DATASHEET Configurable Inputs and Outputs Wide choice of communications options EziForth Programmable Internet Ready Comms options SD Card Logging Low power operation FEATURES Inputs and/or Outputs (Analog or Digital) 9 0V dc powered. SD Memory Card Slot for offline data logging. Onboard temperature sensor and voltage monitor Low Power operation Integral RealTime Clock with Battery Backup Programmable for a wide range of applications. Wide operating temperature range Compact size for tight spaces Convenient DIN Rail mounting OVERVIEW The TELETERM M series is a stateoftheart RTU range designed to expand the possibilities of remote monitoring and control by providing a cost effective platform with a wide range of features. Communications options include GSM, G UMTS (NextG Australia), CDMA, licencefree Radio in a number frequency bands, Conet Industrial LAN for use over existing plant cabling, and RS and RS85 serial. The TELETERM M comes with universal I/O that can be configured for analogue or digital input or output according to your needs. The on board RS/85 port can be used to acquire data from other third party devices using either the Modbus protocol, or by downloading a custom software protocol plugin. This feature allows a wide variety of third party devices to be supported. The low power consumption of the the Teleterm M makes it suitable for use in solar powered and battery powered applications. The Teleterm M series can be programmed in the EziFORTH programming language, providing the ability to do local control, and custom logic. The Teleterm M also incorporates an SD memory card slot to support local data logging. Typical applications for the M include: Energy Management and Remote Meter Reading. Environmental Monitoring Remote Site Monitoring Utilities monitoring Remote inventory monitoring Traffic Management Remote Digital Advertising Sign management Transport/Cargo Monitoring Vending machines Stay in touch Take control with the Teleterm M Series from Omniflex. Datasheet DSC60BR5 sheet of 8
General Layout Mechanical Dimensions 09,5 Height including serial cable 55 5,5 6,5 7,5 5 5 89,5 Datasheet DSC60BR5 sheet of 8
Communication Functions by Model Product Name M Order Code C60B0 Notes I/O RS/ RS85 GSM/ EGSM/ GPRS G UMTS Conet.GHz 6mW Radio 90MHz868MHz 00mW5mW Radio Radio 90MHz W Radio x RS x RS/ RS85 MG C60B MG C60B MC C60B MR C60B, MR C60B,5 MR C60B,6 MR C60B,7 MS C60B NOTES:. The EGSM/GPRS port is a quad band device operating on 900/800/850/900MHz. This is suitable for use on most countries GSM networks. Consult the factory for specific compatibility with your network.. The G UMTS port is a tri band device operating on 850/900/00MHz. This interface is specifically approved for use on the Australian Telstra NextG network.. The MR version is available in a number radio band options to comply with different country regulations. Please ensure that the correct unit is specified for your application...ghz Band is suitable for use all countries. 5. 90MHz Band is suitable for use in USA, Australia and New Zealand. The MR version has fixed output power of 00mW. This version is not recommended for new installations. This model has been replaced with the MR. 6. 868MHz Band is suitable for use in Europe, and Southern Africa. 7. 90MHz Band is suitable for use in USA, Australia and New Zealand. The MR version has presettable output power of mw to W. The MR is NOT compatible with MR installations. Datasheet DSC60BR5 sheet of 8
Input/Output Configurable Options The MG is equipped with versatile input/output points (I/O points or IOP s). Each I/O point can be individually configured from the options given in the following table: I/O Point Terminal No. Digital Input Analogue Input Digital Output Analogue Output 5 Yes 00Vdc Yes 6 Yes 00Vdc Yes 7 Yes 05Vdc Yes 8 Yes 05Vdc Yes 5 9 Yes 05Vdc Yes 6 0 Yes 05Vdc Yes 7 Yes 05Vdc Yes 8 Yes 05Vdc Yes 9 Yes 05Vdc Yes 0 Yes 05Vdc Yes 5 Yes 00Vdc 0/0mA 6 Yes 00Vdc 0/0mA Note : See the Specifications section of this document for detailed specifications of each I/O point option. Note : All 00V analogue inputs have increased resolution over the range 06V (equivalent to the 05V inputs). Note : All Digital Inputs can be configured as Pulse Counters or Hours Counter. Note : All Digital Outputs can be configured as Pulse outputs (normally ON or normally OFF). 90Vdc Supply 90Vdc Supply n V 0V n V 0V V 90Vdc Supply IOP IOP DIGITAL INPUTS IOP IOP 0 DIGITAL OUTPUTS 90Vdc Supply V 0V V 0V 05/0V 0mA n n V IOP IOP ANALOGUE INPUTS IOP IOP ANALOGUE OUTPUTS Datasheet DSC60BR5 sheet of 8
SPECIFICATIONS COMMON TO ALL MODELS Input/Outputs All M RTU s have Input/Output Points (IOP configurable in software as analogue or digital, inputs or outputs. (See the table above for a matrix of available functions on each I/O Point.) As a Digital Input (IO Points to ) Input Impedance Input OFF Condition Input ON Condition Functions Current Sink (Switch to V to operate) 5 kohms nominal. Input < Vdc Input > Vdc As a Digital Output (IO Points to 0) ON State Rated Current ON State Volt Drop OFF State Rated Leakage Current Functions Software selectable as: ON/OFF Input Counter Input (counts rising edge pulses) Hours Input (counts hours while input is on to resolution of 0.0 hours). Voltage Source (Solid State Switch to V) < 00mA continuous maximum per output < 00mA peak (<0ms) max, per output < 500mA total for all outputs simultaneously < V at maximum rated load < 0.mA at maximum supply voltage Software selectable as: ON/OFF ON Pulse (configurable 0ms 00s) OFF Pulse ( configurable 0ms = 00s) Range 00Vdc (software configurable to smaller ranges such as 5Volts) Accuracy < 0.5% of reading 6mV from 0 to 5.5V < 0.5% of reading 0mV from 5.5 to 0V Resolution As an Analogue Input (I/O Points to 0) Range Accuracy Resolution 6mV from 0 to 5.5 Volts nominal (0 bits) mv from 5.5 to 0Volts nominal (0 bits) Voltage Input referenced to 0V supply. 05.5Vdc (software configurable to smaller ranges such as 5Volts) < 0.5% of reading 6mV 6mV nominal (0 bits) As an Analogue Output (I/O Points and ) Load Maximum Range Accuracy 0mA Source into 0V connected load Calculate maximum load as follows: R max = (V supply 5V).0 ohms Examples: V Supply: R max = 00 ohms.8v Supply: R max = 0 ohms V Supply: R max = 00 ohms V Supply: R max = 950 ohms 7.6V Supply: R max = 0 ohms 0 to ma (software configurable to smaller ranges such as 0mA or 00mA) < 0.5% of full scale As an Analogue Input (I/O Points,,, ) Voltage Input referenced to 0V supply. General Specifications Power Requirements Power Supply Voltage 9 0Vdc (ripple < 5%) Average Current 80mA at Vdc 0mA at Vdc Programming Language Program Space Environmental Conditions Storage Temperature Operating Temperature MG Radio compliance Processor Clock Speed Memory Flash / RAM EziForth 6kBytes Program memory 8kBytes User RAM memory 5 C 85 C ( F 85 F) 0 C 60 C ( F 0 F) 0 C 50 C ( F F) 6 Bit Processor 0MHz 5kB / 56kB Accuracy Battery Life Battery Compliance with Standards min per month > year with power off > 5 years with power on. V Lithium Cell type CR0 Safety EN 60950:995 Emissions EN 550 EN5008:99 Group I, Class A EN5008 Immunity ESD IEC 6000:995, level Immunity RF Fields IEC 6000:995, level Immunity Fast Transients Weight Packed/Unpacked IEC 6000:995 kv DC power port kv input/output lines 50gm/50gm approx. Real Time Clock Resolution 0ms Front Panel Serial ( available on all models ) Asynchronous serial port Protocols Supports the following protocols as Datasheet DSC60BR5 sheet 5 of 8
Baud Rate Maximum cable length Connection RS//85 standard: Conet/s Modbus ASCII (Master or Slave) Modbus RTU (Master or Slave). Other protocols written in the EventForth programming language may be downloaded. 00 8,00 baud. 5 meters (50ft) in RS mode 00m (000ft) in RS85 mode 9 pin subminiature DB9 (male). Selected by the wiring to the DB9 connector 5 9 8 7 6 Pin Communication Standard RS RS85 Do not connect Rx Data (In) Rx Data (In) Rx Data (In) Tx Data (Out) Do not connect Do not connect Tx Data (Out) 5 Ground Ground 6 Do not connect Vcc 7 RTS (Out) Do not connect 8 CTS (In) Do not connect 9 Do not connect Tx Data (Out) Plugin Memory Card ( available on all models ) Storage Capacity Standard SD Memory Card (mm x mm x.mm) SD Memory Card dependent: Up to Gb supported Data Format Data writable by program to suit application. Any text based file format may be written such as CSV File Format compatible with Microsoft Excel etc. Card Format PC Compatible FAT File Format Network Communications Specifications for the Teleterm MG Model C6xB (EGSM/GPRS) Network GSM/GPRS Connectivity GSM Capability GPRS Capability SIM Card SMS GSM/GPRS mobile network Quad Band EGSM/GPRS (900/800/850/900MHz) designed for SMS and data applications Fully compliant with ETSI GSM Phase GPRS Class 0, PBCCH support Coding schemes: CS to CS Small (Volt only) Remote mounted antenna connected via SMA connector on MG. Remote Programming and Configuration Method DataDesktop Service Compatibility The Teleterm MG allows remote dialin for the purpose of configuration and program changes remotely. (CAUTION: GSM only supports up to 00 baud in remote dial in, so large program downloads will be time consuming.) Secure Access to data from the MG is made possible from a standard Web Browser using the Omniflex DatDesktop Web Service. The Omniflex DataDesktop Service stays in touch with your RTU s and keeps an uptodate copy of data in real time. This service is available by monthly subscription in selected regions. Transmission Method Number of messages GPRS SMS s can be sent by the user program in the MG. Only limited by the installed User program. (Consult factory for application advice). Compatibility The MG is designed for full compatibility with the OMNIFLEX DataDesktop service via GPRS. Installation of the DD Software pack is required to connect to this service. (Consult the factory for application advice). Transmission Method The GPRS service can be used to send UDP/IP packets or TCP/IP session data to third party applications. This is an advanced function, only recommended to experienced programmers. Network Communications Specifications for the Teleterm MG Model C6xB (G/UMTS) Network Network Bands Network compatibility SMS UMTS/HxDPA mobile network 850/900/00 MHz WCDMA/FDD 850/900/800/900 GSM/GPRS/EDGE Compatible with Telstra NextG(Australia) Remote mounted antenna connected via SMA connector on MG. Transmission Method Number of messages Remote Programming and Configuration Method SMS s can be sent and received by the user program. Only limited by the installed User program. (Consult factory for application advice). The Teleterm MU allows remote dialin for the purpose of configuration and program changes remotely. Datasheet DSC60BR5 sheet 6 of 8
DataDesktop Service Compatibility Secure Access to data from the MG is made possible from a standard Web Browser using the Omniflex DataDesktop Web Service. This service is available by monthly subscription. (DD software pack required to be installed on MU) Network Communications Specifications for the Teleterm MS Network s s RS Connector Serial Protocols supported Baud Rate Maximum cable length x RS x RS/85 9 pin subminiature male (DB9M). Supports Conet/s and Modbus ASCII and RTU Master or Slave as standard, but other protocols may be downloaded. (Consult the factory for advice on additional protocols) 00 8,00 baud. 5 meters (50ft) PIN I/O RS DESCRIPTION I CD Carrier Detect I RD Receive Data O TD Transmit Data O DTR Data Terminal Ready 5 SG Signal Ground 6 I DSR Data Set Ready 7 O RTS Request To Send 8 I CTS Clear To Send 9 I RI Ring Indicator Modem Power Connector Uses Molex 778 ( pins) This connector may be used to power an external modem PIN NAME DESCRIPTION Vs V supply voltage (switched) A max RD 5Vdc (50mA max.) TD 0V return Network Communications Specifications for the Teleterm MC Network Applications CONET Industrial LAN (token passing peertopeer network designed to operate on existing plant cabling). Baud Rates Cable length No of nodes 6.5 kbaud on Standard Baud Rate 7800 Baud on Slow Baud Rate. 0km maximum 6 max on one network Network Communications Specifications for the Teleterm MR Model C6xB (.GHz 6mW) Operating Band Special Radio Licence Requirements Transmit Power Receiver Sensitivity Modulation ISM.Ghz None. (operates in licencefree ISM band) 6mW (8dBm) 00dBm typical DSSS FSK RF Data Rate Serial Data Rate Indoor/Urban Range Outdoor (LOS) Approvals 50,000 bits per second 9,600 bits per second 90m km RPSMA Connector for external antenna Approved for use internationally Network Communications Specifications for the Teleterm MR Module C6xB (90MHz 00mW) Operating Band Special Radio Licence Requirements Transmit Power Receiver Sensitivity Modulation 9596 MHz None. (operates in licencefree ISM band) 00mW (0dBm) 0dBm typical DSSS FSK Throughput Data Rate Number of Channels Outdoor Range (Line of Sight) Approvals 9600 bits per second 7 Frequency Hopping Sequences Up to km with dipole Up to 8 km with higain antenna RPSMA Connector for external antenna Approved for use in USA and Australia Network Communications Specifications for the Teleterm MR Module C6xB (868MHz 5mW) Operating Band Special Radio Licence Requirements Transmit Power Receiver Sensitivity Modulation SRD g Band (869.55 MHz) None. (operates in licencefree ISM band) 5mW (5dBm) dbm typical FSK Throughput Data Rate Number of Channels Outdoor Range (Line of Sight) Approvals,00 bits per second 0% duty cycle Single Channel Up to 0 km with dipole Up to 0 km with higain antenna RPSMA Connector for external antenna Approved for use in Europe and S.Africa Network Communications Specifications for the Teleterm MR Module C6xB (90MHz W) Datasheet DSC60BR5 sheet 7 of 8
Operating Band Special Radio Licence Requirements Transmit Power Receiver Sensitivity 9598 MHz None. (operates in licencefree ISM band) Settable mw (0dBm) to W(0dBm) 0dBm typical Throughput Data Rate Number of Channels Outdoor Range (Line of Sight) 9,600 bits per second 0 Frequency Hopping Sequences Up to 0 km with dipole Up to 0 km with higain antenna RPSMA Connector for external antenna Modulation FHSS FSK Approvals Approved for use in USA and Australia Ordering Information ORDER CODE PRODUCT DESCRIPTION C60B0 Teleterm M Teleterm MG Programmable RTU C60B Teleterm MG Teleterm MG Programmable RTU with GSM/GPRS integral modem. C60B Teleterm MG Teleterm MG Programmable RTU with G HSDPA/UMTS integral modem (Telstra NextG compatible) C60B Teleterm MC Teleterm MC Programmable RTU equipped with CONET network port. C60B Teleterm MR Teleterm MR Programmable RTU equipped with integral.ghz FHSS licencefree radio network port (Internationally acceptable) C60B Teleterm MR Teleterm MR Programmable RTU equipped with integral 90MHz 00mW FHSS licencefree radio network port (USA, Australia, NZ only) C60B Teleterm MR Teleterm MR Programmable RTU equipped with integral 868MHz FHSS licencefree radio network port (UK, South Africa & European aligned countries) C60B Teleterm MR Teleterm MR Programmable RTU equipped with integral 900MHz W FHSS licencefree radio network port (USA, Australia, NZ only) C60B Teleterm MS Teleterm MS Programmable RTU equipped with second and third RS/85 serial ports. ACCESSORIES C669 Conet Terminator Board Provides Conet compliant termination of field cabling with added surge suppression M8A MX Programming Cable RS Male DB9 connector (PC end) to FC (Target end) metres. M8A Conet Patch Cable Male DB9 connector (CPU end) to loose ends. metres. Use to connect MC to C669 Conet Terminator. M8A MX RS/85 Serial Patch Cable RS/85 Female DB9 connector (M end) to loose ends. metres. Datasheet DSC60BR5 sheet 8 of 8