MN026005EN. EAFR-101S Arc Point Sensor Relay User Manual

Size: px
Start display at page:

Download "MN026005EN. EAFR-101S Arc Point Sensor Relay User Manual"

Transcription

1 MN0005EN EAFR-0S Arc Point Sensor Relay User Manual

2 DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED IMPLIED, INCLUDING WARRANTIES OF FITNESS F A PARTICULAR PURPOSE MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. DCAUTION D ELECTRICAL EQUIPMENT SHOULD BE INSTALLED, OPERATED, SERVICED, AND MAINTAINED ONLY BY QUALIFIED PERSONNEL. LOCAL SAFETY REGULATIONS SHOULD BE FOLLOWED. NO RESPONSIBILITY IS ASSUMED BY EATON F ANY CONSEQUENCES ARISING OUT OF THE USE OF THIS MATERIAL. ii

3 MN0005EN Contents. INTRODUCTION.... Abbreviations.... GENERAL.... EAFR-0S Features.... Simplified Block Diagram.... OPERATION AND CONFIGURATION.... LED Indicator Functions.... LED Operation Quick Guide...5. Push-button Description...5. Reset....5 Dipswitch Settings Non-volatile Memory.... ARC SENSS.... Arc Light Point Sensor EAFR SYSTEM SELF-SUPERVISION APPLICATION EXAMPLES MV or LV Double Busbar Application with Current and Light condition...8. Circuit Breaker Failure Protection (CBFP)...9. CONNECTIONS Outputs...0. Inputs...0. Auxiliary Voltage WIRING DIAGRAM DIMENSIONS AND INSTALLATION TESTING Carrying Out Testing in the Light Only Mode Carrying Out Testing in Light and Current Mode Testing the Arc Flash Protection Unit Operation Time Test Plan Example...5. TROUBLESHOOTING GUIDE... 5 iii

4 MN0005EN. TECHNICAL DATA Protection...5. Auxiliary Voltage.... Trip Relays T, T, and T.... Binary Output BO, BO, and BO....5 Binary Inputs BI, BI, BI, BI, BI5, and BI Disturbance Tests.... Voltage Tests....8 Mechanical Tests....9 Casing and Package....0 Environmental Conditions.... DERING CODES... iv

5 . Introduction. Introduction Read these instructions carefully and inspect the equipment to become familiar with it before trying to install, operate, service, or maintain it. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. Local safety regulations should be followed. No responsibility is assumed by Eaton for any consequences arising out of the use of this material. Eaton reserves right to changes without further notice.. Abbreviations CB Circuit breaker CBFP EMC Circuit breaker failure protection Electromagnetic compatibility EPROM Erasable programmable read only memory HW Hardware LED LV Light emitting diode Low voltage ms Millisecond MV NC NO PMSG Medium voltage Normally closed Normally open Permanent magnet synchronous generator Rx Receiver SF System failure SW Software Tx Transceiver up Microprocessor. General The Eaton Arc Flash Relay 0S (EAFR-0S) is a sophisticated micro-processor based arc flash protection relay including complete self-supervision functionality. It is designed to minimize the damage caused by an arcing fault (arc flash) by sensing light from the point sensor and tripping the circuit breaker sourcing the fault current. The EAFR-0S complete system self-supervision function provides the highest level of dependability by continuously monitoring all internal system functions along with external connections. The EAFR-0S is designed according to the latest protection relay standards and is therefore suitable for installations in rough environments, such as utility, traditional or renewable power plants, off shore, marine, oil and gas, mining, steel, or any other heavy industry applications. It is also well suited for commercial and institutional electrical systems. The EAFR-0S is suitable for either medium voltage or low voltage switchgear and motor control center applications in both new and retrofit installations.. EAFR-0S Features The EAFR-0S is a multipurpose arc flash protection relay that can receive light from four different channels of light point sensors and can be applied for variety of applications. The EAFR-0S can be used as a stand-alone relay or as part of a more complex arc protection system through the binary bus. Main features of EAFR-0S: (0-0) Vac / (5-50) Vdc auxiliary power supply; Four arc point sensor channels (S, S, S, and S); Six binary inputs (BI, BI, BI, BI, BI5, and BI) nominal voltage of Vdc; Three normally open trip relay outputs with direct trip circuit rated contacts (T, T, and T); One normally open electronic lock-out trip relay with direct trip circuit rated contacts (T); Three VDC binary outputs (BO, BO, and BO); One system failure relay, form C output (SF); indication LEDs; and One push-button (SET).

6 . General Figure. The EAFR-0S Arc Protection IO Relay.

7 . General. Simplified Block Diagram The EAFR-0S simplified block diagram (see Figure ) shows the main components of the EAFR-0S relay. Figure. EAFR-0S Simplified Block Diagram. X X 5 5 BI BI BI BI EN SW 0 BI5 T 0 LATCH 9 9 T 8 EN LATCH SW 8 BI T up BO 5 SF 5 BO BO Uaux Vdc Vdc Vdc Power Error Vdc Vac/dc Vdc S 0 9 S 8 Vdc 5Vdc X Self supervision Control and power supply S 5 S ON OFF 8 5 T,T T,T BI BI BI BI BI5 BI BO BO BO S S S S Light / Light and Current S: Light / Light and Current Latch / Non Latch 00 / 50 ms Configuration Select

8 . Operation and Configuration. Operation and Configuration. LED Indicator Functions TThe EAFR-0S contains indication LEDs. A user definable text pocket can be slid in under the label for identifying each LED function (except POWER and ERR LEDs). LEDs are located at the front plate of the relay for clear viewing without a need for opening doors. During power up, the relay performs a LED test. All LEDs are turned on for two seconds and then off. Only the blue POWER LED will remain on. After powered up, the relay goes into protection mode in 50 ms even while the LED test is being performed. During normal operation, only the blue power LED is ON. The sensor LEDs are off during the inactive condition. If a point arc sensor is activated, the corresponding sensor channel LED will turn on if the activation is longer than.5 ms. The sensor LED activation function is latched (steady light). To clear the LED, the SET button should be pressed. In case of a loose sensor wire and binary input wires or configuration mismatch (new sensor attached without running auto-configuration system setup [see Section..) situation, the corresponding LED for that sensor will start flashing and the ERR LED will activate. The Binary I/O LEDs are indicating the I/O-line status. If any of the lines become active for more than.5 ms, the corresponding LED will turn on (latch). In a trip situation, the corresponding trip LED will turn on. Trip outputs are controlled by the dipswitch settings (see Section.5). All activation and trip indication LEDs are latched, even if the dipswitch setting is in the non-latched mode. They have to be cleared by pushing the SET button. LED indications are stored in non-volatile EPROM memory for identifying the trip information in case the auxiliary power is lost. When re-powering the relay after power supply loss, the actual LED status can be visualized from the front of the relay.

9 . Operation and Configuration. LED Operation Quick Guide Table. LED Operation Quick Guide. LED Off Steady On Blinking Action if Abnormal POWER - Blue Auxiliary supply disconnected. Auxiliary power connected. N/A Check the power source. ERR - Red System healthy. System failure. Configuration mismatch. Protection partly operational. T, and T - Red Normal status. Trip relays T and T activated. T, and T - Red Normal status. Trip relays T and T activated. N/A N/A Verify system condition. See Sections : Troubleshooting Guide and 5: System Selfsupervision. Check the reason for trip. Clear the fault and reset indications by pushing SET button. Check the reason for trip. Clear the fault and reset indications by pushing SET button. BI - Amber Normal status. Binary input activated. Binary input has loose connection. Check the binary input wiring. BI - Amber Normal status. Binary input activated. Binary input has loose connection. Check the binary input wiring. BI - Amber Normal status. Binary input activated. Binary input has loose connection. Check the binary input wiring. BI - Amber Normal status. Binary input activated. Binary input has loose connection. Check the binary input wiring. BI5 - Amber Normal status. Binary input 5 activated. Binary input 5 has loose connection. Check the binary input wiring. BI - Amber Normal status. Binary input activated. Binary input has loose connection. Check the binary input wiring. BO - Amber Normal status. Binary Output activated. N/A N/A BO - Amber Normal status. Binary Output activated. N/A N/A BO - Amber Normal status. Binary Output activated. N/A N/A S - Amber Normal status. Sensor channel activated by light information S - Amber Normal status. Sensor channel activated by light information. S - Amber Normal status. Sensor channel activated by light information. S - Amber Normal status. Sensor channel activated by light information Sensor channel has loose connection or the system set-up was not performed. Also activated by pressure information. Sensor channel has loose connection or system set-up not performed. Also activated by pressure information. Sensor channel has loose connection or system set-up not performed. Also activated by pressure information. Sensor channel has loose connection or system set-up not performed. Also activated by pressure information. Check why the sensor activated, check the sensor wire connection, or perform the system set-up (see Section..: Auto-Configuration (System Setup). Check why the sensor activated, or check the sensor wire connection, or perform system set-up (see Section..: Auto-Configuration (System Setup). Check why the sensor activated, or check the sensor wire connection, or perform system set-up (see Section..: Auto-Configuration (System Setup). Check why the sensor activated, check the sensor wire connection, or perform system set-up (see Section..: Auto-Configuration (System Setup).. Push-button Description The EAFR-0S contains one single push-button (SET) that can be used for all operational functions of the relay. The push-button is used to initialize the auto-configuration of the system (see Section..) and for resetting the indicators and latched output relays... Auto Configuration (System Setup) When all sensors and binary lines have been connected, an auto-configuration procedure must be executed. The initialization sequence is performed by pressing the Set button for two seconds. The EAFR-0S sensor LEDs and all binary LEDs start blinking. The relay scans these inputs to see if they are connected and when an input is detected, the corresponding LEDs are illuminated to mark that a connection was found. The inputs without connection continue blinking during the remaining three seconds. After five seconds, all LEDs are turned off. During this system setup, the dipswitch setting are also stored in non-volatile memory. All sensor inputs will remain operational even when they are not auto-configured. The auto-configuration is only used for self-supervision purposes. NNote: To redo auto-configuration for a relay containing less connections (binary inputs/outputs or sensors) than in a previously memorized set-up, a dip-switch (anyone) must be moved back and forth prior to performing auto-configuration. The timeout allowing a new configuration is one minute. Reconfiguration with more connections is allowed without moving a dipswitch. 5

10 . Operation and Configuration. Reset All LED indications and latched trip relays are reset by pressing the SET button for one second. Otherwise, the latched trip relays will remain activated until auxiliary power is disconnected. All LED indications will remain active until reset is performed by the operator, even when auxiliary power supply is disconnected (see Section.: Non-volatile Memory)..5 Dipswitch Settings EAFR-0S functionality, such as tripping logic, is configured using dipswitch settings. Different trip configurations can be easily programmed by selecting the appropriate dipswitch positions. This gives users the flexibility to change. settings dependent on the application. Tripping may be selected based on arc light only or arc light and current thresholds. Current threshold or other tripping criteria may be applied to binary input BI for blocking a trip caused by natural light sources. Also, the CBFP configuration may be enabled using the dipswitches (dipswitch number is enabling the CBFP function for corresponding configuration selections). Dipswitches through are used as configuration selection. The configuration number is according to binary arithmetic. Switch equals a count of, switch equals a count of, switch equals a count of, and switch equals a count of five. Dipswitches are located at the back of the relay for easy access (see Figure : EAFR-0S Dipswitch SW and Table : EAFR-0S Dipswitch Setting Selection for details of settings). Figure. EAFR-0S Dipswitch SW. Configuration Select: Light S: Light Latch 8 00 ms 5 50 ms Light and Current Light and Current Non Latch Table. EAFR-0 Dipswitch Setting Selection. Dipswitch Function Selection ON (Left Position) OFF (Right Position) 8 Point sensor channels S, S, S trip criteria. S Latch or non-latch for trip relays T and T. Trip on light only. (L) Trip on light and over-current. (L+C) Both signals are required simultaneously to trip. Point sensor channel S trip criteria. Trip on light only. (L) Trip on light and over-current. (L+C) T and T operate as latched. NNote: Both signals are required simultaneously to trip. T and T operate as non-latched. Trip relay T is always latched. Binary output BO function is always non-latched. 5 CBFP time setting. CBFP time is set to 00 ms. CBFP time is set to 50 ms. Configuration selection. Refer to Sections.5.0 and. Refer to Sections.5. and. Configuration selection. Refer to Sections.5. and. Refer to Sections.5. and. Configuration selection. Refer to Sections.5. and. Refer to Sections.5. and. Configuration selection. Refer to Sections.5.0 and. Refer to Sections.5. and.

11 . Operation and Configuration Figure. EAFR-0S Configuration Selection. Configuration Select: Light and Current Light and Current Non Latch Light 8 S: Light Latch 00 ms 5 50 ms.5. Configuration Select Dipswitch Settings This section describes the available configurations that are available using the Configuration Select through dipswitches..5.. Configuration Selection The EAFR-0S logic Configuration is mainly utilized in selective arc protection solutions. The point sensor S monitors the outgoing feeder cable compartment. The point sensor S monitors the corresponding feeder breaker compartment and busbar compartment. Trip contact T is responsible for tripping circuit breaker of the outgoing feeder. The detailed instruction is described in EAFR Standard Arc Configurations booklet. Table. General Trip Logic for the EAFR-0S Standard Arc Configuration. Tripping Signals Fault Location T T T BO BO BO S x x S x x x S x x S x x x

12 . Operation and Configuration Figure 5. EAFR-0S Configuration Selection. Light Light Latch 00 ms 8 5 Light and Current Light and Current S: Non Latch 50 ms Configuration Select:.5.. Configuration Selection. The EAFR-0S logic Configuration is utilized in selective arc protection solution. S is used for monitoring the incoming feeder breaker compartment. S monitors the reserve busbar. S monitors the main busbar compartment. The contact T is responsible for tripping the section circuit breaker. T is responsible for tripping the tie circuit breaker. BI and BI are responsible for recognizing the incoming circuit breaker position. BI receives over-current information from the EAFR-0P of the incoming feeder. BI, BI5, and BI are used for sending light information from a different location of the busbar. BO, BO, and BO send arc fault information to incoming feeder units and the intermediate units. Table. General Trip Logic for the EAFR-0S Standard Arc Configuration. Tripping Signals Fault Location T T T BO BO BO S x x x x x x S x x x x S x x x x x 8

13 . Operation and Configuration Figure. EAFR-0S Configuration Selection. Light 8 Light and Current Light Light and Current S: Latch Non Latch 00 ms 5 50 ms Configuration Select:.5.. Configuration Selection The EAFR-0S logic Configuration is very similar to Configuration. S is used for monitoring the incoming feeder breaker compartment. S monitors the reserve busbar. S monitors the main busbar compartment. The contact T is responsible for tripping the section circuit breaker. T is responsible for tripping the tie circuit breaker. BI and BI are responsible for recognizing the incoming circuit breaker position. BI receives over-current information from the EAFR-0P of the incoming feeder. BI, BI5, and BI are used for sending light information from the different location of the busbars. BO, BO, and BO send arc fault information to the incoming feeder units and intermediate units. Table 5. General Trip Logic for the EAFR-0S Standard Arc Configuration. Tripping Signals Fault Location T T T BO BO BO S x x x x x x S x x x x S x x x x 9

14 . Operation and Configuration Figure. EAFR-0S Configuration Selection. Configuration Select: Light and Current Light and Current Non Latch Light 8 S: Light Latch 00 ms 5 50 ms.5.. Configuration Selection The EAFR-0S logic Configuration is used as the intermediate unit. Sensors are monitoring the section circuit breaker and the busbar between the section circuit breaker. BI and BI receive over-current information from the two main busbar sections respectively. BO and BO represent the arc fault detected at both main busbar sections. Table. General Trip Logic for the EAFR-0S Standard Arc Configuration. Tripping Signals Fault Location T T T BO BO BO S x x x S x x x x x S x x x S x x x 0

15 . Operation and Configuration Figure 8. EAFR-0S Configuration Selection 5. Configuration Select: Light 8 S: Light Latch 00 ms 5 50 ms Light and Current Light and Current Non Latch.5..5 Configuration Selection 5 The EAFR-0S logic Configuration 5 is used in the single busbar arc protection solution. Sensors are monitoring the section circuit breaker and the busbar between the section circuit breaker. BI and BI receive the MT signal from both incoming EAFR-0P relays. BI and BI receive overcurrent information from both incoming EAFR-0P relays. BO and BO send detected arc fault information from the busbar and section CB to both incoming EAFR-0P relays. Table. General Trip Logic for the EAFR-0S Standard Arc Configuration 5. Tripping Signals Fault Location T T T BO BO BO S x x x x S x x x x x S x x x x S x x x x

16 . Operation and Configuration Figure 9. EAFR-0S Configuration Selection. S S S S BI BI BI BI SW/8 SW/8 SW/8 T T T BO BO BO BI5 BI Configuration Select: SW Light 8 S: Light Latch 00 ms 5 50 ms Light and Current Light and Current Non Latch.5.. Configuration Selection The EAFR-0S logic Configuration is used in the double busbar without BS BC arc protection solution. Sensors are monitoring the incoming circuit breaker, main busbar, and reserve busbar. S monitors the incoming CB. S monitors reserve busbar. S monitors the main busbar. BI and BI are responsible for recognizing the incoming circuit breaker position. BI receives over-current information from the EAFR-0P of incoming feeder. BI, BI5, and BI are used for sending light information from a different location of the busbar.

17 . Operation and Configuration Figure 0. EAFR-0S Configuration Selection. S SW/ SW/5 00ms!SW/5 50ms S S S BI BI SW/8 SW/8 SW/8 T T T BO BI BI BI5 BI SW/8 BO BO SW SW/8 Configuration Select: Light 8 Light and Current S: Light Light and Current Latch Non Latch 00 ms 5 50 ms.5.. Configuration Selection The EAFR-0S logic Configuration is utilized in the selective arc protection solution. The point sensor S monitors the outgoing feeder cable compartment. S is used for monitoring the corresponding feeder breaker compartment. S and S monitor the busbar compartment. The contact T is responsible for tripping the circuit breaker of the outgoing feeder. BI receives over-current information from the EAFR-0P of the incoming feeder. BO sends light information to the EAFR-0P of the incoming feeder when there is any arc fault detected by the EAFR-0S.

18 . Operation and Configuration Figure. EAFR-0S Configuration Selection 8. SW/8 SW/8 SW/8 00ms!SW/5 50ms T T T BO 5 BO BO SW Configuration Select: Light and Current Light and Current Non Latch Light 8 S: Light Latch 00 ms 5 50 ms.5..8 Configuration Selection 8 The EAFR-0S logic Configuration 8 is utilized in the selective arc protection solution. The point sensor S monitors the outgoing feeder cable compartment. S is used for monitoring the corresponding feeder breaker compartment. S and S monitor the busbar compartment. The contact T is responsible for tripping the circuit breaker of the outgoing feeder. BI receives over-current information from the EAFR-0P of the incoming feeder. BO sends light information to the EAFR-0P of incoming feeder when there is any arc fault detected by EAFR-0S. The CBFP module is applied in this configuration.

19 . Operation and Configuration Figure. EAFR-0S Configuration Selection 9. S S S S BI BI BI BI BI5 SW/8 SW/8 SW/8 SW/8 SW/5!SW/5 SW/5!SW/5 T T T BO BO BO BI SW/ SW/5!SW/5 Configuration Select: SW Light 8 Light and Current S: Light Light and Current Latch Non Latch 00 ms 5 50 ms.5..9 Configuration Selection 9 The EAFR-0S logic Configuration 9 is utilized in the selective arc protection solution. S is used for monitoring the incoming feeder breaker compartment. S monitors the reserve busbar. S monitors the main busbar compartment. The contact T is responsible for tripping the section circuit breaker. T is responsible for tripping the tie circuit breaker. BI and BI are responsible for recognizing the incoming circuit breaker position. BI receives over-current information from the EAFR0P of the incoming feeder. BI, BI5, and BI are used for sending light information from different locations of the busbars. BO, BO, and BO send arc fault information to the incoming feeder units and intermediate units. The CBFP feature is applied in this configuration. 5

20 . Operation and Configuration Figure. EAFR-0S Configuration Selection 0. S S S S BI BI BI BI BI5 SW/8 SW/8 SW/8 SW/8 SW/5!SW/5 SW/5!SW/5 T T T BO BO BO BI SW/ SW/5!SW/5 Configuration Select: SW Light 8 Light and Current S: Light Light and Current Latch Non Latch 00 ms 5 50 ms.5..0 Configuration Selection 0 The EAFR-0S logic Configuration 0 is very similar to Configuration 9. S is used for monitoring the incoming feeder breaker compartment. S monitors the reserve busbar. S monitors the main busbar compartment. The contact T is responsible for tripping the section circuit breaker. T is responsible for tripping the tie circuit breaker. BI and BI are responsible for recognizing the incoming circuit breaker position. BI receives over-current information from the EAFR-0P of the incoming feeder. BI, BI5, and BI are used for sending light information from a different location of the busbar. BO, BO, and BO send arc fault information to the incoming feeder units and intermediate units. The CBFP feature is applied into this configuration.. Non-volatile Memory All critical system data, including dipswitch settings and auto-configuration file described in Section.., are stored in EPROM non-volatile memory to ensure correct operation and full self-supervision, even if auxiliary power is temporarily lost. Also, all LED indications described in Section. are stored in non-volatile memory in order to provide quick recovery of the system status indication, even if auxiliary power is temporarily lost. This feature is especially important if auxiliary power is lost after tripping. Non-volatile memory does not require a power supply to maintain information and will retain settings and indications permanently without power.

21 . Arc Sensors. Arc Sensors The EAFR series provides the choice of different types of arc sensors to be utilized in different units and different switchgear types, according to the specific application requirements. Available sensor types are arc light point sensors and arc light fiber optic loop sensors. Arc light point sensors are typically installed in metal clad compartments, providing quick accurate location of the faulted area. Arc light fiber loop sensors are installed typically to cover a wider protected area with one fiber when no need for more exact fault location exists.. Arc Light Point Sensor EAFR-0 The EAFR-0 is an arc light point sensor with a light sensitive photodiode element activated by receiving arc light. The EAFR-0 arc sensors should be mounted in the switchgear cubicles in such a way that the light sensitive part can receive light from the protected area. Typically, one sensor per closed metal clad compartment is used. In open spaces, such as the busbar section, arc sensors should be mounted at a maximum of two meters (.5 ft) apart. The fixed light sensitivity of the EAFR-0-A sensor is 8,000 Lux. The sensor does not require any user settings. The point sensor s light detection radius is 80 degrees. Other point sensors are available with different Lux sensitivities, EAFR-0-B at 5,000 Lux and EAFR-0-C at 50,000 Lux... EAFR-0 Installation and Wiring The EAFR-0 point sensor can be installed either on or through the compartment wall. An example of on the wall mounting is seen in Figure. The EAFR-0 is fixed against the wall using two screws. The same screw pattern is utilized in a through wall mounting arrangement. In this arrangement the unit is turned around and the point of the eye of the photodiode sensor protrudes through a small hole cut in the wall. The point of the sensor now faces the compartment to be protected. This allows for the body of the sensor and cabling to be located outside the compartment. For both types of installation, two screws are attached from the back side of the sensor. No external mounting plates are needed. The EAFR-0 comes without the connection cable. Connection cable installation on site is simple. The cable connectors are located beneath the covers that can be conveniently detached for fastening the sensor wires. The cover will be attached after installing the wires. The cable connectors are located at both ends of the sensor for series connecting a maximum three sensors in one line. Figure 5. EAFR-0 Point Sensor Mounted to the Compartment Wall. Figure. EAFR-0 Arc Light Point Sensor. Table Ω Compatible. Manufacturer Part No. Atten. db/00 at Mhz Data AWG Cable Diameter mm (in.) Temperature Rating C ( F) Voltage Rating Belden 0F (0.) -0/+5 (-0/+) 00 V Belden (0.) -0/+80 (-/+) 00 V Belden (0.0) -0/+00 (-9/+9) 00 V

22 BI BI Eaton Arc Flash Relay POWER ERR T,T T,T BI BI BI BI BI5 BI BO BO BO S S S S SET EAFR-0S Main reserve 5. System Self-supervision.. EAFR-0 Point Sensor Technical Data Table 9. EAFR-0 Point Sensors Technical Data. Light Intensity Threshold Detection Radius Mechanical Protection IP Sensor Wiring Arrangement Sensor Cable Specification Maximum Sensor Cable Length per Sensor Channel Operating Temperature 5. System Self-supervision 8,000 Lux/5,000 Lux/50,000 Lux 80 Degrees Two Wires and Shield Shielded Twisted Pair 0.5 mm (0.0 in.) 00 m (5 ft) -0 to 85 C (- to 85 F) The EAFR-0S includes an extensive self-supervision feature. Self-supervision includes both internal functions and external connections. The self-supervision module monitors power supply, hardware and software malfunctions, and binary input connection and sensor problems. Dipswitch settings are also supervised by comparing the actual value with stored non-volatile memory data (see Section..: Auto Configuration [System Setup]). In a healthy condition, the POWER LED is on and the System Failure (SF) relay is energized. If the self-supervision function detects a faulty condition or the power supply fails, the self-supervision relay is released and the ERR LED is illuminated.. Application Examples The EAFR-0S may be applied to a variety of power switchgear and control gear layouts and technologies. Some typical applications are described in this section. Please consult your nearest Eaton representative for a solution to your particular application.. MV or LV Double Busbar Application with Current and Light condition The EAFR-0S may be applied requiring both over-current and arc light conditions for trip. In this application, tripping is performed only if both conditions are fulfilled simultaneously. Typically, the over-current condition is obtained from an EAFR-0 relay or monitored by non-eaton products (e.g. generic feeder protection relay) and the total operation time is then dependent on device feeding the over-current signal to EAFR-0S. Figure shows an example of a double busbar arc protection system applying both over-current and arc light for tripping. S channel is typically monitoring the outgoing cable compartment. S channel is monitoring the breaker compartment. S and S are respectively monitoring the reserve busbar and main busbar. The busbar arc light fault information is sent out through the binary output channel BO (main busbar) and channel BO (reserve busbar). Figure. Double Busbar Application. If a sensor failure occurs, the relay will go into ERR mode. The ERR LED will illuminate, the SF relay will released-energize, and the corresponding faulty sensor channel LED will start blinking. In this situation, the relay is still in the protection mode, but with the faulty sensor channel blocked. If the error is resolved, the ERR LED will automatically clear the SF-status and failed sensor channel LED will remain in blinking status. This means that the SF relay will energize and the ERR LED will turn off. If one or more of the sensors are disconnected, the healthy sensors remain in use and relay remains operational. The EAFR-0S will remain in error mode until the disconnected sensors are repaired. CB S S If a dipswitch setting is changed after the auto-configuration function (see Section..: Auto Configuration) has been executed, the relay will go into SF alarm mode. The configured (stored) setting is however still valid and the relay is still operational. T S S T(Trip Alarm ) BI BO BO EAFR-0S 8

23 GND Vaux BO SF BO BO T BI T BI5 T BI BI BI BI. Connections The current monitoring signal in this application is coming from an external over-current relay through the binary input channel BI. The position of the breaker can be manually connected with either the main busbar or reserve busbar. For indicating the precise breaker location, its position information is sent to EAFR-0S via the binary input channel BI (main busbar) or BI (reserve busbar). The trip contact T is responsible for tripping the breaker. The trip contact T gives trip alarm information synchronically. The connection of this example application is also shown in Section 8: Wiring Diagram.. Connections Figure. EAFR-0S Terminals at the Rear Plate. X X. Circuit Breaker Failure Protection (CBFP) The EAFR-0S includes a selective circuit breaker failure function that can be enabled by the dipswitch settings (see Section.5: Dipswitch Settings). When enabled, the breaker failure function activates when the tripped breaker fails to operate. The breaker failure function is activated if the EAFR-0S detects the presence of light after a set operating time. When the EAFR-0S is set to operate on light and current, both parameters must persist to activate CBFP. Breaker failure can be set to operate either on 00 ms or 50 ms delay (see Section.5: Dipswitch Settings) S S S S ON OFF S/S/S Chan L L+C S Channel L L+C T / T Latch N L CBFP Time Config. Select L = Light C = Current N L = Non Latch SW 9

24 . Connections. Outputs.. Trip Relays T, T, and T The EAFR-0S relay has integrated trip relays T and T for tripping of the circuit-breakers. T and T relays are normally open type (NO) relays. Trip relay T is a (NO) trip relay that operates anytime the T or T relay operates and can be used either for tripping one more disconnecting device or for a trip alarm to local or remote monitoring and alarming system... Binary Output BO, BO, and BO Three binary outputs are available (+ Vdc). The binary output function can be configured using the dipswitches (see Section.5: Dipswitch Settings. NNote: The binary output is polarity sensitive (see Section 8: Wiring Diagram)... System Failure (SF) Relay The SF relay is a form C type (NO/NC) and is energized in the healthy condition. Whenever the EAFR-0S detects a system error or disconnection of the auxiliary power supply, the contact changes its state. The state of the SF relay remains the same until the EAFR-0S returns to a healthy condition and SF relay is again energized... Binary Inputs BI, BI, BI, BI, BI5, and BI The EAFR-0S contains six binary inputs. Typically, BI and BI are reserved for the breaker position signal information. In the most applications, the BI is responsible for the receiving over-current from the EAFR-0P. The BI, BI5, and BI can be used for receiving a trip signal or arc light signal (see Section.5: Dipswitch Settings). NNote: When the EAFR-0S receives an over-current signal from a non-eaton device, the actual operation time depends on the operation time of the external device and so the total operational time cannot be specified or guaranteed. The inputs are activated by connecting a dc signal exceeding the specified nominal threshold level of the corresponding input. The nominal threshold level is Vdc. The actual activation of the binary input occurs at 80% of the specified nominal threshold value (i.e. Vdc).. Auxiliary Voltage The auxiliary power supply voltage is (0-0) Vac / (5-50) Vdc. After powering up the relay, protection is active and operational within 50 ms.. Inputs.. Arc Sensor Channels S, S, S, and S The EAFR-0S has four arc point sensor channels. A maximum of three arc point sensors (type EAFR-0) may be connected to each channel. For details on sensors refer to Section : Arc Sensors. 0

25 _ + _ + _ + _ + 8. Wiring Diagram 8. Wiring Diagram Figure 8. Wiring Diagram of the EAFR-0S Relay. CB Station battery _ + X EAFR-0S X 5 _ + BI BI CB 0 9 _ + BI T BI BI5 8 T T BI UAUX SF BO BO BO CB S S S ON OFF 8 5 Light / Light and Current S: Light / Light and Current Latch / Non Latch 00 / 50 ms Configuration Select S

26 9. Dimensions and Installation 9. Dimensions and Installation The EAFR-0S is either door mounted or panel mounted in standard, 9 in. (8. mm) rack (height of U and /8 of a unit wide). Figure 9. EAFR-0S Dimensions in Millimeters (In.) (Side View). 5 (.89) 0 (.0) 0 (0.9) (0.) 5 (.8) 0 (0.9)

27 0. Testing Figure 0. EAFR-0S Cut Out for Panel Mounting (mm [in.]). (.85).5 (0.9) 0. Testing It is recommended that the EAFR-0S relay be tested prior to substation energizing. Testing is carried out by simulating arc light to each sensor and verifying the tripping and LED indication. For arc light simulation, a superior camera flash type is used: Canon Speedlite 0EX or equivalent. For testing of non-latched signals and the CBFP function, use a Mini Maglite Cell AAA or equivalent type of flashlight. Check that the camera flash or flashlight has fully charged battery(ies) when testing. M 59 (.) 8 (.) 0. Carrying Out Testing in the Light Only Mode. Check that the dipswitch setting positions are in accordance to your application.. Activate the camera flash within 0 cm (.8 in.) of the EAFR-0 to be used.. Verify that the corresponding sensor channel indication LED status is changed to ON.. Verify the relay output(s) activation(s) by checking the circuit breaker status or by monitoring trip contact status. The circuit breaker should open or contacts operate. NNote: A best practice is to operate the circuit breaker during testing. 5. Verify that the corresponding relay output(s) LED(s) indication status is changed to ON.. If the binary output (BO) signal is utilized, verify the BO signal activation by the status change of the relevant input where the binary output signal is connected, or by measuring the signal output voltage. NNote: The BO signal is a non-latched type.. If a binary output signal is utilized, verify that the BO LED is illuminated. 8. Press the SET push-button to reset all indications and latches.

28 0. Testing 0. Carrying Out Testing in Light and Current Mode. Check that the dipswitch setting positions are in accordance with your application.. Activate the camera flash within 0 cm (8 in.) of the EAFR-0 sensor relay and simultaneously activate the binary input BI used for over-current condition.. Verify that the sensor channel indication LED status is changed to ON.. Verify that the binary input indication LED status is changed to ON. 5. Verify the relay output(s) activation(s) by checking the circuit breaker status or by monitoring trip contact status. NNote: A best practice is to operate circuit breaker at testing. The circuit breaker should open or the contacts should operate.. Verify that the corresponding relay output(s) LED(s) indication status is changed to ON.. If a binary output (BO, BO, and BO) signals are utilized, verify the BO signal activation by status change of relevant input where binary output signal is connected, or by measuring the signal output voltage. 8. Verify that the corresponding relay output(s) LED(s) indication status is changed to ON 9. If the dipswitch No. 8 and No. are both set as light only mode, activate the camera flash within 0 cm (8 in.) from the EAFR-0 sensor relay and Do Not activate the binary input used for over-current condition. 0. Verify that no trip has occurred and only the sensor activation indication LED is ON.. Verify that the BOUT signal is activated (if in use and configured to send light information).. Press the SET push-button to reset all indications and latches. 0. Testing the Arc Flash Protection Unit Operation Time The EAFR-0 operation time test is not required at commissioning as it is performed by Eaton as a type test and routine production test. Refer to the routine test reports sent with EAFR-0 relay and consult your nearest Eaton representative for type test reports. However, if it is deemed necessary, a site timing test may be conducted using the following instructions.. Use a calibrated relay test set.. Connect an output from the relay test set to the camera flash (Metz 0B or equivalent input) for initializing the flash and configure a relay test set timer to be started simultaneously with flash.. Connect the EAFR-0 trip output T, T, or T to the relay test set input and configure the input to stop the timer.. Place camera flash to a maximum 0 cm (8 in.) distance of the EAFR-0 or EAFR fiber sensor. 5. Initiate the flash and timer using the relay test set output.. Read the measured time between simulated arc and trip contact operation.. Subtract the digital input delay of the relay test set from the final measured time if applicable. For specific test instructions consult the manufacturer of the relay test set.

29 . Troubleshooting Guide 0. Test Plan Example Date: Substation: Switchgear: EAFR-0S Serial Number: Preconditions Light Only Light + Current Remarks Sensor Channel Setting Sensor Channel,, Setting Circuit Breaker Failure Protection (CBFP) in Use (Yes / No): 00 ms: / 50 ms: Object Activated Sensor Channel Sensor Sensor Sensor Sensor Channel Sensor Sensor Sensor Sensor Channel Sensor Sensor Sensor Sensor Channel Sensor Sensor Sensor BIN BIN BIN BIN BIN 5 BIN LED Indication T, T, and T Active BO Active BO Active BO Active Tested by: Approved by: NNote: If the revelant configuration includes the CBFP function, then the CBFP time setting is in use.. Troubleshooting Guide. Technical Data Table 0. Troubleshooting Guide. Problem Check Cross Reference Sensor does not activate when testing. Sensor cable wiring Trip relay(s) does not Dipswitch settings operate even if sensor is activated. Section of this manual Camera (or other test Section 0 of this equipment) flash intensity manual Section.5 of this manual. Protection Trip time using mechanical trip relays. Reset time (arc light stage). Protection operational after power up. ms* ms 88 ms * = Total trip time using arc light or phase/residual over-current from EAFR-0 and arc light. 5

30 . Technical Data. Auxiliary Voltage Vaux Maximum Interruption Maximum Power Consumption Standby Current. Trip Relays T, T, and T Number Rated Voltage Continuous Carry Make and Carry for 0.5 s Make and Carry for s Breaking Capacity DC, When Time Constant L/R=0 ms (0-0) Vac / (5-50) Vdc ± 0% 00 ms 5 W 90 ma NO 50 Vac/dc 5 A 0 A A Contact Material AgNi 90/0 0 W; 0. A at 0 Vdc. Disturbance Tests EMC Test Emission - Conducted (EN 550 Class A) MHz - Emitted (EN 550 Class A) 0 -,000 MHz Immunity - Static Discharge (ESD) (According to IEC-- and EN000--, severity Class ) - Fast Transients (EFT) (According to EN000--, Class III and IEC80-, Level ) - Surge (According to EN [09/9], Level ) CE approved and tested according to EN 5008-, EN Air discharge 5 kv Contact discharge 8 kv Power supply input kv, 5/50 ns Other inputs and outputs kv, 5/50 ns Between wires kv /./50 µs Between wire and earth kv /./50 µs. Binary Output BO, BO, and BO Rated Voltage + Vdc Rated Current 0 ma (max) Number of Outputs - RF Electromagnetic Field Test (According. to EN 000--, Class III) - Conducted RF Field (According. to EN 000--, Class III) f = 80...,000 MHz 0 V/m f = 50 khz MHz 0 V.5 Binary Inputs BI, BI, BI, BI, BI5, and BI Rated Voltage + Vdc Threshold Pick up, 88, or 8 Vdc Threshold Drop off 5, 5, or 55 Vdc Rated Current ma Number of Inputs. Voltage Tests Insulation Test Voltage Acc - to IEC Impulse Test Voltage Acc - to IEC Mechanical Tests Vibration Test kv, 50 Hz, min 5 kv,./50 us, 0.5 J 0 to 50 Hz, 0.0 mm (.00 in.), 0.5 gn (0 to 50Hz) 0 to 50 Hz, gn (0 to 50Hz) Shock/Bump Test Acc. to IEC g,,000 bumps/dir..9 Casing and Package Protection Degree (Front) IP 50 Protection Degree (Back) IP 0 Dimensions - W x H x D mm (W x H x D in.) 5 x x 5 mm (. x. x.8 in.) Weight 0. kg (.9 oz).0 kg (5. oz) (with package).0 Environmental Conditions Specified Ambient Service Temp. Range -5 to 0 C (- to 58 F) Transport and Storage Temp. Range -5 to 0 C (- to 58 F) Relative Humidity Up to 9%

31 . Ordering Codes. Ordering Codes Eaton Catalog Number Eaton Style Number Part Number Description EAFR-0P 5C00G0 Current, point sensor unit EAFR-0F 5C00G0 Current, fiber loop sensor unit EAFR-0 5C00G0 Point Sensor unit EAFR-0D 5C00G0 Point Sensor unit, DIN Rail mounted EAFR-0 5C00G0 Fiber loop sensor unit EAFR-0PB 5C00G0 Current, point sensor unit, NC Trip Relay EAFR-0FB 5C00G08 Current, fiber loop sensor unit, NC Trip Relay EAFR-0B 5C00G09 Point Sensor unit, NC Trip Relay EAFR-0DB 5C00G0 Point Sensor unit, DIN Rail mounted, NC Trip Relay EAFR-0B 5C00G Fiber loop sensor unit, NC Trip Relay EAFR-0-A 5C0G0 Arc light point Sensor - 8,000 Lux EAFR-0-B 5C0G0 Arc light point Sensor - 5,000 Lux EAFR-0-C 5C0G0 Arc light point Sensor - 50,000 Lux EAFR-0-0 5C0G0 Arc light plastic fiber sensor - 0 m (.8 ft) EAFR-0-5 5C0G0 Arc light plastic fiber sensor - 5 m (9. ft) EAFR-0-0 5C0G0 Arc light plastic fiber sensor - 0 m (5. ft) EAFR-0-5 5C0G0 Arc light plastic fiber sensor - 5 m (8.0 ft) EAFR-0-0 5C0G05 Arc light plastic fiber sensor - 0 m (9.ft) EAFR-0-5 5C0G0 Arc light plastic fiber sensor - 5 m (.8 ft) EAFR-0-0 5C0G0 Arc light plastic fiber sensor - 0 m (. ft) EAFR-0-0 5C0G0 Arc light glass fiber sensor - 0 m (.8 ft) EAFR-0-5 5C0G0 Arc light glass fiber sensor - 5 m (9. ft) EAFR-0-0 5C0G0 Arc light glass fiber sensor - 0 m (5. ft) EAFR-0-5 5C0G0 Arc light glass fiber sensor - 5 m (8.0 ft) EAFR-0-0 5C0G05 Arc light glass fiber sensor - 0 m (9.ft) EAFR-0-5 5C0G0 Arc light glass fiber sensor - 5 m (.8 ft) EAFR-0-0 5C0G0 Arc light glass fiber sensor - 0 m (. ft) EAFR-0-5 5C0G08 Arc light glass fiber sensor - 5 m (. ft) EAFR C0G09 Arc light glass fiber sensor - 50 m (.05 ft) EAFR C05G0 Arc light glass fiber sensor (High Temperature) - 0 m (.8 ft) EAFR C05G0 Arc light glass fiber sensor (High Temperature) - 5 m (9. ft) EAFR C05G0 Arc light glass fiber sensor (High Temperature) - 0 m (5. ft) EAFR C05G0 Arc light glass fiber sensor (High Temperature) - 5 m (8.0 ft) EAFR C05G05 Arc light glass fiber sensor (High Temperature) - 0 m (9.ft) EAFR C05G0 Arc light glass fiber sensor (High Temperature) - 5 m (.8 ft) EAFR C05G0 Arc light glass fiber sensor (High Temperature) - 0 m (. ft) EAFR C05G08 Arc light glass fiber sensor (High Temperature) - 5 m (. ft) EAFR C05G09 Arc light glass fiber sensor (High Temperature) - 50 m (.05 ft)

32 Eaton 000 Eaton Boulevard Cleveland, OH United States Eaton.com 0 Eaton All Rights Reserved Printed in USA Publication No. MN0005EN / TBG February 0 Eaton is a registered trademark. All trademarks are property of their respective owners.

MN026004EN. EAFR-101 Arc Point Sensor Relay User Manual

MN026004EN. EAFR-101 Arc Point Sensor Relay User Manual MN0600EN EAFR-0 Arc Point Sensor Relay User Manual DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on

More information

Arc Sensor User Manual

Arc Sensor User Manual MN026008EN Arc Sensor User Manual EAFR-01 EAFR-06 EAFR-08 EAFR-07 DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document

More information

Series NRX with PXR - Instructions for Neutral Current Sensor Type NF

Series NRX with PXR - Instructions for Neutral Current Sensor Type NF Supersedes March 2016 Series NR Series NR with PR - Instructions for Neutral Current Sensor Type NF Instructions apply to: UL1066/ANSI, UL489 series NR NF frame IEC IZM16 WARNING (1) ONLY QUALIFIED ELECTRICAL

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

INSTRUCTION LEAFLET IL17553B IQ UNIVERSAL POWER SENTINEL TM INSTALLATION INSTRUCTIONS FOR THE IQ UNIVERSAL POWER SENTINEL TM INTERNAL CT

INSTRUCTION LEAFLET IL17553B IQ UNIVERSAL POWER SENTINEL TM INSTALLATION INSTRUCTIONS FOR THE IQ UNIVERSAL POWER SENTINEL TM INTERNAL CT IQ UNIVERSAL POWER SENTINEL TM INSTALLATION INSTRUCTIONS FOR THE IQ UNIVERSAL POWER SENTINEL TM INTERNAL CT INSTRUCTION LEAFLET IL17553B IL17553B For more information visit: www.cutler-hammer.eaton.com

More information

COOPER POWER SERIES. External application of a motor start capacitor on a single-phase voltage regulator. Voltage Regulators MN225063EN

COOPER POWER SERIES. External application of a motor start capacitor on a single-phase voltage regulator. Voltage Regulators MN225063EN Voltage Regulators MN225063EN Effective March 2017 Supersedes January 2012 (S225-60-10) COOPER POWER External application of a motor start capacitor on a single-phase voltage regulator SERIES DISCLAIMER

More information

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C) XR1 Rotor Earth Fault Relay Manual XR1 (Revision C) Woodward Manual XR1 (EN) Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by

More information

INSTRUCTION LEAFLET IL17537B F FRAME IQ ENERGY SENTINEL TM INSTALLATION INSTRUCTIONS FOR F FRAME IQ ENERGY SENTINEL TM

INSTRUCTION LEAFLET IL17537B F FRAME IQ ENERGY SENTINEL TM INSTALLATION INSTRUCTIONS FOR F FRAME IQ ENERGY SENTINEL TM F FRAME IQ ENERGY SENTINEL TM INSTALLATION INSTRUCTIONS FOR F FRAME IQ ENERGY SENTINEL TM INSTRUCTION LEAFLET IL17537B IL17537B For more information visit: www.cutler-hammer.eaton.com Effective 10/02 IL

More information

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New) XR1 Rotor Earth Fault Relay (May 2007) Manual XR1 (Revision New) Woodward Manual XR1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided

More information

Magnum low voltage drawout circuit breaker IEC horizontal stab cassette shutter kit (double wide A cassettes)

Magnum low voltage drawout circuit breaker IEC horizontal stab cassette shutter kit (double wide A cassettes) kit (double wide 4000 6300A cassettes) i WARNING (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT. (2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A CIRCUIT

More information

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice Issued: April 1999 Status: Updated Version: B/08.11.200 Data subject to change without notice Features Versatile, multifunction line fault indicator for distribution networks Overcurrent, earth-fault and

More information

Overcurrent Protection / 7SJ45

Overcurrent Protection / 7SJ45 Overcurrent Protection / SJ SIPROTEC easy SJ numerical overcurrent protection relay powered by CTs Fig. / Description SIPROTEC easy SJ numerical overcurrent protection relay powered by current transformers

More information

COOPER POWER SERIES. Upgrade instructions for CL-6 series control firmware. Voltage Regulators MN225071EN

COOPER POWER SERIES. Upgrade instructions for CL-6 series control firmware. Voltage Regulators MN225071EN Voltage Regulators MN225071EN Effective March 2017 Supersedes September 2012 (S225-11-4) COOPER POWER Upgrade instructions for CL-6 series control firmware SERIES DISCLAIMER OF WARRANTIES AND LIMITATION

More information

Phase and neutral overcurrent protection

Phase and neutral overcurrent protection Phase and neutral overcurrent protection Page 1 ssued June 1999 Changed since July 1998 Data subject to change without notice (SE970165) Features Two-phase or three-phase time-overcurrent and earth fault

More information

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W ADC5000 SERIES AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications 60W, 125W and 250 W Input voltage 230/115 VAC voltages 12, 24, 36 or 48 VDC Statistical MTBF >3 000

More information

Time over/underfrequency relay with protection assemblies

Time over/underfrequency relay with protection assemblies Time over/underfrequency relay with protection assemblies RXFK 2H and RAFK 509 009-BEN Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970104) (SE970108) Features

More information

Multilin A60 Arc Flash System

Multilin A60 Arc Flash System GE Grid Solutions Multilin A60 Arc Flash System E57838 LISTED IND.CONT. EQ. 9D58 Instruction manual Manual P/N: 1601-0037-A5 GE publication code: GEK-113633D *1601-0037-A5* Copyright 2015 GE Multilin Inc.

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC Catalogue 1SFC 266006-en, Edition 3 November 2003 Supersedes Catalogue 1SFC 266006-en, Edition 2 November 2000 Arc Guard System TVOC System units The two units of the are used as below: Approvals 1. with

More information

CAMTO. Arc detecting relay. system. January Revised August D D1200

CAMTO. Arc detecting relay. system. January Revised August D D1200 NEW ARC DETECTING SYSTEM FROM Based on our experience with arc protection since 1962, has developed a new. The units are built into boxes that all fit on a 35 mm DIN-rail. All front plates are dimensioned

More information

A1000 ALPHA and A1200 ALPHA Meter Installation Instructions. General. Installation. For A1000 ALPHA Type R, A1000 ALPHA Type C, and A1200 ALPHA Meters

A1000 ALPHA and A1200 ALPHA Meter Installation Instructions. General. Installation. For A1000 ALPHA Type R, A1000 ALPHA Type C, and A1200 ALPHA Meters January 003 IL4-401B A1000 ALPHA and A100 ALPHA Meter Installation Instructions For A1000 ALPHA Type R, A1000 ALPHA Type C, and A100 ALPHA Meters General This leaflet contains general installation instructions

More information

Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control

Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control Gain Electronic Co. Ltd. Table Of Contents Safety Considerations ------------------------------------------------------------2

More information

AU INSTALLATION INSTRUCTIONS. Revision B1 Rapid City, SD, USA, 02/2010 II_201A-AU_B1

AU INSTALLATION INSTRUCTIONS. Revision B1 Rapid City, SD, USA, 02/2010 II_201A-AU_B1 INSTALLATION INSTRUCTIONS Revision B1 Rapid City, SD, USA, 02/2010 MODELS 201A-AU 201-575-AU II_201A-AU_B1 2880 North Plaza Drive, Rapid City, South Dakota 57702 (800) 843-8848 (605) 348-5580 fax (605)

More information

QUINT-PS/ 3AC/24DC/10

QUINT-PS/ 3AC/24DC/10 Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system

More information

Model Number Structure

Model Number Structure Current Sensor CSM DS_E Solid-state, Plug-in Current Sensor Applicable to motor overcurrent protection and 3-phase AC current detection. Inverse-type, start-up lock type, and instantaneous type overcurrent

More information

Thermistor motor protection relays

Thermistor motor protection relays Thermistor motor protection relays Content Benefits and advantages... / 68 Selection table... / 68 Ordering details CM-MSE... / 69 CM-MSS... / 69 CM-MSN... / 7 PTC sensor C0... / 7 Technical data... /

More information

XU2-AC AC voltage relay. (Februar 1997) Manual XU2-AC (Revision New)

XU2-AC AC voltage relay. (Februar 1997) Manual XU2-AC (Revision New) XU2-AC AC voltage relay (Februar 1997) Manual XU2-AC (Revision New) Woodward Manual XU2-AC GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

presentation contents application advantages

presentation contents application advantages presentation contents page presentation protection functional and connection schemes other connection schemes connection characteristics 9 installation 0 commissioning ordering information Sepam 00 is

More information

REF 610 Feeder Protection Relay. Technical Reference Manual

REF 610 Feeder Protection Relay. Technical Reference Manual REF 610 1MRS 755310 Issued: 05.10.2004 Version: A/05.10.2004 REF 610 Contents 1. Introduction...6 1.1. About this manual...6 1.2. The use of the relay...6 1.3. Features...6 1.4. Guarantee...8 2. Safety

More information

XF2 Frequency Relay. Manual XF2 (Revision A)

XF2 Frequency Relay. Manual XF2 (Revision A) XF2 Frequency Relay Manual XF2 (Revision A) Woodward Manual XF2 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by Woodward Governor

More information

MDW-45 Converter RS RS-422/485

MDW-45 Converter RS RS-422/485 www.westermo.com MDW-45 Converter RS-232 - RS-422/485 2 6617-2203 General information Legal information The contents of this document are provided as is. Except as required by applicable law, no warranties

More information

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide Relion 605 series Relion 605 series Self-Powered Feeder Protection Product Guide Contents 1 Description...3 2 Protection functions...3 3 Application...4 4 Self-supervision...4 5 Inputs and outputs...4

More information

Digital Panel Meter K3TE. Model Number Structure. Model Number Legend. Easy-to-use, Low-cost Digital Panel Meter that Accepts DC Input K3TE

Digital Panel Meter K3TE. Model Number Structure. Model Number Legend. Easy-to-use, Low-cost Digital Panel Meter that Accepts DC Input K3TE Digital Panel Meter K3TE Easy-to-use, Low-cost Digital Panel Meter that Accepts DC Input Compact DIN-size (96 x 48 (W x H)) body. Mounting thickness of only 3.5 mm required. Highly visible display with

More information

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Overcurrent Protection / 7SJ46 SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Function overview Fig. /11 Description The SIPROTEC easy 7SJ46 is a numerical overcurrent protection relay which

More information

Type CP-S, CP-C & CP-A Switch mode

Type CP-S, CP-C & CP-A Switch mode Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting

More information

Multi-function (MI, ME, M2, M1) 2 NO (2 SPST-NO) 12 / / 400 3,000 1, / 0.3 / (5 / 5) AgNi

Multi-function (MI, ME, M2, M1) 2 NO (2 SPST-NO) 12 / / 400 3,000 1, / 0.3 / (5 / 5) AgNi Features Special relay for alternating loads, for applications with pumps, compressors, air conditioning or refrigeration units 2 independent NO output, 12 A 4 functions 2 independent control signals,

More information

SPAE 010, 011 High Impedance Protection Relay

SPAE 010, 011 High Impedance Protection Relay SPAE 010, 011 High Impedance Protection Relay User s manual and Technical description f n = 50/60 Hz U n = 50 / 100 / 200 V 2 5 U REF > SPAE 010 0.8 U aux 0.6 1.0 RESET OK x 80... 265 V ~ _ 0.4 U > U n

More information

SPECIFICATION FOR OVERCURRENT RELAYS

SPECIFICATION FOR OVERCURRENT RELAYS SPECIFICATION FOR OVERCURRENT RELAYS 1/9 1. Procedure A manufacturer willing to classify an overcurrent relay according to this specification should provide: A complete file providing a clear, unambiguous

More information

QUINT-PS/ 3AC/24DC/40

QUINT-PS/ 3AC/24DC/40 Primary-switched power supply unit with SFB technology, 3 AC, output current 40 A INTERFACE Data sheet 103133_en_00 1 Description PHOENIX CONTACT - 07/2009 Features QUINT POWER power supply units Maximum

More information

SPAD 346 C Stabilized differential relay

SPAD 346 C Stabilized differential relay SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

satech SynchroStar GPS 200 Series

satech SynchroStar GPS 200 Series satech SynchroStar GPS 200 Series KEY BENEFITS Designed with high quality oscillator OCXO the device is characterized by superior frequency stability and improved holdover performance that allows maintaining

More information

XI1-I Time overcurrent relay. (Januar 2007) Manual XI1-I (Revision New)

XI1-I Time overcurrent relay. (Januar 2007) Manual XI1-I (Revision New) XI1-I Time overcurrent relay (Januar 2007) Manual XI1-I (Revision New) Woodward Manual XI1-I GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New) XUA1 AC Voltage and phase balance relay (August 1996) Manual XUA1 (Revision New) Woodward Manual XUA1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

LIGHT ARC DETECTOR Type LAD

LIGHT ARC DETECTOR Type LAD APPLICATIONS Prevent internal arc in MV HV switchgear or transformers Selective fault detection for fast plant recovery HIGHLIGHTS Remote indication by change-over contact for fault condition Local fault

More information

AUXILIARY RELAYS FOR TRIPPING APPLICATIONS

AUXILIARY RELAYS FOR TRIPPING APPLICATIONS AUXILIARY RELAYS FOR TRIPPING APPLICATIONS This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products described here. Moving together INDEX.

More information

200Amp AC Clamp Meter + NCV Model MA250

200Amp AC Clamp Meter + NCV Model MA250 User's Guide 200Amp AC Clamp Meter + NCV Model MA250 Introduction Congratulations on your purchase of this Extech MA250 Clamp Meter. This meter measures AC Current, AC/DC Voltage, Resistance, Capacitance,

More information

38 Series - Relay interface modules A

38 Series - Relay interface modules A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information

Moxa ICF-1280I Series Industrial PROFIBUS-to-Fiber Converter

Moxa ICF-1280I Series Industrial PROFIBUS-to-Fiber Converter Moxa ICF-1280I Series Industrial PROFIBUS-to-Fiber Converter Hardware Installation Guide First Edition, August 2013 2013 Moxa Inc. All rights reserved. P/N: 1802012800011 Introduction The ICF-1280I series

More information

QUINT-PS AC/24DC/40

QUINT-PS AC/24DC/40 Power supply unit INTERFACE Data sheet 102315_en_02 1 Description PHOENIX CONTACT 2010-04-23 Features QUINT POWER power supply units for plant and special engineering reliably start heavy loads with high

More information

XP2-R Power and Reverse Power Relay

XP2-R Power and Reverse Power Relay XP2-R Power and Reverse Power Relay Manual XP2-R (Revision C) Woodward Manual XP2-RE Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward

More information

QUINT-PS/ 1AC/24DC/20

QUINT-PS/ 1AC/24DC/20 Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data sheet 103129_en_04 1 Description PHOENIX CONTACT - 02/2010 Features QUINT POWER power supply units Maximum system

More information

Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK

Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK (RXLK_2H.tif) RALK.psd Features Micro-processor based time-overexcitation relay with continuous settings for

More information

Capacitor protection relay

Capacitor protection relay Capacitor Protection Relay FEATURES Capacitor unbalance protection Line current unbalance protection Overvoltage protection Overheating protection Ground fault protection Overcurrent protection Undercurrent

More information

Multi-voltage Multi-function. Wiring diagram (without control signal)

Multi-voltage Multi-function. Wiring diagram (without control signal) 80 Modular timers 16 A 80 Multi-function and mono-function timer range 80.01T - Multi-function & multi-voltage 80.11T - On-delay, multi-voltage Complies with EN 45545-2:2013 (protection against fire of

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy ejection by plastic clip Dual screw head (blade+cross)

More information

ASHIDA Numerical 3OC + 1EF Protection Relay

ASHIDA Numerical 3OC + 1EF Protection Relay PROTH. ERR L5 PKP FAULT DT REC LOCK BF L6 L7 CLOSE TRIP ADR 241B Protection Features : 4 Element (3 Phase + EF + Sensitive EF) Over current IDMT/DMT with instant trip. Programmable (Non- Volatile) Setting

More information

Phase-sequence Phase-loss Relay

Phase-sequence Phase-loss Relay Phase-sequence Phase-loss Relay K8AB-PH Three-phase Phase-sequence Phase-loss Relay Using Voltage Detection Method Prevents reverse motor rotation due to incorrect wiring. Distinguishes between positive

More information

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New)

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New) XP2-R Power and reverse power relay (January 2006) Manual XP2-R (Revision New) Woodward Manual XP2-R GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy

More information

PESD24VL1BA. 1. General description. 2. Features and benefits. 3. Applications. 4. Quick reference data

PESD24VL1BA. 1. General description. 2. Features and benefits. 3. Applications. 4. Quick reference data Low capacitance bidirectional ESD protection diode in SOD323 12 July 2018 Product data sheet 1. General description Bidirectional ElectroStatic Discharge (ESD) protection diode in a very small SOD323 (SC-76)

More information

100BASE-T1 / OPEN Alliance BroadR-Reach automotive Ethernet Low-Voltage Differential Signaling (LVDS) automotive USB 2.

100BASE-T1 / OPEN Alliance BroadR-Reach automotive Ethernet Low-Voltage Differential Signaling (LVDS) automotive USB 2. 28 September 2018 Product data sheet 1. General description 2. Features and benefits 3. Applications 4. Quick reference data Ultra low capacitance double rail-to-rail ElectroStatic Discharge (ESD) protection

More information

CB Scheme UL508 UL ATEX II3G

CB Scheme UL508 UL ATEX II3G Industrial Power Supplies UL Hazloc Class I, division 2 approval and ATEX certification SEMI F47 compliant for voltage sag immunity Rugged metal case with optional side-mounting Very high efficiency up

More information

G7K. Latching Relay. Compact Mechanical Lock Latching Relays with Manual Buttons. Model Number Structure. Ordering Information

G7K. Latching Relay. Compact Mechanical Lock Latching Relays with Manual Buttons. Model Number Structure. Ordering Information Latching Relay CSM DS_E Compact Mechanical Lock Latching Relays with Manual Buttons Compact design with a height of 7 mm, width of. mm, and depth of 8. mm. Plus, one Relay only weighs 7 g. Quick set and

More information

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area. Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103129_en_01 PHOENIX CONTACT - 05/2008 1 Description QUINT POWER power supply units highest system availability

More information

Model Microphone Preamplifier Power Supply Manual

Model Microphone Preamplifier Power Supply Manual Model 2221 Microphone Preamplifier Power Supply Manual Larson Davis Model 2221 Microphone Preamplifier Power Supply Manual I2221.01 Rev H Copyright Copyright 2009-2015 by PCB Piezotronics, Inc. This manual

More information

Smart Power Relay E I...

Smart Power Relay E I... Smart Power Relay E-48-8I... Description The Smart Power Relay E-48-8I.- is a remotely controllable electronic load disconnecting relay with three functions in a single unit: l electronic relay l electronic

More information

VOLTAGE DETECTING SYSTEMS

VOLTAGE DETECTING SYSTEMS INTEGRATED OPTOELECTRIC SYSTEM OF VOLTAGE DETECTION WITH TOTAL SAFETY GUARANTEED BY GALVANIC INSULATION AND INTERNAL FAULT SUPERVISION pag.1 di 13 INDE 1.PREVIEW.. 3 2.GENERAL.. 3 3.STANDARD REFERENCES..

More information

38 Series - Relay interface modules A

38 Series - Relay interface modules A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

Model Number Structure

Model Number Structure Single-phase Voltage Relay CSM DS_E_3_1 Ideal for voltage monitoring for industrial facilities and equipment. Monitor for overvoltages or undervoltages. Manual resetting and automatically resetting supported

More information

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

DSA150 Series. xxx Series. 150 Watts.   AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125. 15 Watts xxx Series Ultra Slim Design 15% Peak Load for 3 seconds Ambient Operation from -1 C to +7 C High Efficiency Selectable Overload Characteristic Selectable Remote Inhibit or Enable 3 Year Warranty

More information

z8801 Local Oscillator PXI

z8801 Local Oscillator PXI TECHNICAL SPECIFICATIONS z8801 Local Oscillator PXI 2014 LitePoint, A Teradyne Company. All rights reserved. Port Descriptions Front Panel Label Type Description REF OUT SMA Backplane reference clock output

More information

Rotational Position Sensor, Kit Type, Hall Effect Technology

Rotational Position Sensor, Kit Type, Hall Effect Technology Rotational Position Sensor, Kit Type, Hall Effect Technology QUICK REFERENCE DATA Sensor type Kit rotational, hall effect Output type Wires Market appliance Industrial Dimensions 48 mm x 43 mm x 12 mm

More information

G70R-SOC08 CSM_G70R-SOC08_DS_E_2_1

G70R-SOC08 CSM_G70R-SOC08_DS_E_2_1 Relay Terminal CSM DS_E 1 Space-saving and Labor-saving 8-point Output Block Relay terminal is just 136 80 55 mm (W H D, when mounted upright). Independent contacts and short bar allow easy common connections.

More information

Instructions for D64RPB30 Series C1 Ground Fault Relay

Instructions for D64RPB30 Series C1 Ground Fault Relay Instructions for D64RPB30 Series C1 Ground Fault Relay Cat. No. D64RPB30 CT 24-240V AC / DC N.C. N.O. 1 2 3 4 5 6 7 8 ON F2024-01-01 FLASHES: 1 = E/F 2 = S/C 3 = BACKUP 4 = CT 5 = F/S CV LOSS CONT = TRIP

More information

Thyristor power controller B DI1002 V1.0 Manual/Operating instructions

Thyristor power controller B DI1002 V1.0 Manual/Operating instructions 1 B DI1002 V1.0 Manual/Operating instructions 2 1 Introduction Before you put the thyristor controller into operation, please read these operating instructions. Keep them in safe place accessible for all

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

IRI1-ER - Stabilized Earth Fault Current Relay

IRI1-ER - Stabilized Earth Fault Current Relay IRI1-ER - Stabilized Earth Fault Current Relay TB IRI1-ER 02.97 E 1 Contents 1. Summary 2. Applications 3. Characteristics and features 4. Design 4.1 Connections 4.1.1 Analog inputs 4.1.2 Output relays

More information

PESD2IVN-U. 1. General description. 2. Features and benefits. 3. Applications. Quick reference data

PESD2IVN-U. 1. General description. 2. Features and benefits. 3. Applications. Quick reference data 15 July 2015 Product data sheet 1. General description ElectroStatic Discharge (ESD) protection diode in a very small SOT323 (SC-70) Surface- Mounted Device (SMD) plastic package designed to protect two

More information

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts Data sheet Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts The CT-MVS.23 is a multifunctional electronic timer from the CT-S range. It provides 11 timing functions and 10 time ranges.

More information

Ampgard The name motor applications rely on

Ampgard The name motor applications rely on Medium-voltage motor control The name motor applications rely on Oil and gas Mining Water/wastewater Pulp and paper Utility A legacy of reliability for more than 4 decades 1950 1960 1970 1980* 1990 2000

More information

PESD3V3S1UB. 1. General description. 2. Features and benefits. 3. Application information. 4. Quick reference data

PESD3V3S1UB. 1. General description. 2. Features and benefits. 3. Application information. 4. Quick reference data 29 November 2018 Product data sheet 1. General description 2. Features and benefits 3. Application information 4. Quick reference data Unidirectional ElectroStatic Discharge (ESD) protection diode in a

More information

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Dual-Source Power Supply Addendum to I.B. 17555 Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Table of Contents Page 1.0 Introduction...1 2.0 General

More information

M5800 Pressure Transducer with Rotatable Display

M5800 Pressure Transducer with Rotatable Display Pressure Transducer with Rotatable Display SPECIFICATIONS Wide Temperature Range Compact Variety of Pressure Ports and customized Electrical Configurations Optional Stainless Steel Snubber CE Compliant

More information

User s Guide. Model MA A AC Mini Clamp-on Meter

User s Guide. Model MA A AC Mini Clamp-on Meter User s Guide Model MA150 200A AC Mini Clamp-on Meter Introduction Congratulations on your purchase of Extech s MA150 AC Mini Clamp Meter. This meter is shipped fully tested and calibrated and, with proper

More information

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. REGULATION AUTOMATIC SYNCHRONIZER for GENERATOR NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection DATASHEET - ETR4-70-A Delivery program Timing relay, 2W, 0.05s-100h, multi-function, 24-240VAC/DC, potentiometer connection Part no. ETR4-70-A Catalog No. 031888 Eaton Catalog No. XTTR6A100H70B EL-Nummer

More information

PTVS20VU1UPA. 1. General description. 2. Features and benefits. 3. Applications. 4. Quick reference data. 300 W Transient Voltage Suppressor

PTVS20VU1UPA. 1. General description. 2. Features and benefits. 3. Applications. 4. Quick reference data. 300 W Transient Voltage Suppressor 12 June 217 Product data sheet 1. General description 3 W unidirectional Transient Voltage Suppressor (TVS) in a DFN22-3 (SOT161) leadless medium power Surface-Mounted Device (SMD) plastic package, designed

More information

TB65 65W Single Output Test and Measurement/Industrial Series

TB65 65W Single Output Test and Measurement/Industrial Series Features 2.0 x 3.5 x 1.3 Package TB65 Up to 65W Convection Cooled Output Power Compliant to high levels of EMC per EN61000-4 15kV ESD (Air), 8kV (Contact) 4kV Surge Meets Class B Conducted EMI with 6db

More information

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator REGULATION Automatic Synchronizer for Generator NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

ESD protection for In-vehicle networks

ESD protection for In-vehicle networks 29 December 217 Product data sheet 1. General description ESD protection device in a small SOT323 (SC-7) Surface-Mounted Device (SMD) plastic package designed to protect two automotive In-vehicle network

More information

XUA1 - AC Voltage and phase balance relay

XUA1 - AC Voltage and phase balance relay XUA1 - AC Voltage and phase balance relay Contents 1. Applications and features 2. Design 3. Function 3.1 Voltage supervision 3.2 Unbalanced voltage supervision 4. Operation and settings 4.1 Setting of

More information

Single Channel Loop Detector

Single Channel Loop Detector Single Channel Loop Detector Model LD120T Series The LD120T is a series of single channel inductive loop detectors. The use of microprocessor and surface mount technology enables a large number of functions

More information

58 SERIES. Relay interface modules 7-10 A 58.P3 58.P4

58 SERIES. Relay interface modules 7-10 A 58.P3 58.P4 58 58 3 & 4 CO relay interface modules, 31 mm wide with Push-in terminals Ideal interface for PLC and electronic systems 58.P3 58.P4 Type 58.P3 3 CO 10 A Push-in terminals Type 58.P4 4 CO 7 A Push-in terminals

More information

PTVS22VU1UPA. 1. General description. 2. Features and benefits. 3. Applications. 4. Quick reference data. 300 W Transient Voltage Suppressor

PTVS22VU1UPA. 1. General description. 2. Features and benefits. 3. Applications. 4. Quick reference data. 300 W Transient Voltage Suppressor 12 July 217 Product data sheet 1. General description 3 W unidirectional Transient Voltage Suppressor (TVS) in a DFN22-3 (SOT161) leadless medium power Surface-Mounted Device (SMD) plastic package, designed

More information

Paperless Recorder PR20

Paperless Recorder PR20 Technical Information TI 075R/24/ae Paperless Recorder PR20 Economical and time saving recorder operates without the need for paper or pens and is exceedingly simple to operate Application Areas Technological

More information

LCL Series. SIngle Output Industrial Supplies. High Efficiency. Low Cost. 150 W Convection Cooled. 300 W & 500 W with Internal Fans

LCL Series. SIngle Output Industrial Supplies. High Efficiency. Low Cost. 150 W Convection Cooled. 300 W & 500 W with Internal Fans LCL Series SIngle Output Industrial Supplies High Efficiency Low Cost 150 W Convection Cooled 300 W & 500 W with Internal Fans Outputs form 12 V to 48 V 3 Year Warranty The LCL series is a low cost chassis

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information