Variation in SFRA plot due to design and external parameter

Similar documents
Chapter 7 Conclusion 7.1 General

Benefits of SFRA - Case Studies

Matz Ohlen Director Transformer Test Systems. Megger Sweden

Vallabh Vidyanagar, Anand, INDIA

Importance of Transformer Demagnetization

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

INTERPRETATION METHODOLOGY TO IDENTIFY FAULT LOCATION IN A POWER TRANSFORMER

OMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

Investigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA)

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

FRAX Series Sweep Frequency Response Analyzers

Operational Management of Grid Transformers An Experience of POWERGRID

Transformers handling and transport

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

Performing reliable and reproducible frequency response measurements on power transformers

Demagnetization of Power Transformers Following a DC Resistance Testing

Mitigating Murphy s Law While Test. Frédéric Dollinger

FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC.

Field Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Power Factor Insulation Diagnosis: Demystifying Standard Practices

Problems connected with Commissioning of Power Transformers

Specialists in HV and MV test and diagnostics. Testing in Substations

Fault Detection in Transformer Using Frequency (Sweep) Response Analysis

REPORT ON INVESTIGATION OF FAILURE OF 100 MVA, 220/66-33/11 KV POWER TRANSFORMER AT 220KV GEETA COLONY SUBSTATION OF DELHI TRANSCO LTD.

Commissioning Manual Distribution Transformers - Three-phase Oil Filled

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope

Basic Principles and Operation of Transformer

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

FRAX Series Sweep Frequency Response Analyzers

TECHNIQUES AND STANDARD

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

PRODUCT PORTFOLIO TEST AND MEASURING SYSTEMS

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy

FAULT IDENTIFICATION IN TRANSFORMER WINDING

IVE(TY) Department of Engineering. Electrical Machines 1. Electrical Machines 1. Hour 13. slide 1

Power Measurements and Basic Electrical Diagnostic Tests

MEDIUM & HIGH VOLTAGE

Testing and Diagnostic of Power Transformers & Distribution Transformers

Advanced Diagnostic Testing Services. Provides detailed and reliable results

PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics

CDAX 605 High Precision Capacitance & Dissipation Factor Test Set

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

Power Transformer Condition Assessment Based on Standard Diagnosis

EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY

ISSN: [IDSTM-18] Impact Factor: 5.164

PARTIAL DISCHARGE MEASUREMENT

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

148 Electric Machines

Circuit design for reproducible on-site measurements of transfer function on large power transformers using the SFRA method

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Test description for dry-type transformers chapter for special tests

PCTS Series. Power Capacitor Test System. Applications: Testing Applications: Benefit and Advantage: and IEC

Diagnostic testing of cast resin transformers

Substation Preventive Maintenance

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

Differential Protection with REF 542plus Feeder Terminal

Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K

HOW TO SAFE GUARD THE TRANSFORMER..???

Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Hands-On Transformer Testing and Maintenance

Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL)

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

متلب سایت MatlabSite.com

Xu Xiao Ming, AP Services, March 2010 Machine services Life expectance analysis program (LEAP)

Module 7. Transformer. Version 2 EE IIT, Kharagpur

Form-IV. Form of Inspection/Test Report. (Under Regulation 43)

Transformer Protection

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

Effective maintenance test techniques for power transformers

CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES

The importance of partial discharge testing throughout the development and operation of power transformers

Federal Power Transformers LLC based in Abu Dhabi, UAE

NETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT

86 chapter 2 Transformers

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

Transformer Factory Testing

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad ELECTRICAL AND ELECTRONICS ENGINEERING

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

Be on guard for effective testing: Introduction

Transformer condition assessment with an integrated test van

Correlation between time and frequency domain polarisation measurements for transformer moisture assessment

PD Diagnostic Applications and TechImp solutions

Martin Stoessl R&D Manager Siemens Transformers Austria - Weiz

EASUN REYROLLE LIMITED

Transcription:

Chapter 6 Variation in SFRA plot due to design and external parameter 6.1 Introduction As the experience grows with Sweep Frequency Response Analysis in world, it is useful to discuss the measurements and results in context of the practical application where SFRA has been used for decision support. It is important to highlights the various aspects of SFRA plot variation due to design and external parameters. By understanding these points, it will be easy to understand the good practice in taking measurements and making conclusions which is supported by evidence from other test data also. SFRA is now accepted, as part of routine test for new transformer at manufacturer place and as a post-fault investigation test for aged transformer. It is observed that although the detailed form of a frequency response depends on the winding design used, usually the basic overall form of the response is surprisingly similar for the same type of winding, even for significantly different winding arrangements, and therefore is presumably determined by some essential distinguishing property of the type of winding involved, rather than the details of its construction. The method of interconnection used, e.g. LV delta connection, also results in very characteristic forms. This chapter discusses SFRA data from several cases in the field in context of variation in plots which is not due to fault in transformer, along with discussion of results and lessons learned. 102

CHAPTER6 Variation in SFRA Plot... External Parameter 103 6.2 Effect of Oil-Comparision of SFRA plot for Sister unit with full and partially filled oil Two nos. of single phase transformer were tested for SFRA and they were sister units with following details. 132 kv/ 33 kv, 25 MVA Power Transformer ON LOAD Tap changer Winding configuration - HV/LV Year of manufacturing - 2006 Serial No.: T-l (With Full oil) and T-2 (Partially filled oil) Figure 6.1: Open circuit SFRA plot of HV winding for both the sister unit (with oil-red color) When SFRA measurement were carried out with full oil in tank, the relative permittivity from air to oil (e,. = 2.2) increases the overall capacitance of transformer and shifted the resonant frequency to lower frequency for full oil filled transformer as shown in Figure 6.1 and Figure 6.2. The overall trends of SFRA variation corresponds well for the SFRA plot of with oil and without oil measurement. The identical low frequency region of SC plot (Figure 6.1) indicate that effect of capacitance is null and it is dominated by resistive and inductive parameter of the winding.

CHAPTERS Variation in SFRA Plot... External Parameter 104 Figure 6.2: Short circuit SFRA plot of HV winding for both the sister unit (with oil- Green color) The inter winding plot is shown in Figure 6.3, which is mainly capacitive in nature at low frequency due to the fact that circuit element of transformer which act is the intertwining capacitance of insulation mainly. 6.3 Variation in SFRA due to Residual Moisture of Winding The effect of excessive moisture content, on the SFRA signatures, is identified by a practical example of the application of SFRA to 17 years old, 16MVA transformer which was having high moisture content [56]. No maintenance was carried out on the transformer since it was commissioned. No history available with the customer. However, major observations made in visual inspection were: Leakages at various points on tank body. Breather completely pink. Huge water logging below the transformer, this gave an idea that transformer was

CHAPTERS Variation in SFRA Plot... External Parameter 105 Figure 6.3: Inter winding SFRA plot of HV-LV winding for both the sister unit (with oil- Red color)

CHAPTERS Variation in SFRA Plot... External Parameter 106 exposed to moisture as indicated in the Figure 6.4 below. Figure 6.4: Water accumulation at the base of transformer All the low voltage routine tests were carried out to verify the electrical parameters. Observationsa: 1. Ta.n delta values too high (> 3.8 percent ) indicating high moisture content. 2. Polarization Index was low (< 1.1 percent) indicating, high moisture content. 3. Moisture content of oil was too high (73 ppm) 4. SFRA was conducted to determine mechanical integrity of transformer. In absence of reference signature, phase to phase comparisons were made as seen in Figure 6.5. " Phase to phase comparison showed good correlation indicating that transformer is mechanically intact. Recommendations Based on visual inspection and the results of off -line tests recommendations given were: 1. To arrest oil leakages. 2. To replace gaskets. 3. To dry out transformer.

CHAPTERS Variation in SFRA Plot... External Parameter 107 For drying out transformer on-site, Low Frequency Heating system was preferred. Around 17 liters of water was removed from the transformer during the application of Low' frequency heating( LFH.) 3:0k/ Fr ftqu&iicyf' Hz '. ::i0.al< Figure 6.5: Comparison of three phase Open circuit Base SFRA plot before drying out After the drying out the three phase SFRA plot were compared and it was identical as shown in Figure 6.6. However, when the SFRA plot before and after drying out was compared, above first resonance, frequency shift in the Plot is observed as shown in Figure 6.7. Variation is mainly due to change in effective capacitance of the transformer circuit [5]. As the resonant peak frequencies has increased for the SFRA plot after drying out, the effective capacitance must have decreased. Since the geometrical parameters of the transformers were unchanged, change in effective capacitance is mainly due to change in moisture content as explained below. Notations: Before LFH drying out, Fn Ref resonant freq Ci = Effective capacitance Li = Effective inductance

CHAPTER6 Variation in SFRA Plot... External Parameter 108 Table 6.1: Improvement in the parameters of transformer after drying out process. Before LFH After LFH BDV 3.4 68 Water content of oil (ppm) 73 10 tan S of oil 0.0237 0.00015 % tan S of winding HV-LV 3.350 0.722 HV-GND 2.699 0.886 LV-GND. 3,854 0.654 HV-LV+GND 3.839 0.789 Capcitance in pf HV-LV 3887.38 3583.23 HV-GND 2960.41 2785.03 LV-GND 6939.32 6419.69 HV-LV+GND 6849.41 6369.1 Insulation Resistance (in M ohms) (in G ohms) 60 Sec HV-LV 57.5 4.07 HV-LV+Earth 47.8 3.89 LV-HV+Earth 40.0 2.38 Insulation Resistance (in M ohms) (in G ohms) 10 min HV-LV 61.5 6.6 HV-LV+Earth 49.8 4.78 LV-HV+Earth 42.0 3.68 PI HV-LV 1.07. 1.6 HV-LV+Earth 1.04 1.23 LV-HV+Earth 1.05 1.55

CHAPTER6 Variation in SFRA Plot... External Parameter 109 '8043. lies? Jp. frequency,. Hz Figure 6.6: Comparison of three phase Open circuit Base SERA plot after drying out After LFH drying out, FT2 = New resonant freq C'2 = Effective capacitance. L2 = Effective inductance Fri = 13AlkHz and Frt 13.86kHz (from Figure 6.7). General formula for resonant frequency Fr (----i=l \2tvs/LC) For two different cases, i.e. before and after LFH as indicated in Figure6.7. (_J-- \2tT yjlici (6.1) ±r2 \2itVLW2) (6.2) Dividing equation (8.1) by equation (8.2) En. = G-vOo) Fr2 (wes) (6.3)

CHAPTER6 Variation in SFRA Plot.., External Parameter 110 -.17,69' OFF ficqvcncy! iz\ ; g^ann^girai 11> iiia Figure 6.7: Expanded view of Comparison of per phase Open circuit SFRA plot before and after drying oitt As the geometrical parameters are unchanged and no shift is observed in the low freq region of SFRA plots, it is assumed that there is no effect, of LFH process on the inductance of the circuit. Therefore, L\ 7,2 (6.4) Applying equation (8.4) in equation (8.3) i.e.. Ci ; Putting values of Fri and Fra (From Figure 6.7) in equation (8.5) t = IS -9361 (6.5) (6.6)

CHAPTER6 Variation in SFRA Plot... External Parameter 111 This means, ratio of the effective capacitances after LFH and before LFH is 0.9361. In order to verify this, capacitance values obtained during C and tan 5 test were compared. C'2 = 6369.1 pf and C[ = 6849.41 pf. Where, C[ = capacitance between HV-LV+GND before LFH C2 = capacitance between HV-LV+GND after LFH 7 = = -9298 (measured) (6.7) As seen from equation (8.6) and equation (6.7) The ratio of capacitances derived (0.9361) from SFRA signature is almost equal to the ratio of capacitances obtained (0.9298) by capacitance measurement. Analysis: 1. Since the geometrical parameters are unchanged, change in capacitance is possible only with change in relative permittivity as C e0era/d (the only variable term is relative permittivity). 2. After application of LFH drying out, it removed excessive moisture which caused relative permittivity to reduce. 3. Therefore, capacitance value has gone down which infact shifted the SFRA signature towards right as Fr = (1/2?x\/LC). 4. The effect of change in moisture content on SFRA plot is due to change in effective capacitance (relative permittivity). 6.4 Variation in SFRA plot due to Residual Magnetism of the Core Residual magnetization within the core must be identified and should not be mis-interpreted. Residual magnetization is caused by a section of core steal holding on the magnetic polarity due to an applied DC bias. DC winding resistance testing, DC insulation test, switching operations, and geomagnetic phenomena are source of residual magnetism. Residual magnetization can be identified by the shifting of the low frequency core resonance (zero)

CHAPTER6 Variation in SFRA Plot... External Parameter 112 to the right from demagnetized results. Residual magnetization can be removed by demagnetizing the core, and should be conducted if there is concern about the condition of the core. SFRA test conducted on a transformer before and after the short circuit test. The details of the transformer is mentioned below. Details of Power Transformer (1 Nos.) Transformer Mfg. year.: - 2006 Rating: - 145/66/33kV, 50MVA (Star/star) Total Nos. of Taps: 17 (3 Normal) 3-Ph Transformer SFRA data was analyzed for the above mentioned new transformer manufactured in 2006, which was subjected to the short circuit test as part of type test. There was variation in the open circuit plots before and after short circuit test in each phase as shown in the Figure 6.8, Figure 6.9 and Figure 6.10. Short circuit SFRA plots are identical before and after the Short circuit test as shown in Figure 6.13, Figure 6.14 and Figure 6.15. Transformer has passed the short circuit test and all the routine test before and after the Short circuit test was within acceptable limit as per standard. In case of Open circuit SFRA plot, above 2kHz all open circuit SFRA measurements before and after the Short circuit test are identical i.e. no sign of any winding movement as indicated in Figure 6.8,Figure 6.9 and ifigure 6.10. For HV responses measured with the LV s shorted there is no difference at lower frequencies either before and after Short circuit test, hence HV winding is intact Figure 6.13, Figure 6.14 and Figure 6.15after the Short circuit type test at high power lab. Observation and Possible Causes of Low Frequency Response Variation in case of open circuit SFRA plots: Below about 2kHz the open circuit HV and LV SFRA measurements show differences before and after the Short circuit test which can be due to core degradation or residual magnetism. To trace the reason, the test data related to core issue like no load magnetization current and magnetic balance test before and after Short circuit, test were evaluated and shown in Table 6.2. When energizing on V phase the balance of induced voltages on the outer phases is

CHAPTER6 Variation in SFRA Plot... External Parameter 113 Figure 6.8: Open circuit HV U phase- winding plot before and after short circuit test Figure 6.9: Open circuit HV V phase- winding plot before and after short circuit test Figure 6.10: Open circuit HV W phase- winding plot before and after short circuit test

CHAPTERS Variation in SFRA Plot... External Parameter 114 Figure 6.11: Open circuit HV winding plot before short circuit, test Figure 6.12: Open circuit HV winding plot after short circuit test slightly better after the Short circuit test. The observation is same with respect to the SFRA plot near the core resonance of 700Hz when we compare the three phase plot in Figure 6.11 and Figure 6.12 and Short circuit test it appears that the trace has renormalised what was a slightly unbalanced pattern of remanent magnetism before the test. Obviously SFRA measurements at low frequencies and magnetic balance measurements will both be affected by remanent magnetism. The magnetic balance test shows a slight change in the voltage measured across the U- and W limb when energising on V, before and after the Short circuit test shown in Table above. Hence, in this case, the variation in SFRA plot below 2kHz is only to be expected due to change in the residual magnetism of the core during short circuit test.

CHAPTERS Variation in SFRA Plot... External Parameter 115 Figure 6.13: Short circuit HV U phase- winding plot before and after short circuit test.. -45 -) Figure 6.14: Short circuit HV V phase- winding plot before and after short circuit test Figure 6.15: Short circuit HV W phase- winding plot before and after short circuit test

CHAPTERS Variation in SERA Plot... External Parameter 116 Table 6.2: Magnetic Balance Before and After short circuit test: Applied Condition of Measured terminal voltage (V) Terminals Transformer 1U-1N 1V-1N 1W-1N 1U-1N Before SC test 230.6 210.7 20.72 1U-1N After SC test 230.8 213.7 17.52 1V-1N Before SC test 123.2 231.1 108.0 1V-1N After SC test 117.7 231.0 113.8 1W-1N Before SC test 20.89 210.9 231.6 1W-1N After SC test 21.71 210.3 231.1 6.5 Variation in Contact Resistance and Earth Resistance 50 MVAR reactor of following details was repaired on site by manufacturer after fault and commissioned on 15.02.2007. The reactor is connected to 400 kv line circuit. The line tripped on 27.07.2007 due to operation of reactor back up protection. The line was charged after withdrawing reactor out of service and the reactor was tested on 28.07.07 for SFRA plot after fault. Reactor Details: 400 kv, 50 MVAR, 3 phase reactor Winding configuration: Star Year of manufacturing: 1989 Test data analysis: Two sets of SFRA plot data was there for analysis, base plot taken on 14.02.07 and post fault data on 28.07.07 Observation: There is a variation in the SFRA plot of individual phases when compared with the previous base plot at high frequency and observations are as follows: The SFRA plot taken on 28.07.07 has high lead resistance characteristics for all the three phases from frequency range 1.6MHzto'lMHz and compared with the plot taken on

CHAPTERS Variation in SFRA Plot... External Parameter 117 14.02.07 as shown in Figure 6.16,Figure 6.17 and Figure 6.18. This variation can happen in SFRA test due to change in contact resistance of measurement set up or variation in earth resistance of the test setup, since it is observed in all the phases. Otherwise, the pattern of resonance in each phase is matching with the base plot which indicate no mechanical deformation of the winding due to change in its overall capacitance or inductance. Conclusion: In summary, the SFRA plot test result, of reactor is not indicating any sign of mechanical damage. Variation in the frequency region from 1.6MHzto2MHz is attributed to the difference in test condition and test set up. But this statement is not generalized for whole frequency range and variation of such magnitude at low frequency below 1 khz need to be investigated always, which is not the case here. Figure 6.16: Comparision of Base and Post fault R-phase SFRA plot for reactor

CHAPTERS Variation in SFRA Plot... External Parameter 118 Figure 6.17: Comparision of Base and Post fault Y-phase SFRA plot for reactor 6.6 Effect on SFRA plot due to Electrical Interfrence in Substation Noise can be defined as unwanted disturbances that may be superimposed upon a useful (desired) signal. Noise tends to obscure the information content of the useful signal and for this reason its detection and mitigation is imperative. As in any other electrical diagnostic method, the SFRA results can also be affected by noise. An understanding of the sources of noise, their effects and suppression methods is very important. In a substation environment the noise can be found basically in two forms, i.e., as a wideband or as narrowband noise. A typical narrowband noise is the power frequency noise (JjOorWHz noise). At frequencies higher than300if;s is it very unusual to find narrowband noise. In substations with high harmonic pollution some narrowband noise at frequencies multiple of the power frequency could also be present. Other possible source of narrowband noise could be some communication signals in the substation, or noise generated by corona discharges, but these sources are in higher frequencies and are very hardly found in the SFRA plots. With respect to wideband noise, there will be always a noise floor that will affect the SFRA plots. The presence of

CHAPTER6 Variation in SFRA Plot... External Parameter 119 Figure 6.18: Comparison of Base and Post fault B-phase SFRA plot for reactor tlois noise is very close related to the dynamic range of the SFRA measuring instrument as indicated in Figure 6.19. One no. of Three phase Auto transformer was tested for base SFRA data having following details. 220/132/11 kv, 150 MVA, 3 phase Auto transformer Winding configuration: Star/Star Year of manufacturing: 1994 Test data analysis: Base SFRA plot was analyzed and it is observed that there is interference signal picked up in open circuit plot as shown in figure6.20. at 50Hz. due to high level of interference in substation. The same is absent in Short circuit plot as the output signal in much better in SC test as shown in figure6.21. Open circuit and Short circuit plots are the good SFRA base plot for this transformer for future comparison.

CHAPTER6 Variation in SFRA Plot... External Parameter 120 Figure 6.19: Characterisation of noise sources in a typical FRA plot Figure 6.20: Comparison of three phase Open circuit Base SFRA plot

CHAPTER6 Variation in SFRA Plot... External Parameter 121 Figure 6.21: Comparison of three phase Short circuit Base SFRA plot