High Voltage Overhead Power Lines, 21 Georgiou Eikosari, Dali

Size: px
Start display at page:

Download "High Voltage Overhead Power Lines, 21 Georgiou Eikosari, Dali"

Transcription

1 On the 22nd of July 2009 at 17:30 pm, electric and magnetic field measurements were performed for 21 Georgiou Eikosari, Dali overhead power lines. The EMF measurements were performed inside and outside the residence and in direct proximity to the overhead power line. {mosmap width='500' height='400' lat=' ' lon=' ' zoom='18' zoomtype='large' zoomnew='0' maptype='satellite' showmaptype='1' overview='0' text='overhead power line, 21 Georgiou Eikosari, Dali' tooltip='dwo' marker='1' align='center' key='abqiaaaa03cwbwhnzyjizsn-wwdqmhqctkyp5l8hb2mjngvvfkvpdgzbixqkqitrafigip chx6gplphdidvzga'} Σελίδα 1 / 7

2 The transmission towers are tall steel lattice structures that support overhead electricity conductors for power transmission. The overhead power line is rated at a nominal power of 900 MVA. At the time when the measurements were performed, the load of the overhead power line was 142 MW and 20 MVar. The Resultant Load of all three phases was % utilization of the nominal load power. Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organisations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP. Reference levels for Occupational exposure ICNIRP Frequency Electric Field Strength E (V/m) Magnetic Field Strength H (A/m) Magnetic Flux Density B (µt) 50 Hz Reference levels for General Public exposure ICNIRP Frequency Electric Field Strength E (V/m) Σελίδα 2 / 7

3 Magnetic Field Strength H (A/m) Magnetic Flux Density B (µt) 50 Hz Table 1: ICNIRP Exposure limits for Occupational and General Public exposure The maximum obtained values are represented below and compared to the ICNIRP standards for the General Public. The highest magnetic field value inside was observed in the 2nd bedroom of the residence, with value 1.80 μt and a percentage of 1.80 % as compared to the ICNIRP General Public standard. Overhead Power lines: Inside Field Measurements Measurement Point Maximum Magnetic Field (µt) at Z Height (m) Percentage of ICNIRP General Public Standard (%) 0.3m 1.75m Measurements inside the residence 1m Measurement Point A - 1st bedroom -1.64% 1.64 Measurement Point B - Bathroom -Σελίδα 3 / 7

4 % Measurement Point C 2nd bedroom % Measurement Point D 3rd bedroom % Measurement Point E Living room % Σελίδα 4 / 7

5 Measurement Point F Dining room % Measurement Point G - Kitchen % Table 2: Maximum field measurements inside Accordingly, the highest magnetic field outside was observed below the overhead power lines, with a value 1.70 μt (0 m away from the starting point) and a percentage of 1.70 % as compared to the ICNIRP General Public standard.. Overhead Power lines: Outside Field Measurements Measurement Point Maximum Magnetic Field (µt) at Z Height (m) Percentage of ICNIRP General Public Standard (%) Σελίδα 5 / 7

6 0.3m 1.75m Measurements inside the residence 1m Measurement Point H 1.22% 1.22 Measurement Point I % Measurements along the Overhead Power Line 30m Measurement Line % 1.29% % Measurements across the Overhead Power Line 30m Measurement Line % 1.14% % Table 3: Maximum field measurements outside area Σελίδα 6 / 7

7 Σελίδα 7 / 7

Overhead Power Lines: Argaki area in Moni, Limassol

Overhead Power Lines: Argaki area in Moni, Limassol The measurements were performed on the 21st of September 2011 at 11:50 am during clear weather conditions. The EMF measurements were performed inside the plot area in direct proximity to the overhead power

More information

Specific Equipment and Area - EAC District Office Substation

Specific Equipment and Area - EAC District Office Substation On the 13th of April 2007 at 10:00 am magnetic field measurements were performed for the District Office Substation. The substation of interest is located on Mykhnon Street in Nicosia. {mosmap width='500'

More information

6.2 Environmental Statement Appendices Volume N Appendix 15.1 EMF Report

6.2 Environmental Statement Appendices Volume N Appendix 15.1 EMF Report The Millbrook Power (Gas Fired Power Station) Order 6.2 Environmental Statement Appendices Volume N Appendix 15.1 EMF Report Planning Act 2008 The Infrastructure Planning (Applications: Prescribed Forms

More information

ELF ELECTRIC AND MAGNETIC FIELDS MEASUREMENTS IN GREECE

ELF ELECTRIC AND MAGNETIC FIELDS MEASUREMENTS IN GREECE ELF ELECTRIC AND MAGNETIC FIELDS MEASUREMENTS IN GREECE E. Karabetsos, G. Filippopoulos, D. Koutounidis CH. Govari, N. Skamnakis Non ionizing radiation office, Greek atomic energy commission, P. O. BOX

More information

Electric and magnetic field levels around Christchurch

Electric and magnetic field levels around Christchurch Electric and magnetic field levels around Christchurch M D Gledhill 1992/1 NRL Report Report NRL 1992/1 ISSN O111-753x ELECTRIC AND MAGNETIC FIELD LEVELS AROUND CHRISTCHURCH M D Gledhill National Radiation

More information

Human Exposure Requirements for R&TTE and FCC Approval

Human Exposure Requirements for R&TTE and FCC Approval Human Exposure Requirements for R&TTE and FCC Approval Derek Y. W. LEUNG Founding and Committee Member of EMC Chapter- IEEE-HK Requirements of Non-Specific Short Range Device (SRD) for CE Marking Radio

More information

The Nature of Electric and Magnetic Fields 2017

The Nature of Electric and Magnetic Fields 2017 The Nature of Electric and Magnetic Fields 2017 FACT SHEET 1 3 4 5 What are Electric and Magnetic Fields (EMF)? How are electricity and EMF related? Many people will have seen the attraction or repulsion

More information

Code of Practice for Proposed Mobile Phone Base Station Installations on University Premises.

Code of Practice for Proposed Mobile Phone Base Station Installations on University Premises. Code of Practice for Proposed Mobile Phone Base Station Installations on University Premises. Introduction. Mobile phone base stations are low power (typically a few tens of watts) radio transmitters with

More information

Appendix 6-F: Electric and Magnetic Field Study Report

Appendix 6-F: Electric and Magnetic Field Study Report Draft Environmental Impact Statement Cricket Valley Energy Project Dover, NY Appendix 6-F: Electric and Magnetic Field Study Report ELECTRIC & MAGNETIC FIELDS (EMFs) STUDY REPORT For the CRICKET VALLEY

More information

Technical Committee106 Methods for the assessment of electric, magnetic and electromagnetic fields associated with human exposure

Technical Committee106 Methods for the assessment of electric, magnetic and electromagnetic fields associated with human exposure Technical Committee106 Methods for the assessment of electric, magnetic and electromagnetic fields associated with human exposure International Electrotechnical Commission Michel Bourdages Secretary International

More information

LOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS

LOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS LOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS Peter Leipold, Klaus-Peter Panzlaff Bewag Aktiengesellschaft, Puschkinallee 52, D-12435 Berlin Tel.: +49 30 267 10 350 - Fax: +49 30 267 10 352 -

More information

Analytical Design Optimization of 765 kv Transmission Line Based on Electric and Magnetic Fields for Different Line Configurations

Analytical Design Optimization of 765 kv Transmission Line Based on Electric and Magnetic Fields for Different Line Configurations Available onlinewww.ejaet.com European Journal of Advances in Engineering and Technology, 2018, 5(2): 91-98 Research Article ISSN: 2394-658X Analytical Design Optimization of 765 kv Transmission Line Based

More information

Biljana Tanatarec Doron Net d.o.o. ISO/HZN National Workshop on Social Responsibility Zagreb, 9 10 September 2010

Biljana Tanatarec Doron Net d.o.o. ISO/HZN National Workshop on Social Responsibility Zagreb, 9 10 September 2010 Biljana Tanatarec Doron Net d.o.o. ISO/HZN National Workshop on Social Responsibility Zagreb, 9 10 September 2010 Introduction Working in Doron Net d.o.o. Head of DN Laboratory Doron Net is a member of

More information

YARRANLEA SOLAR PROJECT. Electromagnetic Radiation Assessment. Zenviron Document: 8013-EL-R

YARRANLEA SOLAR PROJECT. Electromagnetic Radiation Assessment. Zenviron Document: 8013-EL-R YARRANLEA SOLAR PROJECT Electromagnetic Radiation Assessment Zenviron Document: 8013-EL-R-160819-1 DOCUMENT DETAILS Revision History REV. DESCRIPTION PREPARED CHECKED APPROVED DATE A Initial Issue ABC

More information

Environmental Exposures to ELF Georg Neubauer

Environmental Exposures to ELF Georg Neubauer Environmental Exposures to ELF Georg Neubauer 1 Table of Content Environmental exposures to ELF sources Measurement methods Requirements on measurements Conclusions 2 Environmental exposure to ELF sources

More information

Magnetic Field Measurement in Residential Areas Göteborg, Borås and Mark Residential Area Measurements SEYED REZA ATEFI

Magnetic Field Measurement in Residential Areas Göteborg, Borås and Mark Residential Area Measurements SEYED REZA ATEFI Magnetic Field Measurement in Residential Areas Göteborg, Borås and Mark Residential Area Measurements Master of Science Thesis in Biomedical Engineering SEYED REZA ATEFI Department of Signals and Systems

More information

v1.0.1 March AlphaLab, Inc. All rights reserved. TriField EMF Meter Owner s Manual

v1.0.1 March AlphaLab, Inc. All rights reserved. TriField EMF Meter Owner s Manual v1.0.1 March 2018 2018 AlphaLab, Inc. All rights reserved. TriField EMF Meter Owner s Manual TABLE OF CONTENTS Overview... 1 Introduction... 1 Features... 1 Applications... 1 Using the TriField EMF Meter...

More information

First South East European Regional CIGRÉ Conference. Portoroz, Slovenia, 7 8 June 2016

First South East European Regional CIGRÉ Conference. Portoroz, Slovenia, 7 8 June 2016 First South East European Regional CIGRÉ Conference Portoroz, Slovenia, 7 8 June 2016 Assessment of new OHL of Slovak Republic Transmission System with regard to the recommendation of the Directive No.

More information

Safety Code 6 Analysis Freedom Mobile 3G & LTE Network. Radio frequency exposure for uncontrolled and controlled environment.

Safety Code 6 Analysis Freedom Mobile 3G & LTE Network. Radio frequency exposure for uncontrolled and controlled environment. Safety Code 6 Analysis Freedom Mobile 3G & LTE Network Radio frequency exposure for uncontrolled and controlled environment Freedom Mobile 207 Queen's Quay West, Suite 710 Toronto, ON M5J 1A7 3655 Wesbrook

More information

Report On. RF Exposure Assessment of the Sepura plc SRG3900 with AQHB Antenna. FCC ID: XX6SRG3900UW Industry Canada ID: 8739A-SRG3900UW

Report On. RF Exposure Assessment of the Sepura plc SRG3900 with AQHB Antenna. FCC ID: XX6SRG3900UW Industry Canada ID: 8739A-SRG3900UW Report On RF Exposure Assessment of the Sepura plc SRG3900 with AQHB Antenna FCC ID: XX6SRG3900UW Industry Canada ID: 8739A-SRG3900UW Document 75908189 Report 04 Issue 2 March 2010 TUV Product Service

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) Electric and Magnetic Field Measurement For Isotropic Measurement of Magnetic and Electric Fields Evaluation of Field

More information

Reducing personal EMF exposure

Reducing personal EMF exposure www.emfields-solutions.com www.powerwatch.org.uk EMFields Solutions Ltd in conjunction with Powerwatch This leaflet and information are written for the EMFields pocket PF5 meter which measures ELF and

More information

Multi Voltage Multi Circuit Transmission Tower Design to Reduce Right of Way

Multi Voltage Multi Circuit Transmission Tower Design to Reduce Right of Way Indian Journal of Science and Technology, Vol 9(33), DOI: 10.17485/ijst/2016/v9i33/95239, September 2016 ISSN (Print) : 0974-6846 ISSN (Online) : 0974-5645 Multi Voltage Multi Circuit Transmission Tower

More information

T E C H N I C A L M E M O R A N D U M. ON PARTICULAR ASPECTS RELATED 400 kv TRANSMISSION

T E C H N I C A L M E M O R A N D U M. ON PARTICULAR ASPECTS RELATED 400 kv TRANSMISSION T E C H N I C A L M E M O R A N D U M ON PARTICULAR ASPECTS RELATED 400 kv TRANSMISSION Prepared by Prepared for : Dr Pieter H Pretorius, Trans-Africa Projects : Mr Henry Nawa, Senior Environmental Advisor,

More information

Developing and Implementing Protective Measures for ELF EMF - Sources and exposures- Rüdiger Matthes Federal Office for Radiation Protection Germany

Developing and Implementing Protective Measures for ELF EMF - Sources and exposures- Rüdiger Matthes Federal Office for Radiation Protection Germany Developing and Implementing Protective Measures for ELF EMF - Sources and exposures- Rüdiger Matthes Federal Office for Radiation Protection Germany 1 Non-ionising Radiation Ionising Radiation >0 to 300

More information

Electromagnetic environment in Electrical Hypersensitives homes and workplaces. Kjell Hansson Mild. National Institute for Working Life, Umeå, Sweden

Electromagnetic environment in Electrical Hypersensitives homes and workplaces. Kjell Hansson Mild. National Institute for Working Life, Umeå, Sweden Electromagnetic environment in Electrical Hypersensitives homes and workplaces National Institute for Working Life, Umeå, Sweden External sources: High voltage power lines, distribution lines magnetic

More information

ELECTROMAGNETIC 0 Hz 300 GHz

ELECTROMAGNETIC 0 Hz 300 GHz ELECTROMAGNETIC 0 Hz 300 GHz Field characterization & occupational exposure sources Laura FILOSA 1. Organization of the NIR Module 2. European frame introduction 3. Electromagnetic field characterization

More information

ELECTROMAGNETIC POLLUTION INSIDE HIGH VOLTAGE SUBSTATION

ELECTROMAGNETIC POLLUTION INSIDE HIGH VOLTAGE SUBSTATION Rev. Roum. Sci. Techn. Électrotechn. et Énerg. Vol. 61, 1, pp. 178 182, Bucarest, 2016 ELECTROMAGNETIC POLLUTION INSIDE HIGH VOLTAGE SUBSTATION BILLEL ALI RACHEDI 1, ABDESSELAM BABOURI 1, ZHANG XUN 2 Key

More information

For Isotropic Measurement of Magnetic and Electric Fields

For Isotropic Measurement of Magnetic and Electric Fields Field Analyzers EFA-300 For Isotropic Measurement of Magnetic and Electric Fields Evaluation of Field Exposure compared to Major Standards and Guidance (selectable) Shaped Time Domain (STD) an innovative

More information

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another.

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another. TRANSMISSION LINES PRELIMINARIES Generators and loads are connected together through transmission lines transporting electric power from one place to another. Transmission line must, therefore, take power

More information

Appendix I. Applicant s Audible Noise and EMF Calculations

Appendix I. Applicant s Audible Noise and EMF Calculations Appendix I Applicant s Audible Noise and EMF Calculations Structure Type Predicted Intensity of Electric Fields (kv/m) at Maximum Operating Voltage Where Not Paralleling Existing Transmission Lines Line

More information

EXPOSURE to electromagnetic fields (EMFs) is not a

EXPOSURE to electromagnetic fields (EMFs) is not a 1800 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 3, JULY 2005 Measurements of Electric and Magnetic Fields Due to the Operation of Indoor Power Distribution Substations Anastasia S. Safigianni, Member,

More information

ELF Magnetic Field Security Zones around High Voltage Power Lines

ELF Magnetic Field Security Zones around High Voltage Power Lines ELF Magnetic Field Security Zones around High Voltage Power Lines Carlos Lemos Antunes 1,2,3 (1) Lab. CAD/CAE, Electrical Engineering Dept, University of Coimbra Pólo II, 3030 290 Coimbra (Portugal) (2)

More information

Comparison of international policies on electromagnetic fields. (power frequency and radiofrequency fields)

Comparison of international policies on electromagnetic fields. (power frequency and radiofrequency fields) Comparison of international policies on electromagnetic fields (power frequency and radiofrequency fields) Comparison of international policies on electromagnetic fields (power frequency and radiofrequency

More information

1. Introduction. Keywords Non-ionizing radiation, Electric field, Magnetic field, Power line, Kaduna metropolis, ICNIRP 2010 guideline

1. Introduction. Keywords Non-ionizing radiation, Electric field, Magnetic field, Power line, Kaduna metropolis, ICNIRP 2010 guideline American Journal of Condensed Matter Physics, (): - DOI:.9/j.ajcmp.. Measurement and Analysis of Health Effects Due to Exposure to Non-Ionizing Radiation from High Tension Cables around Kaduna Metropolis,

More information

Electromagnetic Fields, Mobile Telephones and Health

Electromagnetic Fields, Mobile Telephones and Health Electromagnetic Fields, Mobile Telephones and Health Dr. Matti Rajala European Commission Directorate General for Health and Consumer Protection - Luxembourg Council Recommendation 12th July (1999/519/EC)

More information

NIR MEASUREMENTS. Principles and practices of EMF characterization and measurements

NIR MEASUREMENTS. Principles and practices of EMF characterization and measurements IRPA 1 1th International Congress of the International Radiation Protection Association 19th-4th October 008, Buenos Aires, Argentina RC-11 NIR MEASUREMENTS. Principles and practices of EMF characterization

More information

RF-EXPOSURE ASSESSMENT REPORT

RF-EXPOSURE ASSESSMENT REPORT RF-EXPOSURE ASSESSMENT REPORT EN 62311 RF-Exposure evaluation of electronic equipment Report Reference No.... : G0M-1206-2043-TEU311E-V01 Testing Laboratory... : Address... : Storkower Str. 38c 15526 Reichenwalde

More information

Experimental Study of Electromagnetic Environment in the Vicinity of High Voltage Lines

Experimental Study of Electromagnetic Environment in the Vicinity of High Voltage Lines American J. of Engineering and Applied Sciences 4 (2): 209-213, 2011 ISSN 1941-7020 2011 Science Publications Experimental Study of Electromagnetic Environment in the Vicinity of High Voltage Lines 1 Wafa

More information

Low Frequency. Precision test equipment for safety in electric and magnetic fields

Low Frequency. Precision test equipment for safety in electric and magnetic fields Low Frequency Precision test equipment for safety in electric and magnetic fields Your One-Stop Shop for Safety in Electromagnetic Fields Narda Safety Test Solutions device technologies highly simplify

More information

ELECTROMAGNETIC SHIELDING PRODUCTS

ELECTROMAGNETIC SHIELDING PRODUCTS ELECTROMAGNETIC SHIELDING PRODUCTS WWW.SATISHIELDING.COM SATI SHIELDING Sati Shielding S.r.l. was set up on 23 December 2015, thanks to the merger of different professional skills: marketing and organisational

More information

Regulatory Framework for RF Safety in Mauritius

Regulatory Framework for RF Safety in Mauritius Regulatory Framework for RF Safety in Mauritius Jerome LOUIS Director Engineering ICTA This Session PART I Background Base Station Site Selection Base Station authorisation process Exposure Limits adopted

More information

Fidler Substation and Transmission Line

Fidler Substation and Transmission Line Fidler Substation and Transmission Line November 2009 Who can you contact for more information? To learn more about the proposed project you can contact: How can you provide input? We want your input so

More information

MAGNETIC FIELD METER Operator s Manual

MAGNETIC FIELD METER Operator s Manual Edition 4.4 September 2011 MAGNETIC FIELD METER 3000 Operator s Manual The MFM 3000 is a professional magnetic field instrument To make the best use of the instrument we recommend that you read this manual

More information

Analysis of magnetic and electromagnetic field emissions produced by a MRI device

Analysis of magnetic and electromagnetic field emissions produced by a MRI device Sept. 8-1, 21, Kosice, Slovakia Analysis of magnetic and electromagnetic field emissions produced by a MRI device D. Giordano, M. Borsero, G. Crotti, M. ucca INRIM Istituto Nazionale di Ricerca Metrologica,

More information

MAGNETIC FIELD COMPUTATION DUE TO HIGH VOLTAGE POWER LINES USING EasyMAG

MAGNETIC FIELD COMPUTATION DUE TO HIGH VOLTAGE POWER LINES USING EasyMAG MAGNETIC FIELD COMPUTATION DUE TO HIGH VOLTAGE POWER LINES USING EasyMAG Tony Richard O. Almeida (1), Carlos F. R. Lemos Antunes (2) Laboratório de CAD/CAE (1, 2), I.S.R. (1) Departamento de Engenharia

More information

DESIGN OF A 45 CIRCUIT DUCT BANK

DESIGN OF A 45 CIRCUIT DUCT BANK DESIGN OF A 45 CIRCUIT DUCT BANK Mark COATES, ERA Technology Ltd, (UK), mark.coates@era.co.uk Liam G O SULLIVAN, EDF Energy Networks, (UK), liam.o sullivan@edfenergy.com ABSTRACT Bankside power station

More information

PROBLEMS on Transformers

PROBLEMS on Transformers PROBLEMS on Transformers (A) Simple Problems 1. A single-phase, 250-kVA, 11-kV/415-V, 50-Hz transformer has 80 turns on the secondary. Calculate (a) the approximate values of the primary and secondary

More information

IOSH Webinar. Control of Electromagnetic Fields at work regulations 2016 Part 2 EMF exposure assessment 4 th May 2017 Julia Clark FSRP CMIOSH

IOSH Webinar. Control of Electromagnetic Fields at work regulations 2016 Part 2 EMF exposure assessment 4 th May 2017 Julia Clark FSRP CMIOSH IOSH Webinar Control of Electromagnetic Fields at work regulations 2016 Part 2 EMF exposure assessment 4 th May 2017 Julia Clark FSRP CMIOSH www.linkmicrotek.com Previously Webinar part one covered: Definition

More information

Research Activities Plan. Appendix K Magnetic Fields from Submarine Cables

Research Activities Plan. Appendix K Magnetic Fields from Submarine Cables VOWTAP Research Activities Plan Appendix K Magnetic Fields from Submarine Cables December 2013 Electrical Engineering and Computer Science Practice Virginia Offshore Wind Technology Advancement Project

More information

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits WREF 01 Paper # 048 Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits Ketut Dartawan Ricardo Austria, Le Hui and Mark Suehiro* Pterra Consulting Maui Electric Company*

More information

WLAN. Date: 20 October 2016

WLAN. Date: 20 October 2016 WLAN Date: 20 October 2016 A wireless local area network (WLAN) allows computers and laptops to be connected to each other, to peripheral devices (printers, scanners etc.) and to an Internet access point.

More information

Simulation Approach in Evaluating the Electromagnetic Fields from the New Lines of Extra High Voltage (EHV) Circuits Near Residential Area in Malaysia

Simulation Approach in Evaluating the Electromagnetic Fields from the New Lines of Extra High Voltage (EHV) Circuits Near Residential Area in Malaysia European Journal of Scientific Research ISSN 1450-216X Vol.40 No.2 (2010), pp.189-198 EuroJournals Publishing, Inc. 2010 http://www.eurojournals.com/ejsr.htm Simulation Approach in Evaluating the Electromagnetic

More information

Safety Code 6 Compliance Analysis of NLA031. Study conducted by Eastlink, Radio Frequency Engineering Department

Safety Code 6 Compliance Analysis of NLA031. Study conducted by Eastlink, Radio Frequency Engineering Department Safety Code 6 Compliance Analysis of NLA031 Study conducted by Eastlink, Radio Frequency Engineering Department Oct 2016 Contents Description of site... 2 Summary... 4 Simulation and Software... 4 Definitions...

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information

National Radiation Commission P.O.Box 743, Arusha, Tanzania.

National Radiation Commission P.O.Box 743, Arusha, Tanzania. Preliminary Measurements of Electromagnetic Radiation Levels from a Radio Transmitter and Cellular Phone Base Stations Randomly Selected at Dar es Salaam City in Tanzania M. M. Nyaruba 1 and J. B. Ngatunga

More information

Radio Frequency Emissions Analysis Report Sprint Wireless Water Tank Facility

Radio Frequency Emissions Analysis Report Sprint Wireless Water Tank Facility Radio Frequency Emissions Analysis Report Sprint Wireless Water Tank Facility Site ID: BS3XC490 Site Name: Cedar St. Water Tank Address: 396 Cedar Street, Ashland, MA 0171 Latitude: 4.35300 Longitude:

More information

City of Medicine Hat Electric Utility

City of Medicine Hat Electric Utility Decision 2014-349 Transmission Line MH-20L Upgrade Project December 17, 2014 The Alberta Utilities Commission Decision 2014-349: Transmission Line MH-20L Upgrade Project Application No. 1610463 Proceeding

More information

Safety Evaluation Within a Magnetic Field Environment

Safety Evaluation Within a Magnetic Field Environment EXPOSURE LEVEL TESTER ELT-400 Safety Evaluation Within a Magnetic Field Environment Direct evaluation of field exposure in comparison with major standards and regulations such as Directive 2013/35/EU for

More information

Exam 3 Review Session

Exam 3 Review Session Exam 3 Review Session I will hold a review for Exam 3 which covers Chapters 27, 28, 29 and 30, on Wednesday November 7 th at 7:15pm in MPHY 205. Exam 3 will be given in class on Thursday, November 8 th.

More information

AC Magnetic Field Survey Report

AC Magnetic Field Survey Report AC Magnetic Field Survey Report of Literature Building - 3 University of California San Diego for University of California San Diego La Jolla, California Report Date: February 15, 21 FMS Ref: 21-182 FIELD

More information

Measurements of Exposures Around Vodafone New Zealand Limited Cellsites from June 2012 to May 2013

Measurements of Exposures Around Vodafone New Zealand Limited Cellsites from June 2012 to May 2013 Measurements of Exposures Around Vodafone New Zealand Limited Cellsites from June 2012 to May 2013 This report was prepared for: Vodafone New Zealand Limited Private Bag 92161 AUCKLAND By M Dirksen Reviewed

More information

EMF risk for operators mounting, adjusting and maintaining base stations

EMF risk for operators mounting, adjusting and maintaining base stations Environmentalist (2007) 27:545 549 DOI 10.1007/s10669-007-9062-3 EMF risk for operators mounting, adjusting and maintaining base stations T. Shalamanova Æ I. Iliev Æ M. Ivanova Æ M. Israel Published online:

More information

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K UNIT II TRANSFORMERS PART A 1. Define a transformer? A transformer is a static device which changes the alternating voltage from one level to another. 2. What is the turns ratio and transformer ratio of

More information

ITU-T Study Group 5. EMF Environmental Characterization

ITU-T Study Group 5. EMF Environmental Characterization International Telecommunication Union EMF Environmental Characterization Jeffrey Boksiner Senior Consultant, Telcordia Technologies, Inc Workshop on: EMC, safety and EMF effects in telecommunications o

More information

The Survey of Electromagnetic Environment near RF Transmitters

The Survey of Electromagnetic Environment near RF Transmitters The Survey of Electromagnetic Environment near RF Transmitters Valeriu David 1, Alexandru Salceanu, Mihai Cretu 3, Eduard Lunca 4 1 "Gh. Asachi" Technical University, Iasi, Faculty of Electrical Engineering,

More information

The SEMONT Network Utilization for the Lowfrequency

The SEMONT Network Utilization for the Lowfrequency The SEMONT Network Utilization for the Lowfrequency EMF Monitoring Nikola Djuric, Jelena Bjelica, Dragan Kljajic, Miodrag Milutinov, Karolina Kasas-Lazetic, Danka Antic Faculty of Technical Sciences, University

More information

Subject: AC ELF EMF EMC Magnetic Field Testing for a Sauna Heater

Subject: AC ELF EMF EMC Magnetic Field Testing for a Sauna Heater EMF Measurements, Surveys & Risk Assessment EMF Mitigation Shielding & Cancellation E-Mail: dvitale@vitatech.net www.vitatech.net VitaTech Electromagnetics, LLC 115 Juliad Ct., Suite 105 Fredericksburg,

More information

Class: RPT Doc. no: RE Rev: A Date: Approved by: JCP

Class: RPT Doc. no: RE Rev: A Date: Approved by: JCP Class: RPT Doc. no: 264001-RE Rev: A Date: 2007-04-25 Approved by: JCP Power Density in Proximity to a 4000/4100 Transceiver using any Terma SD, HG or LA SCANTER 4000/4100 Template no: 199997-FA, Rev.

More information

Mr. Aaron Zack Tel: Subject: AC ELF EMF EMC Magnetic Field Testing for a Sauna Heater

Mr. Aaron Zack Tel: Subject: AC ELF EMF EMC Magnetic Field Testing for a Sauna Heater 115 Juliad Court, Suite 105 Fredericksburg VA, 22406 Phone 540 286 1984 Fax 540 268 1865 www.vitatech.net November 14th, 2012 Mr. Aaron Zack Tel: 877.292.0020 President/CEO Email: azack@sunlighten.com

More information

Fatima Michael college of Engineering and Technology

Fatima Michael college of Engineering and Technology Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric

More information

in Midtown EXCEL HOMES LOCKEPORT SECOND FLOOR 762 sq. ft. MAIN FLOOR 762 sq. ft. LANED DUPLEX TWO STOREY excelhomes.ca Nook 12'11" x 9'0"

in Midtown EXCEL HOMES LOCKEPORT SECOND FLOOR 762 sq. ft. MAIN FLOOR 762 sq. ft. LANED DUPLEX TWO STOREY excelhomes.ca Nook 12'11 x 9'0 Nook 12'11" x 9'0" Bedroom 2 9'4" x 9'10" Bedroom 3 9'4" x 9'8" Half DW 12'11" x 13'6" 12'0" x 13'0" Down Up Laundry W D Down BATHROOMS 2.5 BEDROOMS 3 LANED DUPLEX TWO STOREY FINISHED SQ. FT. 1524 DEVELOPED

More information

Report On. Radio Frequency Exposure Testing of the Winland Electronics, Inc. EnviroAlert Electronic Multi-Zone Environmental Alarm System

Report On. Radio Frequency Exposure Testing of the Winland Electronics, Inc. EnviroAlert Electronic Multi-Zone Environmental Alarm System America Report On Radio Frequency Exposure Testing of the Winland Electronics, Inc. EnviroAlert Electronic Multi-Zone Environmental Alarm System EN62311 January 2008 AS/NZS 2772.2:2011 October 2017 REPORT

More information

Selective and broadband low frequency field analysis

Selective and broadband low frequency field analysis ELECTRIC AND MAGNETIC FIELD ANALYZER EHP-50C Selective and broadband low frequency field analysis Electric and magnetic low frequency field analysis up to 100 khz Isotropic measurement with a dynamic range

More information

Copper and Electricity: Transformers and. the Grid. Transformers

Copper and Electricity: Transformers and. the Grid. Transformers PHYSICS Copper and Electricity: Transformers and 16-18 YEARS the Grid Transformers Using transformers We use transformers to change the size of a voltage. We can step the voltage down from a high voltage

More information

RF Field Strength Meter TDM-200. Instruction Booklet. Laplace Instruments Ltd. Supplied by:

RF Field Strength Meter TDM-200. Instruction Booklet. Laplace Instruments Ltd. Supplied by: Supplied by: Laplace Instruments Ltd 3B, Middlebrook Way CROMER, Norfolk NR27 9JR UK Tel: 01263 51 51 60 Fax: 01263 51 25 32 E-mail: tech@laplace.co.uk RF Field Strength Meter TDM-200 Instruction Booklet

More information

SECTION 26. Glossary of Terms and Abbreviations

SECTION 26. Glossary of Terms and Abbreviations SECTION 26 Glossary of Terms and Abbreviations Prepared for the BioInitiative Working Group July 2007 Absorption. In radio wave propagation, attenuation of a radio wave due to dissipation of its energy,

More information

*X025/11/01* X025/11/01 ELECTRONIC AND ELECTRICAL FUNDAMENTALS INTERMEDIATE 2 NATIONAL QUALIFICATIONS 2015 WEDNESDAY, 3 JUNE 9.00 AM 11.

*X025/11/01* X025/11/01 ELECTRONIC AND ELECTRICAL FUNDAMENTALS INTERMEDIATE 2 NATIONAL QUALIFICATIONS 2015 WEDNESDAY, 3 JUNE 9.00 AM 11. X05//0 NATIONAL QUALIFICATIONS 05 WEDNESDAY, JUNE 9.00 AM.0 AM ELECTRONIC AND ELECTRICAL FUNDAMENTALS INTERMEDIATE 00 marks are allocated to this paper. Answer all questions in Section A (50 marks). Answer

More information

Executive Summary: Report on Health Canada Survey of Ultraviolet Radiation and Electric and Magnetic Fields from Compact Fluorescent Lamps

Executive Summary: Report on Health Canada Survey of Ultraviolet Radiation and Electric and Magnetic Fields from Compact Fluorescent Lamps Executive Summary: Report on Health Canada Survey of Ultraviolet Radiation and Electric and Magnetic Fields from Compact Fluorescent Lamps Lasers and Electro-Optics Division Electromagnetics Division Consumer

More information

Harmonic resonances due to transmission-system cables

Harmonic resonances due to transmission-system cables International Conference on Renewable Energies and Power Quality (ICREPQ 14) Cordoba (Spain), 8 th to 1 th April, 214 Renewable Energy and Power Quality Journal (RE&PQJ) ISSN 2172-38 X, No.12, April 214

More information

SNC0080 Abbott & Iber

SNC0080 Abbott & Iber SNC0080 Abbott & Iber Municipal Review and Concurrence of an Antenna System Application Public Notification Package Wireless Communications Site 145 Iber Rd., Ottawa, Ontario, K2S 1E7 Purpose This information

More information

Technical Note 2. Standards-compliant test of non-ionizing electromagnetic radiation on radar equipment

Technical Note 2. Standards-compliant test of non-ionizing electromagnetic radiation on radar equipment Technical Note 2 Standards-compliant test of non-ionizing electromagnetic radiation on radar equipment Technical Note: Standards-compliant test of non-ionizing electromagnetic radiation on radar equipment

More information

CHAPTER 6 ALTERNATING CURRENT

CHAPTER 6 ALTERNATING CURRENT HDR102 PHYSICS FOR RADIOGRAPHERS 1 CHAPTER 6 ALTERNATING CURRENT PREPARED BY: MR KAMARUL AMIN BIN ABDULLAH SCHOOL OF MEDICAL IMAGING FACULTY OF HEALTH SCIENCES LEARNING OUTCOMES At the end of the lesson,

More information

INVESTIGATION OF ENERGY LOSS IN A TRANSMISSION SUBSTATION USING ONITSHA 330/132KV AS A CASE STUDY F.O. Enemuoh, T.L. Alumona and C.H.

INVESTIGATION OF ENERGY LOSS IN A TRANSMISSION SUBSTATION USING ONITSHA 330/132KV AS A CASE STUDY F.O. Enemuoh, T.L. Alumona and C.H. INVESTIGATION OF ENERGY LOSS IN A TRANSMISSION SUBSTATION USING ONITSHA 330/132KV AS A CASE STUDY F.O. Enemuoh, T.L. Alumona and C.H. Aliche 1,2 nnamdi azikiwe university, awka, anambra state, nigeria.

More information

THE RUSSIAN STANDARDS AND THE OPINION ABOUT INTERNATIONAL HARMONIZATION OF ELECTROMAGNETIC STANDARDS

THE RUSSIAN STANDARDS AND THE OPINION ABOUT INTERNATIONAL HARMONIZATION OF ELECTROMAGNETIC STANDARDS It was published: International Seminar on Electromagnetic Fields. GLOBAL NEED FOR STANDARDS HARMONIZATION. October 9, 1998. Ljubljana, Slovenia.pp. 1I-6I. THE RUSSIAN STANDARDS AND THE OPINION ABOUT INTERNATIONAL

More information

Modelling of Electric and Magnetic Fields Around 132kV Transmission Line

Modelling of Electric and Magnetic Fields Around 132kV Transmission Line Acta Technica Jaurinensis Vol. 7., No.3., pp. 247-257, 2014 DOI: 10.14513/actatechjaur.v7.n3.302 Available online at acta.sze.hu Modelling of Electric and Magnetic Fields Around 132kV Transmission Line

More information

Magnetic Field Meter EM-191

Magnetic Field Meter EM-191 Magnetic Field Meter EM-191 1 Introduction Safety precautions should be taken against electric appliances in places including medical institutions, schools and residential districts, where people usually

More information

Workplace safety for demagnetizer operators

Workplace safety for demagnetizer operators Content Basics International recommendations according to ICNIRP Accident prevention regulation BGV B11 (Germany) Electromagnetic exposure of classic demagnetizers Safety concept of Maurer Magnetic AG

More information

Declaration of Compliance for the Ohio Willow Wood second generation Limb Logic Vacuum System with inductive charger

Declaration of Compliance for the Ohio Willow Wood second generation Limb Logic Vacuum System with inductive charger Declaration of Compliance for the Ohio Willow Wood second generation Limb Logic Vacuum System with inductive charger Overview Ohio Willow Wood is submitting final documentation for our inductively charged

More information

Evaluation of exposure to pulsed magnetic fields by examining the variations in the spectrum and over time with ELT-400

Evaluation of exposure to pulsed magnetic fields by examining the variations in the spectrum and over time with ELT-400 EXPOSURE LEVEL TESTER ELT-400 Application Note 1108 Evaluation of exposure to pulsed magnetic fields by examining the variations in the spectrum and over time with ELT-400 Introduction The ELT-400 is a

More information

GEISLAVARNIR RÍKISINS ICELANDIC RADIATION SAFETY AUTHORITY

GEISLAVARNIR RÍKISINS ICELANDIC RADIATION SAFETY AUTHORITY GEISLAVARNIR RÍKISINS ICELANDIC RADIATION SAFETY AUTHORITY Danish National Board of Health (Sundhedsstyrelsen) Finnish Radiation and Nuclear Safety Authority (Säteilyturvakeskus, STUK) Icelandic Radiation

More information

RF EMISSIONS COMPLIANCE REPORT. Verizon Wireless. Report Status: Verizon Wireless is Compliant

RF EMISSIONS COMPLIANCE REPORT. Verizon Wireless. Report Status: Verizon Wireless is Compliant RF EMISSIONS COMPLIANCE REPORT Verizon Wireless Site: Site ID: 199 Address: TBD 8/12/2015 Report Status: Verizon Wireless is Compliant Prepared By: Sitesafe, Inc. 200 North Glebe Road, Suite 1000 Arlington,

More information

Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web

Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web An Coimisiún um Rialáil Cumarsáide Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel +353 1 804 9600 Fax +353 1 804 9680 Email info@comreg.ie Web www.comreg.ie Programme of Measurement of Non-Ionising

More information

Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web

Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web An Coimisiún um Rialáil Cumarsáide Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel +353 1 804 9600 Fax +353 1 804 9680 Email info@comreg.ie Web www.comreg.ie Programme of Measurement of Non-Ionising

More information

Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web

Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web An Coimisiún um Rialáil Cumarsáide Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel +353 1 804 9600 Fax +353 1 804 9680 Email info@comreg.ie Web www.comreg.ie Programme of Measurement of Non-Ionising

More information

Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web

Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web An Coimisiún um Rialáil Cumarsáide Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel +353 1 804 9600 Fax +353 1 804 9680 Email info@comreg.ie Web www.comreg.ie Programme of Measurement of Non-Ionising

More information

Beskrivelse av simuleringsmodell ==> Description of simulation model

Beskrivelse av simuleringsmodell ==> Description of simulation model Infrastruktur Elkraft / Energy Side / Page: 1 av / of 6 Beskrivelse av simuleringsmodell ==> Description of simulation model General The modelled system consists of one rotary converter (synchronous-synchronous

More information

Trade of Electrician. The Transformer

Trade of Electrician. The Transformer Trade of Electrician Standards Based Apprenticeship The Transformer Phase 2 Module No. 2.1 Unit No. 2.1.10 COURSE NOTES Created by Gerry Ryan - Galway TC Revision 1 April 2000 by Gerry Ryan - Galway TC

More information

CALCULATING RADIOFREQUENCY FIELD STRENGTH SAFETY CODE 6 SITE VALIDATION

CALCULATING RADIOFREQUENCY FIELD STRENGTH SAFETY CODE 6 SITE VALIDATION CALCULATING RADIOFREQUENCY FIELD STRENGTH SAFETY CODE 6 SITE VALIDATION FOR SITE: W2352 Study conducted by: RF Designer: Henry Phan, P.Eng Henry Phan, P.Eng Report Date: August 19, 2013 Department: Radio

More information

Investigation of skin effect on coaxial cables

Investigation of skin effect on coaxial cables Investigation of skin effect on coaxial cables Coaxial cables describe a type of cables that has an inner conductor surrounded by an insulator, which is surrounded by another layer of conductor and insulator

More information