CHAPTER 11. Balanced Three-Phase Circuits

Similar documents
Electric Circuits II Three-Phase Circuits. Dr. Firas Obeidat

EE 221 CIRCUITS II. Chapter 12 Three-Phase Circuit

Study Guide for Chapter 11

Chapter Objectives: Payam zarbakhsh EElE301 Circuit Theory II Department of Electrical and Electronic Engineering Cyprus International university

Polyphase Systems. Dr Gamal Sowilam

Experiment 45. Three-Phase Circuits. G 1. a. Using your Power Supply and AC Voltmeter connect the circuit shown OBJECTIVE

A) For the Y-Y circuit shown in Fig. 1, find the line currents, the line voltages, and the load voltages.

EE 221 CIRCUITS II. Chapter 12 Three-Phase Circuit

Chapter 7. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.

ESO 210 Introduction to Electrical Engineering

Chapter 11 Thre r e e e P has a e e C i C rc r u c its t

The Two-Wattmeter Method

AC Power Instructor Notes

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

Chapter 12 Three Phase Circuits. Chapter Objectives:

ESO 210 Introduction to Electrical Engineering

Transformers 3: connections

Electric Circuits I. Simple Resistive Circuit. Dr. Firas Obeidat

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Spring 2000 EE361: MIDTERM EXAM 1

Rarely used, problems with unbalanced loads.

Unit 27 Three-Phase Circuits

MILWAUKEE SCHOOL OF ENGINEERING LABORATORY SESSION 4 THREE PHASE TRANSFORMERS

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

Hours / 100 Marks Seat No.

Three-Phase, Step-Wave Inverter Circuits

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK UNIT I BASIC CIRCUITS ANALYSIS PART A (2-MARKS)

El-Hawary, M.E. The Transformer Electrical Energy Systems. Series Ed. Leo Grigsby Boca Raton: CRC Press LLC, 2000

Sample Question Paper

ELECTROTECHNOLOGY ELTK1200 ASSIGNMENT #8 SOLUTIONS

Level 6 Graduate Diploma in Engineering Electro techniques

Chapter 3 - Waveforms, Power and Measurement

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.

Question Paper Profile

TRANSFORMER THEORY. Mutual Induction

86 chapter 2 Transformers

EN Assignment No.1 - TRANSFORMERS

CONSTRUCTION ELECTRICIAN APPRENTICESHIP PROGRAM Line H: Install Electrical Equipment H-2 LEARNING GUIDE H-2 INSTALL TRANSFORMERS

Conventional Paper-II-2011 Part-1A

ECE 2006 University of Minnesota Duluth Lab 11. AC Circuits

Downloaded from / 1

UNIVERSITY OF NORTH CAROLINA AT CHARLOTTE Department of Electrical and Computer Engineering

UNIVERSITY OF TECHNOLOGY By: Fadhil A. Hasan ELECTRICAL MACHINES

148 Electric Machines

5.0 THREE PHASE SYSTEM

Unit 29 Three-Phase Transformers

CHAPTER 9. Sinusoidal Steady-State Analysis

For the circuit in Fig. 1, determine the current in the neutral line.

EE6201 CIRCUIT THEORY QUESTION BANK PART A

SECTION 4 TRANSFORMERS. Yilu (Ellen) Liu. Associate Professor Electrical Engineering Department Virginia Tech University

VALLIAMMAI ENGINEERING COLLEGE

2.0 AC CIRCUITS 2.1 AC VOLTAGE AND CURRENT CALCULATIONS. ECE 4501 Power Systems Laboratory Manual Rev OBJECTIVE

VOLTAGE AND CURRENT RELATIONS AND POWER PART1: THREE PHASE VOLTAGE AND CURRENT RELATIONSHIPS

Module 7. Transformer. Version 2 EE IIT, Kharagpur

Lecture (11) Three Phase Transformers

CHAPTER 2. Transformers. Dr Gamal Sowilam

V.S.B ENGINEERING COLLEGE DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING I EEE-II Semester all subjects 2 & 16 marks QB

Note: 1. All the students must strictly follow all the safety precautions. 2. In case of any question or concern, please contact LAB INSTRUCTOR or TA.

Three Phase Transformers

Three Phase System. c 2 ω Fig.1a -----(1) Eb1b2 ) -----(2) Ea1a Ea1a2, Eb1b2 & Ec1c2 are RMS values. Ec1c2. Fig.

Module 1. Introduction. Version 2 EE IIT, Kharagpur

Contents. Core information about Unit

DISCUSSION OF FUNDAMENTALS

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT B.Tech. [SEM I (EE, EN, EC, CE)] QUIZ TEST-3 (Session: ) Time: 1 Hour ELECTRICAL ENGINEE

Transformers. gpmacademics.weebly.com

ELEN 140 ELECTRICAL CIRCUITS II Winter 2013

UPQC (Unified Power Quality Conditioner)

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

Phasor. Phasor Diagram of a Sinusoidal Waveform

VETRI VINAYAHA COLLEGE OF ENGINEERING AND TECHNOLOGY

UNIT 1 CIRCUIT ANALYSIS 1 What is a graph of a network? When all the elements in a network is replaced by lines with circles or dots at both ends.

Fundamentals of Electric Circuits Chapter 2. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.

1. Explain in detail the constructional details and working of DC motor.

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

PROBLEMS. Figure13.74 For Prob Figure13.72 For Prob Figure13.75 For Prob Figure13.73 For Prob Figure13.76 For Prob

Power and Energy Measurements. MYcsvtu Notes

Experiment 9 AC Circuits

University of Pennsylvania Department of Electrical and Systems Engineering. ESE 206: Electrical Circuits and Systems II - Lab

13. Magnetically Coupled Circuits

UNBALANCED CURRENT BASED TARRIF

Table of Contents. Table of Figures. Table of Tables

Code No: RR Set No. 1

Chapter 2-1 Transformers

Power Metering Fundamentals Jim Spangler Cirrus Logic 1 March 2011

Transformer Factory Testing

In Class Examples (ICE)

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING. MIDTERM EXAMINATION, February Forth Year Electrical and Computer Engineering

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

A Practical Guide to Free Energy Devices

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

THE SINUSOIDAL WAVEFORM

Bhoj Reddy Engineering College for Women, Hyderabad Department of Electronics and Communication Engineering Electrical and Electronics Instrumentation

Reg. No. : BASIC ELECTRICAL TECHNOLOGY (ELE 101)

Generator Protection GENERATOR CONTROL AND PROTECTION

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

UNIT II MEASUREMENT OF POWER AND ENERGY PART-A

Three-Phase AC Power Circuits

Transcription:

CHAPTER 11 Balanced Three-Phase Circuits

11.1 Balanced Three-Phase Voltages Three sinusoidal voltages Identical amplitudes and frequencies Out of phase 120 with each other by exactly As the a-phase voltage, the b-phase voltage, and the c-phase voltage. abc (or positive) phase sequence acb (or negative) phase sequence

Figure 11.1 A basic three-phase circuit.

abc (or positive) phase sequence Figure 11.2 Phasor diagrams of a balanced set of three-phase voltages. (a) The abc (positive) sequence.

acb (or negative) phase sequence Figure 11.2 Phasor diagrams of a balanced set of three-phase voltages. (b) The acb (negative) sequence.

11.2 Three-Phase Voltage Sources Figure 11.3 A sketch of a threephase voltage source.

There are two ways of interconnecting the separate phase windings to form a three-phase source: in either a wye (Y) or a delta (Δ) n in Fig. 11.4(a), is called the neutral terminal of the source. Figure 11.4 The two basic connections of an ideal three-phase source. (a) A Y-connected source. (b) A -connected source.

Three-phase sources and loads can be either Y- connected or Δ-connected

Three-phase source with winding impedance Figure 11.5 A model of a three-phase source with winding impedance: (a) a Y-connected source; and (b) a -connected source.

11.3 Analysis of the Wye-Wye Circuit Figure 11.6 A three-phase Y-Y system.

Conditions for a balanced three-phase circuit 1. The voltage sources form a set of balanced threephase voltages. In Fig. 11.6, this means that V V and are a set of balanced three-phase voltages. Vc,n,, a,n b,n 2. The impedance of each phase of the voltage source is the same. In Fig. 11.6, this means that Z ga = Z gb = Z gc. 3. The impedance of each line (or phase) conductor is the same. In Fig. 11.6, this means that Z 1a = Z 1b = Z 1c. 4. The impedance of each phase of the load is the same. In Fig. 11.6, this means that Z A = Z B = Z C.

where a balanced three phase circuit,

When the system is balanced, the three line currents are

Single-phase equivalent circuit The current in the a-phase conductor line is simply the voltage generated in the a-phase winding of the generator divided by the total impedance in the a- phase of the circuit. Figure 11.7 A single-phase equivalent circuit.

Line-to-line and line-to-neutral voltages Figure 11.8 Line-to-line and line-to-neutral voltages.

Relationship between line-to-line and line-to-neutral voltages 1. The magnitude of the line-to-line voltage is 3 times the magnitude of the line-to-neutral voltage. 2. The line-to-line voltages form a balanced threephase set of voltages. 3. The set of line-to-line voltages leads the set of lineto-neutral voltages by 30.

Phasor diagrams Figure 11.9 Phasor diagrams showing the relationship between line-to-line and line-to-neutral voltages in a balanced system. (a) The abc sequence. (b) The acb sequence.

Line voltage v.s. Phase voltage Line voltage refers to the voltage across any pair of lines; phase voltage refers to the voltage across a single phase. Line current refers to the current in a single line; phase current refers to current in a single phase. In a Δ connection, line voltage and phase voltage are identical. In a Y connection, line current and phase current are identical.

Example 11.1 A balanced three-phase Y-connected generator with positive sequence has an impedance of 0.2 + j0.5ω/f and an internal voltage of 120 V/f The generator feeds a balanced three-phase Y-connected load having an impedance of 39 + j28ω/f. The impedance of the line connecting the generator to the load is 0.8 + j1.5ω/f. The a-phase internal voltage of the generator is specified as the reference phasor. a) Construct the a-phase equivalent circuit of the system. b) Calculate the three line currents I aa, I bb, and I cc.

Example 11.1 c) Calculate the three phase voltages at the load, V AN, V BN, and V CN. d) Calculate the line voltages V AB, V BC, and V CA at the terminals of the load. e) Calculate the phase voltages at the terminals of the generator, I an, I bn, and I cn. f) Calculate the line voltages I ab, I bc, and I ca and at the terminals of the generator. g) Repeat (a) (f) for a negative phase sequence.

Example 11.1 Figure 11.10 The single-phase equivalent circuit for Example 11.1.

Example 11.1

Example 11.1

Example 11.1

Example 11.1

Example 11.1

11.4 Analysis of the Wye-Delta Circuit When the load is balanced, the impedance of each leg of the wye is one third the impedance of each leg of the delta. Relationship between three-phase delta-connected and wye-connected impedance

After the D load has been replaced by its Y equivalent, the a-phase can be modeled by the single phase equivalent circuit shown in Fig. 11.11. Figure 11.11 A single-phase equivalent circuit.

When a load (or source) is connected in a delta, the current in each leg of the delta is the phase current, and the voltage across each leg is the phase voltage. Figure 11.12 A circuit used to establish the relationship between line currents and phase currents in a balanced load.

To demonstrate the relationship between the phase currents and line currents, we assume a positive phase sequence and let I f represent the magnitude of the phase current

Figure 11.13 Phasor diagrams showing the relationship between line currents and phase currents in a -connected load. (a) The positive sequence. (b) The negative sequence.

Example 11.2 The Y-connected source in Example 11.1 feeds a - connected load through a distribution line having an impedance of 0.3 + j0.9ω/f. The load impedance is 118.5 + j85.5ω/f.use the a-phase internal voltage of the generator as the reference. a) Construct a single-phase equivalent circuit of the three-phase system. b) Calculate the line currents I aa, I bb, and I cc. c) Calculate the phase voltages at the load terminals. d) Calculate the phase currents of the load. e) Calculate the line voltages at the source terminals.

Example 11.2 Figure 11.14 The single-phase equivalent circuit for Example 11.2.

Example 11.2

Example 11.2

Example 11.2

Example 11.2

11.5 Power Calculations in Balanced Three-Phase Circuits Average Power in a Balanced Wye Load Figure 11.15 A balanced Y load used to introduce average power calculations in three-phase circuits.

Average Power in a Balanced Wye Load

Total real power in a balanced threephase load

Complex Power in a Balanced Wye Load Total reactive power in a balanced three-phase load Total complex power in a balanced threephase load

Power Calculations in a Balanced Delta Load Figure 11.16 A -connected load used to discuss power calculations.

The total power delivered to a balanced Δ-connected load

Instantaneous Power in Three-Phase Circuits The total instantaneous power is the sum of the instantaneous phase powers, which reduces to 1.5V m I m cosθ f ; that is, Note this result is consistent with Eq. 11.35 since V 2 and I 2. m V f m I f

Example 11.3 a) Calculate the average power per phase delivered to the Y-connected load of Example 11.1. b) Calculate the total average power delivered to the load. c) Calculate the total average power lost in the line. d) Calculate the total average power lost in the generator. e) Calculate the total number of magnetizing vars absorbed by the load. f) Calculate the total complex power delivered by the source.

Example 11.3

Example 11.3

Example 11.3

Example 11.4 a) Calculate the total complex power delivered to the D- connected load of Example 11.2. b) What percentage of the average power at the sending end of the line is delivered to the load?

Example 11.4

Example 11.5 A balanced three-phase load requires 480 kw at a lagging power factor of 0.8. The load is fed from a line having an impedance of 0.005 + j0.025ω/f. The line voltage at the terminals of the load is 600V. a) Construct a single-phase equivalent circuit of the system. b) Calculate the magnitude of the line current. c) Calculate the magnitude of the line voltage at the sending end of the line. d) Calculate the power factor at the sending end of the line.

Example 11.5 Figure 11.17 The single-phase equivalent circuit for Example 11.5.

Example 11.5

Example 11.5

Example 11.5

Example 11.5

11.6 Measuring Average Power in Three-Phase Circuits Electrodynamometer wattmeter: current coil, potential coil. The wattmeter deflects upscale when (1) the polarity-marked terminal of the current coil is toward the source, and (2) the polarity-marked terminal of the potential coil is connected to the same line in which the current coil has been inserted. Figure 11.18 The key features of the electrodynamometer wattmeter.

The Two-Wattmeter Method To measure the total power at the terminals of the box, we need to know n 1currents and voltages. Figure 11.19 A general circuit whose power is supplied by n conductors.

Figure 11.20 A circuit used to analyze the two-wattmeter method of measuring average power delivered to a balanced load.

For a positive phase sequence, To find the total power, we add W 1 and W 2 thus

Readings of the two wattmeters A closer look at Eqs. 11.58 and 11.59 reveals the following about the readings of the two wattmeters: 1. If the power factor is greater than 0.5, both wattmeters read positive. 2. If the power factor equals 0.5, one wattmeter reads zero. 3. If the power factor is less than 0.5, one wattmeter reads negative. 4. Reversing the phase sequence will interchange the readings on the two wattmeters.

Example 11.6 Calculate the reading of each wattmeter in the circuit in Fig. 11.20 if the phase voltage at the load is 120 V and (a) Z 8 j6 ;(b) Z 8 j6 ; f (c) Z j and (d) Z f 10 75. (e) Verify for (a) (d) that the sum of the wattmeter readings equals the total power delivered to the load f 5 f 5 3 ;

Example 11.6

Example 11.6

Example 11.6

Example 11.6