HARDWARE BASED CHARACTERISATION OF LV INVERTER FAULT RESPONSE

Similar documents
Technical Information Short-Circuit Currents Information on short-circuit currents of SMA PV inverters

Inverter-Based Resource Disturbance Analysis

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

900 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report

Fault Ride Through Technical Assessment Report Template

Harmonic filter design for electrified railways

ASSESSMENT OF HARMONIC DISTORTION LEVELS IN LV NETWORKS WITH INCREASING PENETRATION LEVELS OF INVERTER CONNECTED EMBEDDED GENERATION

Application of a MW-Scale Motor-Generator Set to Establish Power-Hardware-in-the-Loop Capability

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC

Power quality emission assessment of photovoltaic inverters based on IEC technical report :2011

WILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS

IEEE sion/1547revision_index.html

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction

Power quality measurements in a singlehouse

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

A REVIEW PAPER ON REGULATION TECHNIQUE FOR VOLTAGE SAG AND SWELL USING DVR

Project acronym: Multi-island

MODELING THE EFFECTIVENESS OF POWER ELECTRONICS BASED VOLTAGE REGULATORS ON DISTRIBUTION VOLTAGE DISTURBANCES

EMERGING distributed generation technologies make it

Tripping of circuit breakers in PV installations due to zero sequence field impedance

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

PQ Monitoring Standards

Hardware Testing of the Alternate Arm Converter Operating in its Extended Overlap Mode

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

5 Summary LOW VOLTAGE RIDE THROUGH WITH HIGH CURRENT INJECTION. Motivation. Future Requirements. Test results for symmetrical failures

Response of Grid Interconnected Solar PV inverters to Transmission System Faults

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

POWER QUALITY MONITORING - PLANT INVESTIGATIONS

Final ballot January BOT adoption February 2015

Target Mchunu and Themba Khoza Eskom Transmission Division, System Operator Grid Code Management

Loss of Solar Resources during Transmission Disturbances due to Inverter Settings II

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

1 INTRODUCTION 2 MODELLING AND EXPERIMENTAL TOOLS

Recommendations for Harmonic and Power Measurements in Electrical Networks

International White Book on DER Protection: Review and Testing Procedures

Southern Company Interconnection Requirements for Inverter-Based Generation

LOW ORDER HARMONICS IMPROVEMENT OF A SINGLE GRID CONNECTED INVERTER SYSTEM UNDER PR CONTROL TECHNIQUE

Open Access Simulation Toolbox for Wind Power Transmission using High Voltage Direct Current Technology

Investigation and Correction of Phase Shift Delays in Power Hardware in Loop Real-Time Digital Simulation Testing of Power Electronic Converters

Transmission Interconnection Requirements for Inverter-Based Generation

Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA

EDS FAULT LEVELS

Volume I Issue VI 2012 September-2012 ISSN

Proposed test procedure for the laboratory characterisation of gridconnected

Induction Machine Test Case for the 34-Bus Test Feeder -Distribution Feeders Steady State and Dynamic Solutions

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER

Mitigation of Power Quality Problems Using DVR in Distribution Network for Welding Load

Statistical analysis of overvoltages due to the energisation of a 132 kv underground cable

A Guide to the DC Decay of Fault Current and X/R Ratios

Power Quality of a Battery Energy Storage System (BESS) with Nonlinear Load Gabriel Haines

Technical information SUNNY TRIPOWER CORE1-US

PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM

1. Introduction to Power Quality

5 Summary test results and additional findings

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

Technical information Grid Support Utility Interactive Inverters for Sunny Central-US and Sunny Central Storage-US

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

Modeling of Distributed Generation under Next Generation Interconnection Requirements. Anna Edwards. A thesis. Submitted in partial fulfillment of the

Power Quality Requirements for Connection to the Transmission System

APPLICATION OF INVERTER BASED SHUNT DEVICE FOR VOLTAGE SAG MITIGATION DUE TO STARTING OF AN INDUCTION MOTOR LOAD

Testing Advanced Photovoltaic Inverters Conforming to IEEE Standard 1547 Amendment 1

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

Study of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T.

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

PFC Lite. How it works OMNIVERTER. OMNIVERTER November 14, 2015 Slide 1

Assessment of Saturable Reactor Replacement Options

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN

Conext CL-60 Inverter Active and Reactive Power Control and LVRT

Harmonic impact of photovoltaic inverter systems on low and medium voltage distribution systems

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

RENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana

Putting a damper on resonance

Company Directive STANDARD TECHNIQUE: SD1E/2. Technical Requirements for Customer Export Limiting Schemes

A Novel Islanding Detection Technique for Distributed Generation (DG) Units in Power System

Impact of High PV Penetration on Grid Operation. Yahia Baghzouz Professor of Electrical engineering University of Nevada Las Vegas

Technical information SUNNY BOY 3.0-US / 3.8-US / 5.0-US / 6.0-US / 7.0-US / 7.7-US

Shunt Active Power Filter with Selective Harmonics Compensation for LV distribution grid

Comparison of the Behaviour of Wind Farms and Conventional Power Stations during Grid Failure Conditions

DC VACUUM CIRCUIT BREAKER

LIMITS FOR TEMPORARY OVERVOLTAGES IN ENGLAND AND WALES NETWORK

ENHANCEMENT OF POWER QUALITY BY INJECTING SERIES VOLTAGE USING DVR

Power System Stability. Course Notes PART-1

BED INTERCONNECTION TECHNICAL REQUIREMENTS

II. RESEARCH METHODOLOGY

Programmable Grid Simulator THE POWER TEST EXPERTS

E N G I N E E R I N G M A N U A L

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY

DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL

On the Evaluation of Power Quality Indices in Distribution Systems with Dispersed Generation

IEEE sion/1547revision_index.html

Transcription:

HARDWARE BASED CHARACTERISATION OF LV INVERTER FAULT RESPONSE Ibrahim ABDULHADI Federico COFFELE Power Networks Demonstration Centre - UK ibrahim.f.abdulhadi@strath.ac.uk federico.coffele@strath.ac.uk Adam DYŚKO University of Strathclyde - UK a.dysko@strath.ac.uk Colin FOOTE Christopher KUNGU SP Energy Networks - UK cfoote@spenergynetworks.co.uk ckungu@spenergynetworks.co.uk Martin LEE Scottish & Southern Electricity Networks - UK martin.lee@sse.com ABSTRACT This paper presents the experimental testing of commercial LV-connected PV inverters to characterise their behaviour during fault conditions. Understanding this behaviour is critical for the proper design and operation of distribution networks with a large amount of inverter-connected generation. Hardware test results for a number of different inverters are discussed and compared. The challenges for modelling, particularly with respect to fault conditions, are discussed with an example simulation. INTRODUCTION An increasing number of inverter interfaced generation is being connected to the distribution grid, necessitating a better understanding of the performance of these inverters during network disturbances. This is particularly important when performing system studies using outdated or outright invalid assumptions about inverter behaviour during such disturbances an aspect that is exacerbated by the seemingly inconsistent behaviour across inverters from different manufacturers. It is thus important to understand said behaviour using empirical data that is obtained through means of physical testing of off-the-shelf inverter hardware. The literature has reported a number of simulation and hardware based studies that detail the response of inverters to fault conditions. For example, the work reported in [1] reported on simulation studies based on manufacturer supplied models. This showed the influence of retained voltages on the inverter output. The reported fault contribution of the inverters did not exceed 1.2pu of inverter rating, while some inverters maintained pre-fault current output levels. A PSCAD inverter model behaviour which was validated using hardware testing of an inverter is presented in [2]. It reports a slight and sustained increase in current contribution during a fault where the pre-fault inverter loading was at 1pu of its rating. Inverter fault response was tested using a power electronic grid simulator as reported in [3]. The authors reported an inverter fault current contribution of 178%-200% lasting for about 9 cycles at 60Hz. A number of guidelines exist for developing inverter models or limiting their fault contribution when connected to the network. For example, guidelines for connecting inverter interfaced generating plant connected to the Medium Voltage (MV) network in Germany assume 100% rated current during fault. Where this is expected to be exceeded and would have an impact on the network, an agreement must be reached between the generator and network operator [4]. The Western Electricity Coordinating Council (WECC) provides guidelines and a specification for developing generic dynamic simulation models for transmission connected PV inverters or aggregated distribution connected PV inverters [5, 6]. This paper presents the main experimental results from testing commercial off-the-shelf LV PV inverters at the Power Networks Demonstration Centre (PNDC) [7]. The paper describes the test setup including the inverters under test, the test network configuration and applied fault conditions. This is followed by a summary of the main characteristics of the inverter behaviour observed during testing. Finally, the results of a simulation designed to mimic one of the PNDC test scenarios are presented and compared with the experimental results. TEST SETUP AND PROCEDURE Inverters under test and test environment Four commercially available LV PV inverters were tested, as summarised in Table 1. Table 1 PV inverters under test (detailed parameters can be obtained from manufacturer data sheets available online) Inverter model ABB PVI-5000-TL-OUTD KACO Powador 6002 SMA Sunny Boy 5000TL SMA Tripower 10000TL Maximum Rating 5.56kVA (single phase) 5kVA (single phase) 5kVA (single phase) 10kVA (three phase) The inverters were connected to the PNDC LV distribution test network as shown in Figure 1. The inverters were supplied using PV emulators. Faults were applied directly to the inverter terminals. A controllable RL load bank was used to load the network. Synchronised LV voltage and current measurements were taken as depicted at a rate of 4kHz. The current measurement upstream of the fault LV thrower is referred to as the grid current in the paper. CIRED 2017 1/5

11kV/0.433kV RL load bank Synchronised Measurements Inverter under test LV fault thrower Figure 1 Distribution network setup used for fault testing Test scenarios Since the inverter terminal voltage is the same as that of the test network (400V during testing), the main uncontrollable parameter of interest is the inverter current and consequently power output. The characterisation of inverter output then considers a number of controllable parameters, namely: Inverter retained voltage during fault. Pre-fault inverter loading. Fault point on wave (PoW). 600V PV Emulator The retained voltage was controlled by applying resistive faults. Up to four power resistor banks (of 0.75Ω each) were used in parallel or series configurations. Table 2 lists the fault resistances used for testing. PoW angles of approximately 0 and 90 were used. Pre-fault inverter loading varied from 30% to 100% depending on the inverter. The faults are applied for a duration of 0.3s. This is to ensure that the inverter built-in under-voltage protection does not operate during the test. Inverters trip after 0.5s if the voltage drops below nominal by 20% as stipulated by G83 and G59 engineering recommendations [8, 9]. Single phase inverters were connected to the A phase and only P-E faults were applied in this case. lower retained voltages, the inverter maintains the prefault current output levels unless the fault is a solid short circuit. At a retained voltage of 32%, the output current is reduced slightly from its pre-fault level. Whereas the prefault current level is maintained with a retained voltage of 47% during a fault. Upon post-fault voltage recovery, the output current returns to its pre-fault level. With a solid phase to earth fault, the output current ceases to be sinusoidal for a few cycles after fault inception then current injection stops. In this case, the current output does not resume immediately after post fault voltage recovery. Figure 2 shows the instantaneous and RMS values of measured inverter voltage and current, measured grid side current and calculated inverter real and reactive power output for a solid fault test case. The instantaneous voltage and current are depicted in blue, while the RMS values are in red. Active and reactive powers are shown in blue and red respectively. Note that the grid current prior to the fault is equal to the inverter current output so it appears very small due to the graph scale. The test case parameters are as indicated in the figure caption, where P out is the pre-fault inverter active power output and R f is the fault resistance. The RMS and power values are calculated using a Simulink library which requires one cycle of input to produce a result. This is why these values are at an initial value zero in the results graphs. Table 2 Fault resistance configurations used for testing Fault type Fault resistance (Ω) P-E (A phase to earth) 1.5, 0.75, 0.38, 0.19, 0 P-P (A-B phase) 1.5, 0.75, 0.38, 0.19, 0 P-P-P (three phases) 1.5, 0.75, 0.38, 0 Test findings In total, 88 fault tests were performed across all inverters. Due to space limitations, this section will summarise the main findings and illustrate them with selected examples from the test measurements (the full test report can be requested directly from the PNDC). ABB inverter behaviour During a fault, the inverter attempts to maintain the prefault output power as set by the PV emulator depending on the retained voltage level. This is achieved by increasing the current output of the inverter for the duration of the fault. This is only the case when the retained inverter voltage is at 62.6% of nominal or above. However, the increase in current output does not occur when the inverter is operating at 100% power output rating pre-fault. With Figure 2 ABB, Pout = 0.5pu, PoW = 0, Rf = 0Ω KACO inverter behaviour During the majority of fault scenarios, the current output generally increases regardless of retained voltage. With a retained voltage of 46.6% and above, the inverter attempts to retain the pre-fault power output levels. During some of the tests, the inverter stops injecting current after several cycles of fault inception. During this condition, it can be observed that the reactive power output is increasing over time. This can also be accompanied by a phase angle jump of the current that causes a step reduction of reactive power output. A gradual increase of reactive power output then ensues unless the current output stops. This adjustment of current angle and reactive power output may be symptomatic of a device limit being breached for which the inverter controls react. Generally, the inverter is capable of increasing its current output to maintain pre- CIRED 2017 2/5

24th International Conference on Electricity Distribution Glasgow, 12-15 June 2017 fault power (bearing in mind that the maximum pre-fault loading of this inverter was 80% of its rating due to issues with the DC side supply). In cases were the current injection stops during the fault, the current does not resume immediately after post fault voltage recovery. As an example, Figure 3 shows the measurements for a resistive fault test with a retained voltage of 31.9%. This is one of the tests where the inverter stops injecting current. Note the gradual increase in reactive power before it goes to zero. retained voltage of 70.7%, the inverter attempts to maintain the pre-fault power by increasing the current output of a healthy phase (phase B). During multi-phase faults, the inverter does not sustain the current output for the tested scenarios and the inverter does not resume current injection immediately after post fault voltage recovery. Figure 5, Figure 6 and Figure 7 show the measurements for a resistive fault test with retained voltages (measured on the A phase) of 72.7%, 50.9% and 67.1% respectively. Instantaneous voltages and current as well as phase active powers are depicted in red, green and blue. RMS values and phase reactive powers are depicted in brown, black and grey. Figure 3 KACO, Pout = 0.5pu, PoW = 0, Rf = 0.19Ω SMA (single phase) inverter behaviour During a fault, with a retained voltage of 77.2% of nominal and above, the inverter attempts to maintain the pre-fault output power determined by the PV emulator. This is manifested by an increase in current output. This is true when the inverter is operating at 50% of rated power. During tests where the inverter is operating at 100% of rated power, the inverter does not increase its current output. For retained voltages lower than 62.2% of nominal, the inverter current output is sustained for up to around 1.5 cycles then stops. In this case, the current output does not resume immediately after post fault voltage recovery. Figure 4 shows the measurements for a resistive fault test with a retained voltage of 77.2%. Note that in this case, with a high retained voltage and the inverter at full power, the inverter current continues at its pre-fault value. Figure 5 SMA 3-ph, Pout = 0.3pu, PoW = 0, Rf = 1.5Ω, A-G Figure 6 SMA 3-ph, Pout = 0.3pu, PoW = 0, Rf = 0.19Ω, A-B Figure 4 SMA, Pout = 1pu, PoW = 90, Rf = 1.5Ω SMA (three phase) inverter behaviour During phase to earth faults, the inverter ceases to output current if the retained voltage falls below 55.4%. At a CIRED 2017 Figure 7 SMA 3-ph, Pout = 0.3pu, PoW = 90, Rf = 1.5Ω, A-B-C 3/5

SIMULATION STUDIES A model of the PNDC test network was built in the PowerFactory analysis software (v15.2.5). The generic PV template available in the PowerFactory library was configured to represent a 3-phase, 10kVA PV inverter. Only the power rating was adjusted; all other parameters (of which there are more than 50 across 11 blocks within the PV model) were left as their default values. Some simple preliminary studies were performed to explore the behaviour of this generic library model and compare it with what was observed in the hardware tests. The results shown below are for a single-phase to ground fault on phase A with a resistance of 1.5Ω. The initial power output of the PV generator is set to 3kW, and so the studies are comparable with those shown in Figure 5. The same model was used to run both an electromagnetic transient (EMT) and unbalanced root mean squared (RMS) simulation. A steady state short circuit analysis was also performed. Figure 8 shows the inverter voltage and current in the EMT simulation, for the red, green and blue phases. The fault is on the red phase. The voltage waveforms are very similar to those in Figure 5 except there is evidence of very fast transient phenomena at 0.1 and 0.4 seconds when the fault is applied and removed. The inverter current waveform appears similar with only the faulted phase showing an increase in current output. In the simulation the remaining healthy phases retain a clean sinusoidal output; in the hardware test case these waveforms are distorted. Also, hardware testing showed that the inverter increased the current output in one of the healthy phases rather than the faulted phase. Figure 8 PowerFactory simulation EMT results Figure 9 shows the inverter voltage and current in the unbalanced RMS simulation, again for the red, green and blue phases. The voltage dip on the faulted red phase is clear. The simulation indicates that all three phases of the inverter current move together and increase by approximately 9% from their pre-fault value before dropping. This is somewhat inconsistent with the EMT results, suggesting that the EMT and RMS models are not directly comparable, or that the PV model is not suitable for unbalanced RMS simulation. Figure 9 PowerFactory simulation RMS results The steady state short circuit study was run using the PowerFactory Complete method with the PV generator modelled as an equivalent synchronous machine with Ik =Ik =14.43376kA, which is rated current. The limitations of this approach are clear but this is still the most practical method when there are very large numbers of generators, as in the large-scale short-circuit analysis routinely performed by network operators. The singlephase to earth fault with resistance 1.5Ω resulted in a voltage on the faulted phase of 190V and fault currents of Ik =Ik =4.35kA on all three phases of the inverter. The PowerFactory documentation notes that the standard short circuit methods cannot give precise results for a controlled PV system and suggest that dynamic simulations are necessary. GENERALISING INVERTER BEHAVIOUR From the observations related to all tested inverters, there is no clear impact of PoW fault inception on the sustained behaviour of the inverter output current during the fault. For faults introduced at 90 of the phase A voltage, the inverters current output experiences a short transient increase. When the inverters stop current output as described in the different scenarios above, it is not clear if the inverter s internal protection is operating or the inverter is merely stopping current injection. This is because the inverters do not provide a clear alarm or indication regarding the trip or the status of the connection. From the network protection point of view, the presence or absence of a current injection is the parameter of greatest interest during fault conditions. From the wider system operation perspective, it is concerning that the inverters display inconsistent and unexplained behaviours in terms of fault ride through. Furthermore, the current injection does not resume immediately after post fault voltage recovery. This suggests that further effort is required to achieve common understanding of capabilities and performance requirements which are heavily influenced by controller design and internal capacitive and inductive components. CIRED 2017 4/5

It can be argued that there is value in developing a generic tuneable inverter model whose parameters can be adjusted to represent specific designs or network operating conditions. In order to develop such model, a comprehensive inverter hardware test should be designed to extract sufficient characteristics to tune this model. This includes identifying the retained voltage boundaries at which the inverters begin to exhibit different behaviours. These characteristics would then have to be translated into the required data to be provided by customers for all new inverter connections. This would then give network operators the information necessary to model inverter behaviour accurately. Furthermore, there is potentially a need to stipulate more consistent inverter behaviour across all manufacturers that would facilitate grid planning and operation. Otherwise, grid operators will be faced with a difficult task managing connected inverter behaviour, as demonstrated by this small sample of tests. CONCLUSION This paper presented the main findings from the experimental testing of LV connected PV inverters during fault conditions. Inverters from different manufacturers exhibited a wide range of behaviours, but the following common features of behaviour have been observed: Inverters are more likely to provide a sustained current contribution with a higher retained voltage. A voltage drop of 38% is sufficient for some of the inverters to cease current injection. Inverters tend to increase their current output to maintain the pre-fault active power output provided that the inverter is within its rating limits. No increase in current over the inverter rating has been observed as reported in some of the literature. The simulation examples illustrate some of the problems faced by network operators when modelling the fault response of inverter-interfaced generation: Generic models can have a very large number of parameters and tuning them to represent specific types of inverter is difficult, and impractical for the smallest devices connected at LV. Different models or different configuration of models may be necessary depending on the type of analysis being performed. The current data submitted as part of the ENA New Generator Application Form process does not allow for the detailed modelling of the LV inverters With the volume of LV-connected PV and other inverterinterfaced generation continuing to grow, it is important that the responses of such devices in fault conditions is well understood. The tests described here indicate that there can be significant differences between devices. Some of the modelling challenges have been illustrated. Further work is required, across the industry, to ensure that the capabilities and performance requirements for this type of generation are widely understood. The authors believe that some level of standardisation with regards to inverter fault response would be a very positive development as it would help to develop more representative models and thus assess the aggregate impact on the existing network. Acknowledgments This project was funded under the core research programme contributed by the members of the University of Strathclyde s PNDC (http://pndc.co.uk/). REFERENCES [1] F. Katiraei, J. Holbach, and T. Chang, "Impact and sensitivity studies of PV inverters contribution to faults based on generic PV inverter models", ed: Quanta Technology, 2012. [2] E. Muljadi, M. Singh, R. Bravo, and V. Gevorgian, "Dynamic Model Validation of PV Inverters under Short-Circuit Conditions", in Green Technologies Conference, 2013 IEEE, 2013, pp. 98-104. [3] R. J. Bravo, R. Yinger, and S. Robles, "Three phase solar photovoltaic inverter testing", in Power and Energy Society General Meeting (PES), 2013 IEEE, 2013, pp. 1-5. [4] BDEW, "Technical Guideline: Generating Plants Connected to the Medium-Voltage Network - Guideline for generating plants' connection to and parallel operation with the medium-voltage network", Germany, 2008. [5] Western Electricity Coordinating Council, "WECC Solar Plant Dynamic Modelling Guidelines", 2014. [6] Western Electricity Coordinating Council, "Generic Solar Photovoltaic System Dynamic Simulation Model Specification", 2012. [7] C. D. Booth, F. Coffele, and G. M. Burt, "The Power Networks Demonstration Centre: An environment for accelerated testing, demonstration and validation of existing and novel protection and automation systems", in Developments in Power System Protection (DPSP 2014), 12th IET International Conference on, 2014, pp. 1-6. [8] Energy Networks Association, "Engineering Recommendation G59, Issue 3, Amendment 2: Recommendations for the Connection of Generating Plant to the Distribution Systems of Licensed Distribution Network Operators", 2015. [9] Energy Networks Association, "Engineering Recommendation G83, Issue 2: Recommendations for the Connection of Type Tested Small-scale Embedded Generators (Up to 16A per Phase) in Parallel with Low-Voltage Distribution Systems", 2012. CIRED 2017 5/5