High-speed Counter Modules

Size: px
Start display at page:

Download "High-speed Counter Modules"

Transcription

1 User s Manual High-speed Counter Modules IM 34M6H53-01E Yokogawa Electric Corporation IM 34M6H53-01E 2nd Edition

2 i Applicable Product: Range-free Multi-controller FA-M3 Model: F3XP01-0H, F3XP02-0H Name: High-speed Counter Modules The document number and document model code for this manual are given below. Refer to the document number in all communications; also refer to the document number or the document model code when purchasing additional copies of this manual. Document No.: IM 34M6H53-01E Document Model Code: DOCIM Media No. IM 34M6H53-01E (CD) 2nd Edition : July, 2001 (YK) All Rights Reserved Copyright 1999, Yokogawa Electric Corporation

3 ii Important T About This Manual - This Manual should be passed on to the end user. - Before using the controller, read this manual thoroughly to have a clear understanding of the controller. - This manual explains the functions of this product, but there is no guarantee that they will suit the particular purpose of the user. - Under absolutely no circumstances may the contents of this manual be transcribed or copied, in part or in whole, without permission. - The contents of this manual are subject to change without prior notice. - Every effort has been made to ensure accuracy in the preparation of this manual. However, should any errors or omissions come to the attention of the user, please contact the nearest Yokogawa Electric representative or sales office. T Safety Precautions when Using/Maintaining the Product - The following safety symbols are used on the product as well as in this manual. Danger. This symbol on the product indicates that the operator must follow the instructions laid out in this instruction manual to avoid the risk of personnel injuries, fatalities, or damage to the instrument. The manual describes what special care the operator must exercise to prevent electrical shock or other dangers that may result in injury or the loss of life. Protective Ground Terminal. Before using the instrument, be sure to ground this terminal. Function Ground Terminal. Before using the instrument, be sure to ground this terminal. Alternating current. Indicates alternating current. Direct current. Indicates direct current.

4 iii The following symbols are used only in the instruction manual. WARNING Indicates a Warning. Draws attention to information essential to prevent hardware damage, software damage or system failure. CAUTION TIP Indicates a Caution Draws attention to information essential to the understanding of operation and functions. Indicates a TIP Gives information that complements the present topic. SEE ALSO Indicates a SEE ALSO reference. Identifies a source to which to refer. - For the protection and safe use of the product and the system controlled by it, be sure to follow the instructions and precautions on safety stated in this manual whenever handling the product. Take special note that if you handle the product in a manner other than prescribed in these instructions, the protection feature of the product may be damaged or impaired. In such cases, Yokogawa cannot guarantee the quality, performance, function and safety of the product. - When installing protection and/or safety circuits such as lightning protection devices and equipment for the product and control system as well as designing or installing separate protection and/or safety circuits for fool-proof design and fail-safe design of processes and lines using the product and the system controlled by it, the user should implement it using devices and equipment, additional to this product. - If component parts or consumable are to be replaced, be sure to use parts specified by the company. - This product is not designed or manufactured to be used in critical applications which directly affect or threaten human lives and safety such as nuclear power equipment, devices using radioactivity, railway facilities, aviation equipment, air navigation facilities, aviation facilities or medical equipment. If so used, it is the user s responsibility to include in the system additional equipment and devices that ensure personnel safety. - Do not attempt to modify the product. T Exemption from Responsibility - Yokogawa Electric Corporation (hereinafter simply referred to as Yokogawa Electric) makes no warranties regarding the product except those stated in the WARRANTY that is provided separately. - Yokogawa Electric assumes no liability to any party for any loss or damage, direct or indirect, caused by the user or any unpredictable defect of the product.

5 iv T Software Supplied by the Company - Yokogawa Electric makes no other warranties expressed or implied except as provided in its warranty clause for software supplied by the company. - Use the software with one computer only. You must purchase another copy of the software for use with each additional computer. - Copying the software for any purposes other than backup is strictly prohibited. - Store the original media, such as floppy disks, that contain the software in a safe place. - Reverse engineering, such as decompiling of the software, is strictly prohibited. - No portion of the software supplied by Yokogawa Electric may be transferred, exchanged, or sublet or leased for use by any third party without prior permission by Yokogawa Electric.

6 v T General Requirements for Using the FA-M3 Avoid installing the FA-M3 in the following locations: - Where the instrument will be exposed to direct sunlight, or where the operating temperature exceeds the range 0 C to55 C (0 F to 131 F). - Where the relative humidity is outside the range 10 to 90%, or where sudden temperature changes may occur and cause condensation. - Where corrosive or flammable gases are present. - Where the instrument will be exposed to direct mechanical vibration or shock. - Where the instrument may be exposed to extreme levels of radioactivity. Use the correct types of wire for external wiring: - Use copper wire with temperature ratings greater than 75 C. Securely tighten screws: - Securely tighten module mounting screws and terminal screws to avoid problems such as faulty operation. - Tighten terminal block screws with the correct tightening torque as given in this manual. Securely lock connecting cables: - Securely lock the connectors of cables, and check them thoroughly before turning on the power. Interlock with emergency-stop circuitry using external relays: - Equipment incorporating the FA-M3 must be furnished with emergency-stop circuitry that uses external relays. This circuitry should be set up to interlock correctly with controller status (stop/run). Ground for low impedance: - For safety reasons, connect the [FG] grounding terminal to a Japanese Industrial Standards (JIS) Class 3 Ground. For compliance to CE Marking, use cables such as twisted cables which can ensure low impedance even at high frequencies for grounding. Configure and route cables with noise control considerations: - Perform installation and wiring that segregates system parts that may likely become noise sources and system parts that are susceptible to noise. Segregation can be achieved by measures such as segregating by distance, installing a filter or segregating the grounding system. Configure for CE Marking Conformance: - For compliance with CE Marking, perform installation and cable routing according to the description on compliance to CE Marking in the Hardware Manual (IM34M6C11-01E). Keep spare parts on hand: - Stock up on maintenance parts including spare modules, in advance.

7 vi Discharge static electricity before operating the system: - Because static charge can accumulate in dry conditions, first touch grounded metal to discharge any static electricity before touching the system. Never use solvents such as paint thinner for cleaning: - Gently clean the surfaces of the FA-M3 with a cloth that has been soaked in water or a neutral detergent and wringed. - Do not use volatile solvents such as benzine or paint thinner or chemicals for cleaning, as they may cause deformity, discoloration, or malfunctioning. Avoid storing the FA-M3 in places with high temperature or humidity: - Since the CPU module has a built-in battery, avoid storage in places with high temperature or humidity. - Since the service life of the battery is drastically reduced by exposure to high temperatures, take special care (storage temperature should be from 20 C to 75 C). - There is a built-in lithium battery in a CPU module and temperature control module which serves as backup power supply for programs, device information and configuration information. The service life of this battery is more than 10 years in standby mode at room temperature. Take note that the service life of the battery may be shortened when installed or stored at locations of extreme low or high temperatures. Therefore, we recommend that modules with built-in batteries be stored at room temperature. Always turn off the power before installing or removing modules: - Failing to turn off the power supply when installing or removing modules, may result in damage. Do not touch components in the module: - In some modules you can remove the right-side cover and install ROM packs or change switch settings. While doing this, do not touch any components on the printed-circuit board, otherwise components may be damaged and modules may fail to work.

8 vii Waste Electrical and Electronic Equipment Waste Electrical and Electronic Equipment (WEEE), Directive 2002/96/EC (This directive is only valid in the EU.) This product complies with the WEEE Directive (2002/96/EC) marking requirement. The following marking indicates that you must not discard this electrical/electronic product in domestic household waste. Product Category With reference to the equipment types in the WEEE directive Annex 1, this product is classified as a Monitoring and Control instrumentation product. Do not dispose in domestic household waste. When disposing products in the EU, contact your local Yokogawa Europe B. V. office.

9 Introduction viii Overview of the Manual Other Manuals This manual, High-speed Counter Modules (IM 34M6H53-01E), explains the specifications and handling of the High-speed Counter module, one of the FA-M3 input/output modules. The manuals to reference depends on the CPU type. Refer to the following manuals accordingly. For BASIC CPU modules F3BP20 and F3BP30 - BASIC CPU Module and YM-BASIC/FA Programming Language (IM 34M6Q22-01E) Common for all sequence CPU modules For the FA-M3 specifications and configurations* 1, installation and wiring, test run, maintenance, and module installation limits for the whole system: *1: Refer to the relevant product manuals for specifications except for power supply modules, base modules, input/output modules, cables and terminal units. - Hardware Manual (IM 34M6C11-01E), 6th Edition or later

10 ix Copyrights and Trademarks Copyrights Copyrights of the programs and online manual included in this CD-ROM belong to Yokogawa Electric Corporation. This online manual may be printed but PDF security settings have been made to prevent alteration of its contents. This online manual may only be printed and used for the sole purpose of operating this product. When using a printed copy of the online manual, pay attention to possible inconsistencies with the latest version of the online manual. Ensure that the edition agrees with the latest CD-ROM version. Copying, passing, selling or distribution (including transferring over computer networks) of the contents of the online manual, in part or in whole, to any third party, is strictly prohibited. Registering or recording onto videotapes and other media is also prohibited without expressed permission of Yokogawa Electric Corporation. Trademarks The trade names and company names referred to in this manual are either trademarks or registered trademarks of their respective companies.

11 Blank Page

12 TOC-1 FA-M3 High-speed Counter Modules IM 34M6H53-01E 2nd Edition CONTENTS Applicable Product...i Important...ii Introduction...viii Copyrights and Trademarks...ix 1. Overview Features Application Example Operation Specifications and Settings Specifications Model Names and Specification Codes Operating Environment Standard Specifications Specifications of I/O Signals External Input Signals External Output Signals Electrical Specifications Timing Specifications Components and Their Functions External Connection Diagram Applicable External Interface Connectors External Dimensions Configuring Function Switches on the Modules Configuring the Channel-1 Function Switch Configuring the Channel-2 Function Switch (F3XP02-0H module only) Attaching and Detaching Modules Attaching/Detaching Modules Detaching Modules Attaching Modules in Intense Vibration Environments Wiring Modules Phase-A/B Pulse Inputs External Preset/External Enable Inputs External Matching Outputs Notes on Wiring

13 TOC-2 3. Functions of the Function Switch Operation Mode T Linear Operation T Ring Operation Counter Modes T Phase Difference x 1 Mode T Phase Difference x 2 Mode T Phase Difference x 4 Mode T Pulse-and-Direction Mode T Addition/Subtraction Mode Counter Enable/Disable External Matching Output Mode Filter Data Types and Settings Counter Value T Reading the Counter Value T Changing (Writing) the Counter Value T Resetting the Counter Value Set Value Maximum Ring Value Preset Value Operation of the Module Comparison Operation T Result of Comparison T External Matching Output Signal T Interrupt Reset T Resetting the Module T Resetting Input Relays (Status) Accessing the Module Accessing Using Ladder Application Instructions T Reading the Counter Value, Set Value, Maximum Ring Value and Preset Value T Writing the Counter Value, Set Value, Maximum Ring Value and Preset Value T Related Input Relays T Related Output Relays T Interrupt T Sample Programs Accessing Using BASIC Statements T Declaring Use of Module T Reading the Counter Value T Reading the Set Value, Maximum Ring Value and Preset Value T Writing the Set Value, Maximum Ring Value and Preset Value T Reading the Input Relay T Writing to Output Relays T Interrupt T Sample Program Revision Information...i

14 1. Overview 1-1 High-speed Counter Modules are designed to connect with a sensor, such as an incremental encoder, to receive and count a high-speed signal of up to 100 kpps. They exchange data through I/O relays and registers with the CPU module of the FA-M3 controller. As noted here, the counter modules are available in two models, as shown below, depending on the number of counting channels and the applicable controller. Features Model Number of Counting Channels F3XP01-0H 1 F3XP02-0H 2 - The 32-bit counter of the modules can count a signal as fast as 100 kpps. - Each channel has two external matching outputs, allowing two setpoints to be defined. - An F3XP02-0H module can be configured so that one channel has four matching outputs. (In this configuration, the other channel cannot have any matching outputs.) - The modules have three counting modes phase difference mode, pulse-anddirection mode and addition/subtraction mode and, therefore, can be connected to various types of sensors. - In the phase difference mode, the modules are capable of twofold or quadruple multiplication, enabling resolution to be improved. Application Example This application quickly positions the axle of a motor using the two external matching outputs on channel 1 of each of the modules. Setting:Configure setpoints 1 and 2 on channel 1 as shown below. Setpoint 1: pulse-based value for a low-speed command Setpoint 2: pulse-based value for a stop command Operation: When a given output relay of a contact output module (for example, F3YD32 module) turns on, the motor starts running at high speed. When the counter value matches setpoint 1, the motor slows down; when it matches setpoint 2, the motor stops. FA-M3 controller F3XP01-0H or F3XP02-0H module F3YD32 or other module Phase-A/B Signal Encoder Motor Speed Startup OUT1 OUT2 Speed control unit High Low Output Stop Startup OUT1 OUT2 Time Figure 1.1 Application Example

15 1-2 Operation Pulse input Preset value *1 Setpoint 1 *1 Counter value Setpoint 2 *1 0 External counter enable (EN) or YVVV33 or YVVV36 relay *2 External preset (PST) or YVVV49 or YVVV50 relay *2 External matching output 1 (OUT1) and XVVV01 or XVVV03 relay *2 External matching output 2 (OUT2) and XVVV02 or XVVV04 relay *2 YVVV40 or YVVV44 relay *2 YVVV41 or YVVV45 relay *2 Interrupt declaration *3 Interrupt XVVV01 to XVVV06 relays *2 Figure 1.2 Operating Timing Diagram *1: Set the value in the I/O register of each of the modules using a ladder program or BASIC application software. *2: The F3XP01-0H module does not have the following input or output relays: XVVV03, XVVV04, XVVV06, YVVV36, YVVV44, YVVV45, YVVV50. *3: Define interrupt for input relays XVVV01 to XVVV06 using a ladder program or BASIC application software.

16 Specifications and Settings 2.1 Specifications T Model Names and Specification Codes Model Basic Specification Code Style Code Specification Code Suffix Remarks F3XP01-0H 0 to 100kpps, 1-point, 32 bit F3XP02-0H 0 to 100kpps, 2-point, 32 bit T Operating Environment There is no restriction on the CPU module that can be used with the High-speed Counter module. T Standard Specifications Table 2.1 Specifications Summary Counter Mode Input signal Item Specifications F3XP01-0H F3XP02-0H Number of channels 1 2 Range of count $ to $FFFFFFFF (32 bits) Input frequency 0 to 100 kpps (400kpps in phase difference X 4 mode) Operating mode Linear, ring or up/down counting Counter mode Phase difference, pulse-and-direction or addition/subtraction Multiplication mode K1, K2 or K4 multiplication (effective only for phase difference mode) Phase A, phase B, 5 V, 12 V or 24 V DC (photocoupler-isolated). preset (phase Z) and Allowed to input a line driver signal equivalent to counter enable the RS-422 signal. Output signal Number of external matching outputs Two on each channel (The signal turns on if the counter value matches the setpoint.) Counter value > setpoint Internal comparison Counter value = setpoint Counter value < setpoint Current consumption 100 ma at 5 V DC 150 ma at 5 V DC External wiring One 40-pin connector Two 40-pin connectors Dimensions 28.9 (W) K 100 (H) K 83.2 (D) (mm)* Weight 150 g *: Dimensions excluding protrusions. (For details, see "T External Dimensions" in Section 2.2) For other specifications, see IM 34M6C11-01E "Hardware Manual.

17 Specifications of I/O Signals All I/O signals are isolated using photocouplers. External Input Signals External Output Signals A: Phase-A pulse input signal B: Phase-B pulse input signal PST: Preset input signal A preset value is set in the counter at the rising edge of the signal in transition from off to on. EN: Counter enable input signal The modules continue to count pulses or compare values as long as this signal is on. OUT1, OUT2: External matching output signals Electrical Specifications Input Signals Table 2.2 DC Input Signals Signal Terminal Input Mode A,B,PST EN For 5 V For 12 V For 24 V For 5 V For 12 V For 24 V DC voltage Rated Input Voltage (Operating Voltage Range) 5 V DC (4.25 to 5.5 V DC) 12 V DC (10.2 to 13.2 V DC) 24 V DC (20.4 to 26.4 V DC) 5 V DC (4.25 to 5.5 V DC) 12 V DC (10.2 to 13.2 V DC) 24 V DC (20.4 to 26.4 V DC) Operating Voltage/Current Rated Input Current ON OFF 16.8 ma 15.5 ma 15.8 ma 4.6 ma 4.6 ma 4.9 ma *: When connecting signals from a line driver, make sure that it ensures this voltage level. 3.5 V min.* 10 ma min. 8 V min. 10 ma min. 16 V min. 10 ma min. 3.5 V min.* 3.2 ma min. 8 V min. 3.2 ma min. 16 V min. 3.2 ma min. 1.5 V min. 2 ma min. 2.4 V min. 2 ma min. 4.8 V min. 2 ma min. 1.5 V min. 0.9 ma min. 2.4 V min. 0.9 ma min. 4.8 V min. 0.9 ma min. Output Signals Signal OUT1 OUT2 Output Mode Transistor contact Table 2.3 DC Output Signals Rated Load Voltage (Maximum Load Voltage) 5-24 V DC (26.4 V DC) Max. Load Current 0.1A/output Residual Voltage When On 1.5 V DC max. Leak Current When Off 0.1 ma max. Surge Protector Response Time (from Input of Pulse to Turning of Output On) Configuration of Common Line None 0.1 ms max. Separate

18 2-3 Timing Specifications Phase-A (A) and Phase-B (B) Pulse Input Signals 10 µs min. 4 µs min. 4 µs min. ON (100%) (50%) OFF (0%) - When in Phase Difference Mode ON Phase A OFF ON Phase B OFF T1 T2 T3 T4 T1 to T4 : 1.25 µs min. - When in Addition/Subtraction Mode ON Phase A OFF Phase B ON 1.25 µs min. OFF

19 2-4 - When in Pulse-and-Direction Mode ON Phase A 1.25 µs min. Phase B (Direction) OFF ON (Forward) OFF (Backward) 1.25 µs min. External Counter Enable Input Signal (EN) ON (100%) (50%) OFF (0%) 1 ms min. 1 ms min. External Counter Enable Input Signal (EN) and Pulse Input Signal (A/B) ON Count Do not count Phase A OFF External counter enable signal ON 300 µs min. 300 µs min. OFF External Preset Input Signal (PST) 10 µs min. 4 µs min. 4 µs min. ON (100%) (50%) OFF (0%) External Matching Output Signals (OUT1 and OUT2)

20 2-5 ON Phase A or B OFF ON External matching output signal OFF 0.1 µs max.

21 2-6 T Components and Their Functions - F3XP01-0H (1 channel type) AP1 BE2 F3XP01 RDY PULSE Green READY indicator : Remains lit when the internal circuitry is in normal operation. Red I/O status indicators : Work as noted below. "A" indicator : Comes on when the phase-a pulse input signal turns on. "B" indicator : Comes on when the phase-b pulse input signal turns on. "P" indicator : Comes on when the external preset input signal turns on "E" indicator : Comes on when the counter is enabled. "1" indicator : Comes on when external matching output signal 1 (OUT1) turns on. "2" indicator : Comes on when external matching output signal 2 (OUT2) turns on. I/O connector : A 40-pin connector. - F3XP02-0H (2 channel type) RDY CH1 CH2 AP1 AP1 BE2 BE2 F3XP02 PULSE Green READY indicator : Remains lit when the internal circuity is in normal operation. Red CH1/CH2 status indicators : Work as noted below on a channel-by-channel basis. "A" indicator : Comes on when the phase-a pulse input signal turns on. "B" indicator : Comes on when the phase-b pulse input signal terns on. "P" indicator : Comes on when the external preset input signal terns on. "E" indicator : Comes on when the counter is ecabled. "1" indicator : Comes on when external matching output signal 1 (OUT1) turns on. "2" indicator : Comes on when external matching output signal 2 (OUT2) turns on. CH2 connector : two 40-pin connectors CH1 connector

22 2-7 External Connection Diagram CN1 OUT2 B 20 A 20 COM CN2 OUT2 B 20 A 20 (F3XP02-0Hのみ) COM OUT COM OUT COM V EN+ PST+ B+ A EN- PST- B- A- 5V EN+ PST+ B+ A EN- PST- B- A EN EN- EN EN- PST+ 12V B+ A PST- B- A- PST+ 12V B+ A PST- B- A EN EN- EN EN- PST+ 24V B PST- B- PST+ 24V B PST- B- A+ SHIELD A- SHIELD A+ SHIELD A- SHIELD CH1 connector CH2 connector (F3XP02-0H module only) Figure 2.1 Terminal Assignments and Connection Applicable External Interface Connectors The counter modules are wired using connectors. Applicable connectors include soldered, crimp-on and pressure-welded connectors. Procure these types of connectors as necessary. Table 2.4 Applicable External Interface Connectors Connection method Applicable connector Remarks Soldered type FUJITSU LIMITED: FCN-361J040-AU connector FCN-360C040-B connector cover Supplied by the customer. Crimping type FUJITSU LIMITED: FCN-363J040 housing FCN-363J-AU contacts Pressure-welded type FCN-360C040-B connector cover FUJITSU LIMITED: FCN-367J040-AU/F

23 2-8 T External Dimensions (Note) The above is for F3XP02-0H. (Unit: mm)

24 2.3 Configuring Function Switches on the Modules 2-9 Each of the counter modules is equipped with function switches on its side panel. Before the counter module is attached to the base module, the function switches need to be configured. Figure 2.2 identifies where these switches are located. Side view Front Back SW3 (Do NOT use.) A switch used for testing by the manufacturer in the factory before shipment. Do not use this switch. Channel-2 DIP function switch O F F O F F O F F This switch, which is not found with an F3XP01-0H module, selects between the on/off setpoints of the operating mode, counter mode, counter enable mode, external matching output mode and filter (see "T Configuring the Channel-2 Function Switch" in this sectiion) Channel-1 DIP function switch Selects between the on/off setpoints of the operating mode counter mode, counter enable mode and filter (see "T Configuring the Channel-1 Function Switch" in this section) This figure is a view when the cover is removed. The factory setting of these switches are as follows : Channel-1 function switch Channel-2 function switch All of the bit-1 to bit-8 subswitches are in the off position. All of the bit-1 to bit-8 subswitches are in the off position. Figure 2.2 Location of Function Switches

25 T Configuring the Channel-1 Function Switch 2-10 The channel-1 DIP function switch is used to select between the on/off setpoints of the operating mode, counter mode, counter enable mode, external matching output mode and filter. Configure the function switch by sliding the subswitches either to the on or off position with a small, flat-blade screwdriver or other similar tool. Initially, all of the bit-1 to bit-8 subswitches are factory-set to the off position. ON Bit numbers OFF OFF (Note) The black side of each subswitch indicates where the switch is positioned. Selects the mode of the filter (see Section 3.5). Place in the on position if the maximum frequency of the external input signal is no greater than 50 kpps. Place in the off position if the maximum frequency of the external input signal is greater 50 kpps. Selects the external matching output mode (see Section 3.4). Place in the on position to select the 4-output mode. Place in the off position to select the 2-output mode. Note: The four-output mode is not available with an F3XP01-0H module. Use the module with this subswitch always in the off position. Selects the setpoint of the counter enable mode (see Section 3.3). Place in the on position to keep the counter always enabled. Place in the off position to be able to select whether the counter is enabled or disabled. Selects the counter mode (see Section 3.2). Configure these four subswitches according to the following table: Bit Number Counter mode Phase Difference x1 Multiplication off off Phase Difference x2 Multiplication off on on on * * * off off off Phase Pulse-and- Difference Direction x4 Multiplication * * * * off on Addition/ Subtraction on on * Don't care. Selects the setpoint of the operation mode (see Section 3.1). Place in the on position to select ring counting. Place in the off position to select linear counting. Figure 2.3 Channel-1 Function Switch

26 2-11 T Configuring the Channel-2 Function Switch (F3XP02-0H module only) The channel-2 DIP function switch is used to select between the on/off setpoints of the operating mode, counter mode, counter enable mode and filter. Configure the function switch by sliding the subswitches either to the on or off position with a small, flat-blade screwdriver or other similar tool. Initially, all of the bit-1 to bit-8 subswitches are factoryset to the off position. ON Bit number OFF OFF (Note) The black side of each subswitch indicates where the switch is positioned. Selects the mode of the filter (see Section 3.5). Place in the on position if the maximum frequency of the external input signal is no greater than 50 kpps. Place in the off position if the maximum frequency of the external input signal greater than 50 kpps. Unused. Use the counter module with this subswitch placed in the factory-set off position. Selects the setpoint of the counter enable mode (see Section 3.3). Place in the on position to keep the counter always enabled. Place in the off position to be able to select whether the counter is enabled or disabled. Selects the setpoint of the counter mode (see Section 3.2). Configure these four subswitches according to the following table. Bit Number Counter mode * Don't care. Phase Difference x1 Multiplication off off Phase Difference x2 Multiplication off on on on * * * off off off Phase Pulse-and- Difference Direction x4 Multiplication * * * * off on Addition/ Subtraction on on Selects the setpoint of the operation mode (see Section 3.1). Place in the on position to select ring counting. Place in the off position to select linear counting. Figure 2.4 Channel-2 Function Switch (F3XP02-0H module only)

27 Attaching and Detaching Modules T Attaching/Detaching Modules Figure 2.5 shows how to attach this module to the base module. First hook the anchor slot at the bottom of the module to be attached onto the anchor pin on the bottom of the base module. Push the top of this module towards the base module until the yellow, spring-loaded anchor/release button clicks into place. CAUTION Always switch off the power before attaching or detaching a module. Figure 2.5 Attaching Modules CAUTION DO NOT bend the connector on the rear of the module by force during the above operation. If the module is pushed with improper force, the connector may bend causing an error. T Detaching Modules To remove this module from the base module, reverse the above operation. Press the anchor/release button on the top of this module to unlock it and tilt the module away from the base module. Then lift the module off the anchor pin at the base.

28 T Attaching Modules in Intense Vibration Environments 2-13 If the module is used in intense vibration environments, fasten the module with a screw. Use a screw described in the table below and tighten it into the guide channel at the top of this module with a Phillips screwdriver. Screw to be provided Binder screw M4, length 12 to 15 mm (For screw with washer, the length should be 14 to 15 mm.) Figure 2.6 Tightening Module

29 Wiring Modules T Phase-A/B Pulse Inputs When the Pulse Generator Is Open-Collector: Power supply 12V 0V 12V DC power supply Counter module IA Encoder output IB Shielded, twisted-pair cable IA IB 24V A+ 12V A+ 5V A+ 24V A 12V A 5V A 24V B+ 12V B+ 5V B+ 24V B 12V B 5V B Phase-A pulse input Phase-B pulse input Pulse generetor E SHIELD IA : Phase-A pulse input current ; IB : Phase-B pulse input current When the Pulse Generator Is Sink-Loaded: Power supply 12V 0V 12V DC power supply Counter module IA Encoder output IB Shielded, twisted-pair cable IA IB 24V A+ 12V A+ 5V A+ 24V A 12V A 5V A 24V B+ 12V B+ 5V B+ 24V B 12V B 5V B Phase-A pulse input Phase-B pulse input Pulse generator E SHIELD IA : Phase-A pulse input current ; IB : Phase-B pulse input current When the Pulse Generator Is Source-Loaded (Voltage Output):

30 2-15 5V 0V 5V DC power supply Counter module Shielded, twisted-pair cable IA IB 24V A+ 12V A+ 5V A+ 24V A 12V A 5V A 24V B+ 12V B+ 5V B+ 24V B 12V B 5V B Phase-A pulse input Phase-B pulse input Pulse generator E SHIELD IA : phase-a pulse input current ; IB : phase-b pulse input current When the Pulse Generator Is Line-Driver-Output (Equivalent to RS-422 Signal): Counter module Shielded, twisted-pair cable IA IB 24V A+ 12V A+ 5V A+ 24V A 12V A 5V A 24V B+ 12V B+ 5V B+ 24V B 12V B 5V B Phase-A pulse input Phase-B pulse input Pulse generator E SHIELD IA : phase-a pulse input current ; IB : phase-b pulse input current

31 2-16 T External Preset/External Enable Inputs 24V 0V 24V DC power supply Counter module Sensor 24V PST+ 12V PST+ 5V PST+ External preset input Sensor output E Shielded, twisted-pair cable 24V PST 12V PST 5V PST Sensor 24V EN+ 12V EN+ 5V EN+ External enable input Sensor output E 24V EN 12V EN 5V EN SHIELD

32 2-17 T External Matching Outputs When the Counter Module Is Relay-Connected: Counter module Power supply OUT1 Relay 5-24V DC COM1 OUT2 Relay 0V COM2 When the Counter Module Is TTL-Connected: Power supply Counter module OUT1 Pull-up resistor 5V DC 0V COM1 OUT2 Pull-up resistor Buffer COM2

33 2-18 T Notes on Wiring Connection to Input Terminals Separate input terminals are provided depending on the level of the signal voltage. Connecting a cable to an input terminal with the wrong voltage may result in not only a failure of the module to operate properly but also damage to the module. Cables for Wiring Use shielded, twisted-pair cables. Connect the end of the cable s shielding wire on the side of the counter module to the module s SHIELD terminal. Connection to Output Terminals Wire the cables to the output terminals in the correct polarities. Reverse-polarity wiring will result in the output load being on. If any inductive load is to be connected, attach a diode or a surge protector in parallel with the load. When attaching a diode, connect the cathode to the positive (+) terminal of the power supply. F3XP0V - 0H OUT1 OUT2 L COM1 COM2 Г 5 to 24V DC OUT1 OUT2 OUT1 OUT2 L Transistor output Diode Г Transistor output Surge protector COM1 COM2 COM1 COM2 - Diode - Surge protector The reverse voltage must be no less than 10 times the circuit voltage and the forward current must be no less than twice the load current. The resistance must be 0.5 to 1 for each volt of the contact voltage. The capacitance must be 0.5 to 1 µf for each ampere of the contact current. Figure 2.7 Connection to Output Terminals

34 For conforming equipment incorporating the high-speed counter module to CE Marking: 2-19 Use a shielded cable for conforming equipment incorporating the High-speed Counter Module to CE Marking. Remove the cable cover to expose the wire, ground and secure with an FG clamp. Shielded cable Remove the cover and secure with an FG clamp. F3XP0V-0H Screw the clamp to the metal plate of the panel enclosure to ground it.

35 Blank Page

36 3. Functions of the Function Switch 3.1 Operation Mode There are two types of operation mode: (1) Linear mode (2) Ring mode The operation mode is set by bit number 1 of the function switch. See Section Linear Operation In linear operation, the counter value varies between $ and $FFFFFFFF ($ denotes a hexadecimal number). When the counter value is $ and a down-pulse is entered, underflow occurs and the counter value $ remains unchanged. When the counter value is $FFFFFFFF and an up-pulse is input, overflow occurs and the counter value $FFFFFFFF remains unchanged. An interrupt can be generated when a counter overflow/underflow occurs. When the operation mode is set to Linear operation, use the initial value $FFFFFFFF as the maximum ring value. When a value other than $FFFFFFFF is set as the maximum ring value, either reset the module or set it to $FFFFFFFF again. Counter value $ $FFFFFFFF UP DOWN Underflow Overflow Figure 3.1 Linear Operation When an underflow or overflow occurs, the counter overflow/underflow input relay becomes 1 (ON). To determine whether a counter overflow or underflow has occurred, read the input relay status corresponding to each channel as shown in Table 3.1. Table 3.1 Input Relay for Counter Overflow/Underflow Input Relay Number *1 Relay Contents Relay Status = 1 (ON) Relay Status = 0 (OFF) X 05 Counter overflow/underflow for channel 1 Occurred Not occurred X 06 *2 Counter overflow/underflow for channel 2 Occurred Not occurred *1: is the slot number where the module is installed. *2: Not applicable to F3XP01-0H.

37 3-2 T Ring Operation For ring operation, the counter value varies between $ and the maximum ring value. If a down-pulse is entered when the counter value is $ , the counter value becomes the maximum ring value. Moreover, if an up-pulse is entered when the counter value is the maximum ring value, the counter value becomes $ When the operation mode is set to Ring operation, you can set any arbitrary value as the ring maximum value (see Section 4.3). Max. value $0 DOWN UP Figure 3.2 Ring Operation

38 Counter Modes There are five types of counter mode: - Phase difference x 1 mode - Phase difference x 2 mode - Phase difference x 4 mode - Pulse-and-direction mode - Addition/subtraction mode The counter mode is set by bit numbers 2, 3, 4, 5 of the function switch. See Section 2.3 of this manual. T PhaseDifferencex1Mode When phase A leads phase B by 90, it increments the counter at the rising edge of phase A. When phase A lags behind phase B by 90, it decrements the counter at the falling edge of phase A. Counter value N N+1 N N 1 Phase A Phase B Figure 3.3 Counting in Phase Difference x1multiplicationmode T PhaseDifferencex2Mode When phase A leads phase B by 90, it increments the counter at the rising and falling edges of phase A. When phase A lags behind phase B by 90, it decrements the counter at the rising and falling edges of phase A. Counter value N N+1 N+2 N+1 N N 1 Phase A Phase B Figure 3.4 Counting in Phase Difference x2multiplicationmode

39 3-4 T PhaseDifferencex4Mode When phase A leads phase B by 90, it increments the counter at the rising and falling edges of phase A and phase B. When phase A lags phase B by 90, it decrements the counter at the rising and falling edges of phase A and phase B. Counter value N N+1 N+2 N+3 N+4 N+3 N+2 N+1 N N 1 Phase A Phase B Figure 3.5 Counting in Phase Difference x4multiplicationmode T Pulse-and-Direction Mode When phase B is OFF, it increments the counter at the rising edge of phase A. When phase B is ON, it decrements the counter at the rising edge of phase A. Counter value N N+1 N Phase A Phase B Figure 3.6 Counting in Pulse Plus Direction Mode T Addition/Subtraction Mode It increments the counter at the rising edge of phase A. It decrements the counter at the rising edge of phase B. Counter value N N+1 N N 1 Phase A Phase B Figure 3.7 Counting in Addition and Subtraction Mode

40 3.3 Counter Enable/Disable 3-5 The module can be set to either count (counter enable) or not count (counter disable) input pulses. When the counter is disabled, the comparison operation (see Section 5.1) explained later is not performed. Table 3.2 Enable/Disable Status List Counter Counter Disable Counting operation Run Stop Comparison operation Run Stop (maintain the status) External matching output Setting allowed Setting allowed signal enable/disable Preset Execution possible Execution possible Register access Allowed Allowed Module reset Allowed Allowed The procedures for setting counter enable/disable are explained below. If the counter is to be always enabled without performing the following setting procedure, turn ON bit number 6 of the function switch. (See Section 2.3 of this manual.) Setting with an external input signal The counter is enabled if the external counter enable input signal (EN) is turned ON, and the counter is disabled if it is turned OFF. Setting with a program The counter is enabled if the output relay corresponding to each channel shown in Table 3.3 is turned ON (1), and the counter is disabled if it is turned OFF (0). Table 3.3 Output Relay for Counter Enable/Disable Output Relay Number *1 Relay Contents Relay Status =1(ON) Relay Status = 0 (OFF) XVVV33 Counting status for channel 1 Enabled Disabled XVVV36 *2 Counting status for channel 2 Enabled Disabled *1: VVVis the slot number where the module is installed. *2: Not applicable to F3XP01-0H. TIP When both methods mentioned above are used, the counter is enabled if it is enabled by either method. The status of the external counter enable input signal (EN) of each channel is obtained by reading the input relay shown in Table 3.4. Table 3.4 Input Relay for Counter Enable Input Signal Input Relay Number *1 Relay Contents Relay Status Relay Status =1(ON) = 0 (OFF) XVVV17 External counter enable input signal for channel 1 ON OFF XVVV8 *2 External counter enable input signal for channel 1 ON OFF *1: VVV is the slot number where the module is installed. *2: Not applicable to F3XP01-0H.

41 3-6 CAUTION To enter a down count during counter disable (see the figure below), reset the module using a program immediately before enabling the counter. (For more details, see Section 5.2, Resetting the Module.) All the registers and counter values within the module will be initialized. Perform setting again if necessary. Example of Phase Difference x 4 Multiplication Phase A ON OFF Phase B ON OFF Enable ON OFF Disable status

42 External Matching Output Mode CAUTION Only the external matching output 2-point mode can be used for F3XP01-0H. External matching output 4-point mode cannot be used. There are two types of external matching output mode: external matching output 2-point mode and external matching output 4-point mode. In this module, each channel has two external matching outputs. External matching output of channel 1 can be converted into 4-point mode by using the external matching outputs of channel 2 for channel 1. External matching output 2-point mode As per the original function of this module, the external matching output for every channel has two points. External matching output 4-point mode This can be used in F3XP02-0H. The External matching output for channel 1 is 4-point and that for channel 2 is 0-point (Nil). In addition to the counting operation, channel 1 performs the comparison operation with four set points and it has a 4-point external matching output. The data position number of the set point, the input relay number showing the result of the comparison operation, and the output relay number for performing reset or enable/disable for the two points added to channel 1 are the same as that for the original channel 2. Counting operation for channel 2 is still performed (counter value can also be read) but the comparison operation and external matching output for channel 2 are absent. To set the external matching output 4-point mode, turn on bit number 7 of the function switch for channel 1. (See Section 2.3). 3.5 Filter The filter removes noise in the external input signals (phase A, phase B, preset and enable of each channel). For proper functioning of the filter, change the characteristics of the filter using bit number 8 of the function switch for each channel. When the maximum frequency of phase A, phase B or external preset signal exceeds 50 kpps, bit number 8 is turned OFF and when it is below 50 kpps, bit number 8 is turned ON. (See Section 2.3).

43 Blank Page

44 4. Data Types and Settings 4-1 The input/output registers of this module are listed in Table 4.1. Data in the registers are in units of long word. Table 4.1 Input/Output Registers Type Input/output register Initial value Counter value Set value Maximum ring value Preset value Data position number Ladder Read Write Data position number BASIC Read Counter value of channel 1 $ Counter value of channel 2* $ Set value 1 of channel 1 $ Set value 2 of channel 1 $ Set value 1 of channel 2* $ Set value 2* of channel 2 $ Maximum ring value of channel 1 $FFFFFFFF 13 9 Maximum value of ring of channel 2* $FFFFFFFF Preset value of channel 1 $ Preset value of channel 2* $ *: Not applicable to F3XP01-0H because channel 2 is not used. Write

45 Counter Value T Reading the Counter Value Counter values are read from registers at the data position numbers shown in Table 4.2. Table 4.2 Data Position Number for Reading the Counter Value Channel 1 Channel 2* Ladder 1 2 BASIC 1 2 *: Not applicable to F3XP01-0H. T Changing (Writing) the Counter Value Changing the counter value means setting it to any value between $ to $FFFFFFFF. Any arbitrary value is written in the register at the data position numbers shown in Table 4.3. The counter value cannot be changed using a BASIC program. Table 4.3 Data Position Number for Changing the Counter Value Channel 1 Channel 2* Ladder 1 2 *: Not applicable to F3XP01-0H. T Resetting the Counter Value Resetting the counter value means setting it to $ There are no special instructions for resetting the counter value. Perform resetting using 'preset' mentioned later (see Section 4.4) or by using 'Changing the counter value' mentioned above. How to reset the counter value is explained below. Resetting the counter value by preset Set the preset value to $ and execute preset. Resetting the counter value by changing the counter value To change the counter value, write $ to the register.

46 4.2 Set Value 4-3 The set value is the standard value used for comparison with the counter value. Two set values (set value 1 and set value 2) can be set for channel 1 in F3XP01-0H and for channel 1 and channel 2 in F3XP02-0H, respectively. Setting is carried out by writing the set value in the register. The set value can also be read from the register. Set values are written and read to/from the register at the data position numbers shown in Table 4.4. Table 4.4 Data Position Number for Set Value Channel 1 Channel 2* Set value 1 Set value 2 Set value 1 Set value 2 Ladder BASIC *: Do not perform setting for F3XP01-0H. 4.3 Maximum Ring Value The maximum ring value is the maximum counter value when the operation mode is ring operation (See Section 3.1). The maximum ring value can be set for channel 1 in F3XP01-0H and for channel 1 and channel 2 in F3XP02-0H, respectively. Perform setting by writing the maximum ring value to the register. The maximum ring value can also be read from the register. The maximum ring value is written and read to/from the data position number shown in Table 4.5. Table 4.5 Data Position Number of Maximum Ring Value Channel 1 Channel 2* Ladder BASIC 9 11 *: Do not perform setting for F3XP01-0H.

47 4.4 Preset Value Presetting means setting any arbitrary value already written in the register to the counter. This value is called the preset value. Preset values can be set for channel 1 in F3XP01-0H and for channel 1 and channel 2 in F3XP02-0H, respectively. Preset values can also be read from the register. Preset values are read from the registers at the data position numbers shown in Table Table 4.6 Data Position Number for Preset Value Channel 1 Channel 2* Ladder BASIC *: Do not perform setting for F3XP01-0H. Setting with an external input signal 1. Write the preset value in the register at the data position number given in Table The preset value is set in the counter at the edge where the external preset input signal (PST) turns from OFF to ON. Setting with a program 1. Write the preset value in the register at the data position number given in Table When the output relay turns ON (1) from OFF (0), the preset value is set in the counter. The output relay corresponding to each channel is turned ON (1) as shown in Table 4.7. Table 4.7 Output Relay for Counter Preset Output relay number *1 Operation when it is ON (1) YVVV49 Execute preset for channel 1 YVVV50 *2 Execute preset for channel 2 *1: VVV is the slot number where the module is installed. *2: Do not perform setting for F3XP01-0H. Furthermore, the ON/OFF status of the external preset input signal (PST) of each channel can be read by reading the status of the input relay corresponding to each channel as shown in Table 4.8. These input relays remain ON till they are reset by the output relays (latch type). Table 4.8 Input Relays for External Preset Input Signal Input relay number *1 Details of relay Relay status = 1 (ON) External preset input signal of XVVV15 ON channel 1 XVVV16 *2 External preset input signal of ON channel 2 *1 :VVV is the slot number where the module is installed. *2 : Not applicable to F3XP01-0H. Relay status = 1 (OFF) OFF OFF

48 5. Operation of the Module 5.1 Comparison Operation 5-1 The comparison operation compares the set value and the counter value and reflects the result in the input relay. As a result of the comparison, if the set value and the counter value is the same, the external matching output signal (OUT1, OUT2) turns ON. Moreover, an interrupt can be generated when the external matching output signal is 'ON'. Result of Comparison The result of the comparison is reflected in the input relay. To determine whether the counter value is larger than, smaller than or equal to the set value, read the corresponding input relay. Table 5.1 Relationship between Input Relay Status and Result of Comparison Input relay *1 number Relay status =1 (ON) Relay status=0 (OFF) Remarks X 01 Counter value of channel 1 = Set value 1 Counter value of channel 1 Set value 1 Latch type X 02 Counter value of channel 1 = Set value 2 Counter value of channel 1 Set value 2 Latch type X 03 *2 Counter value of channel 2 = Set value 1 Counter value of channel 2 Set value 1 Latch type X 04 *2 Counter value of channel 2 = Set value 2 Counter value of channel 2 Set value 2 Latch type X 07 Counter value of channel 1 < Set value 1 Counter value of channel 1 Set value 1 X 08 Counter value of channel 1 > Set value 1 Counter value of channel 1 Set value 1 X 09 Counter value of channel 1 < Set value 2 Counter value of channel 1 Set value 2 X 10 Counter value of channel 1 > Set value 2 Counter value of channel 1 Set value 2 X 11 *2 Counter value of channel 2 < Set value 1 Counter value of channel 2 Set value 1 X 12 *2 Counter value of channel 2 > Set value 1 Counter value of channel 2 Set value 1 X 13 *2 Counter value of channel 2 < Set value 2 Counter value of channel 2 Set value 2 X 14 *2 Counter value of channel 2 > Set value 2 Counter value of channel 2 Set value 2 Latch type: Remains ON, until reset by the output relay. *1 : is the slot number where the module is installed. *2 : Not applicable to F3XP01-0H. External Matching Output Signal As a result of comparison, if the set value and the counter value are the same, the corresponding input relays X 01 to X 04 (X 01 to X 02 for F3XP01-0H) turns ON (1). At the same time the external matching output signals (OUT1, OUT2) turns ON. For each channel, the external matching output signals are External Matching Output 1 signal (OUT1) corresponding to set value 1 and External Matching Output 2 signal (OUT2) corresponding to set value 2. Reset Input relays X 01 to X 04 (X 01 to X 02 for F3XP01-0H) and the external matching output signal are of the latch type. Once the relay is turned ON, it stays ON until the corresponding output relay is set to ON (1). To reset the relay, turn ON (1) the output relay corresponding to each channel shown in Table 5.2. Table 5.2 Relationship between Output Relay Status and External Matching Output Reset Output relay *1 number Operation when it is ON (1) Y 40 Reset the input relay X 01 and external matching output 1 signal of channel 1. Y 41 Reset the input relay X 02 and external matching output 2 signal of channel 1. Y 44 *2 Reset the input relay X 03 and external matching output 1 signal of channel 2. Y 45 *2 Reset the input relay X 04 and external matching output 2 signal of channel 2. *1 : is the slot number where the module is installed. *2 : Do not perform setting for F3XP01-0H.

Instruction Manual. Pulse Input Module IM 34M6H54-01E IM 34M6H54-01E. 1st Edition. Yokogawa Electric Corporation

Instruction Manual. Pulse Input Module IM 34M6H54-01E IM 34M6H54-01E. 1st Edition. Yokogawa Electric Corporation Instruction Manual Pulse Input Module IM 34M6H54-E Yokogawa Electric Corporation IM 34M6H54-E st Edition i Preface Applicable Products Revision History FA-M3 Range-free Multi-controllers

More information

Temperature Monitoring Module

Temperature Monitoring Module User s Manual Temperature Monitoring Module Model: F3CX04-0N IM 34M6H63-01E Yokogawa Electric Corporation IM 34M6H63-01E 1st Edition i Applicable Product Range Free Controller FA-M3 - Model Code : F3CX04-0N

More information

PULSE INPUT MODULE PI232/PI272 USER S MANUAL

PULSE INPUT MODULE PI232/PI272 USER S MANUAL UM-TS02 -E021 PROGRAMMABLE CONTROLLER PROSEC T2-series PULSE INPUT MODULE PI232/PI272 USER S MANUAL TOSHIBA CORPORATION Important Information Misuse of this equipment can result in property damage or human

More information

User s Manual Current Probe IM E. 8th Edition

User s Manual Current Probe IM E. 8th Edition User s Manual 701931 Current Probe 8th Edition Thank you for purchasing the Current Probe (Model 701931). This instruction manual contains useful information about the instrument s functions and operating

More information

Model /701913/ PBA1000/2500/1500 Active Probe

Model /701913/ PBA1000/2500/1500 Active Probe User s Manual Model 701912/701913/701914 PBA1000/2500/1500 Active Probe Yokogawa Electric Corporation 3rd Edition Foreword Thank you for purchasing the PBA Series Active Probe. This user s manual contains

More information

Model PR300 Power and Energy Meter

Model PR300 Power and Energy Meter User s Manual Model PR300 Power and Energy Meter 4th Edition Introduction Thank you for purchasing the PR300 Power and Energy Meter. This manual provides information about the procedure for installing,

More information

Models UT350/UT320 Digital Indicating Controllers

Models UT350/UT320 Digital Indicating Controllers User s Manual Models UT350/UT320 Digital Indicating Controllers User s Manual IM 05D01D02-41E IM 05D01D02-41E 4th Edition Blank Page Introduction i Thank you for purchasing the UT350/UT320

More information

Copyright / Trademarks -This manual and its contents are copyrighted. -You may not copy this manual,in whole or part,without written consent of

Copyright / Trademarks -This manual and its contents are copyrighted. -You may not copy this manual,in whole or part,without written consent of Safety Precautions Observe the following notices to ensure personal safety or to prevent accidents. To ensure that you use this product correctly, read this User s Manual thoroughly before use. Make sure

More information

User s Manual Current Probe. IM E 2nd Edition IM E

User s Manual Current Probe. IM E 2nd Edition IM E User s Manual 700937 Current Probe 2nd Edition Introduction Thank you for purchasing the 700937 Current Probe. This Instruction Manual contains useful information about the instrument s functions and operating

More information

User s Manual Current Probe. IM E 2nd Edition. Yokogawa Electric Corporation

User s Manual Current Probe. IM E 2nd Edition. Yokogawa Electric Corporation User s Manual 701930 Current Probe Yokogawa Electric Corporation 2nd Edition Foreword Revisions Thank you for purchasing the Current Probe (Model 701930). This instruction manual contains useful information

More information

Models UT550/UT520 Digital Indicating Controllers User s Manual for Single-loop Control

Models UT550/UT520 Digital Indicating Controllers User s Manual for Single-loop Control User s Manual Models UT550/UT520 Digital Indicating Controllers User s Manual for Single-loop Control IM 05D01C02-41E IM 05D01C02-41E 3rd Edition Blank Page Introduction i Thank you for purchasing

More information

Original instructions INCA-1 Tina Emergency stop for enclosure installation INCA-1S Tina Safety stop for enclosure installation

Original instructions INCA-1 Tina Emergency stop for enclosure installation INCA-1S Tina Safety stop for enclosure installation Original instructions INCA-1 Tina Emergency stop for enclosure installation INCA-1S Tina Safety stop for enclosure installation ABB AB / Jokab Safety Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden www.abb.com/lowvoltage

More information

CONTENTS. SAFETY PRECAUTIONS: Before use, read the following safety precautions

CONTENTS. SAFETY PRECAUTIONS: Before use, read the following safety precautions CONTENTS [1] SAFETY PRECAUTIONS: Before use, read the following safety precautions 2 [2] APPLICATION AND FEATURES 5 [3] NAME OF COMPONENT UNITS 6 [4] DESCRIPTION OF FUNCTIONS 8 [5] MEASUREMENT PROCEDURE

More information

User s Manual Current Probe IM E. 6th Edition

User s Manual Current Probe IM E. 6th Edition User s Manual 701932 Current Probe 6th Edition Thank you for purchasing the 701932 Current Probe. This user s manual contains useful information about the functions and operating procedures of the 701932

More information

CD770 DIGITAL MULTIMETER INSTRUCTION MANUAL

CD770 DIGITAL MULTIMETER INSTRUCTION MANUAL CD770 DIGITAL MULTIMETER INSTRUCTION MANUAL Table of Contents 1 SAFETY PRECAUTIONS Before use, read the following safety precautions.- 1-1 Explanation of Warning Symbols 001 1-2 Warning Messages for Safe

More information

DVM1190 DIGITAL MULTIMETER

DVM1190 DIGITAL MULTIMETER DIGITAL MULTIMETER 1. Introduction Thank you for buying the. This digital multimeter has a large LCD, a data-hold function and a backlight. The device uses a very practical safety mechanism that keeps

More information

User s Manual Model PR300 Power and Energy Meter

User s Manual Model PR300 Power and Energy Meter User s Manual Model PR300 Power and Energy Meter Yokogawa Electric Corporation st Edition Model PR300 Power and Energy Meter Contents Introduction...i Notices... ii Checking the Package... iii Checking

More information

User s Manual. Model MXS Universal Computing Unit (1-input, Isolated 2-output Type) MODEL AND SUFFIX CODES

User s Manual. Model MXS Universal Computing Unit (1-input, Isolated 2-output Type) MODEL AND SUFFIX CODES User s Manual Model MXS Universal Computing Unit (1-input, Isolated 2-output Type) IM 77J04X11-01E Network Solutions Business Division 2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan Phone: 81-422-52-7179

More information

Model Number Structure

Model Number Structure Total Counter/Time Counter (DIN 72 x 36) CSM DS_E_4_1 DIN 72 x 36-mm Total Counter/Time Counter with Easy-to-read Displays and Water and Oil Resistance Equivalent to IP66 Large, easy-to-read displays:

More information

2015 RIGOL TECHNOLOGIES, INC.

2015 RIGOL TECHNOLOGIES, INC. Service Guide DG000 Series Dual-channel Function/Arbitrary Waveform Generator Oct. 205 TECHNOLOGIES, INC. Guaranty and Declaration Copyright 203 TECHNOLOGIES, INC. All Rights Reserved. Trademark Information

More information

INVERTER INSTRUCTION MANUAL. 16 bit digital input function. Plug-in option FR-A7AX PRE-OPERATION INSTRUCTIONS INSTALLATION AND WIRING

INVERTER INSTRUCTION MANUAL. 16 bit digital input function. Plug-in option FR-A7AX PRE-OPERATION INSTRUCTIONS INSTALLATION AND WIRING INVERTER Plug-in option FR-A7AX INSTRUCTION MANUAL 16 bit digital input function PRE-OPERATION INSTRUCTIONS INSTALLATION AND WIRING CONNECTION DIAGRAM AND TERMINAL PARAMETERS 1 2 3 4 Thank you for choosing

More information

User s Manual. Model CA51/71 HANDY CAL (Calibrator) IM CA71-E IM CA71-E

User s Manual. Model CA51/71 HANDY CAL (Calibrator) IM CA71-E IM CA71-E User s Manual Model CA51/71 HANDY CAL (Calibrator) IM CA71-E IM CA71-E 2nd Edition: Dec. 2006 Introduction Thank you for purchasing the CA51/71 HANDY CAL Calibrator. This User s Manual explains the functions

More information

This section is specifically about safety matters

This section is specifically about safety matters 6 4 ) 1 6 4 1 -, 1 8-4 6-4 1 6 4 7 + 6 1 ) 7 ) 4 ) 6 1-6 6-4. 4. 0 J E? A Thank you for choosing this Mitsubishi transistorized Inverter option. This instruction manual gives handling information and precautions

More information

Keysight 16440A SMU/Pulse Generator Selector

Keysight 16440A SMU/Pulse Generator Selector Keysight 16440A SMU/Pulse Generator Selector User s Guide Notices Keysight Technologies 1994-2014 No part of this manual may be reproduced in any form or by any means (including electronic storage and

More information

G70R-SOC08 CSM_G70R-SOC08_DS_E_2_1

G70R-SOC08 CSM_G70R-SOC08_DS_E_2_1 Relay Terminal CSM DS_E 1 Space-saving and Labor-saving 8-point Output Block Relay terminal is just 136 80 55 mm (W H D, when mounted upright). Independent contacts and short bar allow easy common connections.

More information

Phase-sequence Phase-loss Relay

Phase-sequence Phase-loss Relay Phase-sequence Phase-loss Relay K8AB-PH Three-phase Phase-sequence Phase-loss Relay Using Voltage Detection Method Prevents reverse motor rotation due to incorrect wiring. Distinguishes between positive

More information

User s Manual. Miniature Passive Probe. IM EN 3rd Edition

User s Manual. Miniature Passive Probe. IM EN 3rd Edition User s Manual Miniature Passive Probe IM 701946-01EN 3rd Edition Thank you for purchasing the miniature passive probe. This miniature passive probe is designed for user s safety and excellent easyto-use

More information

Model Number Structure. Ordering Information. Solid-state Power OFF-delay Timer H3DE-H. Model Number Legend. List of Models

Model Number Structure. Ordering Information. Solid-state Power OFF-delay Timer H3DE-H. Model Number Legend. List of Models Solid-state Power OFF-delay Timer H3DE-H Timers Two delay-time models available. 0.1 to 12 seconds (S Series) 1 to 120 seconds (L Series) Covers wide range of supply voltage. Model Number Structure Model

More information

Overtravel of 3.5 mm max. Power source DC D5C-1DS0 D5C-1DP0 D5C-1DA0 AC D5C-1AS0 D5C-1AP0 D5C-1AA0 Antenna only D5C-00S0 D5C-00P0 D5C-00A0

Overtravel of 3.5 mm max. Power source DC D5C-1DS0 D5C-1DP0 D5C-1DA0 AC D5C-1AS0 D5C-1AP0 D5C-1AA0 Antenna only D5C-00S0 D5C-00P0 D5C-00A0 Touch Switch Unique 18 mm Capacitive Touch Switch with Choice of Three Actuators is Activated with Only a Very Slight Physical Contact Lightweight objects, such as thin wire or foil can be accurately detected.

More information

DIGITAL MULTIMETER CONTENTS DIGITAL MULTIMETER CONTENTS

DIGITAL MULTIMETER CONTENTS DIGITAL MULTIMETER CONTENTS CONTENTS CONTENTS CONTENTS 1. SAFETY INFORMATION...1 1.1 Preliminary...1 1.2 Dos and don ts...2 1.3 Symbols...3 1.4 Precautions...4 2. DESCRIPTION...5 2.1 Names of parts...6 2.2 Switches, buttons and input

More information

TETRIS 1000 High Impedance Active Probe. Instruction Manual

TETRIS 1000 High Impedance Active Probe. Instruction Manual TETRIS 1000 High Impedance Active Probe Instruction Manual Copyright 2015 PMK GmbH All rights reserved. Information in this publication supersedes that in all previously published material. Specifications

More information

RIGOL. User s Guide. RP5600 Passive Probe. July 2010 RIGOL Technologies, Inc.

RIGOL. User s Guide. RP5600 Passive Probe. July 2010 RIGOL Technologies, Inc. User s Guide RP5600 Passive Probe July 2010 RIGOL Technologies, Inc. Guaranty and Declaration Copyright 2010 RIGOL Technologies, Inc. All Rights Reserved. Trademark Information RIGOL is a registered trademark

More information

PARM-SIZED, 16-CHANNEL RELAY TERMINALS

PARM-SIZED, 16-CHANNEL RELAY TERMINALS Pressure connector connect type Wire-direct connect type PARM-SIZED, -CHANNEL RELAY TERMINALS FEATURES Compact, space-saving design: The Relay Terminal with I/O channels measures only (W) (D) (H) mm (W).

More information

User s Manual. Model MA5 Distributor (Free Range Type) CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT MODEL AND SUFFIX CODES

User s Manual. Model MA5 Distributor (Free Range Type) CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT MODEL AND SUFFIX CODES User s Manual Model MA5 Distributor (Free Range Type) IM 77J04A05-0E Network Solutions Business Division 2-9-32, Naka-cho Musashino-shi, Tokyo 80-8750 Japan Phone 8-422-52-779 Facsimile 8-422-52-6793 Please

More information

Safety Precautions. Copyright / Trademarks

Safety Precautions. Copyright / Trademarks Safety Precautions Observe the following notices to ensure personal safety or to prevent accidents. To ensure that you use this product correctly, read this User s Manual thoroughly before use. Make sure

More information

TETRIS User's Guide. High Impedance Active Probe DO177-1

TETRIS User's Guide. High Impedance Active Probe DO177-1 TETRIS 1500 High Impedance Active Probe User's Guide DO177-1 TETRIS 1500 Copyright 2010 Ltd. All rights reserved. Information in this publication supersedes that in all previously published material. Specifications

More information

VECTOR INVERTER -INSTRUCTION MANUAL- 16-BIT DIGITAL INPUT FR-V5AH

VECTOR INVERTER -INSTRUCTION MANUAL- 16-BIT DIGITAL INPUT FR-V5AH VECTOR INVERTER -INSTRUCTION MANUAL- 16-BIT DIGITAL INPUT FR-V5AH Thank you for choosing the Mitsubishi vector inverter option unit. This instruction manual gives handling information and precautions for

More information

Solid-State Digital Counter H7AN

Solid-State Digital Counter H7AN Solid-State Digital Counter Preset and Totalizing Counters with Up to 8-Digit LED Displays Draw-out construction allows setting, servicing without disconnecting wiring Choose from selectable UP/DOWN or

More information

MELSEC-Q Multi Function Counter/Timer Module User's Manual -QD65PD2

MELSEC-Q Multi Function Counter/Timer Module User's Manual -QD65PD2 MELSEC-Q Multi Function Counter/Timer Module User's Manual -QD65PD2 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant

More information

200Amp AC Clamp Meter + NCV Model MA250

200Amp AC Clamp Meter + NCV Model MA250 User's Guide 200Amp AC Clamp Meter + NCV Model MA250 Introduction Congratulations on your purchase of this Extech MA250 Clamp Meter. This meter measures AC Current, AC/DC Voltage, Resistance, Capacitance,

More information

User s Manual. Model MS5 Potentiometer Converter (Free Range Type) MODEL AND SUFFIX CODES CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT

User s Manual. Model MS5 Potentiometer Converter (Free Range Type) MODEL AND SUFFIX CODES CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT User s Manual Model MS5 Potentiometer Converter (Free Range Type) IM 77J04S05-0E Network Solutions Business Division 2-9-32, Naka-cho Musashino-shi, Tokyo 80-8750 Japan Phone: +8-422-52-779 Facsimile:

More information

Digital Interface Option "OPC-E1-DIO"

Digital Interface Option OPC-E1-DIO Instruction Manual Digital Interface Option "OPC-E1-DIO" Thank you for purchasing our digital interface option. Read through this instruction manual and be familiar with the digital interface option before

More information

IF30. User's manual. Description. Table of contents IF30

IF30. User's manual. Description. Table of contents IF30 User's manual IF30 Description IF30 is an encoder interface unit designed to convert the output signals delivered by so-called sine-cosine-encoders and similar measuring systems (devices which deliver

More information

USER'S MANUAL DMR-6700

USER'S MANUAL DMR-6700 USER'S MANUAL Multimeter True RMS DMR-6700 CIRCUIT-TEST ELECTRONICS www.circuittest.com Introduction This meter measures AC/DC Voltage, AC/DC Current, Resistance, Capacitance, Frequency (electrical & electronic),

More information

Universal Alarm Indicator

Universal Alarm Indicator Universal Alarm Indicator Model: PCA13 User s Manual CM2-PCA100-2001 4th edition Copyright, Notices and Trademarks 1996-2012 Azbil Corporation All Rights Reserved. While this information is presented in

More information

Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control

Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control Gain Electronic Co. Ltd. Table Of Contents Safety Considerations ------------------------------------------------------------2

More information

Models UT550/UT520 Digital Indicating Controllers User s Manual for Loop Control for Backup

Models UT550/UT520 Digital Indicating Controllers User s Manual for Loop Control for Backup Instruction Manual Models UT550/UT520 Digital Indicating Controllers User s Manual for Loop Control for Backup IM 05D01C02-45E IM 05D01C02-45E 1st Edition Blank Page Introduction Thank you

More information

User s Manual Current Probe. IM E 1st Edition. Yokogawa Electric Corporation

User s Manual Current Probe. IM E 1st Edition. Yokogawa Electric Corporation User s Manual 701932 Current Probe Yokogawa Electric Corporation 1st Edition Foreword Revisions Thank you for purchasing the 701932 Current Probe. This user's manual contains useful information about the

More information

SYSMAC C200H-NC112 Position Control Unit

SYSMAC C200H-NC112 Position Control Unit Cat. No. W28-E-4 SYSMAC C2H-NC2 Position Control Unit C2H-NC2 Position Control Unit Operation Manual September 2 Notice: OMRON products are manufactured for use according to proper procedures by a qualified

More information

DIGITAL DUAL DISPLAY AC/DC CLAMP METER MODEL-860A OPERATION MANUAL

DIGITAL DUAL DISPLAY AC/DC CLAMP METER MODEL-860A OPERATION MANUAL DIGITAL DUAL DISPLAY AC/DC CLAMP METER MODEL-860A OPERATION MANUAL DIGITAL DUAL DISPLAY AC/DC CLAMP METER MODEL-860A TABLE OF CONTENTS TITLE PAGE Safety Information Safety Symbols... 1 Meter Description...

More information

F4 16DA 2 16-Channel Analog Voltage Output

F4 16DA 2 16-Channel Analog Voltage Output F46DA2 6-Channel Analog Voltage In This Chapter.... Module Specifications Setting Module Jumpers Connecting the Field Wiring Module Operation Writing the Control Program 22 F46DA2 6-Ch. Analog Voltage

More information

712B. Users Manual. RTD Calibrator. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.

712B. Users Manual. RTD Calibrator. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot. 712B RTD Calibrator Test Equipment Depot - 800.517.8431-99 Washington Street Melrose, MA 02176 - TestEquipmentDepot.com Users Manual January 2014 2014 Fluke Corporation. All rights reserved. Specifications

More information

AC/DC Clamp Meter. Owner's Manual. Model No Safety Operation Maintenance Español

AC/DC Clamp Meter. Owner's Manual. Model No Safety Operation Maintenance Español Owner's Manual AC/DC Clamp Meter Model No. 82369 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product. Safety Operation Maintenance Español

More information

Module Type Controller SRX. Communication Instruction Manual IMS01N01-E6 RKC INSTRUMENT INC.

Module Type Controller SRX. Communication Instruction Manual IMS01N01-E6 RKC INSTRUMENT INC. Module Type Controller SRX Communication Instruction Manual RKC INSTRUMENT INC. IMS01N01-E6 is a registered trademark of Schneider Electric. Company names and product names used in this manual are the

More information

F4 04DAS 1 4-Channel Isolated 4 20mA Output

F4 04DAS 1 4-Channel Isolated 4 20mA Output F44DAS 4-Channel Isolated 4mA F44DAS 4-Channel Isolated 4mA Module Specifications The F44DAS 4-channel Isolated Analog module provides several features and benefits. ANALOG 4 CHANNELS PUT F44DAS 4-Ch.

More information

Model Number Structure

Model Number Structure Total Counter/Time Counter (DIN 72 x 36) CSM DS_E_5_3 DIN 72 x 36-mm Total Counter/Time Counter with Easy-to-read Displays and Water and Oil Resistance Equivalent to IP66 Large, easy-to-read displays:

More information

Radio System Strobe Wizard Plus Freemask

Radio System Strobe Wizard Plus Freemask Radio System Strobe Wizard Plus Freemask User manual Translation of the original German user manual Doc. No.: 900.0509.00 Version: 09/2017 Contents Information about this manual and about the manufacturer...

More information

User s Manual. Model US1000 Digital Indicating Controller Functions. IM 5D1A01-02E 2nd Edition IM 5D1A01-02E

User s Manual. Model US1000 Digital Indicating Controller Functions. IM 5D1A01-02E 2nd Edition IM 5D1A01-02E User s Manual Model US1000 Digital Indicating Controller Functions 2nd Edition Introduction This instruction manual describes the functions of the US1000 Digital Indicating Controller in detail. Read

More information

ProfiScale MULTI Multimeter

ProfiScale MULTI Multimeter 1,5 V 9V 200 mv 600 V 200 ma 1/10 A ProfiScale MULTI Multimeter en Operating instructions BURG-WÄCHTER KG Altenhofer Weg 15 58300 Wetter Germany Introduction Want the reassurance of knowing whether current

More information

PH201G (Style B) Distributor

PH201G (Style B) Distributor User s Manual PH201G (Style B) Distributor R 6th Edition Blank Page INTRODUCTION This instruction manual describes the procedures for installing, wiring and carrying out simple maintenance

More information

P1-04THM Analog Input

P1-04THM Analog Input Thermocouple Input Specifications Input Channels differential Data Format Floating Point Common Mode Range ±.2 V Common Mode Rejection 00dB @ DC Input Impedance >MΩ Maximum Ratings Fault Protected Inputs

More information

Media Storage Systems Fixed Media Cabinets

Media Storage Systems Fixed Media Cabinets Owner s Manual Media Storage Systems Fixed Media Cabinets Contents 1-Column Fixed Media Storage Cabinet Important User Information...........................2 Safety Precautions.................................3

More information

DCM730. Digital Clamp Meter User s Manual

DCM730. Digital Clamp Meter User s Manual DCM730 Digital Clamp Meter User s Manual Table of Contents LIMITED WARRANTY AND LIMITATION OF LIABILITY...1 Out of the Box...1 Safety Information...2 INTRODUCTION...4 Components and Buttons...6 Names of

More information

F4-04DA-1 4-Channel Analog Current Output

F4-04DA-1 4-Channel Analog Current Output F4-4DA- 4-Channel Analog Current 32 Analog Current Module Specifications The Analog Current Module provides several features and benefits. ANALOG PUT 4-Ch. Analog It is a direct replacement for the popular

More information

This Errata Sheet contains corrections or changes made after the publication of this manual.

This Errata Sheet contains corrections or changes made after the publication of this manual. Errata Sheet This Errata Sheet contains corrections or changes made after the publication of this manual. Product Family: DL4 Date: September 12, 218 Manual Number D4-ANLG-M Revision and Date th Ed., Rev.

More information

This section is specifically about safety matters

This section is specifically about safety matters 6 4 ) 5 1 5 6 4 1 -, 1 8-4 6-4 1 5 6 4 7 + 6 1 ) 7 ) 5 2 - -,, - 6 - + 6 4. 4. 2 J E? A Thank you for choosing this Mitsubishi transistorized Inverter option. This instruction manual gives handling information

More information

High Intensity LED Stroboscope Digital Tachometer DT-361/365. Instruction manual. Be sure to read before use.

High Intensity LED Stroboscope Digital Tachometer DT-361/365. Instruction manual. Be sure to read before use. 98585A High Intensity LED Stroboscope Digital Tachometer DT-361/365 Instruction manual Be sure to read before use. Before use, please carefully read these safety precautions as well as instructions, and

More information

PX-42SP1U/PX-42SP1U/S Instruction Manual

PX-42SP1U/PX-42SP1U/S Instruction Manual SPEAKES PX-42SP1U/PX-42SP1U/S Instruction Manual Thank you for purchasing the PX-42SP1U PX-42SP1U/S attachable speakers. Before using this product, please read this Instruction Manual thoroughly so that

More information

Model UP350 Program Controller

Model UP350 Program Controller User s Manual Model UP350 Program Controller User s Manual IM 05E01D02-41E IM 05E01D02-41E 2nd Edition Blank Page Introduction i Thank you for purchasing the UP350 program controller. How to

More information

Palm-sized, 16-channel Relay Terminals

Palm-sized, 16-channel Relay Terminals Palm-sized, -channel Relay Terminals RELAY TERMINAL FEATURES. Possible to select relay for use in the relay terminal in accordance with load. [Mountable relay: PA relay and Power PhotoMOS (voltage sensitive

More information

The Allen-Bradley Servo Interface Module (Cat. No SF1) when used with the Micro Controller (Cat. No UC1) can control single axis

The Allen-Bradley Servo Interface Module (Cat. No SF1) when used with the Micro Controller (Cat. No UC1) can control single axis Table of Contents The Allen-Bradley Servo Interface Module (Cat. No. 1771-SF1) when used with the Micro Controller (Cat. No. 1771-UC1) can control single axis positioning systems such as found in machine

More information

Installation instructions for encoders. RM3xxx RM7xxx RN3xxx RN7xxx /02 08/2015

Installation instructions for encoders. RM3xxx RM7xxx RN3xxx RN7xxx /02 08/2015 Installation instructions for encoders RMxxx RM7xxx RNxxx RN7xxx 897/ 8/ Contents Preliminary note.... Notes on this document.... Symbols used... Safety instructions.... General.... Installation and connection...

More information

Keychain Radio Remote Control System

Keychain Radio Remote Control System Innovation in Mobility Keychain Radio Remote Control System Operator Manual 04/23/02 95-2002 RICON CORPORATION All Rights Reserved U.S. and foreign patents pending Printed in the United States of America

More information

VLA574-01R V I + V CC DETECT C trip V O V I - F O C S V EE TIMER & RESET LATCH DETECT. 1kΩ INTERFACE UVL 240Ω GATE SHUT DOWN BLOCK DIAGRAM DESCRIPTION

VLA574-01R V I + V CC DETECT C trip V O V I - F O C S V EE TIMER & RESET LATCH DETECT. 1kΩ INTERFACE UVL 240Ω GATE SHUT DOWN BLOCK DIAGRAM DESCRIPTION DESCRIPTION VLA74 is a hybrid integrated circuit designed for driving n-channel IGBT modules in any gate-amplifier application. OUTLINE DRAWING Dimensions : mm This device operates as an isolation amplifier

More information

TOSVERT VF-PS1 series BACnet option unit Instruction Manual BCN001Z

TOSVERT VF-PS1 series BACnet option unit Instruction Manual BCN001Z TOSVERT VF-PS1 series BACnet option unit Instruction Manual BCN001Z NOTICE 1. Make sure that this instruction manual is delivered to the end user of BACnet Option unit. 2. Read this manual before installing

More information

Emitting and receiving element pitch: 10 mm in

Emitting and receiving element pitch: 10 mm in Small / Slim Object Detection Area Sensor Cross-beam scanning system to detect slim objects Letter or visiting card detectable! Slim objects can be detected by using the cross-beam scanning system. Emitting

More information

Parallel. Parallel. data transmission. Technical Information TR - ECE - TI - GB /05/2016

Parallel. Parallel. data transmission. Technical Information TR - ECE - TI - GB /05/2016 TR - ECE - TI - GB - 0054-01 04/05/2016 Parallel Parallel data transmission Technical Information TR-Electronic GmbH D-78647 Trossingen Eglishalde 6 Tel.: (0049) 07425/228-0 Fax: (0049) 07425/228-33 email:

More information

P1-04DAL-1 Analog Output

P1-04DAL-1 Analog Output Output Specifications Output Channels Output Range ma Signal Resolution -bit Resolution Value of SB (least significant bit) Data Range 9 counts Output Type Output Value in Fault Mode ess than ma oad Impedance

More information

F2A3X Frequency to Analog Converter Module

F2A3X Frequency to Analog Converter Module the professional s choice F2A3X Frequency to Analog Converter Module Instruction Manual MONARCH INSTRUMENT 15 Columbia Drive Amherst, NH 03031 USA Phone: (603) 883-3390 Fax: (603) 886-3300 E-mail: support@monarchinstrument.com

More information

P1-04ADL-2 Analog Input

P1-04ADL-2 Analog Input Input Specifications Input Channels Input Range VDC Signal Resolution -bit Resolution Value of SB (least significant bit) Data Range Input Type Maximum Continuous Overload ±VDC Input Impedance kω Hardware

More information

AZ Series. Function Edition. Closed Loop Stepping Motor and Driver Package. Operation. I/O signals. Parameter

AZ Series. Function Edition. Closed Loop Stepping Motor and Driver Package. Operation. I/O signals. Parameter HM-6262 Closed Loop Stepping Motor and Driver Package Operation I/O signals Parameter AZ Series Function Edition Method of control via Modbus RTU (RS-485 communication) Method of control via industrial

More information

Operator s Manual. PP022 Passive Probe

Operator s Manual. PP022 Passive Probe Operator s Manual PP022 Passive Probe 700 Chestnut Ridge Road Chestnut Ridge, NY, 10977-6499 Tel: (845) 425-2000, Fax: (845) 578 5985 teledynelecroy.com PP022 Passive Probe Instruction Manual 2017 Teledyne

More information

General Specifications

General Specifications General I/O Adaptors (for N-IO) GS 33J62F30-01EN [Release 6] GENERAL This General (GS) describes the hardware specifications of I/O adaptors that enable extended functions setting for analog digital I/O

More information

Custom Pendant- Hardwire Assembly and Installation Instructions

Custom Pendant- Hardwire Assembly and Installation Instructions Custom Pendant- Hardwire Assembly and Installation Instructions CAUTION: BEFORE INSTALLING FIXTURE, MAKE SURE THE POWER TO THE CIRCUIT IS TURNED OFF AT THE MAIN FUSE BOX / CIRCUIT BREAKER UTILITY BOX.

More information

400Amp True RMS AC Clamp Meter + NCV

400Amp True RMS AC Clamp Meter + NCV User Guide 400Amp True RMS AC Clamp Meter + NCV Model MA410T Introduction Thank you for selecting the Extech MA410 Clamp Meter. This meter measures AC Current, AC/DC Voltage, Resistance, Capacitance, Frequency,

More information

3B SCIENTIFIC PHYSICS

3B SCIENTIFIC PHYSICS 3B SCIENTIFIC PHYSICS Digital Multimeter E 1018832 Instruction sheet 12/16 SD/UD 1 probe 1a Finger guards 2 Measurement socket 10 A for current measurement in 10-A (positive) 3 Measurement socket COM (negative)

More information

RSMFX-2R MULTIFUNCTIONAL

RSMFX-2R MULTIFUNCTIONAL Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND

More information

AI controller. Mitsubishi Electric Air Conditioner Network System PAC-YG63MCA. Table of Contents. Installation/Instruction Manual

AI controller. Mitsubishi Electric Air Conditioner Network System PAC-YG63MCA. Table of Contents. Installation/Instruction Manual Mitsubishi Electric Air Conditioner Network System AI controller PAC-YG63MCA Installation/Instruction Manual Table of Contents Page 1. Safety Precautions...1 2. Usage...2 3. Parts List...2 4. Specifications...2

More information

DDM350 Pen-Type Digital Multimeter User s Manual

DDM350 Pen-Type Digital Multimeter User s Manual DDM350 Pen-Type Digital Multimeter User s Manual CONTENTS LIMITED WARRANTY AND LIMITATION OF LIABILITY....1 Out of the Box...1 Accessories......2 Safety Information...2 Safety Symbols...3 Certification......4

More information

Installation instructions

Installation instructions Installation instructions T70RX-03AIB, T70RX-03AWB, T70TX-02TTB, T70TX-03STB, T70TX-06TTB LANGUAGE: English (original) IM-T70-RX001-A01-EN CONTENTS Chapter 1: CUSTOMER INFORMATION 3 Chapter 2: PRODUCT

More information

User s Manual. Model CA51, CA71 HANDY CAL (Calibrator) IM CA71-E. Store this manual in an easily accessible place for quick reference.

User s Manual. Model CA51, CA71 HANDY CAL (Calibrator) IM CA71-E. Store this manual in an easily accessible place for quick reference. User s Manual Model CA51, CA71 HANDY CAL (Calibrator) IM CA71-E Store this manual in an easily accessible place for quick reference. IM CA71-E 9th Edition: Oct. 2017 (YMI) Introduction Thank you for purchasing

More information

PU202 Level converter & encoder signal generator without potential separation

PU202 Level converter & encoder signal generator without potential separation Operating Manual PU202 Level converter & encoder signal generator without potential separation Product features: Converts HTL signals from 10 up to 30 V (A / B / Z) into the corresponding TTL / RS422 format

More information

Model: PR-55. High Voltage Oscilloscope Probe 10 kv, 40 MHz USER MANUAL

Model: PR-55. High Voltage Oscilloscope Probe 10 kv, 40 MHz USER MANUAL Model: PR-55 High Voltage Oscilloscope Probe 10 kv, 40 MHz USER MANUAL 1 2017 All rights reserved. B&K Precision products are covered by US and foreign patents, issued and pending. Information is this

More information

F4 08DA 2 8-Channel Analog Voltage Output

F4 08DA 2 8-Channel Analog Voltage Output 8-Channel Analog Voltage In This Chapter.... Module Specifications Setting the Module Jumper Connecting the Field Wiring Module Operation Writing the Control Program 92 8-Ch. Analog Voltage Module Specifications

More information

Cat. No. W902-E2-03. CS1W-CT021 CS1W-CT041 High-speed Counter Units OPERATION MANUAL

Cat. No. W902-E2-03. CS1W-CT021 CS1W-CT041 High-speed Counter Units OPERATION MANUAL Cat. No. W902-E2-03 CS1W-CT021 CS1W-CT041 High-speed Counter Units OPERATION MANUAL CS1W-CT021/CT041 High-speed Counter Units Operation Manual Revised August 2004!!! !" Notice: OMRON products are manufactured

More information

User s Manual. Model PBD2000 Differential Probe. IM E 1st Edition. Yokogawa Electric Corporation

User s Manual. Model PBD2000 Differential Probe. IM E 1st Edition. Yokogawa Electric Corporation User s Manual Model 701923 PBD2000 Differential Probe Yokogawa Electric Corporation 1st Edition Foreword Revisions Thank you for purchasing the PBD2000 Differentil Probe (Model 701923). This user s manual

More information

IP Series DUAL POWER AMPLIFIERS

IP Series DUAL POWER AMPLIFIERS OPERATING INSTRUCTIONS IP Series DUAL POWER AMPLIFIERS IP-600D IP-450D IP-300D TABLE OF CONTENTS 1. SAFETY PRECAUTIONS... 2 2. GENERAL DESCRIPTION... 4 3. FEATURES... 4 4. HANDLING PRECAUTIONS... 4 5.

More information

AI controller. Mitsubishi Electric Air Conditioner Network System PAC-YG63MCA. Contents. Installation/Instruction Manual

AI controller. Mitsubishi Electric Air Conditioner Network System PAC-YG63MCA. Contents. Installation/Instruction Manual Mitsubishi Electric Air Conditioner Network System AI controller PAC-YG63MCA Installation/Instruction Manual Contents Page 1. Safety Precautions... 1 2. Device Capabilities... 1 3. Confirmation of Parts...

More information

Panther. Installation instructions. Receivers PN-R15-1 PN-R15-2 PN-R15-13 PN-R IM-PN-RX103-A03-EN Language: English (original)

Panther. Installation instructions. Receivers PN-R15-1 PN-R15-2 PN-R15-13 PN-R IM-PN-RX103-A03-EN Language: English (original) Panther Installation instructions Receivers IM-PN-RX0-A0-EN Language: English (original) PN-R5- PN-R5-2 PN-R5- PN-R5-4 CONTENTS Chapter : CUSTOMER INFORMATION Chapter 2: FUNCTIONAL SAFETY 6 Chapter : PRODUCT

More information

Model UP351 Program Controller

Model UP351 Program Controller User s Manual Model UP351 Program Controller User s Manual IM 05E01D12-41E IM 05E01D12-41E 4th Edition Blank Page Introduction i Thank you for purchasing the UP351 program controller. How to

More information