High Voltage Overhead Power Lines, 21 Georgiou Eikosari, Dali
|
|
- Maximillian Cobb
- 5 years ago
- Views:
Transcription
1 On the 22nd of July 2009 at 17:30 pm, electric and magnetic field measurements were performed for 21 Georgiou Eikosari, Dali overhead power lines. The EMF measurements were performed inside and outside the residence and in direct proximity to the overhead power line. {mosmap width='500' height='400' lat=' ' lon=' ' zoom='18' zoomtype='large' zoomnew='0' maptype='satellite' showmaptype='1' overview='0' text='overhead power line, 21 Georgiou Eikosari, Dali' tooltip='dwo' marker='1' align='center' key='abqiaaaa03cwbwhnzyjizsn-wwdqmhqctkyp5l8hb2mjngvvfkvpdgzbixqkqitrafigip chx6gplphdidvzga'} Σελίδα 1 / 7
2 The transmission towers are tall steel lattice structures that support overhead electricity conductors for power transmission. The overhead power line is rated at a nominal power of 900 MVA. At the time when the measurements were performed, the load of the overhead power line was 142 MW and 20 MVar. The Resultant Load of all three phases was % utilization of the nominal load power. Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organisations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP. Reference levels for Occupational exposure ICNIRP Frequency Electric Field Strength E (V/m) Magnetic Field Strength H (A/m) Magnetic Flux Density B (µt) 50 Hz Reference levels for General Public exposure ICNIRP Frequency Electric Field Strength E (V/m) Σελίδα 2 / 7
3 Magnetic Field Strength H (A/m) Magnetic Flux Density B (µt) 50 Hz Table 1: ICNIRP Exposure limits for Occupational and General Public exposure The maximum obtained values are represented below and compared to the ICNIRP standards for the General Public. The highest magnetic field value inside was observed in the 2nd bedroom of the residence, with value 1.80 μt and a percentage of 1.80 % as compared to the ICNIRP General Public standard. Overhead Power lines: Inside Field Measurements Measurement Point Maximum Magnetic Field (µt) at Z Height (m) Percentage of ICNIRP General Public Standard (%) 0.3m 1.75m Measurements inside the residence 1m Measurement Point A - 1st bedroom -1.64% 1.64 Measurement Point B - Bathroom -Σελίδα 3 / 7
4 % Measurement Point C 2nd bedroom % Measurement Point D 3rd bedroom % Measurement Point E Living room % Σελίδα 4 / 7
5 Measurement Point F Dining room % Measurement Point G - Kitchen % Table 2: Maximum field measurements inside Accordingly, the highest magnetic field outside was observed below the overhead power lines, with a value 1.70 μt (0 m away from the starting point) and a percentage of 1.70 % as compared to the ICNIRP General Public standard.. Overhead Power lines: Outside Field Measurements Measurement Point Maximum Magnetic Field (µt) at Z Height (m) Percentage of ICNIRP General Public Standard (%) Σελίδα 5 / 7
6 0.3m 1.75m Measurements inside the residence 1m Measurement Point H 1.22% 1.22 Measurement Point I % Measurements along the Overhead Power Line 30m Measurement Line % 1.29% % Measurements across the Overhead Power Line 30m Measurement Line % 1.14% % Table 3: Maximum field measurements outside area Σελίδα 6 / 7
7 Σελίδα 7 / 7
Overhead Power Lines: Argaki area in Moni, Limassol
The measurements were performed on the 21st of September 2011 at 11:50 am during clear weather conditions. The EMF measurements were performed inside the plot area in direct proximity to the overhead power
More informationSpecific Equipment and Area - EAC District Office Substation
On the 13th of April 2007 at 10:00 am magnetic field measurements were performed for the District Office Substation. The substation of interest is located on Mykhnon Street in Nicosia. {mosmap width='500'
More information6.2 Environmental Statement Appendices Volume N Appendix 15.1 EMF Report
The Millbrook Power (Gas Fired Power Station) Order 6.2 Environmental Statement Appendices Volume N Appendix 15.1 EMF Report Planning Act 2008 The Infrastructure Planning (Applications: Prescribed Forms
More informationELF ELECTRIC AND MAGNETIC FIELDS MEASUREMENTS IN GREECE
ELF ELECTRIC AND MAGNETIC FIELDS MEASUREMENTS IN GREECE E. Karabetsos, G. Filippopoulos, D. Koutounidis CH. Govari, N. Skamnakis Non ionizing radiation office, Greek atomic energy commission, P. O. BOX
More informationElectric and magnetic field levels around Christchurch
Electric and magnetic field levels around Christchurch M D Gledhill 1992/1 NRL Report Report NRL 1992/1 ISSN O111-753x ELECTRIC AND MAGNETIC FIELD LEVELS AROUND CHRISTCHURCH M D Gledhill National Radiation
More informationHuman Exposure Requirements for R&TTE and FCC Approval
Human Exposure Requirements for R&TTE and FCC Approval Derek Y. W. LEUNG Founding and Committee Member of EMC Chapter- IEEE-HK Requirements of Non-Specific Short Range Device (SRD) for CE Marking Radio
More informationThe Nature of Electric and Magnetic Fields 2017
The Nature of Electric and Magnetic Fields 2017 FACT SHEET 1 3 4 5 What are Electric and Magnetic Fields (EMF)? How are electricity and EMF related? Many people will have seen the attraction or repulsion
More informationCode of Practice for Proposed Mobile Phone Base Station Installations on University Premises.
Code of Practice for Proposed Mobile Phone Base Station Installations on University Premises. Introduction. Mobile phone base stations are low power (typically a few tens of watts) radio transmitters with
More informationAppendix 6-F: Electric and Magnetic Field Study Report
Draft Environmental Impact Statement Cricket Valley Energy Project Dover, NY Appendix 6-F: Electric and Magnetic Field Study Report ELECTRIC & MAGNETIC FIELDS (EMFs) STUDY REPORT For the CRICKET VALLEY
More informationTechnical Committee106 Methods for the assessment of electric, magnetic and electromagnetic fields associated with human exposure
Technical Committee106 Methods for the assessment of electric, magnetic and electromagnetic fields associated with human exposure International Electrotechnical Commission Michel Bourdages Secretary International
More informationLOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS
LOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS Peter Leipold, Klaus-Peter Panzlaff Bewag Aktiengesellschaft, Puschkinallee 52, D-12435 Berlin Tel.: +49 30 267 10 350 - Fax: +49 30 267 10 352 -
More informationAnalytical Design Optimization of 765 kv Transmission Line Based on Electric and Magnetic Fields for Different Line Configurations
Available onlinewww.ejaet.com European Journal of Advances in Engineering and Technology, 2018, 5(2): 91-98 Research Article ISSN: 2394-658X Analytical Design Optimization of 765 kv Transmission Line Based
More informationBiljana Tanatarec Doron Net d.o.o. ISO/HZN National Workshop on Social Responsibility Zagreb, 9 10 September 2010
Biljana Tanatarec Doron Net d.o.o. ISO/HZN National Workshop on Social Responsibility Zagreb, 9 10 September 2010 Introduction Working in Doron Net d.o.o. Head of DN Laboratory Doron Net is a member of
More informationYARRANLEA SOLAR PROJECT. Electromagnetic Radiation Assessment. Zenviron Document: 8013-EL-R
YARRANLEA SOLAR PROJECT Electromagnetic Radiation Assessment Zenviron Document: 8013-EL-R-160819-1 DOCUMENT DETAILS Revision History REV. DESCRIPTION PREPARED CHECKED APPROVED DATE A Initial Issue ABC
More informationEnvironmental Exposures to ELF Georg Neubauer
Environmental Exposures to ELF Georg Neubauer 1 Table of Content Environmental exposures to ELF sources Measurement methods Requirements on measurements Conclusions 2 Environmental exposure to ELF sources
More informationMagnetic Field Measurement in Residential Areas Göteborg, Borås and Mark Residential Area Measurements SEYED REZA ATEFI
Magnetic Field Measurement in Residential Areas Göteborg, Borås and Mark Residential Area Measurements Master of Science Thesis in Biomedical Engineering SEYED REZA ATEFI Department of Signals and Systems
More informationv1.0.1 March AlphaLab, Inc. All rights reserved. TriField EMF Meter Owner s Manual
v1.0.1 March 2018 2018 AlphaLab, Inc. All rights reserved. TriField EMF Meter Owner s Manual TABLE OF CONTENTS Overview... 1 Introduction... 1 Features... 1 Applications... 1 Using the TriField EMF Meter...
More informationFirst South East European Regional CIGRÉ Conference. Portoroz, Slovenia, 7 8 June 2016
First South East European Regional CIGRÉ Conference Portoroz, Slovenia, 7 8 June 2016 Assessment of new OHL of Slovak Republic Transmission System with regard to the recommendation of the Directive No.
More informationSafety Code 6 Analysis Freedom Mobile 3G & LTE Network. Radio frequency exposure for uncontrolled and controlled environment.
Safety Code 6 Analysis Freedom Mobile 3G & LTE Network Radio frequency exposure for uncontrolled and controlled environment Freedom Mobile 207 Queen's Quay West, Suite 710 Toronto, ON M5J 1A7 3655 Wesbrook
More informationReport On. RF Exposure Assessment of the Sepura plc SRG3900 with AQHB Antenna. FCC ID: XX6SRG3900UW Industry Canada ID: 8739A-SRG3900UW
Report On RF Exposure Assessment of the Sepura plc SRG3900 with AQHB Antenna FCC ID: XX6SRG3900UW Industry Canada ID: 8739A-SRG3900UW Document 75908189 Report 04 Issue 2 March 2010 TUV Product Service
More informationAdvanced Test Equipment Rentals ATEC (2832)
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) Electric and Magnetic Field Measurement For Isotropic Measurement of Magnetic and Electric Fields Evaluation of Field
More informationReducing personal EMF exposure
www.emfields-solutions.com www.powerwatch.org.uk EMFields Solutions Ltd in conjunction with Powerwatch This leaflet and information are written for the EMFields pocket PF5 meter which measures ELF and
More informationMulti Voltage Multi Circuit Transmission Tower Design to Reduce Right of Way
Indian Journal of Science and Technology, Vol 9(33), DOI: 10.17485/ijst/2016/v9i33/95239, September 2016 ISSN (Print) : 0974-6846 ISSN (Online) : 0974-5645 Multi Voltage Multi Circuit Transmission Tower
More informationT E C H N I C A L M E M O R A N D U M. ON PARTICULAR ASPECTS RELATED 400 kv TRANSMISSION
T E C H N I C A L M E M O R A N D U M ON PARTICULAR ASPECTS RELATED 400 kv TRANSMISSION Prepared by Prepared for : Dr Pieter H Pretorius, Trans-Africa Projects : Mr Henry Nawa, Senior Environmental Advisor,
More informationDeveloping and Implementing Protective Measures for ELF EMF - Sources and exposures- Rüdiger Matthes Federal Office for Radiation Protection Germany
Developing and Implementing Protective Measures for ELF EMF - Sources and exposures- Rüdiger Matthes Federal Office for Radiation Protection Germany 1 Non-ionising Radiation Ionising Radiation >0 to 300
More informationElectromagnetic environment in Electrical Hypersensitives homes and workplaces. Kjell Hansson Mild. National Institute for Working Life, Umeå, Sweden
Electromagnetic environment in Electrical Hypersensitives homes and workplaces National Institute for Working Life, Umeå, Sweden External sources: High voltage power lines, distribution lines magnetic
More informationELECTROMAGNETIC 0 Hz 300 GHz
ELECTROMAGNETIC 0 Hz 300 GHz Field characterization & occupational exposure sources Laura FILOSA 1. Organization of the NIR Module 2. European frame introduction 3. Electromagnetic field characterization
More informationELECTROMAGNETIC POLLUTION INSIDE HIGH VOLTAGE SUBSTATION
Rev. Roum. Sci. Techn. Électrotechn. et Énerg. Vol. 61, 1, pp. 178 182, Bucarest, 2016 ELECTROMAGNETIC POLLUTION INSIDE HIGH VOLTAGE SUBSTATION BILLEL ALI RACHEDI 1, ABDESSELAM BABOURI 1, ZHANG XUN 2 Key
More informationFor Isotropic Measurement of Magnetic and Electric Fields
Field Analyzers EFA-300 For Isotropic Measurement of Magnetic and Electric Fields Evaluation of Field Exposure compared to Major Standards and Guidance (selectable) Shaped Time Domain (STD) an innovative
More informationPRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another.
TRANSMISSION LINES PRELIMINARIES Generators and loads are connected together through transmission lines transporting electric power from one place to another. Transmission line must, therefore, take power
More informationAppendix I. Applicant s Audible Noise and EMF Calculations
Appendix I Applicant s Audible Noise and EMF Calculations Structure Type Predicted Intensity of Electric Fields (kv/m) at Maximum Operating Voltage Where Not Paralleling Existing Transmission Lines Line
More informationEXPOSURE to electromagnetic fields (EMFs) is not a
1800 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 3, JULY 2005 Measurements of Electric and Magnetic Fields Due to the Operation of Indoor Power Distribution Substations Anastasia S. Safigianni, Member,
More informationELF Magnetic Field Security Zones around High Voltage Power Lines
ELF Magnetic Field Security Zones around High Voltage Power Lines Carlos Lemos Antunes 1,2,3 (1) Lab. CAD/CAE, Electrical Engineering Dept, University of Coimbra Pólo II, 3030 290 Coimbra (Portugal) (2)
More informationComparison of international policies on electromagnetic fields. (power frequency and radiofrequency fields)
Comparison of international policies on electromagnetic fields (power frequency and radiofrequency fields) Comparison of international policies on electromagnetic fields (power frequency and radiofrequency
More information1. Introduction. Keywords Non-ionizing radiation, Electric field, Magnetic field, Power line, Kaduna metropolis, ICNIRP 2010 guideline
American Journal of Condensed Matter Physics, (): - DOI:.9/j.ajcmp.. Measurement and Analysis of Health Effects Due to Exposure to Non-Ionizing Radiation from High Tension Cables around Kaduna Metropolis,
More informationElectromagnetic Fields, Mobile Telephones and Health
Electromagnetic Fields, Mobile Telephones and Health Dr. Matti Rajala European Commission Directorate General for Health and Consumer Protection - Luxembourg Council Recommendation 12th July (1999/519/EC)
More informationNIR MEASUREMENTS. Principles and practices of EMF characterization and measurements
IRPA 1 1th International Congress of the International Radiation Protection Association 19th-4th October 008, Buenos Aires, Argentina RC-11 NIR MEASUREMENTS. Principles and practices of EMF characterization
More informationRF-EXPOSURE ASSESSMENT REPORT
RF-EXPOSURE ASSESSMENT REPORT EN 62311 RF-Exposure evaluation of electronic equipment Report Reference No.... : G0M-1206-2043-TEU311E-V01 Testing Laboratory... : Address... : Storkower Str. 38c 15526 Reichenwalde
More informationExperimental Study of Electromagnetic Environment in the Vicinity of High Voltage Lines
American J. of Engineering and Applied Sciences 4 (2): 209-213, 2011 ISSN 1941-7020 2011 Science Publications Experimental Study of Electromagnetic Environment in the Vicinity of High Voltage Lines 1 Wafa
More informationLow Frequency. Precision test equipment for safety in electric and magnetic fields
Low Frequency Precision test equipment for safety in electric and magnetic fields Your One-Stop Shop for Safety in Electromagnetic Fields Narda Safety Test Solutions device technologies highly simplify
More informationELECTROMAGNETIC SHIELDING PRODUCTS
ELECTROMAGNETIC SHIELDING PRODUCTS WWW.SATISHIELDING.COM SATI SHIELDING Sati Shielding S.r.l. was set up on 23 December 2015, thanks to the merger of different professional skills: marketing and organisational
More informationRegulatory Framework for RF Safety in Mauritius
Regulatory Framework for RF Safety in Mauritius Jerome LOUIS Director Engineering ICTA This Session PART I Background Base Station Site Selection Base Station authorisation process Exposure Limits adopted
More informationFidler Substation and Transmission Line
Fidler Substation and Transmission Line November 2009 Who can you contact for more information? To learn more about the proposed project you can contact: How can you provide input? We want your input so
More informationMAGNETIC FIELD METER Operator s Manual
Edition 4.4 September 2011 MAGNETIC FIELD METER 3000 Operator s Manual The MFM 3000 is a professional magnetic field instrument To make the best use of the instrument we recommend that you read this manual
More informationAnalysis of magnetic and electromagnetic field emissions produced by a MRI device
Sept. 8-1, 21, Kosice, Slovakia Analysis of magnetic and electromagnetic field emissions produced by a MRI device D. Giordano, M. Borsero, G. Crotti, M. ucca INRIM Istituto Nazionale di Ricerca Metrologica,
More informationMAGNETIC FIELD COMPUTATION DUE TO HIGH VOLTAGE POWER LINES USING EasyMAG
MAGNETIC FIELD COMPUTATION DUE TO HIGH VOLTAGE POWER LINES USING EasyMAG Tony Richard O. Almeida (1), Carlos F. R. Lemos Antunes (2) Laboratório de CAD/CAE (1, 2), I.S.R. (1) Departamento de Engenharia
More informationDESIGN OF A 45 CIRCUIT DUCT BANK
DESIGN OF A 45 CIRCUIT DUCT BANK Mark COATES, ERA Technology Ltd, (UK), mark.coates@era.co.uk Liam G O SULLIVAN, EDF Energy Networks, (UK), liam.o sullivan@edfenergy.com ABSTRACT Bankside power station
More informationPROBLEMS on Transformers
PROBLEMS on Transformers (A) Simple Problems 1. A single-phase, 250-kVA, 11-kV/415-V, 50-Hz transformer has 80 turns on the secondary. Calculate (a) the approximate values of the primary and secondary
More informationIOSH Webinar. Control of Electromagnetic Fields at work regulations 2016 Part 2 EMF exposure assessment 4 th May 2017 Julia Clark FSRP CMIOSH
IOSH Webinar Control of Electromagnetic Fields at work regulations 2016 Part 2 EMF exposure assessment 4 th May 2017 Julia Clark FSRP CMIOSH www.linkmicrotek.com Previously Webinar part one covered: Definition
More informationResearch Activities Plan. Appendix K Magnetic Fields from Submarine Cables
VOWTAP Research Activities Plan Appendix K Magnetic Fields from Submarine Cables December 2013 Electrical Engineering and Computer Science Practice Virginia Offshore Wind Technology Advancement Project
More informationHarmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits
WREF 01 Paper # 048 Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits Ketut Dartawan Ricardo Austria, Le Hui and Mark Suehiro* Pterra Consulting Maui Electric Company*
More informationWLAN. Date: 20 October 2016
WLAN Date: 20 October 2016 A wireless local area network (WLAN) allows computers and laptops to be connected to each other, to peripheral devices (printers, scanners etc.) and to an Internet access point.
More informationSimulation Approach in Evaluating the Electromagnetic Fields from the New Lines of Extra High Voltage (EHV) Circuits Near Residential Area in Malaysia
European Journal of Scientific Research ISSN 1450-216X Vol.40 No.2 (2010), pp.189-198 EuroJournals Publishing, Inc. 2010 http://www.eurojournals.com/ejsr.htm Simulation Approach in Evaluating the Electromagnetic
More informationSafety Code 6 Compliance Analysis of NLA031. Study conducted by Eastlink, Radio Frequency Engineering Department
Safety Code 6 Compliance Analysis of NLA031 Study conducted by Eastlink, Radio Frequency Engineering Department Oct 2016 Contents Description of site... 2 Summary... 4 Simulation and Software... 4 Definitions...
More informationBE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %
BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and
More informationNational Radiation Commission P.O.Box 743, Arusha, Tanzania.
Preliminary Measurements of Electromagnetic Radiation Levels from a Radio Transmitter and Cellular Phone Base Stations Randomly Selected at Dar es Salaam City in Tanzania M. M. Nyaruba 1 and J. B. Ngatunga
More informationRadio Frequency Emissions Analysis Report Sprint Wireless Water Tank Facility
Radio Frequency Emissions Analysis Report Sprint Wireless Water Tank Facility Site ID: BS3XC490 Site Name: Cedar St. Water Tank Address: 396 Cedar Street, Ashland, MA 0171 Latitude: 4.35300 Longitude:
More informationCity of Medicine Hat Electric Utility
Decision 2014-349 Transmission Line MH-20L Upgrade Project December 17, 2014 The Alberta Utilities Commission Decision 2014-349: Transmission Line MH-20L Upgrade Project Application No. 1610463 Proceeding
More informationSafety Evaluation Within a Magnetic Field Environment
EXPOSURE LEVEL TESTER ELT-400 Safety Evaluation Within a Magnetic Field Environment Direct evaluation of field exposure in comparison with major standards and regulations such as Directive 2013/35/EU for
More informationExam 3 Review Session
Exam 3 Review Session I will hold a review for Exam 3 which covers Chapters 27, 28, 29 and 30, on Wednesday November 7 th at 7:15pm in MPHY 205. Exam 3 will be given in class on Thursday, November 8 th.
More informationAC Magnetic Field Survey Report
AC Magnetic Field Survey Report of Literature Building - 3 University of California San Diego for University of California San Diego La Jolla, California Report Date: February 15, 21 FMS Ref: 21-182 FIELD
More informationMeasurements of Exposures Around Vodafone New Zealand Limited Cellsites from June 2012 to May 2013
Measurements of Exposures Around Vodafone New Zealand Limited Cellsites from June 2012 to May 2013 This report was prepared for: Vodafone New Zealand Limited Private Bag 92161 AUCKLAND By M Dirksen Reviewed
More informationEMF risk for operators mounting, adjusting and maintaining base stations
Environmentalist (2007) 27:545 549 DOI 10.1007/s10669-007-9062-3 EMF risk for operators mounting, adjusting and maintaining base stations T. Shalamanova Æ I. Iliev Æ M. Ivanova Æ M. Israel Published online:
More informationTRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K
UNIT II TRANSFORMERS PART A 1. Define a transformer? A transformer is a static device which changes the alternating voltage from one level to another. 2. What is the turns ratio and transformer ratio of
More informationITU-T Study Group 5. EMF Environmental Characterization
International Telecommunication Union EMF Environmental Characterization Jeffrey Boksiner Senior Consultant, Telcordia Technologies, Inc Workshop on: EMC, safety and EMF effects in telecommunications o
More informationThe Survey of Electromagnetic Environment near RF Transmitters
The Survey of Electromagnetic Environment near RF Transmitters Valeriu David 1, Alexandru Salceanu, Mihai Cretu 3, Eduard Lunca 4 1 "Gh. Asachi" Technical University, Iasi, Faculty of Electrical Engineering,
More informationThe SEMONT Network Utilization for the Lowfrequency
The SEMONT Network Utilization for the Lowfrequency EMF Monitoring Nikola Djuric, Jelena Bjelica, Dragan Kljajic, Miodrag Milutinov, Karolina Kasas-Lazetic, Danka Antic Faculty of Technical Sciences, University
More informationSubject: AC ELF EMF EMC Magnetic Field Testing for a Sauna Heater
EMF Measurements, Surveys & Risk Assessment EMF Mitigation Shielding & Cancellation E-Mail: dvitale@vitatech.net www.vitatech.net VitaTech Electromagnetics, LLC 115 Juliad Ct., Suite 105 Fredericksburg,
More informationClass: RPT Doc. no: RE Rev: A Date: Approved by: JCP
Class: RPT Doc. no: 264001-RE Rev: A Date: 2007-04-25 Approved by: JCP Power Density in Proximity to a 4000/4100 Transceiver using any Terma SD, HG or LA SCANTER 4000/4100 Template no: 199997-FA, Rev.
More informationMr. Aaron Zack Tel: Subject: AC ELF EMF EMC Magnetic Field Testing for a Sauna Heater
115 Juliad Court, Suite 105 Fredericksburg VA, 22406 Phone 540 286 1984 Fax 540 268 1865 www.vitatech.net November 14th, 2012 Mr. Aaron Zack Tel: 877.292.0020 President/CEO Email: azack@sunlighten.com
More informationFatima Michael college of Engineering and Technology
Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric
More informationin Midtown EXCEL HOMES LOCKEPORT SECOND FLOOR 762 sq. ft. MAIN FLOOR 762 sq. ft. LANED DUPLEX TWO STOREY excelhomes.ca Nook 12'11" x 9'0"
Nook 12'11" x 9'0" Bedroom 2 9'4" x 9'10" Bedroom 3 9'4" x 9'8" Half DW 12'11" x 13'6" 12'0" x 13'0" Down Up Laundry W D Down BATHROOMS 2.5 BEDROOMS 3 LANED DUPLEX TWO STOREY FINISHED SQ. FT. 1524 DEVELOPED
More informationReport On. Radio Frequency Exposure Testing of the Winland Electronics, Inc. EnviroAlert Electronic Multi-Zone Environmental Alarm System
America Report On Radio Frequency Exposure Testing of the Winland Electronics, Inc. EnviroAlert Electronic Multi-Zone Environmental Alarm System EN62311 January 2008 AS/NZS 2772.2:2011 October 2017 REPORT
More informationSelective and broadband low frequency field analysis
ELECTRIC AND MAGNETIC FIELD ANALYZER EHP-50C Selective and broadband low frequency field analysis Electric and magnetic low frequency field analysis up to 100 khz Isotropic measurement with a dynamic range
More informationCopper and Electricity: Transformers and. the Grid. Transformers
PHYSICS Copper and Electricity: Transformers and 16-18 YEARS the Grid Transformers Using transformers We use transformers to change the size of a voltage. We can step the voltage down from a high voltage
More informationRF Field Strength Meter TDM-200. Instruction Booklet. Laplace Instruments Ltd. Supplied by:
Supplied by: Laplace Instruments Ltd 3B, Middlebrook Way CROMER, Norfolk NR27 9JR UK Tel: 01263 51 51 60 Fax: 01263 51 25 32 E-mail: tech@laplace.co.uk RF Field Strength Meter TDM-200 Instruction Booklet
More informationSECTION 26. Glossary of Terms and Abbreviations
SECTION 26 Glossary of Terms and Abbreviations Prepared for the BioInitiative Working Group July 2007 Absorption. In radio wave propagation, attenuation of a radio wave due to dissipation of its energy,
More information*X025/11/01* X025/11/01 ELECTRONIC AND ELECTRICAL FUNDAMENTALS INTERMEDIATE 2 NATIONAL QUALIFICATIONS 2015 WEDNESDAY, 3 JUNE 9.00 AM 11.
X05//0 NATIONAL QUALIFICATIONS 05 WEDNESDAY, JUNE 9.00 AM.0 AM ELECTRONIC AND ELECTRICAL FUNDAMENTALS INTERMEDIATE 00 marks are allocated to this paper. Answer all questions in Section A (50 marks). Answer
More informationExecutive Summary: Report on Health Canada Survey of Ultraviolet Radiation and Electric and Magnetic Fields from Compact Fluorescent Lamps
Executive Summary: Report on Health Canada Survey of Ultraviolet Radiation and Electric and Magnetic Fields from Compact Fluorescent Lamps Lasers and Electro-Optics Division Electromagnetics Division Consumer
More informationHarmonic resonances due to transmission-system cables
International Conference on Renewable Energies and Power Quality (ICREPQ 14) Cordoba (Spain), 8 th to 1 th April, 214 Renewable Energy and Power Quality Journal (RE&PQJ) ISSN 2172-38 X, No.12, April 214
More informationSNC0080 Abbott & Iber
SNC0080 Abbott & Iber Municipal Review and Concurrence of an Antenna System Application Public Notification Package Wireless Communications Site 145 Iber Rd., Ottawa, Ontario, K2S 1E7 Purpose This information
More informationTechnical Note 2. Standards-compliant test of non-ionizing electromagnetic radiation on radar equipment
Technical Note 2 Standards-compliant test of non-ionizing electromagnetic radiation on radar equipment Technical Note: Standards-compliant test of non-ionizing electromagnetic radiation on radar equipment
More informationCHAPTER 6 ALTERNATING CURRENT
HDR102 PHYSICS FOR RADIOGRAPHERS 1 CHAPTER 6 ALTERNATING CURRENT PREPARED BY: MR KAMARUL AMIN BIN ABDULLAH SCHOOL OF MEDICAL IMAGING FACULTY OF HEALTH SCIENCES LEARNING OUTCOMES At the end of the lesson,
More informationINVESTIGATION OF ENERGY LOSS IN A TRANSMISSION SUBSTATION USING ONITSHA 330/132KV AS A CASE STUDY F.O. Enemuoh, T.L. Alumona and C.H.
INVESTIGATION OF ENERGY LOSS IN A TRANSMISSION SUBSTATION USING ONITSHA 330/132KV AS A CASE STUDY F.O. Enemuoh, T.L. Alumona and C.H. Aliche 1,2 nnamdi azikiwe university, awka, anambra state, nigeria.
More informationTHE RUSSIAN STANDARDS AND THE OPINION ABOUT INTERNATIONAL HARMONIZATION OF ELECTROMAGNETIC STANDARDS
It was published: International Seminar on Electromagnetic Fields. GLOBAL NEED FOR STANDARDS HARMONIZATION. October 9, 1998. Ljubljana, Slovenia.pp. 1I-6I. THE RUSSIAN STANDARDS AND THE OPINION ABOUT INTERNATIONAL
More informationModelling of Electric and Magnetic Fields Around 132kV Transmission Line
Acta Technica Jaurinensis Vol. 7., No.3., pp. 247-257, 2014 DOI: 10.14513/actatechjaur.v7.n3.302 Available online at acta.sze.hu Modelling of Electric and Magnetic Fields Around 132kV Transmission Line
More informationMagnetic Field Meter EM-191
Magnetic Field Meter EM-191 1 Introduction Safety precautions should be taken against electric appliances in places including medical institutions, schools and residential districts, where people usually
More informationWorkplace safety for demagnetizer operators
Content Basics International recommendations according to ICNIRP Accident prevention regulation BGV B11 (Germany) Electromagnetic exposure of classic demagnetizers Safety concept of Maurer Magnetic AG
More informationDeclaration of Compliance for the Ohio Willow Wood second generation Limb Logic Vacuum System with inductive charger
Declaration of Compliance for the Ohio Willow Wood second generation Limb Logic Vacuum System with inductive charger Overview Ohio Willow Wood is submitting final documentation for our inductively charged
More informationEvaluation of exposure to pulsed magnetic fields by examining the variations in the spectrum and over time with ELT-400
EXPOSURE LEVEL TESTER ELT-400 Application Note 1108 Evaluation of exposure to pulsed magnetic fields by examining the variations in the spectrum and over time with ELT-400 Introduction The ELT-400 is a
More informationGEISLAVARNIR RÍKISINS ICELANDIC RADIATION SAFETY AUTHORITY
GEISLAVARNIR RÍKISINS ICELANDIC RADIATION SAFETY AUTHORITY Danish National Board of Health (Sundhedsstyrelsen) Finnish Radiation and Nuclear Safety Authority (Säteilyturvakeskus, STUK) Icelandic Radiation
More informationRF EMISSIONS COMPLIANCE REPORT. Verizon Wireless. Report Status: Verizon Wireless is Compliant
RF EMISSIONS COMPLIANCE REPORT Verizon Wireless Site: Site ID: 199 Address: TBD 8/12/2015 Report Status: Verizon Wireless is Compliant Prepared By: Sitesafe, Inc. 200 North Glebe Road, Suite 1000 Arlington,
More informationAbbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web
An Coimisiún um Rialáil Cumarsáide Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel +353 1 804 9600 Fax +353 1 804 9680 Email info@comreg.ie Web www.comreg.ie Programme of Measurement of Non-Ionising
More informationAbbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web
An Coimisiún um Rialáil Cumarsáide Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel +353 1 804 9600 Fax +353 1 804 9680 Email info@comreg.ie Web www.comreg.ie Programme of Measurement of Non-Ionising
More informationAbbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web
An Coimisiún um Rialáil Cumarsáide Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel +353 1 804 9600 Fax +353 1 804 9680 Email info@comreg.ie Web www.comreg.ie Programme of Measurement of Non-Ionising
More informationAbbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web
An Coimisiún um Rialáil Cumarsáide Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel +353 1 804 9600 Fax +353 1 804 9680 Email info@comreg.ie Web www.comreg.ie Programme of Measurement of Non-Ionising
More informationBeskrivelse av simuleringsmodell ==> Description of simulation model
Infrastruktur Elkraft / Energy Side / Page: 1 av / of 6 Beskrivelse av simuleringsmodell ==> Description of simulation model General The modelled system consists of one rotary converter (synchronous-synchronous
More informationTrade of Electrician. The Transformer
Trade of Electrician Standards Based Apprenticeship The Transformer Phase 2 Module No. 2.1 Unit No. 2.1.10 COURSE NOTES Created by Gerry Ryan - Galway TC Revision 1 April 2000 by Gerry Ryan - Galway TC
More informationCALCULATING RADIOFREQUENCY FIELD STRENGTH SAFETY CODE 6 SITE VALIDATION
CALCULATING RADIOFREQUENCY FIELD STRENGTH SAFETY CODE 6 SITE VALIDATION FOR SITE: W2352 Study conducted by: RF Designer: Henry Phan, P.Eng Henry Phan, P.Eng Report Date: August 19, 2013 Department: Radio
More informationInvestigation of skin effect on coaxial cables
Investigation of skin effect on coaxial cables Coaxial cables describe a type of cables that has an inner conductor surrounded by an insulator, which is surrounded by another layer of conductor and insulator
More information