REPORT OF PERFORMANCE TIC

Similar documents
76 / 132 (145) kv 1x1200 mm 2 CU/XLPE/CWS/AL/HDPE

This Certificate consists of 75 pages in total.

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET

Date: / TECHNICAL SPECIFICATIONS FOR 11 KV XLPE INSULATED UNDERGROUND CABLES

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED)

EXTREMELY LOW MAGNETIC FIELD (ELMF) XLPE INSULATED CABLES, TYPE N2XY/FR1 0.6/1 KV

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES

Connecting Systems for Cable Repair (Cable Splices)

DNVGL-CP-0400 Edition December 2015

Testing Manual for Electrical Equipment

Medium Voltage Power Cables

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured)

Type Test of a 145 kv Termination Type TS 145-II

Specification for pvc-insulated cables for electricity supply

conductor Extruded Cross - Linked Polyethylene Insulated (XLPE) Power Cable Rated Voltage U 0 /U = 12/20 kv U 0 /U = 18/30 kv

CERTIFICATE OF CONFORMANCE

SANS 1339:2010 Electric cables Cross-linked polyethylene (XLPE) insulated cables for rated voltages 3,8/6,6 kv to 19/33 kv

Testing 320 kv HVDC XLPE Cable System

ASTA TEST REPORT NO: HEATSHRINK TERMINATIONS 3 CORE 12kV PILC AND XLPE

DATA SHEET MKP 435 X2

Technical Specification. for 1.1 KV Copper Control Cable

TwenCombi Cat-5E FTP(3x) - Coax 9 - EIBA - tube PE 5 mm

XLPE CABLE (33KV) September Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

Tratos High Voltage cables

GLOBAL STANDARD Page 1 of 66 UNDERGROUND MEDIUM VOLTAGE CABLES UNDERGROUND MEDIUM VOLTAGE CABLES

KP 376 KP/MMKP 376. AC and pulse metallized polypropylene film capacitors. Fig.1 Simplified outlines.

Interference Suppression Film Capacitor - Class X2 Axial MKT 253 V AC - Continuous Across the Line

Metallized Polycarbonate film capacitors MKC 344

EC 200 CHARACTERISTICS D A T A S H E E T. Kabelwerk EUPEN AG cable. M e c h a n i c a l c h a r a c t e r i s t i c s

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

MV water-proof and water tree retardant power cable

Disclosure to Promote the Right To Information

Interference Suppression Film Capacitor - Class X2 Radial MKT 310 V AC - High Stability Grade

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137

Kerman & Kavian Cable Industries ( KCI )

Power Cables and their Application

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations

DETAIL SPECIFICATION SHEET INSULATION SLEEVING, ELECTRICAL, HEAT SHRINKABLE, POLYOLEFIN, DUAL-WALL, OUTER WALL CROSSLINKED

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

Interference Suppression Film Capacitors MKP Radial Potted Type

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

Notes 3 Explanatory Information 4-10

Tests on Extruded Cables

SUBMERSIBLE PUMP CABLES

High Votage Module AC/DC/Impulse Test System

MarineLine YOZp 0,6/1 kv

For information transmission at dry and moist production sites, in and under plaster, outdoors for fixed installation.

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM

VSD cables in. Working with. industrial & automation applications

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Cables

EDS LV WAVEFORM MAINS CABLE RATINGS

ENERGY CORDAFLEX (SMK) (N)SHTOEU Low Voltage Reeling Cable

High-ohmic/high-voltage resistors

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

CABLE JOINTING KITS &

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

EDS KV TRIPLEX CABLE RATING

AC and Pulse Double Metallized Polypropylene Film Capacitors MMKP Radial Potted Type

Y-CY-JZ flexible, CU-screened, transparent, EMC-preferred type, meter marking

Underground System Design TADP 547

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

Interference Suppression Film Capacitors MKP Radial Potted Type

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

INTERNATIONAL STANDARD

TECHNICAL DATA SHEET FOR Single Mode Optical Fibre Cable Direct Burial Application

POLYIMIDE INSULATED WIRES AND CABLES, LOW FREQUENCY, 600V, -200 TO +200 C BASED ON TYPE SPL. ESCC Detail Specification No.

OFFSHORE CABLES GENERAL CATALOGUE. Offshore Cables. technergy INTEGRATED CABLING SOLUTIONS

INSTRUCTIONS FOR THE SAFE APPLICATION OF CABLES

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s

SOLARLOK PV BAR Junction Box

Prepared by Mick Maytum

FUSIBLE RESISTOR - NFR25H

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

Datasheet Platinum Resistance Pt100 In-head (Push Button) Temperature Transmitter TX203P mA output, default range supplied C

High Voltage Instrumentation Cables for the ITER Superconducting Magnet Systems

AC and Pulse Film Foil Capacitors KP Radial Potted Type

INTERNATIONAL STANDARD

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION)

Compact Substation or Prefabricated Substation Inside Totally Enclosed Weatherproof Enclosure COPYRIGHT REGISTERED

Pre-printed PVC Cable Markers O-Type, K-type, Z-type, V-Type

Industrial Ethernet OPT cable manufactured for Petrol Forecourt Applications.

HYDROFIRM (T) Cables. for use in Ground Water and Drinking Water

MKP X1 Vishay BCcomponents Interference Suppression Film Capacitors MKP Radial Potted Type

Fault location on power cables. Fault location on power cables

Selection table for flat & ribbon cables

MILITARY SPECIFICATION SHEET CABLE, RADIO FREQUENCY, FLEXIBLE, COAXIAL, 50 OHMS, M17/

High Voltage Surge Resistor

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

EXTRUDED, CROSS-LINKED FLUOROPOLYMER INSULATED WIRES AND CABLES ON SILVER-PLATED COPPER CONDUCTOR, LOW FREQUENCY, 600V, -100 TO +200 C

Armoured Power and Control Cables Fire Resistant

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

7. INSPECTION AND TEST PROCEDURES

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Metallized Polypropylene Film Capacitor AC Filtering Radial Type

Transcription:

REPORT OF PERFORMANCE TIC 1580-13 OBJECT TYPE Three-core power cable 18/30(36) kv, 3x500 mm2, 2XWY(P)-FR XLPE Rated voltage, U 0/U (U m) 18/30 (36) kv Conductor material Cu Conductor cross-section 3x500 mm² Insulation material XLPE CLIENT MANUFACTURER KEC INTERNATIONAL LIMITED, Vadodara, Gujarat, India KEC INTERNATIONAL LIMITED, Vadodara, Gujarat, India TESTED BY KEMA Nederland B.V., Arnhem, The Netherlands DATE(S) OF TESTS 10 October to 22 November 2013 TEST SPECIFICATION SUMMARY AND CONCLUSION The programme was specified by the client and was based on IEC 60502-2 (2005). The cable passed the tests. This report applies only to the object tested. The responsibility for conformity of any object having the same type references as that tested rests with the manufacturer. This report consists of 38 pages in total. Copyright: Only integral reproduction of this report is permitted without written permission from KEMA. Electronic copies in e.g. PDF-format or scanned version of this report may be available and have the status for information only. The sealed and bound version of the report is the only valid version. KEMA Nederland B.V. S.A.M. Verhoeven Director Testing, Inspections & Certification The Netherlands Arnhem, 14 January 2014

-2- TIC 1580-13 CONTENTS page 1 Identification of the object tested... 4 1.1 Ratings/characteristics of the object tested and proved by tests... 4 1.2 Description of the object tested... 4 1.3 List of drawings... 6 2 General information... 7 2.1 The tests were carried out by... 7 2.2 Subcontracting... 7 2.3 Purpose of the tests... 7 2.4 Measurement uncertainty... 7 3 Electrical type tests... 8 3.1 Test arrangement... 8 3.1.1 Determination of the cable conductor temperature... 8 3.1.2 Photograph of test set-up... 9 3.2 Bending test...10 3.3 Partial discharge test...11 3.4 Tan δ measurement...12 3.5 Heating cycle test...13 3.6 Partial discharge test...14 3.7 Impulse test...15 3.8 Voltage test for 15 min...18 3.9 Voltage test for 4 h...19 3.10 Resistivity of semi-conducting screens...20 4 Non-electrical type tests...21 4.1 Measurement of thickness of insulation...21 4.2 Measurement of thickness of non-metal sheaths (including extruded separation sheaths, but excluding inner coverings)...22 4.3 Tests for determining the mechanical properties of insulation before and after ageing...23 4.4 Tests for determining the mechanical properties of non-metallic sheaths before and after ageing...24 4.5 Additional ageing test on pieces of completed cable...25 4.6 Loss of mass test on PVC sheaths of type ST 2...26 4.7 Pressure test at high temperature non-metallic sheaths...27 4.8 Test on PVC separation sheaths at low temperature...28 4.9 Test for resistance of PVC sheaths to cracking (heat shock test)...29 4.10 Hot set test for XLPE insulation...30 4.11 Water absorption test on insulation...31 4.12 Flame spread on single cables...32 4.14 Shrinkage test for XLPE insulation...33 4.15 Strippability test for insulation screen...34

-3- TIC 1580-13 5 Check of cable construction...35 6 Drawing...37 7 Measurement uncertainty...38

-4- TIC 1580-13 1 IDENTIFICATION OF THE OBJECT TESTED 1.1 Ratings/characteristics of the object tested and proved by tests Rated voltage, U 0 /U (U m ) 18/30 (36) kv Rated maximum conductor temperature in normal operation 90 C Rated conductor cross-section 3x500 mm 2 The test voltages were based on U 0 test = 18 kv. 1.2 Description of the object tested Standard IEC 60502-2, Clause 5-14 Manufacturer (as stated by the client) KEC INTERNATIONAL LIMITED, Vadodara, Gujarat, India Type U 0 = 18 kv 3x500 mm 2 XLPE CABLE Manufacturing date 2013 Sampling procedure By the manufacturer Quantity submitted 60 m Rated voltage, U 0 /U (U m ) 18/30 (36) kv Nominal capacitance between conductor 0,303 µf/km and metal screen No. of cores (core identification) 1 Overall diameter 121,4 mm Embossing on the oversheath KEC INTL.LTD. RPG CABLES 18/30(36)kV ELECTRIC CABLE 3x500mm 2 XLPE 2XWY(P) FR 2013 Construction See List of drawings Conductor material Copper cross-section 500 mm 2 nominal diameter 26,8 mm type Stranded compacted maximum conductor temperature in 90 C normal operation presence and nature of measures to achieve longitudinal watertightness no Conductor screen material Semi-conducting compound 33 kv nominal thickness 0,3 mm material designation DYM 515 manufacturer of the material DYM, South Korea

-5- TIC 1580-13 Insulation material Cross linkable compound 66 kv nominal thickness 8,0 mm material designation Dow HFDB 4201 EC manufacturer of the material DOW CHEMICALS Insulation (core) screen material Semi conducting compound 33 kv strippable yes nominal thickness 0,6 mm material designation Pramkor 3005 ES manufacturer of the material Pramkor Metallic screen material Copper tape, 1 layer nominal thickness and width of tape 65 x 0,04 mm Diameter over copper tape screen 45,25 mm Longitudinally watertightness presence and nature of measures to achieve longitudinal watertightness along insulation screen no Inner coverings and fillers material Polypropylene fillers & Polyester tape binder Separation sheath material PVC, type ST 2 nominal thickness 2,5 mm manufacturer of the material YASH POLYMERS Metallic armour material GS round wires number of wires 73 nominal diameter of wires 4 mm cross-sectional area 917 mm 2 manufacturer of the material BEDMUTHA Oversheath material PVC, type ST 2 nominal thickness 4,8 mm nominal overall diameter of the cable (D) 121,42 mm manufacturer of the material YASH POLYMERS colour black graphite coating applied no

-6- TIC 1580-13 Fire retardant (according to IEC 60332-1) no Manufacturing details insulation system location of manufacturing Vadodara, Gujarat, India type of extrusion line CCV type of extrusion Triple extrusion factory identification of extrusion line EPL-50 Maillefer manufacturer of the extrusion line Maillefer, Finland identification of production batch Cable UID no.2946 curing means Dry curing cooling means Dry cured water cooled manufacturing length (where cable sample for testing has been taken from) 200 m length markings on cable sample sent to KEMA begin: 0002 m, end: 0062m 1.3 List of drawings The manufacturer has guaranteed that the object submitted for tests has been manufactured in accordance with the following drawing and/or document. KEMA has verified that this drawing and/or document adequately represents the object tested. The manufacturer is responsible for the correctness of this drawing and/or document and the technical data presented. The following drawing and/or document have been included in this report: Drawing no./document no. Revision XLPE/3 /W / KEMA Rev 0

-7- TIC 1580-13 2 GENERAL INFORMATION The tests were carried out without a representative of the client present. 2.1 The tests were carried out by Name Mr A. Sengers Mr E. Pultrum Company KEMA Nederland B.V., Arnhem, The Netherlands 2.2 Subcontracting The following tests were subcontracted to DNV KEMA New Energy Technology (NET): measurement of resistivity of semi-conducting screens in accordance with Sub clause 18.1.9. non-electrical type tests in accordance with Clause 19. check of cable constructions in accordance with clauses 5-14 of IEC 60502-2. 2.3 Purpose of the tests Purpose of the tests was to verify whether the material complies with the specified requirements. 2.4 Measurement uncertainty A table with measurement uncertainties is enclosed in this report. Unless otherwise stated, the measurement uncertainties of the results presented in this report are as indicated in that table.

-8- TIC 1580-13 3 ELECTRICAL TYPE TESTS 3.1 Test arrangement 3.1.1 Determination of the cable conductor temperature Standard Standard IEC 60840, Annex A, Subclause A.3.1 was used as a guide For the tests at elevated temperature, a reference loop for temperature control of the conductor was installed and conductor current was used for heating. The reference loop was installed close to the test loop in order to create the same environmental conditions, thus the conductor temperature of the reference loop is representative for the conductor temperature of the test loop. IEC 60840, Annex A was used as a guide and IEC 60840, Subclause A.3.1, method 1 was applied. The tests at elevated temperature are carried out two hours after thermal equilibrium has been established.

-9- TIC 1580-13 3.1.2 Photograph of test set-up

-10- TIC 1580-13 3.2 Bending test Standard IEC 60502-2, Subclause 18.1.3 Test date 10 October 2013 Environmental conditions Ambient temperature 12 C Characteristic test data Temperature of test object 12 C Required bending diameter 15(d + D) + 5% Length of cable bended 21 m Actual external diameter of cable D (mm) Actual diameter of conductor d (mm) Required bending diameter D r (mm) Diameter of test cylinder D t (mm) 125,5 26,8 2056 D r 2399 2200 The test was carried out successfully.

-11- TIC 1580-13 3.3 Partial discharge test Standard IEC 60502-2, Subclause 18.1.4 Test date 23 October 2013 Environmental conditions Ambient temperature 21 C Characteristic test data Temperature of test object 21 C Circuit direct Calibration 5 pc Noise level at 1,73 U 0 < 2 pc Sensitivity 4 pc Required sensitivity 5 pc Centre frequency 140 khz Bandwidth 100 khz Test frequency 50 Hz Coupling capacitor 2600 pf Core Voltage applied, 50 Hz Duration Partial discharge level... x U 0 (kv) (s) (pc) red 2 36 10-1,73 31,1 - Not detectable yellow 2 36 10-1,73 31,1 - Not detectable blue 2 36 10-1,73 31,1 - Not detectable Requirement There shall be no detectable discharge exceeding the declared sensitivity from the test object at 1,73 U 0.

-12- TIC 1580-13 3.4 Tan δ measurement Standard IEC 60502-2, Subclause 18.1.5 Test date 29 October 2013 Environmental conditions Ambient temperature 21 C Characteristic test data Temperature of test object 97 C Length of test object 18,93 m Standard capacitor 100 pf Core Voltage applied, 50 Hz Capacitance of core 1) Tan δ (kv) (µf/km) 1, 2 and 3 5 0,399 7,6 x 10-4 1) for information only Requirement The measured value shall not be higher than 40 x 10-4 2 kv.

-13- TIC 1580-13 3.5 Heating cycle test Standard IEC 60502-2, Subclause 18.1.6 Test dates 30 October to 10 November 2013 Environmental conditions Ambient temperature 20 C Characteristic test data Heating method conductor current Stabilized temperature 97 C No. of heating cycles Required steady conductor temperature ( C) Heating current during steady condition (A) Heating cycle Cooling cycle Total duration (h) Duration of conductor at steady temperature (h) Total duration (h) 20 95-100 approx.877 5 2 6

-14- TIC 1580-13 3.6 Partial discharge test Standard IEC 60502-2, Subclause 18.1.4 Test date 11 November 2013 Environmental conditions Ambient temperature 20 C Characteristic test data Temperature of test object 22 C Circuit direct Calibration 5 pc Noise level at 1,73 U 0 < 2,5 pc Sensitivity 5 pc Required sensitivity 5 pc Centre frequency 123 khz Bandwidth 100 khz Test frequency 50 Hz Coupling capacitor 2600 pf Core Voltage applied, 50 Hz Duration Partial discharge level... x U 0 (kv) (s) (pc) red 2 36 10-1,73 31,1 - Not detectable yellow 2 36 10-1,73 31,1 - Not detectable blue 2 36 10-1,73 31,1 - Not detectable Requirement There shall be no detectable discharge exceeding the declared sensitivity from the test object at 1,73 U 0.

-15- TIC 1580-13 3.7 Impulse test Standard IEC 60502-2, Subclause 18.1.7 Test date 14 November 2013 Environmental conditions Ambient temperature 20 C Characteristic test data Temperature of test object 97 C Specified test voltage 170 kv Testing arrangement Polarity Voltage applied No. of impulses See figure on next pages Voltage applied to Earthed (% of test voltage) Conductors of all Metal Positive 50 1 1 (waveshape) three cores screens 65 1 2 80 1 2 100 10 3 and 4 Conductors of all Metal Negative 50 1 5 (waveshape) three cores screens 65 1 6 80 1 6 100 10 7 and 8 Requirement Each core of the cable shall withstand without failure 10 positive and 10 negative voltage impulses.

-16- TIC 1580-13 Lightning impulse test with positive voltage

-17- TIC 1580-13 Lightning impulse test with negative voltage

-18- TIC 1580-13 3.8 Voltage test for 15 min Standard IEC 60502-2, Subclause 18.1.7 Test date 15 November 2013 Environmental conditions Ambient temperature 20 C Characteristic test data Temperature of test object 20 C Testing arrangement Voltage applied, 50 Hz Duration Voltage applied to Earth connected to x U 0 (kv) (min) Conductors Metal screens 3,5 63 15 Requirement No breakdown of the insulation shall occur.

-19- TIC 1580-13 3.9 Voltage test for 4 h Standard IEC 60502-2, Subclause 18.1.8 Test date 15 November 2013 Environmental conditions Ambient temperature 20 C Characteristic test data Temperature of test object 20 C Testing arrangement Voltage applied, 50 Hz Duration Voltage applied to Earth connected to x U 0 (kv) (h) Conductors Metal screens 4 72 4 Requirement No breakdown of the insulation shall occur.

-20- TIC 1580-13 3.10 Resistivity of semi-conducting screens Standard IEC 60502-2, Subclause 18.1.9 Test date 21 November 2013 Characteristic test data Temperature during ageing 100 C Duration 7 days Resistivity measured at 90 ± 2 C Item Unit Requirement Measured/determined Red Yellow Blue Conductor screen without ageing Ωm 1000 0,44 0,32 0,49 after ageing Ωm 1000 1,07 0,88 0,68 Insulation screen without ageing Ωm 500 14,20 13,79 11,95 after ageing Ωm 500 38,64 28,37 40,08

-21- TIC 1580-13 4 NON-ELECTRICAL TYPE TESTS 4.1 Measurement of thickness of insulation Standard IEC 60502-2, Subclause 19.1 Test date 19 November Item Unit Requirement Specified Measured/determined Red Yellow Blue Nominal mm - 8,00 - - - Average mm - - 8,09 8,09 8,18 Minimum [t min ] mm 7,10 7,10 7,85 7,85 8,06 Maximum [t max ] mm - - 8,48 8,38 8,34 (t max t min ) / t max - 0,15-0,07 0,06 0,03

-22- TIC 1580-13 4.2 Measurement of thickness of non-metal sheaths (including extruded separation sheaths, but excluding inner coverings) Standard IEC 60502-2, Subclause 19.2 Test date 8 November 2013 Separation sheath thickness Thickness Unit Requirement Specified Measured/determined Nominal mm 1,2 2,50 - Average mm - - 3,28 Minimum mm 1,80-2,76 Oversheath thickness Thickness Unit Requirement Specified Measured/determined Nominal mm 1,80 4,80 - Average mm - - 6,74 Minimum mm 3,64 3,64 6,02

-23- TIC 1580-13 4.3 Tests for determining the mechanical properties of insulation before and after ageing Standard IEC 60502-2, Subclause 19.3 Test dates 8 to 15 November 2013 Characteristic test data Temperature during aging 135 ± 3 C Ageing duration 7 days Item Unit Requirement Measured/determined Red Yellow Blue Without ageing Tensile strength N/mm 2 12,5 33,9 34,1 33,6 Elongation at break % 200 652 716 609 After ageing in air oven Tensile strength value after ageing N/mm 2-32,9 30,5 31,9 variation % ± 25 max. -3-11 -5 Elongation at break value after ageing % - 610 599 631 variation % ± 25 max. -6-16 4

-24- TIC 1580-13 4.4 Tests for determining the mechanical properties of non-metallic sheaths before and after ageing Standard IEC 60502-2, Subclause 19.4 Test dates 8 to 15 November 2013 Characteristic test data Temperature during aging 100 ± 2 C Ageing duration 7 days Separation sheath Item Unit Requirement Measured/determined Without ageing Tensile strength N/mm 2 12,5 17,0 Elongation at break % 150 172 After ageing in air oven Tensile strength value after ageing N/mm 2 12,5 18,4 variation % ± 25 max. 9 Elongation at break value after ageing % 150 180 variation % ± 25 max. 5 Oversheath Item Unit Requirement Measured/determined Without ageing Tensile strength N/mm 2 12,5 18,0 Elongation at break % 150 157 After ageing in air oven Tensile strength value after ageing N/mm 2 12,5 17,9 variation % ± 25 max. -0 Elongation at break value after ageing % 150 155 variation % ± 25 max. -2

-25- TIC 1580-13 4.5 Additional ageing test on pieces of completed cable Standard IEC 60502-2, Subclause 19.5 Test dates 8 to 15 November 2013 Characteristic test data Temperature during aging 100 ± 2 C Ageing duration 7 days Insulation Item Unit Requirement Measured/determined Red Yellow Blue Tensile strength value after ageing N/mm 2-31,9 31,9 32,4 variation % ± 25 max. -6-7 -4 Elongation at break value after ageing % - 655 611 651 variation % ± 25 max. 1-15 7 Separation sheath Item Unit Requirement Measured/determined Tensile strength value after ageing N/mm 2 12,5 16,9 variation % ± 25 max. 0 Elongation at break value after ageing % 150 209 variation % ± 25 max. 22 Oversheath Item Unit Requirement Measured/determined Tensile strength value after ageing N/mm 2 12,5 18,9 variation % ± 25 max. 5 Elongation at break value after ageing % 150 167 variation % ± 25 max. 6

-26- TIC 1580-13 4.6 Loss of mass test on PVC sheaths of type ST 2 Standard IEC 60502-2, Subclause 19.6 Test dates 1 to 8 November 2013 Characteristic test data Temperature treatment 100 ± 2 C Duration 7 days Separation sheath Item Unit Requirement Measured/determined Loss of mass mg/cm 2 1,5 1,0 Oversheath Item Unit Requirement Measured/determined Loss of mass mg/cm 2 1,5 0,5

-27- TIC 1580-13 4.7 Pressure test at high temperature non-metallic sheaths Standard IEC 60502-2, Subclause 19.7 Test dates 11 and 12 November 2013 Characteristic test data sheaths PVC ST 2 Temperature 90 ± 2 C Heating time 6 hours Load 17,6 N Separation sheath Item Unit Requirement Measured/determined Depth of Indentation % 50 24,8 Characteristic test data sheaths PE ST 2 Temperature 90 ± 2 C Heating time 6 hours Load 28,2 N Oversheath Item Unit Requirement Measured/determined Depth of indentation % 50 16,7

-28- TIC 1580-13 4.8 Test on PVC separation sheaths at low temperature Standard IEC 60502-2, Subclause 19.8 Test dates 11 to 19 November 2013 Characteristic test data PVC ST 2 Temperature -15 ± 2 C Cooling time Mass of hammer 16 h 1500 g Inner sheath/ separation sheath Item Unit Requirement Measured/determined Cold elongation test % 20 90 Cold impact test - No cracks No cracks

-29- TIC 1580-13 4.9 Test for resistance of PVC sheaths to cracking (heat shock test) Standard IEC 60502-2, Subclause 19.9 Test date 7 November 2013 Characteristic test data Temperature 150 ± 3 C Duration 1 h Diameter of mandrel 8 mm Number of turns 4 Inner sheath/separation sheath Item Unit Requirement Measured/determined Visual examination - No cracks No cracks Characteristic test data Temperature 150 ± 3 C Duration 1 h Diameter of mandrel 10 mm Number of turns 2 Oversheath Item Unit Requirement Measured/determined Visual examination - No cracks No cracks

-30- TIC 1580-13 4.10 Hot set test for XLPE insulation Standard IEC 60502-2, Subclause 19.11 Test date 5 November 2013 Characteristic test data Air temperature 200 ± 3 C Time under load 15 min Mechanical stress 20 N/cm 2 Insulation Item Unit Requirement Measured/determined Red Yellow Blue Elongation under load % 175 49 58 54 Permanent elongation after cooling % 15-1 -3-3

-31- TIC 1580-13 4.11 Water absorption test on insulation Standard IEC 60502-2, Subclause 19.13 Test dates 4 to 22 November 2013 Characteristic test data XLPE Temperature of water 85 ± 2 C Duration 336 h Test method Gravimetric Insulation Item Unit Requirement Measured/determined Core red Core yellow Core blue Increase of mass mg/cm 2 1 0,01 0,03 0,01 The object passed the test

-32- TIC 1580-13 4.12 Flame spread on single cables Standard IEC 60502-2, Subclause 19.14 Test date 11 November 2013 Characteristic test data Overall diameter of test piece Time for flame application Flame type 124,84 mm 480 s 1 kw pre-mixed flame Complete cable Unit Requirement Measured/determined The distance between the lower mm 50 352 edge of the top support and the onset of charring The distance between the lower edge of the top support and charring extends downwards to a point mm 540 503

-33- TIC 1580-13 4.14 Shrinkage test for XLPE insulation Standard IEC 60502-2, Subclause 19.16 Test date 5 November 2013 Characteristic test data Temperature 130 ± 3 C Duration 1 h Distance between marks 200 mm Insulation Item Unit Requirement Measured/determined Red Yellow Blue Shrinkage % 4 1,8 1,6 1,6

-34- TIC 1580-13 4.15 Strippability test for insulation screen Standard IEC 60502-2, Subclause 19.21 Test date 18 November 2013 Item Unit Requirement Measured Red Yellow Blue Before ageing N 4 F 45 32 25 28 22 27 29 22 23 24 After ageing N 4 F 45 15 13 11 12 11 10 10 11 9 The object passed the test

-35- TIC 1580-13 5 CHECK OF CABLE CONSTRUCTION Standard IEC 60502-2, Subclause 5-14 Test dates 1 to 8 November 2013 Item Unit Requirement Specified Measured/determined Core red Core yellow Core blue Conductor Diameter of mm 25,3 d 27,6 26,80 26,50 26,50 26,48 conductor (d) Number of wires - 53-55 55 55 Diameter of wires mm - - 3,23 3,19 3,22 Resistance at 20 C Ω/km 0,0366-0,03648 0,03659 0,03650 Conductor screen Diameter over mm - - 27,58 27,45 27,46 conductor screen Thickness mm 0,3-0,53 0,45 0,42 Insulation Diameter over mm - - 43,94 43,77 43,92 insulation Thickness mm 7,10 8,0 8,09 8,09 8,18 Insulation screen Diameter over mm - - 45,84 45,84 45,84 insulation screen Thickness mm 0,6-0,65 0,63 0,72 Metallic screen Overlap % - 10 17 15 19 Thickness x width of tape Fillers Inner/separation sheath Diameter over innersheath mm - 65 x 0,04 64,43 x 0,05 64,30 x 0,04 64,01 x 0,04 Polypropylene fillers & polyester tape binder mm - - 97,77 Thickness mm - 2,50 3,275 Metallic armour Number of wires - - 73 73 Diameter mm - 4,00 3,91 Tape Thickness x width of tape mm - 61,90 x 0,10 overlap % - 40 Number of layers - 3

-36- TIC 1580-13 Item Unit Requirement Specified Measured/determined Oversheath Diameter over mm - 121,42 124,84 oversheath Thickness mm - 4,80 6,74 Colour - - black black Embossing on the cable KEC INTL LTD RPG CABLES 18/30(36)kV ELECTRIC CABLE 3x500mm2 XLPE 2XWY(P) FR 2013

-37- TIC 1580-13 6 DRAWING

-38- TIC 1580-13 7 MEASUREMENT UNCERTAINTY The measurement uncertainties in the results presented are as specified below unless otherwise indicated. Measurement Measurement uncertainty Dielectric tests and impulse current tests: peak value 3% time parameters 10% Capacitance measurement 0,3% Tan δ measurement ± 0,5% ± 5 x 10-5 Partial discharge measurement: < 10 pc 2 pc 10 to 100 pc 5 pc > 100 pc 20% Measurement of impedance AC-resistance measurement 1% Measurement of losses 1% Measurement of insulation resistance 10% Measurement of DC resistance: 1 to 5 µω 1% 5 to 10 µω 0,5% 10 to 200 µω 0,2% Radio interference test 2 db Calibration of current transformers 2,2 x 10-4 I i /I u and 290 µrad Calibration of voltage transformers 1,6 x 10-4 U i /U u and 510 µrad Measurement of conductivity 5% Measurement of temperature: -50 to -40 C 3 K -40 to125 C 2 K 125 to 150 C 3 K Tensile test 1% Sound level measurement type 1 meter as per IEC 60651 and ANSI S1,4,1971 Measurement of voltage ratio 0,1%