1 NTNU Faculty of Chemistry and Biology Norwegian University of Department of Chemical Engineering Science and Technology FORDYPNINGSEMNE FALL 200 SIK 2092 Prosess-Systemteknikk Project tittle: Evaluation of simple methods for tuning of PID-Controllers by Sigurd Myhre Hellem Under the supervision of: Professor Sigurd Skogestad 26. November 200

2 Abstract Ziegler and Nichols published their famous paper Optimum settings for automatic controllers in 942. Based on Ziegler and Nichols experience with the transient for many types of processes they developed a method for tuning of closed-loop response. In the literature there are still discussed whether they used a controller with a configuration in accordance with the cascade or the parallel form. The question was examined through literature study and by reproduction of the simulations Ziegler and Nichols presented in their paper. A series of simulations was carried out and the results pointed out that Ziegler and Nichols tunings was most likely for an ideal PID controller. Coughanowr and Koppel have derived a transfer function for the Taylor Fulscope controller Ziegler- Nichols had been using when developing their tunings. According to that function for infinite baffle-nozzle gain, Ziegler and Nichols tunings could not be applied strictly to a Taylor Fulscope controller. A more complex controller transfer function with finite gain would be on a modified cascade form. Ziegler-Nichols also used a mechanical differential analyzer at MIT to simulate processes at a higher speed. Transfer function for a PID controller had to be implemented on the analyzer and a PID controller on the ideal form would most probably have been applied to the differential analyzer. It was according to the experimental results and references in the literature concluded that Ziegler-Nichols tunings are for ideal controller Performance values reflect controller stability and robustness. Different PID controller tunings were judged by the performance values Integral Absolute Error (IAE), computed for the process output, and Total Variation (TV), computed for the process input (controller output). Ziegler-Nichols tunings gave a generally fast but a more unstable response. This was evident by low values for integral absolute error (IAE) and higher values for total variation (TV). Skogestad s tunings gave in general somewhat slow response. This corresponded in higher IAE values and lower TV values. It was concluded that Skogestad s tunings offered the best stability and robustness of the reviewed tunings.

3 . Introduction... 2 Theory Ziegler-Nichols Tuning rules Z-N controller settings Controlled process in the Ziegler-Nichols article Controller configuration Taylor Fulscope, a pneumatic PID-Controller Cascade PID- Controller Literature references for Ziegler- Nichols pneumatic PID controller Integrated Absolute Error, IAE, and Total Variation, TV Results An approximate to Z-N s process example Simulation results Deadtime process Process with integrating action and deadtime Processes with deadtime, integrating action and a first-order transfer function Processes with deadtime and a second-order transfer function Performance criteria for controllers Pure dead time process Integrating process Process examples Discussion The PID controller of Ziegler and Nichols The preliminary evaluation of processes Settings and simulation results for PID-Controllers The Taylor Fulscope Controller and related topics Performance criteria for controllers Conclusion Appendix

4 . Introduction Ziegler and Nichols published their famous paper Optimum settings for automatic controllers in 942. The tuning rules were developed after numerous simulations with the pneumatic Taylor Fulscope controller. It is however some disagreement in the literature if this pneumatic controller was really working according to an ideal or a cascade PID (proportional-integral-derivative) controller transfer function. The effect of this confusion is important when considering the derivative action added to the PIcontroller. The main objective of this report is to try to answer the question regarding which form represents the pneumatic controller (cascade or ideal). The question is to be examined through literature study and by trying to reproduce the simulations Ziegler and Nichols presented in their paper. Controller performance is an important subject to investigate. Different performance values reflect the controller stability and robustness. PID-controller performances for different controller tunings are to be tested. The integral Absolute Error (IAE), i.e. deviation from the set point, is to be calculated for the process output. Total Variation (TV) for the process input (controller output) was the second performance criteria that were to be calculated. Performances for Skogestad s tunings are to by compared with other well known tuning rules.

5 2 Theory 2. Ziegler-Nichols Tuning rules In 942 Ziegler and Nichols, who were engineers for a major control hardware company in the United States (Taylor Instruments Co), proposed tuning rules for the Optimum settings for automatic controllers. Based on their experience with transient for many types of processes they developed a method for tuning of closed-loop response, this implied keeping the controller in the closed loop as an active controller in automatic mode. The principal control effects found in PID-controller where examined and practical names and units proposed for each effect. They suggested that ultimate controller gain, Kcu, and ultimate period, Pu, where to be obtained from a closed-loop test of the actual process, and not from a study of frequency responses. The basis for proportional, sensibility, adjustment was a reduction of amplitude at a :4 rate. The basic steps in determining the controller setting are described in the next section. 2.. Z-N controller settings. When the process is in steady state within the normal level of operating, the integral and the derivative modes of the PID-controller are removed leaving only the proportional control. On some controllers, this might require setting the deviate time to its minimal value and the integrating time to its maximum value. 2. Disturb the system by adding an increasing value of proportional gain to the controller, until the system response with a sustained constant oscillating output. The corresponding Kc is denoted as the ultimate gain, Kcu, and the period of oscillation is the ultimate period, Pu. 3. The Ziegler-Nichols tuning rules, given in Table 2., are then used to set the controller parameters for a Proportional (P)-, a Proportional-integral (PI)- or a Proportional-integral-derivative (PID) - controller. 2

6 Table 2- Controller settings with reference to Z-N Type of controller KC I D Proportional (P) 0.5 * KU - - Proportional-integral (PI) 0.45 * KU PU -.2 Proportional-integral-derivative (PID) 0.6 * KU P U P U 2 8 The Z-N tuning rules are given in the table above. The tunings and variations of them are frequently used in the industry because they are simple to implement 2..2 Controlled process in the Ziegler-Nichols article It was stated that a paper cowering laboratory and field data and developed mathematical relations were not to be presented in their article. They considered most important that the information were available for use by persons interested in the application of automatic-control instruments. The article therefore included only a single illustrative example. For this example effects of load disturbance and different controller settings were shown. The controller gain in the paper was referred to as the proportional-response sensitivity, or only sensitivity. The applied controller had a range of gain from 000 to psi per inch, as the output pressure change per inch of the tracker pen travel. The tracker pen speed was min per plot unit The adjustment of the gain affects primarily the stability of control. The ultimate sensitivity, KCU was obtained by disturbing the process by altering the controller gain until the output had a sustained oscillation. 3

7 Figure 2- Offset versus sensitivity. Effect of load change. The amplitude ratio :4 corresponded to a controller gain, KC, equal ½ * KCU, which was the recommended setting for a P-controller according to Z-N. This was evaluated for load change when a P-controller was applied to the process. The process response had an increasing offset from the set point with a decreasing value for KC lower than the KCU, as seen in Figure 2-. At KCU the response was a sustained oscillation with period P u. The period of oscillation (Pu) at the stability limit, produced a good index of required integration time, I. The Pu of the process was 0.8 min, see Figure 2-, and the optimum setting for a PI-controller was according to Z-N KC = 0.45*KCU and I = Pu /.2. Integration time, I, was inverse the denoted reset rate in the article. The gain was reduced compared with the P-controller, because otherwise the amplitude ratio would have been increased markedly. 4

8 Figure 2-2 Reset-rate versus recovery. Load change. The derivative action part of the controller was introduced in the last experiment for the closed-loop example. D or pre-act-time improved the controller performance for this example. The optimum D was reported to be 8 P (for further details ). U 5

9 Figure 2-3 PID-Controller. Load change. A supplementary piece of information in the paper was that when the gain, integral and derivative action used in the last example in the paper (Figure 2-3): - The maximum deviation form the set point was cut 7 percent T, - the period of oscillation was reduced by 43 percent, - and the time required for the oscillation to die out was halved Controller configuration The industrial pneumatic PID-controllers, which were used at the time Ziegler and Nichols wrote the paper on simple tuning rules, had mainly two different setups. The ideal (or parallel) and the cascade (or series) arranged PID-controllers, with general transfer functions show in the next equations and in the figures.. An ideal PID-Controller: GC KC ( Ds) Equation 2- Ideal PID-controller. s I 6

10 An ideal PID controller was however physically unrealizable. Commercial controllers approximated the ideal behavior by using transfer functions of the following forms, with typical between : 2. Cascade transfer function for a pneumatic PID-controller. G K C I D C( )( ) I D Equation 2-2 Pneumatic cascade PID-controller Figure 2-4 Series/Cascade -coupled PID-controller The restrictors shown in the figure were placed after one another, i.e. the controller was on the cascade form. 3. Ideal () transfer function for a pneumatic PID-controller. I D GC K C I D ) Equation 2-3 Pneumatic ideal () PID-controller 4. Ideal (2) transfer function for a pneumatic PID-controller 2. I D GC K C I D ) Equation 2-4 Pneumatic ideal (2) PID-controller 7

11 Figure 2-5 Parallel-coupled pneumatic PID-controller The first industrial PID controllers were of the interacting type. These were designed to solve a process control problem, and not a particular mathematical as today s PID controllers 3. The principal design differences between the two controller setups, are placement of the derivative and integrating functions in series or parallel, which brought about different kind of interaction between the modes. The result of the interaction was that in real pneumatic controllers the proportional, integral and derivative parts produced actions that differed from those of a completely ideal controller, which would have had no interaction between the modes. This is described in detail in the follow text, mainly through function analysis of a pneumatic PID controller Taylor Fulscope, a pneumatic PID-Controller Transfer function for a three-mode controller (Figure 2-6) was compared with the previous ones descried earlier. The Taylor Fulscope was a PID controller with interacting controller parts. The functional behavior of the Fulscope controller has been described in several publications 4, 5, 6, 7, and is described in the follow section. The main components in the controller is the baffle-nozzle system, bellows, resistances and the relay ( see Figure 2-6). 8

12 Figure 2-6 The Taylor Fulscope controller A schematic diagram for the same controller is presented in Figure 2-7. This arrangement has the integral and derivative action restrictors in parallel. Figure 2-7 A schematic diagram The parameters in the diagram and equations are described below: - p is controller output pressure. - c is the amplification factor relating a small flapper movement to a large change in output pressure. 9

13 - a and b are the relative effect of movement of the deviation and feed-back linkages. - g is the spring constant of the feed-back bellows. - is the distance between the nozzle and the flapper, or the error detecting device. - p and p2 represent bellow pressures. - is the time-constant of the derivative action restrictor and the space surrounding the bellows in the drum. - 2 is time constant of the integral action restrictor and feed-back bellows. The differential equations for the Taylor are shown in the following equations 4,5. b a p c cg ( p2 p) a b a b dp2 ( p p ) Equation 2-5 dt s dp2 ( p p ) dt r After the equation was rearranged and with the assumption c>>, which is equivalent to stating that c approaches infinite or an infinite baffle-nozzle gain, this gave an equation that was similar to an ideal controller. G C b 2 2 s ag 2 ( 2 ) s 2 Equation 2-6 Taylor Fulscope The Equation 2-6 gives an ideal controller when inserted for the following parameters. K I C b 2 ' ag 2 2 D 2 2 Equation 2-7 Taylor Fulscope on the ideal form For the intermediate frequencies, the response is that of an ideal controller, except that the gain, derivative time, and the reset time differ from the dial settings 6. They are KC, I and D and given in the Equation The dial controller settings are therefore only 0

14 nominal values. The effective values may differ from the nominal values by as much as 30%, because off the interactions among the modes 2. The effect of the interaction on the controller gain could be even larger, since the gain is increased by a factor of about ( + 2)/( -2). This can be denoted as an interaction factor, I, according to an approximated ideal formula: D GC KC ( Ds) Equation 2-8 s D D According to the equation, as approaches D, the gain approaches infinity. When 2 is greater than the denominator term containing affecting the gain becomes negative, indicating unstable behavior. This instability arises because the pressure in the reset (derivative) bellows changes more rapidly than the pressure in the feedback bellows. The interaction factor (I + D)/(I -D) becomes infinite and therefore the gain of the controller becomes infinite 5. The controller would in such situations behave as a 2-step (on/off) action controller when I = D. This must clearly be avoided if the controller is to be operated as a continuous 3-action controller. It should in accordance with the facts above be emphasized that the interacting character of such controllers means that they have to be calibrated for different derivative and the integrating tasks. 2.3 Cascade PID- Controller The instability arising from too much derivative action in a parallel controller can be avoided by putting the derivative and integral resistances in series 6. The two resistances and capacities form a dead-end interacting system, or a series arrangement, as illustrated in Figure 2-4. Aikman and Rutherford 4 have derived a transfer function and the corresponding blended parameters for such a controller.

15 GC KC( 2 ) s 2 2( 2 ) s Equation 2-9 Cascade PID b KC, I 2( 2 ), D ag The interaction factor, I, has become greater than that with parallel feedback, but the controller is stabile for all derivative times. This is because the controller gain stays finite for D = I. Generating proportional, integrating and derivative signals separately and then combining the signals would have eliminated the interaction factors which parallel and cascade old fashion controllers have. A fully ideal controller would have required a more complex pneumatic controller, but in such cases an electrical instrument with ideal response would be installed nowadays. 2.4 Literature references for Ziegler- Nichols pneumatic PID controller Several authors have discussed the pneumatic controller Z-H used to regulate processes and thereby derived their tuning rules for industrial controllers. In the next part, some of the views will be introduced. PID controllers were at the time Z-N did their experimental work of the interacting according to Shinskey 3. He states that the Z-N used a single stage pneumatic controller, which was on some sort of cascade form, when they developed their tuning rules. This affected the proportional action (P). The Peffective differed from the action a noninteracting controller in the following way according to Shinskey: P eff P Equation 2-0 Effective Proportional action D D ( ) * ( ) I I This was a serious limitation to that controller. Setting D = I forced the proportional gain to maximum, and setting D > I reversed the action for the controller. Because of this, Ziegler and Nichols kept the ratio D/I = ¼ stated Shinskey. 2

16 Connell 8 argued that Z & N were obliged to promote the ideal Taylor Fulscope controller (section 2.2.), which had the reset and derivative needle valves in parallel. Applying the same position to the two needles valves would make the controller go into on-off control. This equal setting the ratio integrating to derivative action equal to one other (see previous section dealing with the same matter). Seborg 2 has also pronounced the ideal controller configuration for the controller used by Ziegler and Nichols. The story of the development work and simulator tests on the Fulscope 00 by Ziegler and Nichols is cover in Modern Control Started with Ziegler-Nichols Tuning 9. Ziegler did preliminary tests of the PID-Fulscope controller using the demonstration room in the factory. It consisted of a series of tanks and capillaries to simulate a multicapacity system for a typical process to control pressure. The system offered slow data collection so they rented out the differential analyzer at MIT, to increase number of simulated processes. 2.5 Integrated Absolute Error, IAE, and Total Variation, TV. IAE is an object or a performance criterion, which can be used to determining the best curve hence the controller tuning which produces the best curve function 2. The design criterion used by Ziegler and Nichols was the ¼ amplitude decay ratio for closed loop response. This is often judged to be too oscillatory by plant operating personnel and only the two first peaks of the closed-loop response are considered. IAE (below) is a controller design relation based on a performance index that considers the entire closed-loop response. IAE e dt Equation 2- Integral of absolute values of the error Total Variation, TV, is also a performance criterion for closed-loop response, but in contrast to the IAE, the objective for TV is to measure the total variation in the controller output signal, u. TV Equation 2-2 u i u i 3

17 3 Results 3. An approximate to Z-N s process example Ziegler and Nichols have in their paper a single illustrative example. The controller setup, cascade or parallel, was to be found. The first goal of this experimental part was therefore to establish a model of the process though a transfer function, which had the same behavior as the process example in the paper. This could subsequently make it possible to determine the controller setup. In accordance with the procedure in section 2.. the ultimate gain and period of the resulting sustained oscillation, referred to as ultimate period, Pu, was given in the paper. One parameter for the process was therefore known. The ultimate period was 48 seconds, and this was used to establish possible transfer functions for the described process. A routine (minbode.m in Appendix D) programmed in Mathlab calculated among other values the exact phase angle for transfer functions. One could then at the phase crossover frequency, 80, determine the ultimate period, 2 P U. It was also known that the process had deadtime, roughly estimated by Ziegler and Nichols to be 2 seconds. The known foundation for experiments and comparisons was then a process with deadtime, process output from Ziegler and Nichols shown in section 2..2 and the value for ultimate period. The controller setups (cascade and parallel) that were investigated are displayed in the two next figures. A difference in controller output and performance would only occur when the three controller modes were in action. The cascade setup was used in simulations with P- and PI-controllers. 80 4

18 u To Workspace input u disturbance Step Kc * [taui ](s) taui.s PI-Controller s Transfer Fcn Transport Delay taud.s+ 0.*tauds+ Derivative part output y y To Workspace 0 Clock tid To Workspace Figure 3- Block diagram for a cascade control system in Simulink.. To Workspace u disturbance Step Sum2 Kc * [taui ](s) taui.s PI-Controller Sum Sum s Transfer Fcn Transport Delay Kc*[taud 0](s) 0.*tauds+ Derivative del output y y To Workspace 0 Clock tid To Workspace2 Figure 3-2 Block diagram for parallel control system in Simulink Simulation results Table 3- Symbols used in this section were: Descriptions Symbol Unit Ultimate period Pu Second Deadtime Second Ultimate gain KU - Controller gain KC - Integral time constant I Second Derivative time I Second 5

19 The load disturbance occurred 0 seconds after simulation was started, and was magnitude a unit. The process transfer function was simulated in Simulink, a dynamic system simulation tool in Mathlab, with proportional, proportional-integral and proportional-integral-derivative controllers according to ZN-experiments Deadtime process G S ( s) e Equation 3- (G = Process transfer function) Table 3-2 Process, simulation parameters and results. Process parameter Simulation Num. Pu KU The ultimate period and gain could also have been calculated through the follow equations: 80 :, 80 2 GM K U 2 2 Equations 3-2 The result for the simulation was that a pure delay process was not comparable with the process Z-N controlled Process with integrating action and deadtime S G S2 e, Equation 3-3 s Table 3-3 Process 2, simulation parameter and results Process parameter Results Simulation Num., sec, sec Pu, sec KU 2 infinite

20 The transfer function was evaluated within a range for the process parameters. Some of the results are presented in the table above. Figure 3-3 shows the results for KC = KU which were compared with the results from Z-N (Figure 2-2). The process had, as seen from the simulations, too little oscillatory behavior and too short period. Proscess 2 P-Controller (Kc=0.45*Ku) output y time [s] infinite (4) Figure 3-3 Simulation results Process Processes with deadtime, integrating action and a first-order transfer function. G S 3 ( s) e Equation 3-4 s s The number of possible solutions was increasing with the complexity of the transfer function. Table 3-4 shows some tested parameter, and the ultimate values for the process, at 2-second deadtime. Table 3-4 Results from calculations in Mathlab. Process parameter Ultimate values Simulation Num., sec, sec Pu, sec KU

21 The first parameter, which the process should have fulfilled, was the ultimate period (48s). The period for sustained oscillation was the most accurate and useful information given in the paper for the preliminary search. Feasible solutions were screened, by using the minbode.m routine in Mathlab, for ranges of deadtimes and time constants,. Results for some of the feasible points after the calculations are in Table 3-5. Table 3-5 Sample results from calculations in Mathlab Process parameter Ultimate values Simulation Num., sec, sec Pu, sec KU Process 3, P-Controller out y Time [s] sim sim 2 sim 3 sim 4 sim 5 Figure 3-4 Process simulation results for P-Controller The controller parameters were set according to experiments in the paper: P-controller: KC = 0.45*KU and PI-controller: KC = 0.45*KU, I = PU/.2 and D = 0 8

22 Process 3, PI-Controller 25 out y sim sim 2 sim 3 sim 4 sim 5 Time [s] Figure 3-5 Process simulation results for PI-Controller Results from simulations (-5) were only in some agreement with the results that ZN obtained in their process example. The crossover did not occur in Ziegler and Nichols experiments Processes with deadtime and a second-order transfer function G S 4 ( s) e Equation 3-5 s 2s The number of possible solutions was further increased by the introduction of another first order transfer function. The assumed process dynamic in this section was a second order transfer function. The feasible region was therefore to be truncated by some assumptions. The derivative action used in the last part of Ziegler and Nichols experiments, remarkably improved the controller performance in PID- setup. The derivative part was assumed to be almost equal to the deadtime, because this could result in a canceling of this term. A selection of the promising parameters for the transfer function resulting from the evaluation of period and simulations are presented in Table

23 All the parameters for the transfer function were simulated with P and PI- controller actions in accordance with the experiments performed in the article (P-controller: KC = 0.45*KU and PI-controller: KC = 0.45*KU, I = PU/.2 and D = 0). Table 3-6 Parameters for the 2.order transfer function. Process parameter Ultimate values Simulation Num., sec, sec 2, sec Pu, sec KU The simulation results for the parameters given in Table 3-6 resulted in a reduction of the feasible region for possible solutions to the transfer function (deadtime [8 0], [5 7.5] and 2 [30 40] (see appendix A). Parameters given for simulations 5 to 0 gave the most promising outputs when compared with Z-N s measured process output (see Figure 2-3 and Figure 3-6). These values were therefore used in the closing simulations, for cascade and the two ideal setups for PID-controllers. The PI-controller actions were as described above. 20

24 output y Process 4, PI-controller time [s] sim5 sim6 sim7 sim8 sim9 sim0 Figure 3-6 Results for parameters 5 to 0. Parameters for Process 4 used in the simulations above, were then simulated with the 3 considered controller transfer functions. The sets of parameters were renumbered from to 5. Knobs setting for the 3 controllers are the same as described by Ziegler and Nichols in their 3-mode controller experiment (see Figure 2-3). Table 3-7 Controller settings for PID experiments. Experiment Num. Controller settings KC I D 0.45 * KU PU /.2 PU / * KU PU /2.08 PU /8 The two experiments listed above were simulated for each of the controllers and graphical presentations of the results are shown in the following parts. 2

25 Ideal () PID Controller. Transfer function for an ideal PID controller 0.50 Ideal () PID-Controller para output y para 2 para 3 para 4 para 5 para 6. time [s] Figure 3-7 Ideal() PID Controller. Experiment Num Ideal () PID -Controller output y para para 2 para 3 para 4 para 5 para time [s] Figure 3-8 Ideal () PID-Controller. Experiment Num. 2 22

26 Ideal (2) PID Controller (page 7). Transfer function for an ideal PID controller stated by Seborg et al 2 Ideal (2) PID-Controller output y time [s] para para 2 para 3 para 4 para 5 para 6 Figure 3-9 Ideal(2) PID Controller. Experiment Num. Ideal (2) PID -Controller output y time [s] para para 2 para 3 para 4 para 5 para 6 Figure 3-0 Ideal (2) PID-Controller. Experiment Num.2 23

27 Cascade PID controller (see page 7) Cascade PID-Controller output y time [s] para para 2 para 3 para 4 para 5 para 6 Figure 3- Cascade PID-Controller. Experiment Num. 0.5 Cascade PID -Controller output y time [s] para para 2 para 3 para 4 para 5 para 6 Figure 3-2 Cascade PID-Controller. Experiment Num.2 24

28 Simulation results from the ideal( ) PID-controlled processes gave responses that were in agreement with the results from Z-N. Tests with wider a controller setting area, i.e. used ZN-tunings as circa specification because of the reported difficulties setting the interacting control modes, but this just slightly improved the result conformities. Calculations were done iterative in Mathlab, by using the improvement effect of derivative action added compared with PI-action as convergence criteria. 25

29 3.3 Performance criteria for controllers There exist different tuning rules for controller settings and some of these tunings were applied to the processes in this section. The equations and the tuning rules are the same as those found in Skogestad s Probably the best simple PID tuning rules in the world 0. The tunings rules used were SIMC, IMC, ZN, Aströms and Tyreus-Luyben. The performance values Integrated Absolute Error, IAE, and Total Variation, TV, for controllers with different tunings were calculated. Tuning rules and the derivation of the corresponding controller parameters for simulated processes can be found in Skogestad 0 except of ZN PID tunings. The applied controller was on the cascade form and processes were regulated with P-, PI and PID-controllers. The processes were simulated in Simulink, and IAE and TV were calculated in Mathlab by using the script IAEandTV.m (see Appendix B). A set point change and a load change were disturbances for the processes. IAE was calculated for process output (y) and TV was calculated for process input (u). Ziegler and Nichols tuning rules were assumed to be valid for a controller on the ideal form. Coefficient for a cascade-controller had to be calculated from coefficient for the ideal form. Primed values are for the cascade form. According to ZN-PID tunings the ratio D / I was equal ¼ and thereby canceled the last term in the equation below. K K ' 4 D / 2 I I I ' 4 D / I 2 Equations 3-6 I D ' 4 D / I 2 26

30 Seven process examples were simulated. Integral absolute error, IAE, and total variation, TV, were calculated from the resulting process input (controller output) and output. Results from simulation outputs are shown in Appendix C. The set point change was a unit, y s, and the input load disturbance, d u, was of magnitude 0.5 if no other is specified for the process Pure dead time process G S ( s) ke Equation 3-7 Time delay process Tunings KC. k K I. k. IAE (set point) IAE (load) TV (set point) TV (load) SIMC (c =) Astrom (Ms =.4) Astrom (Ms = 2.0) ZN Table 3-8 Process Tunings and performance values Integrating process S e G2 ( s) k' Equation 3-8 Integrating process with time delay. s Table 3-9 Process 2- Tunings and performance values Tunings KC. k. I / D / IAE (set IAE TV TV point) (load) (set point) (load) SIMC (c =) IMC infinite Astrom (Ms =.4) Astrom (Ms = 2.0) Tyreus Luyben ZN-PI ZN-PID

31 3.3.3 Process examples ( 0.3s )(0.08s ) G 3( s) 20 (2s )(s )(0.4s )(0.2s )(0.05 ) 3 Table 3-0 Processes 3, tunings and performance value. Tunings KC. k I D IAE IAE TV TV (set point) (load) (set point) (load) SIMC- PI SIMC- PID ZN-PID G4 ( s) k ( s ) 0 4 Table 3- Processes 4, tunings and performance value Tunings KC. k I / O D / O IAE (set point) IAE (load) TV (set point) TV (load) SIMC-PI SIMC-PID ZN-PI ZN-PID G 5 ( s) ( s )(0.2s )(0.04s )(0.008 s ) Table 3-2 Process 5, tunings and performance values. Tunings KC I D IAE (set IAE TV (set TV (load) point) (load) point) SIMC-PI SIMC-PID Astrom-PI (Ms=2.0) ZN-PI ZN-PID Remark: Ziegler-Nichols tunings on a PI-controller would have led to instability. 2 (0.7s ) G 6 ( s) 2 s( s ) (0.028 s ) 28

32 Table 3-3 Process 6, tunings and performance values. (Load disturbance of magnitude 2) Tunings KC I D IAE IAE TV TV (set point) (load) (set point) (load) SIMC-PI SIMC-PID Aström (Ms = 2.0) ZN-PID ZN s PI- tunings gave an unstable response, i.e. increasing amplitudes, if it were applied to the controller. 29

33 4 Discussion 4. The PID controller of Ziegler and Nichols. 4.. The preliminary evaluation of processes Based on Ziegler and Nichols experience with the transient for many types of processes they developed a method for tuning in closed-loop. They suggested that ultimate controller gain, Kcu, and ultimate period, Pu, where to be obtained from a closed-loop test of the actual process. They published their paper in 942, but in the literature there are still discussed whether they used a controller with a configuration in accordance with the cascade or the parallel form. Trough finding a process model matching the one Ziegler and Nichols were controlling, one should have had a good start point for investigating different controller transfer functions. The simulation results in the previous chapter gave reasons for some notes. Implementations of the oscillation results were done only with the means of visual interpretation. This was however judged to give enough accuracy, because transferring the plotted results from ZN to data output could only be done at low precession. The dead time process, Process 2 and Process 3 were tested, but gave too little oscillatory movement when comparing with the results from ZN. Adding more dynamical behavior through a 2.order transfer function with dead time (process 4, p.9) was therefore an approach to the transfer function for Z-N s process. Numerous variations in transfer function parameters, i.e. dynamical responses, were tested and compared with ZN s. Presented process responses for parameters 5 to 0 in Table 3-6 were judged comparable to experimental example in the paper Settings and simulation results for PID-Controllers Figure 3-7 to Figure 3-2 showed simulation results for the different PID-controllers. Results from the first experiment for the cascade controller agreed visual with the corresponding ZN results (Figure 2-3). The second experiment on the other hand had response not in agreement. The output oscillated with some amplitude decrease around 30

34 zero, rather than having a ¼ amplitude reduction ratio, which was the aim in Ziegler- Nichols tuning rules and also the result from their experiment. The ideal pneumatic PID-controller (Ideal-2) equation proposed by Seborg et al. 2, had simulation results far from the Ziegler-Nichols. Experiment gave considerable amplitude decrease, but the second experiment gave an unstable response with increasing amplitude. The unsuitability was an effect of the major difference between this controller and the two other. Ideal-2 controller brought along an extra term in the derivative part. D G K ) Equation 2-4) D I ( C C I An increase of the proportional gain to 90 % of the ultimate gain, which was the case for the last experiment, would almost denote a doubled proportional action for this type of controller. The controller gain was therefore brought higher than the corresponding gain margin permitted for closed loop stability. Simulation results for closed loop response for the Ideal ()-controller distinguished itself in the aspect of approximating the ZN -process and thereby the controller transfer function. The Ideal () was the controller equation with most resemblance to a completely ideal controller. Visual interpretations of results were earlier considered accurate enough. Ziegler-Nichols gave however for the PI- and PID-experiments the effect of adding derivative action (see chapter. 2..2). The effect of adding derivative action for the control of Process 4 was a 38 percent reduced deviation from the set point (ZN had 7 percent) and period of oscillation was reduced by 26 percent (ZN reported 43 percent). The process could therefore be sub-optimal and/or the almost ideal transfer function did not represent the reel one used by Ziegler-Nichols. Other parameters than presented in this report were also tested in the 2.order transfer function with dead time. This was done iteratively with a fixed increment on the parameter within wide ranges, but gave poor result improvements. An optimizing problem could have been formulated, but this would then have required an effective solver, which integrated both Mathlab-scripts and a Simulink-model, and the solver had to handled constraints. Higher order transfer function could then have been investigated effectively if this was formulated. The lack of 3

35 accuracy in ZN s reported data and the true controller equation would still cause problems The Taylor Fulscope Controller and related topics According to the article Modern Control Started with Ziegler-Nichols Tuning 9, Connell 8 and others, Ziegler and Nichols were using the Taylor Fulscope controller when they developed their tuning rules. The choice of controller was obvious because they both worked for Taylor Instrument Companies, and were actively participating in finding application for the controller. Ziegler-Nichols tuning rule for PID-control is to have I = 4. D, and this is assumed to be for an ideal controller: GC KC ( Ds) I s Equation 2- Comparing the ideal equation with the one derived for Taylor Fulscope controller; G C b 2 2 s ag 2 ( 2 ) s 2 Equation 2-6 and inserted for I = 4. D, this would eventually mean having = 2. The actual gain would at this point approach infinity and the response would be unstable. If instead one tried setting 2 = 4. the corresponding effective time constants would have be D = 25/4. I. The ratio 25/4 differs considerable from Ziegler-Nichols tuning rules presented in the paper. Ratio value for their last experiment in the paper was D = I, and consequently the controller settings should have led to instability. This aspect stands in contrast to what ZN reported, which was a considerable improved control performance. The simple Taylor Fulscope equation had also some resemblance with a controller on the cascade form. The difference was the interaction term for the controller gain, which could lead to infinite gain. If the equation above was assumed to be correct, a cascade controller setup should have been a good approximation to the controller transfer function. 32

36 The equation for Taylor Fulscope controller was derived for infinite baffle-nozzle gain. Infinite gain is however not physically realizable. An equation describing the controller should perhaps take a limited gain in to count. Hougen 2 derived an equation for a pneumatic parallel PID-controller with finite gain. Deriving a transfer function with finite gain for the Taylor Fulscope controller gave results agreeing with Hougen s results. The function complexity was increased, and thereby the reducing the ease to compare it with an ideal PID controller transfer function. G C K C ( s)( 2s) ( s)( s) a b Equation 4- PID transfer function from Hougen Where a and b are dependent on both and 2. G C ( s)( s) K ( ) ( ) s 2 2 2s 2 Equation 4-2 PID transfer function from C&K The equation above was derived from the book of Coughanowr and Koppel 7, by using nomenclature and assumptions from their derivation of PI- and PD-equations for the Taylor Fulscope controller. As earlier noted are these equations more difficult to handle than the simpler one with infinite baffle-nozzle gain, the constants in the denominators have to be calculated after experimental work according to Hougen. The transfer functions shown above maybe less restrictive to D / I ratios, and thereby not have the strange limitation that their own tunings could not be applied to the Taylor Fulscope controller. Pneumatic controllers depart from the theoretical ideal controller. Ziegler-Nichols used the differential analyzer at MIT to speed up data collection from simulated processes 9. The analyzer consisted of mechanical integrators that solved differential equations. A PID controller could be utilized on this device through differential equations. The controller could then be ideal, only limited by the machine accuracy and mechanical limits. A mathematical analysis of the functional behavior of the pneumatic PIDcontroller was yet to be done at that time. Implementing a PID controller on the analyzer 33

37 would therefore have had more similarities with an ideal equation than a pneumatic controller. 4.2 Performance criteria for controllers Set point changes or load changes were the process disturbances. The integral absolute errors for the process outputs, y, and total variation were depending on applied tuning rules to the controllers. The controller gain, K C, given from the different controller settings was varying considerably from setting to setting. Ziegler-Nichols tunings had in most cases the highest K C values. Increasing the controller gain leads to a larger change in the controller output. Increasing the gain to a certain limit can lead to response instability, causing overshoots and oscillation if the process is disturbed. An effect of the high-controller gain from ZN-tuning is relatively low IAE values, but on the other hand the controller output tends to oscillate with corresponding higher values for total variation, TV (see Table 3-8 to Table 3-3). Skogestad s settings have relatively low K C values and hence slower response also observed by Holm et al. 3, but do not have the same problem with robustness and stability. Aström s settings gave controller gain in the mid-area compared with ZN s and Skogestad s settings. The offset from set point is reduced at different rates for the tunings. ZN s tunings have relatively small integral time constants and therefore a faster response to error. As for the high-gain, a small integral time reduces the stability (see figures in Appendix C). This would easily be seen in a Bode-diagram by the lowered gain and phase margins. The IAEs for set point and load changes were small, but because the controller output often oscillated a higher total variation was reached. Skogestad s settings had in general higher I s and with those had somewhat slower response to error, but the stability was kept. Skogestad s rules gave small IAEs for set point changes. At load disturbance the integral absolute errors were slightly larger because of the slower response. Derivative action in the controller adds sensitivity to the direction of the error, and generally reduced the overshot and IAE. For Skogestad s tunings the process output tends to oscillate for processes with small time constants, because of the slower response, with corresponding higher TV as in example Process 5. 34

38 5 Conclusion Based on the results from the simulations of different processes with controllers on the cascade and ideal forms, a conclusion could be drawn. Simulations with a controller on the ideal () form (Equation 2-3) gave results that were agreeing with Ziegler-Nichols results in the paper. The two other tested controller settings gave results that were not corresponding to ZN s results. Ziegler and Nichols tunings are therefore most likely for an ideal PID controller. They were running simulations on the Taylor Fulscope controller, and several authors have done functional analysis of this pneumatic controller. Coughanowr and Koppel derived a transfer function for the Taylor instrument, but according to that function with infinite gain, Ziegler and Nichols tunings could not be applied to the Fulscope controller. Transfer function with finite gain should therefore be considered if a true picture of the pneumatic controller is sought. The transfer function would then be a more complex interaction function, which would be difficult to transpose to an ideal equation. Ziegler-Nichols used a differential analyzer at MIT to simulate processes at a higher speed. Transfer function for a PID controller had to be implemented on the analyzer and a PID controller on the ideal form would most probably have been applied to the differential analyzer. Depending on the true transfer function for the Taylor Fulscope controller, tuning results from MIT could only been used on the pneumatic device after translating them. An accurate translation would be troublesome without knowing the Fulscopes transfer function. There are according to mentioned aspects reasons to believe that the tuning rules are for ideal controller, and were mainly worked out on a mechanical differential analyzer. Verifying this statement could be done in an extension to this report. A functional analysis of the Taylor Fulscope controller should be done. The easiest way to verify this conclusion is to run experiments where Ziegler- Nichols tunings are applied to the Taylor Fulscope controller. Different tunings for PID-controllers for were judged by performance criteria, Ziegler- Nichols tunings gave a generally fast but unstable response. This was evident by the low values for integral absolute error (IAE) for the process output, and the higher values for total variation (TV). Skogestad s tunings gave in general somewhat slower but more stable response. This corresponded in higher IAE values and lower TV values. Sigurd Myhre Hellem Trondheim,

39 Literature Citations Ziegler, J.G. and Nichols, N.B., Optimum settings for automatic controllers, American Society of Mechanical Engineers (64), (pp ), Nov Seborg, D.E., Edgar, T.F.and Mellichamp, D.A., Process Dynamics and Control, Wiley, Shinskey, F.G., Process Control Systems (Application, Design and Tuning), McGraw, 4.ed., Tustin, A., Automatic and Manual Control (paper A.R. Aikman and C.I Rutherford: The Characteristic of Air-operated Controllers ), Butherworths Scientific Publications, Young, A.J., An Introduction Process Control System Design, Longmans, Harriott, Process Control, McGraw-Hill, Coughanowr, D.R, and Koppel, L.B., Process systems analysis and control, McGraw- Hill, Connell, B., Process Instrumentation Applications Manual, McGraw-Hill, Blickley, G.J., Modern Control Started with Ziegler-Nichols Tuning, Control Engineering, (pp. -7) 2.ed., Oct Skogestad, S., Probably the best simple tuning rules in the world, submitted to Journal of Process Control, July 3, 200. Aström, K.J., Automatic Tuning of PID, Instrument Society of America, Hougen, J.O., Measurements and Control Applications, 2.ed, Holm, O. and Butler, A, Robustness and Performance Analysis of PI and PID Controller Tunings, NTNU, Nov 5,

Various Controller Design and Tuning Methods for a First Order Plus Dead Time Process

Various Controller Design and Tuning Methods for a First Order Plus Dead Time Process International Journal of Computer Science & Communication Vol. 1, No. 2, July-December 2010, pp. 161-165 Various Controller Design and Tuning Methods for a First Order Plus Dead Time Process Pradeep Kumar

More information

PID TUNING WITH INPUT CONSTRAINT: APPLICATION ON FOOD PROCESSING

PID TUNING WITH INPUT CONSTRAINT: APPLICATION ON FOOD PROCESSING 83 PID TUNING WITH INPUT CONSTRAINT: APPLICATION ON FOOD PROCESSING B L Chua 1, F.S.Tai 1, N.A.Aziz 1 and T.S.Y Choong 2 1 Department of Process and Food Engineering, 2 Department of Chemical and Environmental

More information

CHBE320 LECTURE XI CONTROLLER DESIGN AND PID CONTOLLER TUNING. Professor Dae Ryook Yang

CHBE320 LECTURE XI CONTROLLER DESIGN AND PID CONTOLLER TUNING. Professor Dae Ryook Yang CHBE320 LECTURE XI CONTROLLER DESIGN AND PID CONTOLLER TUNING Professor Dae Ryook Yang Spring 2018 Dept. of Chemical and Biological Engineering 11-1 Road Map of the Lecture XI Controller Design and PID

More information

BINARY DISTILLATION COLUMN CONTROL TECHNIQUES: A COMPARATIVE STUDY

BINARY DISTILLATION COLUMN CONTROL TECHNIQUES: A COMPARATIVE STUDY BINARY DISTILLATION COLUMN CONTROL TECHNIQUES: A COMPARATIVE STUDY 1 NASSER MOHAMED RAMLI, 2 MOHAMMED ABOBAKR BASAAR 1,2 Chemical Engineering Department, Faculty of Engineering, Universiti Teknologi PETRONAS,

More information

-binary sensors and actuators (such as an on/off controller) are generally more reliable and less expensive

-binary sensors and actuators (such as an on/off controller) are generally more reliable and less expensive Process controls are necessary for designing safe and productive plants. A variety of process controls are used to manipulate processes, however the most simple and often most effective is the PID controller.

More information

F. Greg Shinskey. "PID Control." Copyright 2000 CRC Press LLC. <

F. Greg Shinskey. PID Control. Copyright 2000 CRC Press LLC. < F. Greg Shinskey. "PID Control." Copyright 2000 CRC Press LLC. . PID Control F. Greg Shinskey Process Control Consultant 97.1 Introduction 97.2 Open and Closed Loops Open-Loop

More information

Performance Analysis of Conventional Controllers for Automatic Voltage Regulator (AVR)

Performance Analysis of Conventional Controllers for Automatic Voltage Regulator (AVR) Performance Analysis of Conventional Controllers for Automatic Voltage Regulator (AVR) Ajit Kumar Mittal M.TECH Student, B.I.T SINDRI Dhanbad, India Dr. Pankaj Rai Associate Professor, Department of Electrical

More information

Design of Model Based PID Controller Tuning for Pressure Process

Design of Model Based PID Controller Tuning for Pressure Process ISSN (Print) : 3 3765 Design of Model Based PID Controller Tuning for Pressure Process A.Kanchana 1, G.Lavanya, R.Nivethidha 3, S.Subasree 4, P.Aravind 5 UG student, Dept. of ICE, Saranathan College Engineering,

More information

Modified ultimate cycle method relay auto-tuning

Modified ultimate cycle method relay auto-tuning Adaptive Control - Autotuning Structure of presentation: Relay feedback autotuning outline Relay feedback autotuning details How close is the estimate of the ultimate gain and period to the actual ultimate

More information

Optimal Control System Design

Optimal Control System Design Chapter 6 Optimal Control System Design 6.1 INTRODUCTION The active AFO consists of sensor unit, control system and an actuator. While designing the control system for an AFO, a trade-off between the transient

More information

Relay Feedback based PID Controller for Nonlinear Process

Relay Feedback based PID Controller for Nonlinear Process Relay Feedback based PID Controller for Nonlinear Process I.Thirunavukkarasu, Dr.V.I.George, * and R.Satheeshbabu Abstract This work is about designing a relay feedback based PID controller for a conical

More information

New PID Tuning Rule Using ITAE Criteria

New PID Tuning Rule Using ITAE Criteria New PID Tuning Rule Using ITAE Criteria Ala Eldin Abdallah Awouda Department of Mechatronics and Robotics, Faculty of Electrical Engineering, Universiti Teknologi Malaysia, Johor, 83100, Malaysia rosbi@fke.utm.my

More information

InstrumentationTools.com

InstrumentationTools.com Author: Instrumentation Tools Categories: Control Systems Ziegler-Nichols Closed-Loop Method (Ultimate Gain) Closed-loop refers to the operation of a control system with the controlling device in automatic

More information

Experiment 9. PID Controller

Experiment 9. PID Controller Experiment 9 PID Controller Objective: - To be familiar with PID controller. - Noting how changing PID controller parameter effect on system response. Theory: The basic function of a controller is to execute

More information

6545(Print), ISSN (Online) Volume 4, Issue 1, January- February (2013), IAEME & TECHNOLOGY (IJEET)

6545(Print), ISSN (Online) Volume 4, Issue 1, January- February (2013), IAEME & TECHNOLOGY (IJEET) INTERNATIONAL International Journal of JOURNAL Electrical Engineering OF ELECTRICAL and Technology (IJEET), ENGINEERING ISSN 0976 & TECHNOLOGY (IJEET) ISSN 0976 6545(Print) ISSN 0976 6553(Online) Volume

More information

Procidia Control Solutions Dead Time Compensation

Procidia Control Solutions Dead Time Compensation APPLICATION DATA Procidia Control Solutions Dead Time Compensation AD353-127 Rev 2 April 2012 This application data sheet describes dead time compensation methods. A configuration can be developed within

More information

MM7 Practical Issues Using PID Controllers

MM7 Practical Issues Using PID Controllers MM7 Practical Issues Using PID Controllers Readings: FC textbook: Section 4.2.7 Integrator Antiwindup p.196-200 Extra reading: Hou Ming s lecture notes p.60-69 Extra reading: M.J. Willis notes on PID controler

More information

Relay Based Auto Tuner for Calibration of SCR Pump Controller Parameters in Diesel after Treatment Systems

Relay Based Auto Tuner for Calibration of SCR Pump Controller Parameters in Diesel after Treatment Systems Abstract Available online at www.academicpaper.org Academic @ Paper ISSN 2146-9067 International Journal of Automotive Engineering and Technologies Special Issue 1, pp. 26 33, 2017 Original Research Article

More information

A Case Study in Modeling and Process Control: the Control of a Pilot Scale Heating and Ventilation System

A Case Study in Modeling and Process Control: the Control of a Pilot Scale Heating and Ventilation System Dublin Institute of Technology ARROW@DIT Conference papers School of Electrical and Electronic Engineering 2006-01-01 A Case Study in Modeling and Process Control: the Control of a Pilot Scale Heating

More information

Some Tuning Methods of PID Controller For Different Processes

Some Tuning Methods of PID Controller For Different Processes International Conference on Information Engineering, Management and Security [ICIEMS] 282 International Conference on Information Engineering, Management and Security 2015 [ICIEMS 2015] ISBN 978-81-929742-7-9

More information

Design of an Intelligent Pressure Control System Based on the Fuzzy Self-tuning PID Controller

Design of an Intelligent Pressure Control System Based on the Fuzzy Self-tuning PID Controller Design of an Intelligent Pressure Control System Based on the Fuzzy Self-tuning PID Controller 1 Deepa S. Bhandare, 2 N. R.Kulkarni 1,2 Department of Electrical Engineering, Modern College of Engineering,

More information

Instrumentation and Process Control. Process Control. Pressure, Flow, and Level. Courseware Sample F0

Instrumentation and Process Control. Process Control. Pressure, Flow, and Level. Courseware Sample F0 Instrumentation and Process Control Process Control Pressure, Flow, and Level Courseware Sample 85982-F0 A INSTRUMENTATION AND PROCESS CONTROL PROCESS CONTROL Pressure, Flow, and Level Courseware Sample

More information

Auto-tuning of PID Controller for the Cases Given by Forbes Marshall

Auto-tuning of PID Controller for the Cases Given by Forbes Marshall International Journal of Electronics Engineering Research. ISSN 0975-6450 Volume 9, Number 6 (2017) pp. 809-814 Research India Publications http://www.ripublication.com Auto-tuning of PID Controller for

More information

CHAPTER 4 AN EFFICIENT ANFIS BASED SELF TUNING OF PI CONTROLLER FOR CURRENT HARMONIC MITIGATION

CHAPTER 4 AN EFFICIENT ANFIS BASED SELF TUNING OF PI CONTROLLER FOR CURRENT HARMONIC MITIGATION 92 CHAPTER 4 AN EFFICIENT ANFIS BASED SELF TUNING OF PI CONTROLLER FOR CURRENT HARMONIC MITIGATION 4.1 OVERVIEW OF PI CONTROLLER Proportional Integral (PI) controllers have been developed due to the unique

More information

Simulation and Analysis of Cascaded PID Controller Design for Boiler Pressure Control System

Simulation and Analysis of Cascaded PID Controller Design for Boiler Pressure Control System PAPER ID: IJIFR / V1 / E10 / 031 www.ijifr.com ijifr.journal@gmail.com ISSN (Online): 2347-1697 An Enlightening Online Open Access, Refereed & Indexed Journal of Multidisciplinary Research Simulation and

More information

CONTROLLER TUNING FOR NONLINEAR HOPPER PROCESS TANK A REAL TIME ANALYSIS

CONTROLLER TUNING FOR NONLINEAR HOPPER PROCESS TANK A REAL TIME ANALYSIS Journal of Engineering Science and Technology EURECA 2013 Special Issue August (2014) 59-67 School of Engineering, Taylor s University CONTROLLER TUNING FOR NONLINEAR HOPPER PROCESS TANK A REAL TIME ANALYSIS

More information

International Journal of Research in Advent Technology Available Online at:

International Journal of Research in Advent Technology Available Online at: OVERVIEW OF DIFFERENT APPROACHES OF PID CONTROLLER TUNING Manju Kurien 1, Alka Prayagkar 2, Vaishali Rajeshirke 3 1 IS Department 2 IE Department 3 EV DEpartment VES Polytechnic, Chembur,Mumbai 1 manjulibu@gmail.com

More information

ChE 4162 Control Laboratory Methodologies Fall Control Laboratory Methodologies

ChE 4162 Control Laboratory Methodologies Fall Control Laboratory Methodologies Control Laboratory Methodologies Edited by: HJT from Material by DBM 1/11 9/23/2016 1. Introduction There seem to be about as many ways to study and tune control systems as there are control engineers.

More information

LAMBDA TUNING TECHNIQUE BASED CONTROLLER DESIGN FOR AN INDUSTRIAL BLENDING PROCESS

LAMBDA TUNING TECHNIQUE BASED CONTROLLER DESIGN FOR AN INDUSTRIAL BLENDING PROCESS ISSN : 0973-7391 Vol. 3, No. 1, January-June 2012, pp. 143-146 LAMBDA TUNING TECHNIQUE BASED CONTROLLER DESIGN FOR AN INDUSTRIAL BLENDING PROCESS Manik 1, P. K. Juneja 2, A K Ray 3 and Sandeep Sunori 4

More information

Non Linear Tank Level Control using LabVIEW Jagatis Kumaar B 1 Vinoth K 2 Vivek Vijayan C 3 P Aravind 4

Non Linear Tank Level Control using LabVIEW Jagatis Kumaar B 1 Vinoth K 2 Vivek Vijayan C 3 P Aravind 4 IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 01, 2015 ISSN (online): 2321-0613 Non Linear Tank Level Control using LabVIEW Jagatis Kumaar B 1 Vinoth K 2 Vivek Vijayan

More information

2.7.3 Measurement noise. Signal variance

2.7.3 Measurement noise. Signal variance 62 Finn Haugen: PID Control Figure 2.34: Example 2.15: Temperature control without anti wind-up disturbance has changed back to its normal value). [End of Example 2.15] 2.7.3 Measurement noise. Signal

More information

Loop Design. Chapter Introduction

Loop Design. Chapter Introduction Chapter 8 Loop Design 8.1 Introduction This is the first Chapter that deals with design and we will therefore start by some general aspects on design of engineering systems. Design is complicated because

More information

CHAPTER 2 PID CONTROLLER BASED CLOSED LOOP CONTROL OF DC DRIVE

CHAPTER 2 PID CONTROLLER BASED CLOSED LOOP CONTROL OF DC DRIVE 23 CHAPTER 2 PID CONTROLLER BASED CLOSED LOOP CONTROL OF DC DRIVE 2.1 PID CONTROLLER A proportional Integral Derivative controller (PID controller) find its application in industrial control system. It

More information

Paul Schafbuch. Senior Research Engineer Fisher Controls International, Inc.

Paul Schafbuch. Senior Research Engineer Fisher Controls International, Inc. Paul Schafbuch Senior Research Engineer Fisher Controls International, Inc. Introduction Achieving optimal control system performance keys on selecting or specifying the proper flow characteristic. Therefore,

More information

Getting the Best Performance from Challenging Control Loops

Getting the Best Performance from Challenging Control Loops Getting the Best Performance from Challenging Control Loops Jacques F. Smuts - OptiControls Inc, League City, Texas; jsmuts@opticontrols.com KEYWORDS PID Controls, Oscillations, Disturbances, Tuning, Stiction,

More information

Consider the control loop shown in figure 1 with the PI(D) controller C(s) and the plant described by a stable transfer function P(s).

Consider the control loop shown in figure 1 with the PI(D) controller C(s) and the plant described by a stable transfer function P(s). PID controller design on Internet: www.pidlab.com Čech Martin, Schlegel Miloš Abstract The purpose of this article is to introduce a simple Internet tool (Java applet) for PID controller design. The applet

More information

EMPIRICAL MODEL IDENTIFICATION AND PID CONTROLLER TUNING FOR A FLOW PROCESS

EMPIRICAL MODEL IDENTIFICATION AND PID CONTROLLER TUNING FOR A FLOW PROCESS Volume 118 No. 20 2018, 2015-2021 ISSN: 1311-8080 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu EMPIRICAL MODEL IDENTIFICATION AND PID CONTROLLER TUNING FOR A FLOW

More information

DESIGN OF PID CONTROLLERS INTEGRATOR SYSTEM WITH TIME DELAY AND DOUBLE INTEGRATING PROCESSES

DESIGN OF PID CONTROLLERS INTEGRATOR SYSTEM WITH TIME DELAY AND DOUBLE INTEGRATING PROCESSES DESIGN OF PID CONTROLLERS INTEGRATOR SYSTEM WITH TIME DELAY AND DOUBLE INTEGRATING PROCESSES B.S.Patil 1, L.M.Waghmare 2, M.D.Uplane 3 1 Ph.D.Student, Instrumentation Department, AISSMS S Polytechnic,

More information

Find, read or write documentation which describes work of the control loop: Process Control Philosophy. Where the next information can be found:

Find, read or write documentation which describes work of the control loop: Process Control Philosophy. Where the next information can be found: 1 Controller uning o implement continuous control we should assemble a control loop which consists of the process/object, controller, sensors and actuators. Information about the control loop Find, read

More information

EVALUATION ALGORITHM- BASED ON PID CONTROLLER DESIGN FOR THE UNSTABLE SYSTEMS

EVALUATION ALGORITHM- BASED ON PID CONTROLLER DESIGN FOR THE UNSTABLE SYSTEMS EVALUATION ALGORITHM- BASED ON PID CONTROLLER DESIGN FOR THE UNSTABLE SYSTEMS Erliza Binti Serri 1, Wan Ismail Ibrahim 1 and Mohd Riduwan Ghazali 2 1 Sustanable Energy & Power Electronics Research, FKEE

More information

Application of Proposed Improved Relay Tuning. for Design of Optimum PID Control of SOPTD Model

Application of Proposed Improved Relay Tuning. for Design of Optimum PID Control of SOPTD Model VOL. 2, NO.9, September 202 ISSN 2222-9833 ARPN Journal of Systems and Software 2009-202 AJSS Journal. All rights reserved http://www.scientific-journals.org Application of Proposed Improved Relay Tuning

More information

Anti Windup Implementation on Different PID Structures

Anti Windup Implementation on Different PID Structures Pertanika J. Sci. & Technol. 16 (1): 23-30 (2008) SSN: 0128-7680 Universiti Putra Malaysia Press Anti Windup mplementation on Different PD Structures Farah Saleena Taip *1 and Ming T. Tham 2 1 Department

More information

LESSON 2: ELECTRONIC CONTROL

LESSON 2: ELECTRONIC CONTROL Module 1: Control Concepts LESSON 2: ELECTRONIC CONTROL MODULE 1 Control Concepts OBJECTIVES: At the end of this module, you will be able to: 1. Sketch an open tank level application and state the mass

More information

Different Controller Terms

Different Controller Terms Loop Tuning Lab Challenges Not all PID controllers are the same. They don t all use the same units for P-I-and D. There are different types of processes. There are different final element types. There

More information

Dr Ian R. Manchester

Dr Ian R. Manchester Week Content Notes 1 Introduction 2 Frequency Domain Modelling 3 Transient Performance and the s-plane 4 Block Diagrams 5 Feedback System Characteristics Assign 1 Due 6 Root Locus 7 Root Locus 2 Assign

More information

Design and Implementation of PID Controller for Single Capacity Tank

Design and Implementation of PID Controller for Single Capacity Tank Design and Implementation of PID Controller for Single Capacity Tank Vikas Karade 1, mbadas Shinde 2, Sagar Sutar 3 sst. Professor, Department of Instrumentation Engineering, P.V.P.I.T. Budhgaon, Maharashtra,

More information

Online Tuning of Two Conical Tank Interacting Level Process

Online Tuning of Two Conical Tank Interacting Level Process Online Tuning of Two Conical Tank Interacting Level Process S.Vadivazhagi 1, Dr.N.Jaya Research Scholar, Dept. of E&I, Annamalai University, Chidambaram, Tamilnadu, India 1 Associate Professor, Dept. of

More information

PID-control and open-loop control

PID-control and open-loop control Automatic Control Lab 1 PID-control and open-loop control This version: October 24 2011 P I D REGLERTEKNIK Name: P-number: AUTOMATIC LINKÖPING CONTROL Date: Passed: 1 Introduction The purpose of this

More information

Comparative Analysis of Controller Tuning Techniques for Dead Time Processes

Comparative Analysis of Controller Tuning Techniques for Dead Time Processes Comparative Analysis of Controller Tuning Techniques for Dead Time Processes Parvesh Saini *, Charu Sharma Department of Electrical Engineering Graphic Era Deemed to be University, Dehradun, Uttarakhand,

More information

Using Root Locus Modeling for Proportional Controller Design for Spray Booth Pressure System

Using Root Locus Modeling for Proportional Controller Design for Spray Booth Pressure System 1 University of Tennessee at Chattanooga Engineering 3280L Using Root Locus Modeling for Proportional Controller Design for Spray Booth Pressure System By: 2 Introduction: The objectives for these experiments

More information

Nonlinear Control Lecture

Nonlinear Control Lecture Nonlinear Control Lecture Just what constitutes nonlinear control? Control systems whose behavior cannot be analyzed by linear control theory. All systems contain some nonlinearities, most are small and

More information

CHAPTER 4 PID CONTROLLER BASED SPEED CONTROL OF THREE PHASE INDUCTION MOTOR

CHAPTER 4 PID CONTROLLER BASED SPEED CONTROL OF THREE PHASE INDUCTION MOTOR 36 CHAPTER 4 PID CONTROLLER BASED SPEED CONTROL OF THREE PHASE INDUCTION MOTOR 4.1 INTRODUCTION Now a day, a number of different controllers are used in the industry and in many other fields. In a quite

More information

Communication Engineering Prof. Surendra Prasad Department of Electrical Engineering Indian Institute of Technology, Delhi

Communication Engineering Prof. Surendra Prasad Department of Electrical Engineering Indian Institute of Technology, Delhi Communication Engineering Prof. Surendra Prasad Department of Electrical Engineering Indian Institute of Technology, Delhi Lecture - 23 The Phase Locked Loop (Contd.) We will now continue our discussion

More information

Cohen-coon PID Tuning Method; A Better Option to Ziegler Nichols-PID Tuning Method

Cohen-coon PID Tuning Method; A Better Option to Ziegler Nichols-PID Tuning Method Cohen-coon PID Tuning Method; A Better Option to Ziegler Nichols-PID Tuning Method Engr. Joseph, E. A. 1, Olaiya O. O. 2 1 Electrical Engineering Department, the Federal Polytechnic, Ilaro, Ogun State,

More information

Closed-Loop Position Control, Proportional Mode

Closed-Loop Position Control, Proportional Mode Exercise 4 Closed-Loop Position Control, Proportional Mode EXERCISE OBJECTIVE To describe the proportional control mode; To describe the advantages and disadvantages of proportional control; To define

More information

COMPARISON OF TUNING METHODS OF PID CONTROLLER USING VARIOUS TUNING TECHNIQUES WITH GENETIC ALGORITHM

COMPARISON OF TUNING METHODS OF PID CONTROLLER USING VARIOUS TUNING TECHNIQUES WITH GENETIC ALGORITHM JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY Journal of Electrical Engineering & Technology (JEET) (JEET) ISSN 2347-422X (Print), ISSN JEET I A E M E ISSN 2347-422X (Print) ISSN 2347-4238 (Online) Volume

More information

Comparative Study of PID Controller tuning methods using ASPEN HYSYS

Comparative Study of PID Controller tuning methods using ASPEN HYSYS Comparative Study of PID Controller tuning methods using ASPEN HYSYS Bhavatharini S #1, Abirami S #2, Arun Prem Anand N #3 # Department of Chemical Engineering, Sri Venkateswara College of Engineering

More information

Position Control of DC Motor by Compensating Strategies

Position Control of DC Motor by Compensating Strategies Position Control of DC Motor by Compensating Strategies S Prem Kumar 1 J V Pavan Chand 1 B Pangedaiah 1 1. Assistant professor of Laki Reddy Balireddy College Of Engineering, Mylavaram Abstract - As the

More information

CHAPTER 11: DIGITAL CONTROL

CHAPTER 11: DIGITAL CONTROL When I complete this chapter, I want to be able to do the following. Identify examples of analog and digital computation and signal transmission. Program a digital PID calculation Select a proper execution

More information

Research Article Multi-objective PID Optimization for Speed Control of an Isolated Steam Turbine using Gentic Algorithm

Research Article Multi-objective PID Optimization for Speed Control of an Isolated Steam Turbine using Gentic Algorithm Research Journal of Applied Sciences, Engineering and Technology 7(17): 3441-3445, 14 DOI:1.196/rjaset.7.695 ISSN: 4-7459; e-issn: 4-7467 14 Maxwell Scientific Publication Corp. Submitted: May, 13 Accepted:

More information

Automatic Controller Dynamic Specification (Summary of Version 1.0, 11/93)

Automatic Controller Dynamic Specification (Summary of Version 1.0, 11/93) The contents of this document are copyright EnTech Control Engineering Inc., and may not be reproduced or retransmitted in any form without the express consent of EnTech Control Engineering Inc. Automatic

More information

1. Consider the closed loop system shown in the figure below. Select the appropriate option to implement the system shown in dotted lines using

1. Consider the closed loop system shown in the figure below. Select the appropriate option to implement the system shown in dotted lines using 1. Consider the closed loop system shown in the figure below. Select the appropriate option to implement the system shown in dotted lines using op-amps a. b. c. d. Solution: b) Explanation: The dotted

More information

6.4 Adjusting PID Manually

6.4 Adjusting PID Manually Setting Display Parameter Setting Display Operation Display > PARAMETER or PARA key for 3 seconds (to [MODE] Menu Display) > Right arrow key (to [PID] Menu Display ) > SET/ENTER key (The setting parameter

More information

REFORMULATION OF THE TANGENT METHOD FOR PID CONTROLLER TUNING

REFORMULATION OF THE TANGENT METHOD FOR PID CONTROLLER TUNING REFORMULTION OF THE TNGENT METHOD FOR PID ONTROLLER TUNING bdul ziz Ishak Muhammed zlan Hussain Department of hemical Engineering Faculty of Engineering, Universiti Malaya 50603 Kuala Lumpur, Malaysia.

More information

Review Paper on Comparison of various PID Controllers Tuning Methodologies for Heat Exchanger Model

Review Paper on Comparison of various PID Controllers Tuning Methodologies for Heat Exchanger Model Review Paper on Comparison of various PID Controllers Tuning Methodologies for Heat Exchanger Model Sumit 1, Ms. Kajal 2 1 Student, Department of Electrical Engineering, R.N College of Engineering, Rohtak,

More information

Chapter 2 Non-parametric Tuning of PID Controllers

Chapter 2 Non-parametric Tuning of PID Controllers Chapter 2 Non-parametric Tuning of PID Controllers As pointed out in the Introduction, there are two approaches to tuning controllers: parametric and non-parametric. Non-parametric methods of tuning based

More information

Comparative Analysis of a PID Controller using Ziegler- Nichols and Auto Turning Method

Comparative Analysis of a PID Controller using Ziegler- Nichols and Auto Turning Method International Academic Institute for Science and Technology International Academic Journal of Science and Engineering Vol. 3, No. 10, 2016, pp. 1-16. ISSN 2454-3896 International Academic Journal of Science

More information

Level control drain valve tuning. Walter Bischoff PE Brunswick Nuclear Plant

Level control drain valve tuning. Walter Bischoff PE Brunswick Nuclear Plant Level control drain valve tuning Walter Bischoff PE Brunswick Nuclear Plant Tuning Introduction Why is it important PI and PID controllers have been accepted throughout process design and all forms of

More information

PID Tuner (ver. 1.0)

PID Tuner (ver. 1.0) PID Tuner (ver. 1.0) Product Help Czech Technical University in Prague Faculty of Mechanical Engineering Department of Instrumentation and Control Engineering This product was developed within the subject

More information

THE general rules of the sampling period selection in

THE general rules of the sampling period selection in INTL JOURNAL OF ELECTRONICS AND TELECOMMUNICATIONS, 206, VOL. 62, NO., PP. 43 48 Manuscript received November 5, 205; revised March, 206. DOI: 0.55/eletel-206-0005 Sampling Rate Impact on the Tuning of

More information

Comparative Study of PID and FOPID Controller Response for Automatic Voltage Regulation

Comparative Study of PID and FOPID Controller Response for Automatic Voltage Regulation IOSR Journal of Engineering (IOSRJEN) ISSN (e): 2250-3021, ISSN (p): 2278-8719 Vol. 04, Issue 09 (September. 2014), V5 PP 41-48 www.iosrjen.org Comparative Study of PID and FOPID Controller Response for

More information

The PID controller. Summary. Introduction to Control Systems

The PID controller. Summary. Introduction to Control Systems The PID controller ISTTOK real-time AC 7-10-2010 Summary Introduction to Control Systems PID Controller PID Tuning Discrete-time Implementation The PID controller 2 Introduction to Control Systems Some

More information

MODEL BASED CONTROL FOR INTERACTING AND NON-INTERACTING LEVEL PROCESS USING LABVIEW

MODEL BASED CONTROL FOR INTERACTING AND NON-INTERACTING LEVEL PROCESS USING LABVIEW MODEL BASED CONTROL FOR INTERACTING AND NON-INTERACTING LEVEL PROCESS USING LABVIEW M.Lavanya 1, P.Aravind 2, M.Valluvan 3, Dr.B.Elizabeth Caroline 4 PG Scholar[AE], Dept. of ECE, J.J. College of Engineering&

More information

Research Article 12 Control of the Fractionator Top Pressure for a Delayed Coking Unit in Khartoum Refinery

Research Article 12 Control of the Fractionator Top Pressure for a Delayed Coking Unit in Khartoum Refinery Research Article 12 Control of the Fractionator Top Pressure for a Delayed Coking Unit in Khartoum Refinery Salah Eldeen F..Hegazi 1, Gurashi Abdallah Gasmelseed 2, Mohammed M.Bukhari 3 1 Department of

More information

Modelling for Temperature Non-Isothermal Continuous Stirred Tank Reactor Using Fuzzy Logic

Modelling for Temperature Non-Isothermal Continuous Stirred Tank Reactor Using Fuzzy Logic Modelling for Temperature Non-Isothermal Continuous Stirred Tank Reactor Using Fuzzy Logic Nasser Mohamed Ramli, Mohamad Syafiq Mohamad 1 Abstract Many types of controllers were applied on the continuous

More information

PID control. since Similarly, modern industrial

PID control. since Similarly, modern industrial Control basics Introduction to For deeper understanding of their usefulness, we deconstruct P, I, and D control functions. PID control Paul Avery Senior Product Training Engineer Yaskawa Electric America,

More information

PROCESS DYNAMICS AND CONTROL

PROCESS DYNAMICS AND CONTROL PROCESS DYNAMICS AND CONTROL CHBE306, Fall 2017 Professor Dae Ryook Yang Dept. of Chemical & Biological Engineering Korea University Korea University 1-1 Objectives of the Class What is process control?

More information

A simple method of tuning PID controller for Integrating First Order Plus time Delay Process

A simple method of tuning PID controller for Integrating First Order Plus time Delay Process International Journal of Electrical Engineering. ISSN 0974-2158 Volume 9, Number 1 (2016), pp. 77-86 International Research Publication House http://www.irphouse.com A simple method of tuning PID controller

More information

UNIT IV CONTROLLER TUNING:

UNIT IV CONTROLLER TUNING: UNIT IV CONTROLLER TUNING: Evaluation Criteria IAE, ISE, ITAE An ¼ Decay Ratio - Tuning:- Process Reaction Curve Metho, Continuous Cycling Metho An Dampe Oscillation Metho Determination Of Optimum Settings

More information

Chapter 4 PID Design Example

Chapter 4 PID Design Example Chapter 4 PID Design Example I illustrate the principles of feedback control with an example. We start with an intrinsic process P(s) = ( )( ) a b ab = s + a s + b (s + a)(s + b). This process cascades

More information

Controller Algorithms and Tuning

Controller Algorithms and Tuning The previous sections of this module described the purpose of control, defined individual elements within control loops, and demonstrated the symbology used to represent those elements in an engineering

More information

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY Design of Self-tuning PID controller using Fuzzy Logic for Level Process P D Aditya Karthik *1, J Supriyanka 2 *1, 2 Department

More information

Understanding PID Control

Understanding PID Control 1 of 5 2/20/01 1:15 PM Understanding PID Control Familiar examples show how and why proportional-integral-derivative controllers behave the way they do. Keywords: Process control Control theory Controllers

More information

Laboratory PID Tuning Based On Frequency Response Analysis. 2. be able to evaluate system performance for empirical tuning method;

Laboratory PID Tuning Based On Frequency Response Analysis. 2. be able to evaluate system performance for empirical tuning method; Laboratory PID Tuning Based On Frequency Response Analysis Objectives: At the end, student should 1. appreciate a systematic way of tuning PID loop by the use of process frequency response analysis; 2.

More information

TUNING OF PID CONTROLLERS USING PARTICLE SWARM OPTIMIZATION

TUNING OF PID CONTROLLERS USING PARTICLE SWARM OPTIMIZATION TUNING OF PID CONTROLLERS USING PARTICLE SWARM OPTIMIZATION 1 K.LAKSHMI SOWJANYA, 2 L.RAVI SRINIVAS M.Tech Student, Department of Electrical & Electronics Engineering, Gudlavalleru Engineering College,

More information

Compensation of Dead Time in PID Controllers

Compensation of Dead Time in PID Controllers 2006-12-06 Page 1 of 25 Compensation of Dead Time in PID Controllers Advanced Application Note 2006-12-06 Page 2 of 25 Table of Contents: 1 OVERVIEW...3 2 RECOMMENDATIONS...6 3 CONFIGURATION...7 4 TEST

More information

A Comparative Novel Method of Tuning of Controller for Temperature Process

A Comparative Novel Method of Tuning of Controller for Temperature Process A Comparative Novel Method of Tuning of Controller for Temperature Process E.Kalaiselvan 1, J. Dominic Tagore 2 Associate Professor, Department of E.I.E, M.A.M College Of Engineering, Trichy, Tamilnadu,

More information

Extensions and Modifications of Relay Autotuning

Extensions and Modifications of Relay Autotuning Extensions and Modifications of Relay Autotuning Mats Friman Academic Dissertation Department of Chemical Engineering Åbo Akademi University FIN-20500 Åbo, Finland Preface This thesis is the result of

More information

MTE 360 Automatic Control Systems University of Waterloo, Department of Mechanical & Mechatronics Engineering

MTE 360 Automatic Control Systems University of Waterloo, Department of Mechanical & Mechatronics Engineering MTE 36 Automatic Control Systems University of Waterloo, Department of Mechanical & Mechatronics Engineering Laboratory #1: Introduction to Control Engineering In this laboratory, you will become familiar

More information

Proportional-Integral Controller Performance

Proportional-Integral Controller Performance Proportional-Integral Controller Performance Silver Team Jonathan Briere ENGR 329 Dr. Henry 4/1/21 Silver Team Members: Jordan Buecker Jonathan Briere John Colvin 1. Introduction Modeling for the response

More information

Hacettepe University, Ankara, Turkey. 2 Chemical Engineering Department,

Hacettepe University, Ankara, Turkey. 2 Chemical Engineering Department, OPTIMAL TUNING PARAMETERS OF PROPORTIONAL INTEGRAL CONTROLLER IN FEEDBACK CONTROL SYSTEMS. Gamze İŞ 1, ChandraMouli Madhuranthakam 2, Erdoğan Alper 1, Ibrahim H. Mustafa 2,3, Ali Elkamel 2 1 Chemical Engineering

More information

AVR221: Discrete PID Controller on tinyavr and megaavr devices. Introduction. AVR 8-bit Microcontrollers APPLICATION NOTE

AVR221: Discrete PID Controller on tinyavr and megaavr devices. Introduction. AVR 8-bit Microcontrollers APPLICATION NOTE AVR 8-bit Microcontrollers AVR221: Discrete PID Controller on tinyavr and megaavr devices APPLICATION NOTE Introduction This application note describes a simple implementation of a discrete Proportional-

More information

Communication Engineering Prof. Surendra Prasad Department of Electrical Engineering Indian Institute of Technology, Delhi

Communication Engineering Prof. Surendra Prasad Department of Electrical Engineering Indian Institute of Technology, Delhi Communication Engineering Prof. Surendra Prasad Department of Electrical Engineering Indian Institute of Technology, Delhi Lecture - 16 Angle Modulation (Contd.) We will continue our discussion on Angle

More information

Temperature Control in HVAC Application using PID and Self-Tuning Adaptive Controller

Temperature Control in HVAC Application using PID and Self-Tuning Adaptive Controller International Journal of Emerging Trends in Science and Technology Temperature Control in HVAC Application using PID and Self-Tuning Adaptive Controller Authors Swarup D. Ramteke 1, Bhagsen J. Parvat 2

More information

Fundamentals of Servo Motion Control

Fundamentals of Servo Motion Control Fundamentals of Servo Motion Control The fundamental concepts of servo motion control have not changed significantly in the last 50 years. The basic reasons for using servo systems in contrast to open

More information

Governor with dynamics: Gg(s)= 1 Turbine with dynamics: Gt(s) = 1 Load and machine with dynamics: Gp(s) = 1

Governor with dynamics: Gg(s)= 1 Turbine with dynamics: Gt(s) = 1 Load and machine with dynamics: Gp(s) = 1 Load Frequency Control of Two Area Power System Using Conventional Controller 1 Rajendra Murmu, 2 Sohan Lal Hembram and 3 Ajay Oraon, 1 Assistant Professor, Electrical Engineering Department, BIT Sindri,

More information

A Comparison And Evaluation of common Pid Tuning Methods

A Comparison And Evaluation of common Pid Tuning Methods University of Central Florida Electronic Theses and Dissertations Masters Thesis (Open Access) A Comparison And Evaluation of common Pid Tuning Methods 2007 Justin Youney University of Central Florida

More information

Andrea Zanchettin Automatic Control 1 AUTOMATIC CONTROL. Andrea M. Zanchettin, PhD Winter Semester, Linear control systems design Part 1

Andrea Zanchettin Automatic Control 1 AUTOMATIC CONTROL. Andrea M. Zanchettin, PhD Winter Semester, Linear control systems design Part 1 Andrea Zanchettin Automatic Control 1 AUTOMATIC CONTROL Andrea M. Zanchettin, PhD Winter Semester, 2018 Linear control systems design Part 1 Andrea Zanchettin Automatic Control 2 Step responses Assume

More information

STANDARD TUNING PROCEDURE AND THE BECK DRIVE: A COMPARATIVE OVERVIEW AND GUIDE

STANDARD TUNING PROCEDURE AND THE BECK DRIVE: A COMPARATIVE OVERVIEW AND GUIDE STANDARD TUNING PROCEDURE AND THE BECK DRIVE: A COMPARATIVE OVERVIEW AND GUIDE Scott E. Kempf Harold Beck and Sons, Inc. 2300 Terry Drive Newtown, PA 18946 STANDARD TUNING PROCEDURE AND THE BECK DRIVE:

More information

Comparison Effectiveness of PID, Self-Tuning and Fuzzy Logic Controller in Heat Exchanger

Comparison Effectiveness of PID, Self-Tuning and Fuzzy Logic Controller in Heat Exchanger J. Appl. Environ. Biol. Sci., 7(4S)28-33, 2017 2017, TextRoad Publication ISSN: 2090-4274 Journal of Applied Environmental and Biological Sciences www.textroad.com Comparison Effectiveness of PID, Self-Tuning

More information