/4... 20 ma, without Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe

More information

MIT415 Insulation tester

MIT415 Insulation tester MIT415 Insulation tester General features o 10V & 100V ESD testing o 25V, 50V, 250V & 500V additional ranges o Insulation testing up to 50Gohms (500V) o Continuity testing at 200mA or 20mA from 0.01ohms

More information

Type EXT with cable, probe sold

Type EXT with cable, probe sold standard signal FF-GLT-Series Description Type INT for duct mounting, probe installed Type EXT with cable, probe sold Type AF for wall mounting, probe sold Characteristic features Standard signal 0...

More information

Wind Transmitter First Class

Wind Transmitter First Class THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA - THE WORLD OF WEATHER DATA Instruction for Use 021310/07/06 Wind Transmitter First Class 4.3350.00.000 4.3350.10.000 ADOLF THIES GmbH & Co. KG Hauptstraße

More information