R 181 Replacement of the CIN 81

Size: px
Start display at page:

Download "R 181 Replacement of the CIN 81"

Transcription

1 898 en / b ants This manual is to be given to the end user d on Roue polaire Main Stator Borne de so W V Y X Z C.T T.I. P Main output term R 8 Installation and maintenance

2 898 en / b We wish to draw your attention to the contents of this maintenance manual. By following certain important points during installation, use and servicing of your alternator, you can look forward to many years of trouble-free operation. SAFETY MEASRES Before using your machine for the first time, it is important to read the whole of this installation and maintenance manual. All necessary operations and interventions on this machine must be performed by a qualified technician. Our technical support service will be pleased to provide any additional information you may require. The various operations described in this manual are accompanied by recommendations or symbols to alert the user to the potential risk of accidents. It is vital that you understand and take notice of the various warning symbols used. The R 8 is an AVR designed for ARES or ARCM type compound excitation alternators. The R 8 is a transistor-controlled AVR. The measured voltage is filtered and rectified. It is not affected by voltage variations caused by non-linear loads. It is totally sealed with an elastomer which protects it from environmental stresses. R 8 AVR function: - AVR accuracy +/- % - nderspeed protection - LAM load shedding system - Parallel operation between alternators by voltage quadrature droop - External potentiometer connection wires, for voltage adjustment (70 ohms: voltage range +/- % - W, or 000 ohms: voltage range +/- 0% - W) - Wires for CT parallel operation output A -. VA - 0 V or 00 V power supply - VA voltage sensing isolated via transformer WARNING Warning symbol for an operation capable of damaging or destroying the machine or surrounding equipment. Warning symbol for general danger to personnel. Warning symbol for electrical danger to personnel. Note: LEROY-SOMER reserves the right to modify the characteristics of its products at any time in order to incorporate the latest technological developments. The information contained in this document may therefore be changed without notice.

3 898 en / b CONNECTION OF THE V S CT S W or Compound eld Y u v n w + E+ A+ 7- E- A- Regulateur / A.V.R. purple P P yellow white blue black P green P P P brown red GB 70 white white External potentiometer 70 - W. If not used, leave the bridge closed. GB 0970 P : Statisme / Quad. droop P : Tension / Voltage P : Fréquence / Frequency P : Stabilité / Stability P : Limitation d'excitation / Excitation limit P : Statisme interne / Internal droop Wire E- - Measure the derivative current with ammeter - 0. A at no load A at / load seeing instructions page COMPOND secondary

4 898 en / b PROCEDRE for REPLACING CIN 8 on ARES alternators - Disconnect the wires from the CIN 8 from the connecting block. - Remove the CIN 8 and its wired connector. - Put the R 8 in position (same fastening). Remove the bridge between + and E+ - Disconnect the compound + wire from the + terminal block on the rectifier bridge and connect it to the free + terminal on the terminal block with the white wire from the R 8. - Connect: The blue wire to the - terminal on the rectifier bridge The yellow wire to the + terminal on the rectifier bridge The red wire to terminal on the terminal block The brown wire to terminal Y on the terminal block The purple wire to terminal Δ on the terminal block The black wire to terminal 9 on the terminal block The green wire to terminal 0 on the terminal block Adjustment of the R 8 on ARES alternators - Attach a A rating ammeter to the -E wire. - ~ 0. A should be obtained at no load. If it is not, reduce or increase the air gap of the compound and adjust the output voltage via potentiometer P on the R 8. - On load, ~ 0.8 A should be obtained at / load. If it is not, perform the following: If less than 0.8A, reduce the % at the compound coils If more than 0.8A, increase the % at the compound coils - Adjust the on-load voltage via P. In both cases, the no-load air gap will have to be re-adjusted and the output voltage adjusted via P on the R 8. CATION : In case of wrong compound adjustment, destruction risk of the automatic voltage regulator. ALTERNATOR REVOLVING DIODES EXCITER armature to main terminals stator (u) auxiliary () (v) (V) (W) (w) compound regulation COMPONDING TRANSFORMER W Z VY T.I. X S (0) (9) S A (t) a Y V w + E+ A+ 7- E- A- 7 REGLATOR rectifier bridge rectifier bridge Rhr Internal "MANAL" adjustment rheostat + - W V to main terminals

5 898 en / b PROCEDRE for REPLACING the CIN 8 on ARCM alternators - Disconnect the wires from the CIN 8 from the connecting block. - Remove the CIN 8 and its wired connector. - Put the R 8 in position (same fastening). - Remove the wire connecting terminal E+ on the terminal block to the + on the rectifier bridge. - Connect: The blue wire to terminal E- on the terminal block The white wire to terminal E+ on the terminal block The yellow wire to the + terminal on the rectifier bridge The green wire to terminal 9 on the terminal block The black wire to terminal 0 on the terminal block The red wire to terminal on the terminal block The brown wire to terminal Y on the terminal block The purple wire to terminal Δ on the terminal block Adjustment - Attach a A rating ammeter to the E- wire. ~ 0. A at no load and ~ 0.8 A on-load (/) should be obtained. At no load: - Adjust the output voltage using potentiometer P on the. - Adjust using the "PV" or "RV" potentiometers to obtain 0. A. On-load (/): - Adjust the output voltage via potentiometer P on the. ~ 0.8 A should be obtained. If it is not, the % of the compound must be modified. - To increase the current, reduce the %. - To reduce the current, increase the %. After modifying the on-load percentage, a further no-load test must be performed. Excitatrice Exciter Alternateurs Alternators Redresseurs tournants Revolving rectifiers Induit Armature Roue polaire Main Stator 7 Regulateur-Regulator CIN8I Inducteur compound Compound Inducteur de regulation Regulation C.T T.I. E+ E Y n au v Man W u P S S P Bornes de sortie W V Y X Z Main output terminals Autotransformateur Autotransformer (if any) A Rv 7 Pc Pv Pont redresseur Rectifier bridge 7 7 Reglages du compound Compound system adjusments

6 898 en / b CONNECTION OF ARCM to Excitatrice Exciter Alternateurs Alternators Redresseurs tournants Revolving rectifiers Induit Armature Inducteur compound Compound Inducteur de regulation Regulation Roue polaire Main Stator Bornes de sortie W V Y X Z E+ E Y n au v Man W u C.T T.I. P S S P Main output terminals Rv 7 Pc Pv 7 7 Regulateur / A.V.R. Jaune/yellow Blanc/white Bleu/blue Noir/black Vert/green Rouge/red P Violet/purple Marron/brown blanc/white blanc/white Potentiomètre extérieur 70 Ω - W. External potentiometer 70 Ω - W. Si non utilisé, laisser le pont fermé. If not used, leave the bridge closed P P P P P P : Statisme / Quad. droop P : Tension / Voltage P : Fréquence / Frequency P : Stabilité / Stability P : Limitation d'excitation / Excitation limit P : Statisme interne / Internal droop

7 898 en / b 7

8 MOTERS LEROY-SOMER 0 ANGOLÊME CEDEX - FRANCE RCS ANGOLÊME S.A. au capital de

R438 A.V.R. Installation and maintenance. This manual is to be given to. the end user CALL US TODAY POWER-58. SHOP ONLINE

R438 A.V.R. Installation and maintenance. This manual is to be given to. the end user CALL US TODAY POWER-58. SHOP ONLINE T1 T7 T2 T8 This manual is to be given to the end user T4 T10 140 mm T5 T11 X2 Z1X1 Z2 E+ E- 0V 110 220 380 200 mm z P1 ST9 AREP PMG This manual concerns the alternator which you have just purchased. We

More information

R448 & R448 V50 A.V.R.

R448 & R448 V50 A.V.R. Armature + 6- This manual is to be given to the end user F1 ST5 Field Slow fuse 250V 10 A with LAM without LAM 10 Yellow 11 Red 12 Black 9 Green X2 Z1 X1 Z2 E+ E- 0V 110 22 ST3 requency 50Hz 60Hz LAM 13

More information

r 450 Installation and maintenance This manual is to be given to the end user R 450 VOLT. STAB. I EXC STAT. AREP PMG FUSIBLES / FUSES

r 450 Installation and maintenance This manual is to be given to the end user R 450 VOLT. STAB. I EXC STAT. AREP PMG FUSIBLES / FUSES 8 7 9 6 5 4 C 45 en -. / a R 45 DETECT. PH PH. SENSING 5 Hz EXT FREQ 6 Hz SETTING This manual is to be given to the end user VOLT. STAB. I EXC FUSIBLES / FUSES EXT.FREQ. SET. ON ONLY FOR SPECIAL CONFIG.

More information

R 450. AVRs. Installation and maintenance. This manual is to be given to. the end user R 450 VOLT. STAB. I EXC STAT. LEDS PMG

R 450. AVRs. Installation and maintenance. This manual is to be given to. the end user R 450 VOLT. STAB. I EXC STAT. LEDS PMG 6 5 4 7 8 9 C US 45 en -. / e 5 Hz EXT FREQ 6 Hz SETTING This manual is to be given to the end user VOLT. STAB. I EXC FUSIBLES / FUSES EXT.FREQ. SET. ON ONLY FOR SPECIAL CONFIG. KNEE 5Hz 65Hz 6Hz PHASE

More information

R448 & R448 V50 A.V.R. Installation and maintenance R 448 ST5 ST3 ST10. Armature + 6- Field X2 Z1 X1 Z2 E+ E- 0V Slow fuse 250V 10 A

R448 & R448 V50 A.V.R. Installation and maintenance R 448 ST5 ST3 ST10. Armature + 6- Field X2 Z1 X1 Z2 E+ E- 0V Slow fuse 250V 10 A Armature + 6- Field Thismanualistobegivento theenduser F1 ST5 Slow fuse 250V 10 A with LAM without LAM 10 Yellow 11 Red 12 Black 9 Green X2 Z1 X1 Z2 E+ E- 0V 110 22 ST3 requency 50Hz 60Hz ST10 R 448 This

More information

VOLTAGE REGULATOR R 449. Installation and maintenance. This manual must be sent to the end user R 449 X2 Z1 X1 Z2 E+ E- (12V - 10A)

VOLTAGE REGULATOR R 449. Installation and maintenance. This manual must be sent to the end user R 449 X2 Z1 X1 Z2 E+ E- (12V - 10A) This manual must be sent to the end user X2 Z1 X1 Z2 E+ E- J1 t (12V - 10A) ~ 10 ohms Exciter field + - Isolated DC power supply Installation and maintenance WARNING TO AVOID HARM EITHER TO PEOPLE OR TO

More information

R438 A.V.R. R438. Installation and maintenance X2 Z1 X1 Z2 E+ E- 0V REQUEST A QUOTE

R438 A.V.R. R438. Installation and maintenance X2 Z1 X1 Z2 E+ E- 0V REQUEST A QUOTE X2 Z1 X1 Z2 E+ E- 0V 110 220 380 This manual concerns the alternator which you have just purchased. We wish to draw your attention to the contents of this maintenance manual. SAFETY MEASURES Before using

More information

R / 8000 RAPIDE FAST RAPIDE 3 PAHASES SENSING SHUNT / AREP SERIES PMG NORMAL NORMAL NORMAL NORMAL 5000 / 6000 LSA 46 / 47

R / 8000 RAPIDE FAST RAPIDE 3 PAHASES SENSING SHUNT / AREP SERIES PMG NORMAL NORMAL NORMAL NORMAL 5000 / 6000 LSA 46 / 47 8 7 9 6 5 4 5 Hz EXT FREQ 6 Hz SETTING VOLT. STAB. I EXC EXT.FREQ. SET. ON ONLY FOR SPECIAL CONFIG. KNEE 65Hz 5Hz 6Hz PHASE SENSING MODE MODE MODE MODE LSA 49 / 5 LSA 46 / 47 7 / 8 5 / 6 LSA 49 / 5 7 /

More information

R241 A. 400 Hz A.V.R. Installation and maintenance. This manual is to be given to. the end user C B. Air craft p

R241 A. 400 Hz A.V.R. Installation and maintenance. This manual is to be given to. the end user C B. Air craft p C1 C B Air craft p This manual is to be given to the end user F 0,1A R3 0,1A A 0 F = 6.3A fast - 250 R1 = 100 Ω - R2 = 10 Ω - 1 R3 = 1 KΩ - 2 x 1 mm 2 F R3 Détail This manual concerns the alternator A.V.R.

More information

R450 T DETECT. 3 PH 3 PH. SENSING 7000 / 8000 RAPIDE FAST RAPIDE VOLTAGE 80V ~ 320V SHUNT / AREP SERIES PMG NORMAL NORMAL NORMAL NORMAL 5000 / 6000

R450 T DETECT. 3 PH 3 PH. SENSING 7000 / 8000 RAPIDE FAST RAPIDE VOLTAGE 80V ~ 320V SHUNT / AREP SERIES PMG NORMAL NORMAL NORMAL NORMAL 5000 / 6000 8 9 R T DETECT. PH PH. SENSING Hz EXT FREQ Hz SETTING VOLT. STAB. I EXC EXT.FREQ. SET. ON ONLY FOR SPECIAL CONFIG. KNEE Hz Hz MODE MODE MODE MODE Hz VOLTAGE V ~ V LSA 9 / LSA / / 8 / LSA 9 / LSA / / 8

More information

R1 Q2 Q1 F2 F1 N A1 A2 FUSE V AC S UF OE SL UF OE R150 R150. AVRs. Installation and maintenance

R1 Q2 Q1 F2 F1 N A1 A2 FUSE V AC S UF OE SL UF OE R150 R150. AVRs. Installation and maintenance Droop R2 R1 Q2 Q1 F2 F1 N W V A1 A2 FUSE V AC S UF OE SL UF OE 50 Hz 60 Hz This manual concerns the alternator AVR which you have just purchased. We wish to draw your attention to the contents of this

More information

R180. AVRs. Installation and maintenance

R180. AVRs. Installation and maintenance This manual concerns the alternator AVR which you have just purchased. We wish to draw your attention to the contents of this maintenance manual. SAFETY MEASURES Before using your machine for the first

More information

A.V.R. R250. Installation and maintenance R250 0V E+ E- VOLT STAB FREQ. & L.A.M. CONFIG. REQUEST A QUOTE

A.V.R. R250. Installation and maintenance R250 0V E+ E- VOLT STAB FREQ. & L.A.M. CONFIG. REQUEST A QUOTE 110 0V E+ E- VOLT STAB KNEE 47.5Hz OFF 9 SPECIAL 8 KNEE 65Hz 7 OFF KNEE 6 57Hz OFF 7 8 50Hz o 9 0 5 6 1 2 3 4 OFF 1 13% 2 25% 3 OFF 4 13% 5 25% 60Hz FREQ. & L.A.M. CONFIG. This manual concerns the alternator

More information

R1 Q2 Q1 F2 F1 N A1 A2 FUSE V AC S UF OE SL UF OE R150 A.V.R. R150. Installation and maintenance

R1 Q2 Q1 F2 F1 N A1 A2 FUSE V AC S UF OE SL UF OE R150 A.V.R. R150. Installation and maintenance Droop R2 R1 Q2 Q1 F2 F1 N W V A1 A2 FUSE V AC S UF OE SL UF OE 50 Hz 60 Hz This manual concerns the alternator which you have just purchased. We wish to draw your attention to the contents of this maintenance

More information

TAL 044 Low Voltage Alternator - 4 pole

TAL 044 Low Voltage Alternator - 4 pole TAL 044 Low Voltage Alternator - 4 pole Three-phase 70 to 65 kva - 50 Hz / 88 to 206 kva - 60 Hz Dedicated single-phase 57 to 82 kva - 50 Hz / 80 to 25 kva - 60 Hz Electrical and mechanical data TAL 044

More information

TAL 049 Low Voltage Alternator - 4 pole

TAL 049 Low Voltage Alternator - 4 pole TAL 049 Low Voltage Alternator - 4 pole 730 to 1000 kva - 50 Hz / 915 to 1250 kva - 60 Hz Electrical and mechanical data Adapted to needs The TAL alternator range is designed to meet the needs of general

More information

TAL 047 Low Voltage Alternator - 4 pole

TAL 047 Low Voltage Alternator - 4 pole TAL 047 Low Voltage Alternator - 4 pole 4 to 660 kva - 50 Hz / 5 to 825 kva - 60 Hz Electrical and mechanical data Adapted to needs The TAL alternator range is designed to meet the needs of general applications

More information

D510 c Automatic Voltage Regulators (AVRs)

D510 c Automatic Voltage Regulators (AVRs) X1 Z1 X2 Z2 B+ B- U alimentations V = = W This manual is to be given to the end user IU IV IW L1 PID µc µp transceiver L2 = DSP This manual concerns the alternator AVR which you have just purchased. We

More information

Using the VR448 in place of the Marathon DVR 2000

Using the VR448 in place of the Marathon DVR 2000 Using the 448 in place of the Marathon D 2000 D2000E (digital A) provides 7.5A 150VDC Max output short time in compareson to model EA448 (Analog A) thats provide 10 A 160VDC Max output short time Both

More information

Low Voltage Alternators

Low Voltage Alternators Low Voltage Alternators Excitation and regulation systems SHUNT - PMG - AREP Low Volta SHUNT excitation for basic applications - The AVR power supply voltage is shunted on the alternator output terminals.

More information

LSA Pole. R 726 Mains paralleling

LSA Pole. R 726 Mains paralleling 498 en-.27 / a Alternators LSA.2-4 Pole Electrical and mechanical data LSA.2-4 Pole SPECIALLY ADAPTED FOR APPLICATIONS The LSA.2 alternator is designed to be suitable for typical generator set applications,

More information

LSA 43.2/ ACT/R - 4P ALTERNATORS

LSA 43.2/ ACT/R - 4P ALTERNATORS This manual is to be given to the end user 323 32 322 325 320 33 30 15 37 28 1 33 Installation and maintenance This manual concerns the alternator which you have just purchased. The latest addition to

More information

V S UF OPEN IN 60Hz OE UF SL R120 V N1 U N F1 F2 A.V.R. R120. Installation and maintenance

V S UF OPEN IN 60Hz OE UF SL R120 V N1 U N F1 F2 A.V.R. R120. Installation and maintenance V S UF OPEN IN 60Hz OE UF SL V N1 U N F1 F2 This manual concerns the alternator which you have just purchased. We wish to draw your attention to the contents of this maintenance manual. SAFETY MEASURES

More information

Low Voltage alternators - 4 pole LSA 47.2

Low Voltage alternators - 4 pole LSA 47.2 Low Voltage alternators - 4 pole 36 to 6 kva - Hz / 46 to 7 kva - 6 Hz Electrical and mechanical data 3782 en - 214.1 / h 36 to 6 kva - Hz / 46 to 7 kva - 6 Hz SPECIALLY ADAPTED TO APPLICATIONS The alternator

More information

Rotek AS440 compatible VOLTAGE REGULATOR (AVR)

Rotek AS440 compatible VOLTAGE REGULATOR (AVR) Rotek AS440 compatible VOLTAGE REGULATOR (AVR) SPECIFICATION INSTALLATION AND ADJUSTMENTS General description Technical specification AS440 is a half wave phase controlled thyristor type AVR and forms

More information

GX 340 SERIES (AUTOMATIC VOLTAGE REGULATOR)

GX 340 SERIES (AUTOMATIC VOLTAGE REGULATOR) GX 340 SERIES (AUTOMATIC VOLTAGE REGULATOR) Email Address: info@powersystems.com.au Web Page: http://www.powersystems.com.au This AVR will replace the following Stamford Part Nos. And many more 350 28700

More information

SPECIFICATION, CONTROLS AND ACCESSORIES

SPECIFICATION, CONTROLS AND ACCESSORIES AS440 Automatic Voltage Regulator (AVR) SPECIFICATION, CONTROLS AND ACCESSORIES English Original Instructions A043Y697 (Issue 2) Table of Contents 1. DESCRIPTION... 1 2. SPECIFICATION... 3 3. CONTROLS...

More information

LSA R & LSA H 49.1 Low Voltage Alternators - 4 pole

LSA R & LSA H 49.1 Low Voltage Alternators - 4 pole LSA R & LSA H 49.1 Low Voltage Alternators - 4 pole 30 to 30 kva - 0 Hz / 420 to 63 kva - 60 Hz Electrical and mechanical data Adapted to applications LSA R and LSA H alternators are enclosed alternators

More information

D510 C A.V.R. Installation and maintenance D 510C W V U X2 Z1 X1 Z2 F+ F- + - L1 L2 U V W. Volt. Exc. Fault. Manu U = U. Power USB +10V - A 1 - A 2 -

D510 C A.V.R. Installation and maintenance D 510C W V U X2 Z1 X1 Z2 F+ F- + - L1 L2 U V W. Volt. Exc. Fault. Manu U = U. Power USB +10V - A 1 - A 2 - D 510C Hz Volt Exc. Manu PF U = U Power USB +10V - A 1 - A 2-0V - A01-0V - D 1 - D 2-0V - D01 - AL.1 - AL.2 - X2 Z1 X1 Z2 F+ F- + - L1 L2 U V W W V U This manual concerns the alternator which you have

More information

/ a. This manual is to be given to the end user. nxs/m. Nh6 OXZ. Pjl Servo gearboxes. Installation and maintenance

/ a. This manual is to be given to the end user. nxs/m. Nh6 OXZ. Pjl Servo gearboxes. Installation and maintenance P Nh6 D H en 36 E W R RU This manual is to be given to the end user OXZ EX EY T nxs/m GA AD F a HB Installation and maintenance LEROY-SOMER INSTALLATION AND MAINTENANCE NOTE - CAUTION - CONTENTS NOTE LEROY-SOMER

More information

X1 Z1 X2 Z2 B+ B- V = IV USB IW PID CAN-H CAN-L PT100/CTP DSP PT100 PT100 A.V.R. AI 1 AI 2 DI1 DI2 D510 C. Installation and maintenance

X1 Z1 X2 Z2 B+ B- V = IV USB IW PID CAN-H CAN-L PT100/CTP DSP PT100 PT100 A.V.R. AI 1 AI 2 DI1 DI2 D510 C. Installation and maintenance X1 Z1 X2 Z2 B+ B- U F+ V = = F- W IU IV µp USB IW PID CAN-H L1 µc CAN-L L2 = DSP PT100/CTP PT100 PT100 AI 1 AI 2 DI1 DI2 This manual concerns the alternator which you have just purchased. We wish to draw

More information

M40FA640A/A - Mark I. User Manual SIN.NT Automatic Voltage Regulator for Three-phase Synchronous Generators. (Issued: 04.

M40FA640A/A - Mark I. User Manual SIN.NT Automatic Voltage Regulator for Three-phase Synchronous Generators. (Issued: 04. M40FA640A/A - Mark I User Manual Automatic Voltage Regulator for Three-phase Synchronous Generators (Issued: 04.2010) SIN.NT.015.6 Instruction Manual Installation Operation Maintenance MARELLI AVR M40FA640A

More information

SPECIFICATION, CONTROLS AND ACCESSORIES

SPECIFICATION, CONTROLS AND ACCESSORIES AS540 Automatic Voltage Regulator (AVR) SPECIFICATION, CONTROLS AND ACCESSORIES English Original Instructions A054N491 (Issue 1) Table of Contents 1. DESCRIPTION... 1 2. SPECIFICATION... 3 3. CONTROLS...

More information

AS440 AUTOMATIC VOLTAGE REGULATOR (AVR)

AS440 AUTOMATIC VOLTAGE REGULATOR (AVR) AS440 AUTOMATIC VOLTAGE REGULATOR (AVR) SPECIFICATION INSTALLATION AND ADJUSTMENTS General description Technical specification AS440 is a half wave phase controlled thyristor type AVR and forms part of

More information

Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302

Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302 Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302 Direct connection up to 65 A (WSx10x) Connection with current transformer (WSx30x) Industrial or meters

More information

Trouble Shooting MagnaPLUS / Mariner / Harsh Duty

Trouble Shooting MagnaPLUS / Mariner / Harsh Duty Trouble Shooting MagnaPLUS / Mariner / Harsh Duty MagnaPLUS models are 12 lead, re-connectable, brushless, AVR regulated generators. Mariner and Harsh Duty models are electrically identical with harsh

More information

MRG 96RM-E Flex RCM Mobile universal measurement device Supplementary description to the operation manual UMG 96RM-E

MRG 96RM-E Flex RCM Mobile universal measurement device Supplementary description to the operation manual UMG 96RM-E Doc. no. 2.040.127.0.b Subject to technical changes. www.janitza.com Mobile universal measurement device MRG 96RM-E Flex RCM Supplementary description to the operation manual UMG 96RM-E Janitza electronics

More information

Users guide and maintenance manual. Leroy Somer LSA POLE Alternators SHUNT - AREP - PMG

Users guide and maintenance manual. Leroy Somer LSA POLE Alternators SHUNT - AREP - PMG Users guide and maintenance manual Leroy Somer LSA 46.2 4 POLE Alternators SHUNT - AREP - PMG Réf. constructeur : 3856 en 04.2004 / a Réf. GPAO : 33522061001 ind1 466 37 This manual is to be given to the

More information

I P. /dt. di p V S+ Applications. Standards. 1) IEC ed1.0: 2007; IEC : ed1.0: 2012

I P. /dt. di p V S+ Applications. Standards. 1) IEC ed1.0: 2007; IEC : ed1.0: 2012 Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and the secondary

More information

MRG 512-PRO PQ Flex Mobile universal measurement device Supplementary description to the operation manual UMG 512-PRO

MRG 512-PRO PQ Flex Mobile universal measurement device Supplementary description to the operation manual UMG 512-PRO Doc. no. 2.054.018.2 Subject to technical changes. www.janitza.com Mobile universal measurement device MRG 512-PRO PQ Flex Supplementary description to the operation manual UMG 512-PRO Janitza electronics

More information

McPherson Voltage Regulators 4501 NW 27 Ave Miami FL

McPherson Voltage Regulators 4501 NW 27 Ave Miami FL McPherson Voltage Regulators 4501 NW 27 Ave Miami FL 33142 305-634-1511 To avoid of possible personal injury or equipment damage read and understand this manual before installation. (A.V.R) 208 / 380 /

More information

SPECIFICATION, CONTROLS AND ACCESSORIES

SPECIFICATION, CONTROLS AND ACCESSORIES MX341 Automatic Voltage Regulator (AVR) SPECIFICATION, CONTROLS AND ACCESSORIES English Original Instructions A043Y699 (Issue 2) Table of Contents 1. DESCRIPTION... 1 2. SPECIFICATION... 3 3. CONTROLS...

More information

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL 1 Contents 1. Application... 5 2. meter set... 6 3. BASIC REQUIREMENTS, OPERATIONAL SAFETy... 6 4. installation... 10 4.1. Mounting... 10 4.2. External

More information

1217 AUDIOPHILE AMPLIFIER POWER SUPPLIER ±24V to ± 80V, 5-20A

1217 AUDIOPHILE AMPLIFIER POWER SUPPLIER ±24V to ± 80V, 5-20A Description Quasar kit No.1217 is part of a new line of constructions which combined form a full stereo system. The line consists of the following KITS Quasar kit No.1214 6 inputs stereo selector Quasar

More information

This manual is to be given to the end user Installation and maintenance

This manual is to be given to the end user Installation and maintenance 3831-03.2005 / a 37 en This manual is to be given to the end user HF HU DH7 T. Nj7 IE E XF XF BF 4 x S3 D1 D2 4 x S3 RU x R XA XB XA XB VA VB V HG R1 nxs2/m2 VF VU RB 4 x S4 Installation and maintenance

More information

PARTNER ALTERNATORS LSA 40-4 Pole

PARTNER ALTERNATORS LSA 40-4 Pole 23 kva - 50 Hz 12,5 28 kva - 60 Hz 4250 en - 2011.03 / c PARTNER ALTERNATORS LSA 40-4 Pole Electrical and mechanical data SPECIALLY ADAPTED TO APPLICATIONS The LSA 40 alternator is designed to be suitable

More information

Low Voltage alternators - 4 pole LSA 46.2

Low Voltage alternators - 4 pole LSA 46.2 Low Voltage alternators - 4 pole 18 to 31 kva - Hz / 228 to 381 kva - 6 Hz Electrical and mechanical data 379 en - 212.11 /h 1-8-POWER-8 18 to 31 kva - Hz / 228 to 381 kva - 6 Hz SPECIALLY ADAPTED TO APPLICATIONS

More information

I Pr I P I OUT R L. Applications. Standards

I Pr I P I OUT R L. Applications. Standards Ref: ATO-XXX-B225-D10 I Pr = 10, 15, 16, 20, 30, 32, 50, 60, 63, 75 A ATO series is a split core current transformer for the electronic measurement of AC waveform current with galvanic separation between

More information

ADVR-053. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

ADVR-053. Hybrid Universal Analog Digital Voltage Regulator Operation Manual ADVR-053 Hybrid Universal Analog Digital Voltage Regulator Operation Manual Self Excited 5 Amp Analog/Digital Voltage Regulator For shunt and auxiliary windings generators With over-excitation and lost

More information

15P0161B1 - DCREG for Applications to Electromagnets - SW Rev. D3.09 R.03 - Updated 01/04/04

15P0161B1 - DCREG for Applications to Electromagnets - SW Rev. D3.09 R.03 - Updated 01/04/04 POWER CONNECTIONS AND DCREG PROTECTING DEVICES DCREG thyristor converter can be used to power very inductive loads, such as electromagnets. Applications problems due to this type of load that can be compared

More information

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability

More information

ELECTRONIC ROTARY GEAR MOTOR SERIES SED (AR2...SE )

ELECTRONIC ROTARY GEAR MOTOR SERIES SED (AR2...SE ) ELECTRIC ROTARY GEAR MOTOR SERIES SED (AR2...SE ) INSTALLATI AND OPERATING INSTRUCTIS 1 GENERAL FEATURES 2 2 TECHNICAL DATA 3 3 INSTALLATI 3 ELECTRIC CNECTIS 5 CALIBRATI 5 5.1 ENDSWITCHES 5 5.2 AUXILIARY

More information

Apprentice Electrical Technician Test (ETT) Preparation Guide

Apprentice Electrical Technician Test (ETT) Preparation Guide Apprentice Electrical Technician Test (ETT) Preparation Guide APPRENTICE ELECTRICAL TECHNICIAN TEST (ETT) About the Test There are 40 questions with a maximum time limit of three hours. This is a closed

More information

AGN 124 AVR Power Supplies

AGN 124 AVR Power Supplies Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 124 AVR Power Supplies DESCRIPTION The simplest way to provide a power supply for an AVR is to take power directly

More information

M16FA655A - Mark V. User Manual SIN.NT Automatic Voltage Regulator for Three-phase Synchronous Generators

M16FA655A - Mark V. User Manual SIN.NT Automatic Voltage Regulator for Three-phase Synchronous Generators M16FA655A - Mark V User Manual Automatic Voltage Regulator for Three-phase Synchronous Generators SIN.NT.002.5 Instruction Manual Installation Operation Maintenance MARELLI AVR M16FA655A hanada technolgoy

More information

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017 Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175, ART-B22-D300 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and

More information

Electrodynamic voltage stabilizer Series STC-T three phase Operating instruction manual

Electrodynamic voltage stabilizer Series STC-T three phase Operating instruction manual Electrodynamic voltage stabilizer Series STC-T three phase Operating instruction manual 1 Dear Sirs, We invite you to read the technical manual that will help you to learn all the necessary elements for

More information

POWER SUPPLIES SPS1000 SERIES CIRCUIT DESCRIPTION AND OPERATING MANUAL

POWER SUPPLIES SPS1000 SERIES CIRCUIT DESCRIPTION AND OPERATING MANUAL POWER SUPPLIES SPS1000 SERIES CIRCUIT DESCRIPTION AND OPERATING MANUAL CIRCUIT DESCRIPTION Power Supplies SPS 1000 series are based on the primary switched AC/DC converters topology. Power supplies of

More information

AGN 124 AVR Power Supplies

AGN 124 AVR Power Supplies Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 124 AVR Power Supplies DESCRIPTION The simplest way to provide a power supply for an AVR is to take power directly

More information

Basic Electrical Training

Basic Electrical Training Basic Electrical Training Electricians Tools Explain how various hand tools are used by an electrician Discuss the safe use of hand tools and power tools Perform basic calculations and measurement conversions

More information

Electrical Machines (EE-343) For TE (ELECTRICAL)

Electrical Machines (EE-343) For TE (ELECTRICAL) PRACTICALWORKBOOK Electrical Machines (EE-343) For TE (ELECTRICAL) Name: Roll Number: Year: Batch: Section: Semester: Department: N.E.D University of Engineering &Technology, Karachi Electrical Machines

More information

POWER SUPPLY UNIT 02R96 REPAIR MANUAL PA

POWER SUPPLY UNIT 02R96 REPAIR MANUAL PA POWER SUPPLY UNIT REPAIR MANUAL 02R96 CONTENTS ANALYSIS-REPAIR FLOW CHART 2 2H032W AC-DC POWER SUPPLY 0 ABOUT ANALYSIS AND REPAIR OPERATIONS 4 CIRCUIT DIAGRAM 5 PARTS LIST 6 PA 0645 HAMAMATSU, JAPAN ANALYSIS-REPAIR

More information

USER MANUAL APG DYNAMIC PROCESSORS MATRIX ARRAY SYSTEMS 4000SP 6000SP 9000SP

USER MANUAL APG DYNAMIC PROCESSORS MATRIX ARRAY SYSTEMS 4000SP 6000SP 9000SP USER MANUAL APG DYNAMIC PROCESSORS MATRIX ARRAY SYSTEMS 4000SP 6000SP 9000SP SAFETY INSTRUCTIONS This symbol, wherever it appears, alerts you to the presence of uninsulated dangerous voltage inside the

More information

Flexible Rogowski Coil Integrator Kit with 0-5Vdc and 0-10Vdc User's Manual

Flexible Rogowski Coil Integrator Kit with 0-5Vdc and 0-10Vdc User's Manual Flexible Rogowski Coil Integrator Kit with 0-5Vdc and 0-10Vdc User's Manual Copyright 2017 V1.00 This manual may not be altered or reproduced in whole or in part by any means without the expressed written

More information

Main Supply Unit. DPS.. Power Suplies. Structure of NCT Drive Systems

Main Supply Unit. DPS.. Power Suplies. Structure of NCT Drive Systems Main Supply Unit Structure of NCT Drive Systems Servo amplifiers of NCT drive system do not contain rectifier unit, but the energy is provided by the same separate power supply module to each servo amplifier.

More information

IRT Eurocard. Type AG-738. Stereo Audio Phase / Failure Detector

IRT Eurocard. Type AG-738. Stereo Audio Phase / Failure Detector I R T Electronics Pty Ltd A.B.N. 000 7 6 Hotham Parade, ARTARMON N.S.W. 06 AUSTRALIA National: Phone: (0) 7 Fax: (0) 7 International: +6 7 +6 7 Email: sales@irtelectronics.com Web: www.irtelectronics.com

More information

PAT-20TB MOBILE PUBLIC ADDRESS AMPLIFIER WITH TALK BACK SYSTEM

PAT-20TB MOBILE PUBLIC ADDRESS AMPLIFIER WITH TALK BACK SYSTEM INSTRUCTION MANUAL POWER ON TALK BACK AUX VOLUME PA & TALK BACK AMPLIFIER TONE VOLUME MIC OFF PAT-20TB PA Min Max Low Hi Min Max Mic input 3mv/5k PAT-20TB MOBILE PUBLIC ADDRESS AMPLIFIER WITH TALK BACK

More information

Practical 2.1 BASIC ELECTRICAL MEASUREMENTS AND DATA PROCESSING

Practical 2.1 BASIC ELECTRICAL MEASUREMENTS AND DATA PROCESSING Practical 2.1 BASIC ELECTRICAL MEASUREMENTS AND DATA PROCESSING September 6, 2017 1 Introduction To measure electrical quantities one uses electrical measuring instruments. There are three main quantities

More information

Anna University of Technology Madurai. Alagar kovil road, Madurai REGULATIONS -2010

Anna University of Technology Madurai. Alagar kovil road, Madurai REGULATIONS -2010 Alagar kovil road, Madurai-6 00. REGULATIONS -00 III Semester B. E. Electronics and Communication Engineering 044EC307 Digital Electronics Lab Requirement for a batch of 30 students Sl. No Name of the

More information

WDG 07 - Technical Data Sheet

WDG 07 - Technical Data Sheet LV 804 S WDG 07 - Technical Data Sheet FRAME LV 804 S SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

Pressure Transmitter SIL

Pressure Transmitter SIL Pressure Transmitter SI Characteristics - TRANSDUCER - Pressure: Range: Output: Accuracy: Temperature of medium: Material enclosure: Pressure connection: Electrical connection: Protection: relative / absolute

More information

DEPARTMENT OF ELECTRICAL ENGINEERING BENGAL ENGINEERING AND SCIENCE UNIVERSITY, SHIBPUR

DEPARTMENT OF ELECTRICAL ENGINEERING BENGAL ENGINEERING AND SCIENCE UNIVERSITY, SHIBPUR DEPARTMENT OF ELECTRICAL ENGINEERING BENGAL ENGINEERING AND SCIENCE UNIVERSITY, SHIBPUR Power system protection Laboratory (EE 852) 8 th Semester Electrical Expt. No. 852/1 BIFFI S METHOD FOR TESTING CURRENT

More information

Strain gauge amplifier

Strain gauge amplifier IFFDM1 Strain gauge amplifier Linearity error < 0,01% for compressive and tension force for full bridges 120Ω adjustable transmission frequency 15Hz; 1,3kHz; 3,5kHz (1 st Order) 3Hz; 5Hz (4 th Order) adjustable

More information

OWNER S MANUAL CPS 1 / CPS 2 CONTRACTOR PRECISION SERIES

OWNER S MANUAL CPS 1 / CPS 2 CONTRACTOR PRECISION SERIES OWNER S MANUAL CPS 1 / CPS 2 CONTRACTOR PRECISION SERIES CONTENTS Introduction................................................................... 9 Front Panel...................................................................

More information

AC Current Monitor model ACM-2

AC Current Monitor model ACM-2 1.0 Safety Warnings The ACM-2 AC Current Monitor should be installed only by qualified technical personnel with knowledge of industrial electrical wiring and the requirements of the national and local

More information

I P I OUT R L. Applications. Standards. N 52.D ; Page 1/8

I P I OUT R L. Applications. Standards. N 52.D ; Page 1/8 Ref: ATO-10-B225-D10/SP3 r = 10 A ATO series is a split core current transformer for the electronic measurement of AC waveform current with galvanic separation between the primary circuit (power) and the

More information

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet LV 804 S WDG 12 - Technical Data Sheet FRAME LV 804 S SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

October ECOsine active Harmonic Filters Failure analysis 100A/120A 4-Wire

October ECOsine active Harmonic Filters Failure analysis 100A/120A 4-Wire October 2018 ECOsine active Harmonic Filters Failure analysis 100A/120A 4-Wire Failure analysis 100A/120A 4-Wire 1. Intended use The ECOsine active harmonic filter is used for active compensation of reactive

More information

DECEMBER 2014 Level 2 Certificate/Diploma in Engineering (IVQ) Principles of electrical and electronics technology

DECEMBER 2014 Level 2 Certificate/Diploma in Engineering (IVQ) Principles of electrical and electronics technology *28502561214* 2850-256 DECEMBER 2014 Level 2 Certificate/Diploma in Engineering (IVQ) Principles of electrical and electronics technology Tuesday 11 December 2014 09:30 11:30 You should have the following

More information

Y-0035 POWER ELECTRONICS TRAINING SET

Y-0035 POWER ELECTRONICS TRAINING SET The Power Electronics Training Set is designed in modular structure to do the applications of basic Power Electronics, industrial automation studying and using the control and measuring of the electrical

More information

Electric Power Systems 2: Generators, Three-phase Power, and Power Electronics

Electric Power Systems 2: Generators, Three-phase Power, and Power Electronics 15-830 Electric Power Systems 2: Generators, Three-phase Power, and Power Electronics J. Zico Kolter October 9, 2012 1 Generators Basic AC Generator Rotating Magnet Loop of Wire 2 Generator operation Voltage

More information

EVC600C User Manual EVC600C SERIES. EVC600C User Manual. Date Version Note. Version. Page 1 of 6. Ver 1.

EVC600C User Manual EVC600C SERIES. EVC600C User Manual. Date Version Note. Version.   Page 1 of 6. Ver 1. Ver 1.0 Date: 2014/07/31 EVC600C SERIES Version Date Version Note 2014-07-31 1.0 Original release http://www.engga.com.cn Page 1 of 6 Introduction EVC600C Automatic Voltage Regulator(AVR)is alternator

More information

PARTNER ALTERNATORS LSA Pole

PARTNER ALTERNATORS LSA Pole 90 16 kva - 0 Hz 1 6 kva - 60 Hz 38 en - 11.04 / g PARTNER ALTERNATORS LSA 44.2-4 Pole Electrical and mechanical data SPECIALLY ADAPTED FOR APPLICATIONS The LSA 44.2 alternator is designed to be suitable

More information

SERVICE MANUAL CUT 60

SERVICE MANUAL CUT 60 SERVICE MANUAL CUT 60 INDEX PURPOSE OF THE MANUAL Chapter MACHINE DESCRIPTION Chapter2 INTRODUCTION OF WORKING PRINCIPLE Chapter3 TROUBLESHOOTING&REPAIR SECTION Chapter4 TESTIN PROCEDURE Chapter5 WARRANTY

More information

Training Fees 4,000 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch.

Training Fees 4,000 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch. Training Title POWER SYSTEM GENERATION & DISTRIBUTION Training Duration 5 days Training Venue and Dates Power System Generation & Distribution 5 08-12 December, 2019 $4,000 Dubai, UAE Trainings will be

More information

October Ecosine active Harmonic Filters Failure analysis 30A/50A 3-Wire

October Ecosine active Harmonic Filters Failure analysis 30A/50A 3-Wire October 2018 Ecosine active Harmonic Filters Failure analysis 30A/50A 3-Wire Failure analysis 30A/50A 3-Wire 1. Intended use The Ecosine active harmonic filter is used for active compensation of reactive

More information

Analogue Meters CQ0x07 series

Analogue Meters CQ0x07 series Analogue Meters CQ0x07 series CQ - Instruments with a moving coil and a rectifier CQ0107, CQ0207, CQ0307, CQ0407 & CQ0507 1) o For measurement of AC currents and voltages o Linear scale o Good read-out

More information

RC-19A relay - Current monitoring

RC-19A relay - Current monitoring - Current monitoring Datasheet Features AC current monitoring relay Compact design 1 C/O contact Easy installation High continuous overcurrent possible Protection against short circuit and low impedance

More information

PROFESSIONAL STEREO AMPLIFIERS USER GUIDE

PROFESSIONAL STEREO AMPLIFIERS USER GUIDE PROFESSIONAL STEREO AMPLIFIERS USER GUIDE 967/9673 - September 00 - Version.0 ENGLISH Ti SERIES - Professional stereo amplifiers Page Ti SERIES - Professional stereo amplifiers ENGLISH - Safety information

More information

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions Operating Instructions SIMEAS-T s Operating Instructions Transducer without auxiliary power for alternating current for alternating voltage for alternating voltage with expanded end range 7KG6111 and 7KG6101

More information

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX SSE-N NEGATIVE FIELD FORCING SHUNT STATIC EXCITER/REGULATOR SYSTEM Control Chassis 6 SCR Power Chassis APPLICATION The SSE-N Negative Field Forcing Exciter/Regulator is used for both new and old installations

More information

STEADY STATE REACTANCE

STEADY STATE REACTANCE INDEX NO. : M-53 TECHNICAL MANUAL FOR STEADY STATE REACTANCE Manufactured by : PREMIER TRADING CORPORATION (An ISO 9001:2008 Certified Company) 212/1, Mansarover Civil Lines, MEERUT. Phone : 0121-2645457,

More information

ELECTRICAL TEST WORKSHOP MANUAL

ELECTRICAL TEST WORKSHOP MANUAL ELECTRICAL TEST WORKSHOP MANUAL GB reference : 755711 DC/ATR 03/2001 CONTENTS 1. ELECTRICAL TESTS... 5 The test apparatus:...5 Wires:... 7 Resistances:... 7 Bulbs:... 8 Saddle control:... 8 Magneto:...

More information

New Redundant Automatic Voltage Regulator (AVR) Solution

New Redundant Automatic Voltage Regulator (AVR) Solution White Paper New Redundant Automatic Voltage Regulator (AVR) Solution Author: David R. Brown, Turbomachinery Control Solutions Senior Consultant, Invensys Operations Management What s Inside: 1. Introduction

More information

Operating instructions optical fork sensor OPU200 OPU200 / / 2018

Operating instructions optical fork sensor OPU200 OPU200 / / 2018 Operating instructions optical fork sensor OPU200 OPU200 / 0 08 / 208 Contents Preliminary note.... Symbols used... 2 Functions and features... Installation... 4 Operating and display elements... 5 Electrical

More information

Type KLF Generator Field Protection-Loss of Field Relay

Type KLF Generator Field Protection-Loss of Field Relay Supersedes DB 41-745B pages 1-4, dated June, 1989 Mailed to: E, D, C/41-700A ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA For Use With Delta Connected Potential Transformers

More information

RT-5005/5006/5007/5008

RT-5005/5006/5007/5008 Replaces: 09.12 Electro-hydraulic Control Digital Proportional Amplifier Type: RT-5005/5006/5007/5008 Series: 3X Table of contents Contents Page Features 1 Ordering code 2 Functional description 2 Block

More information

ENGLISH S-CO2 AMBIENT AIR SENSOR INSTALLATION AND OPERATING INSTRUCTIONS CO 2. TF5701_B_v1_web

ENGLISH S-CO2 AMBIENT AIR SENSOR INSTALLATION AND OPERATING INSTRUCTIONS CO 2. TF5701_B_v1_web S-CO2 CO 2 AMBIENT AIR SENSOR INSTALLATION AND OPERATING INSTRUCTIONS ENGLISH TF5701_B_v1_web 1 DESCRIPTION This module measures carbon dioxide (CO 2 ) in the range of 0 to 2 000 ppm and is equipped with

More information

Spec Information. Reactances Per Unit Ohms

Spec Information. Reactances Per Unit Ohms GENERATOR DATA Spec Information Generator Specification Frame: 1647 Type: SR5 No. of Bearings: 1 Winding Type: RANDOM WOUND Flywheel: 21.0 Connection: SERIES STAR Housing: 00 Phases: 3 No. of Leads: 6

More information