Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives

Similar documents
How adjustable speed drives affect power distribution

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

How Harmonics have led to 6 Power Factor Misconceptions

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

McGill Power Sales & Engineering, INC.

Look over Chapter 31 sections 1-4, 6, 8, 9, 10, 11 Examples 1-8. Look over Chapter 21 sections Examples PHYS 2212 PHYS 1112

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

LV PFC Basics. Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1

VARIABLE FREQUENCY DRIVE

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

NJWA - Harmonics and Drives Proper System Design

HARMONICS CAUSES AND EFFECTS

DSP-BASED CURRENT SHARING OF AVERAGE CURRENT CONTROLLED TWO-CELL INTERLEAVED BOOST POWER FACTOR CORRECTION CONVERTER

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

Power Quality Monitoring and Power Metering Tutorial

Reducing Total Harmonic Distortion with Variable Frequency Drives

Introduction to Rectifiers and their Performance Parameters

Chapter 30 Inductance, Electromagnetic. Copyright 2009 Pearson Education, Inc.

Application Guidance Notes: Technical Information from Cummins Generator Technologies

Chapter L Power factor correction and harmonic filtering

ZENER ELECTRIC PTY LTD

POWER FACTOR CORRECTION USING BOOST CONVERTER

UNIT-III STATOR SIDE CONTROLLED INDUCTION MOTOR DRIVE

MIRUS International Inc.

Power Factor. Power Factor Correction.

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

AC Drive Technology. An Overview for the Converting Industry. Siemens Industry, Inc All rights reserved.

Power Electronics. Exercise: Circuit Feedback

AC Power Instructor Notes

Solution of EMI Problems from Operation of Variable-Frequency Drives

Harmonics White Paper

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions

ABB drives. Technical guide No. 6 Guide to harmonics with AC drives

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD)

ECET Modern Power

Modeling and Simulation of STATCOM

Economical Solutions to Meet Harmonic Distortion Limits[4]

7/15/2002 PP.AFD.08 1 of 28

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

Conventional Paper-II-2013

POWER FACTOR CORRECTION AND ITS PITFALLS

Cable Solutions for Servo and Variable Frequency Drives (VFD)

APPLICATION GUIDE. Harmonics in HVAC applications

Influence of Switching Elements on Harmonics and Power Factor Improvement

Speed Control Of Transformer Cooler Control By Using PWM

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Construction Electrician/Industrial Electrician/Power Electrician Common Core Level 2

Vacon Baltic Days Tallinn, Estonia

1. (a) Determine the value of Resistance R and current in each branch when the total current taken by the curcuit in figure 1a is 6 Amps.

Study of Power Factor Correction in Single Phase AC-DC Converter

( ) ON s inductance of 10 mh. The motor draws an average current of 20A at a constant back emf of 80 V, under steady state.

Type of loads Active load torque: - Passive load torque :-

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

DOWNLOAD PDF POWER ELECTRONICS DEVICES DRIVERS AND APPLICATIONS

IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs

PFC Lite. How it works OMNIVERTER. OMNIVERTER November 14, 2015 Slide 1

What does Power Factor mean?

Power Factor and Power Factor Correction

Operation of a Three-Phase PWM Rectifier/Inverter

CHAPTER 1 INTRODUCTION

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

AGN 026 Harmonic Voltage Distortion

VSD cables in. Working with. industrial & automation applications

CHAPTER 4 HARMONICS AND POWER FACTOR

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN

Automatic Power Factor Correction by Using Synchronous Condenser with Continuous Monitoring.

Simulation & Hardware Implementation of APFC Meter to Boost Up Power Factor Maintain by Industry.

Generator Advanced Concepts

APPLICATION NOTE - 018

Active Harmonic Filter (AF3)

Switched Mode Power Conversion Prof. L. Umanand Department of Electronics Systems Engineering Indian Institute of Science, Bangalore

A Subsidiary of Regal-Beloit Corporation. AC Inverter Terminology

Power Quality improvement of a three phase four wire system using UPQC

SHUNT ACTIVE POWER FILTER

ECET 211 Electric Machines & Controls Lecture 9-1 Adjustable-Speed Drives and PLC Installations (1 of 2)

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY

Placement Paper For Electrical

Harmonic Filters and Reactors

Question Paper Profile

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012

ECET Industrial Motor Control. Variable Frequency Drives. Electronic Motor Drives

Harmonic Requirements

Power Factor Improvement Using Thyristor Switched Capacitor Using Microcontroller Kacholiya Saurabh 1, Phapale Sudhir 2, Satpute Yuvraj 3, Kale.S.

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.

Exercise 1: Series RLC Circuits

Large PWM Inverters for Rolling Mills

VFDs and Harmonics in HVAC Applications

POWER ELECTRONICS. Alpha. Science International Ltd. S.C. Tripathy. Oxford, U.K.

Testing Power Sources for Stability

Power Factor & Harmonics

Alternators Reactance for Nonlinear Loads

An induced emf is the negative of a changing magnetic field. Similarly, a self-induced emf would be found by

World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013

VARIABLE FREQUENCY DRIVE

Thermal Imaging, Power Quality and Harmonics

Transcription:

For your business and technology editors Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives The use of AC induction motors is essential for industry and utilities. AC induction motors consume more than 50 percent of the energy used in industry. As compared to other type of loads, the induction motor has a relatively poor power factor, causing higher line currents, which causes additional heat in line cables and transformers. The power factor is especially low in cases when the motor is oversized for the application and, therefore, running lightly loaded. The use of Variable speed AC Drives (VSD) to control motor speed has the advantage of clearly improving the power factor and thus reducing losses in the supply cables and transformers. It also avoids the cost of investment in power-factor-correction equipment. This article explains the reason for the phenomena, which may result in the input current to the Variable speed AC Drive can be lower than the output current. The article also gives some guidelines when compared with fixed speed applications or other speed control methods like DC drives. What is the Difference Between Power Factor and Cosϕ? Power Factor (PF) is an important measure for electrical systems and it is defined as ratio of Real or Active Power, in total kilowatts, to total Apparent Power, in kilovolt amps. P PF = = S Real Power Apparent Power The Power Factor topic is of interest to a large number of people. An Internet search with one of the search engines gave more than three million hits. There sometimes seems to be confusion between the terms Power Factor and cosϕ (phi). Just remember that the cosϕ is equal to Power Factor only in cases where both system voltage (U) and system current (I) are sinusoidal (cosϕ is equal to Power Factor only when the voltage and current considered are at the same frequency). In real-world electrical installations, both voltages and currents contain harmonics and the Power Factor is not equal to cosϕ. To understand Power Factor, it can help to consider phasor diagrams. An electrical circuit under consideration is shown in Fig. 1. The supply voltage U connected to the circuit is at a single frequency; that voltage causes current I to flow through the components. According to Ohms law, the voltage drop in each component is calculated by multiplying the current I (in Amps) by the resistance (in Ohms). The phasor diagrams for this circuit are shown in Fig. 2.

Figure 1. The three basic linear electrical components in serial connection with the voltage U, causing the current I to flow through the circuit. The components are:! Resistor R with resistance measured in Ohms and a voltage drop u R! Inductor with inductive impedance X L measured in Ohms and a voltage drop u L! Capacitor with capacitive impedance X C measured in Ohms and a voltage drop u C The voltages and currents in Fig. 1 can be illustrated in phasor form in Fig. 2. The current I is common for each component in the system, but the voltages are of different magnitude and their phasors are in different directions -- 90 degrees apart from each other s. The three diagrams in Fig. 2. show the steps for defining the voltage phasors and the angle between the total voltage U and the current I. As result, we get the definition for the cos ϕ: Real Power cos ϕ = = UI R Apparent Power UI = U R U

u L u C u R I φ I U u L u R u C U φ I u L u R u C u = u - u X L C Figure 2. The current phasor I rotates in phase with the voltage vector u R, but it is lagging the voltage phasor u L and leading the voltage phasor u C. All phasors rotate counter-clockwise. Because the u L and u C are pointing in opposite directions, they are subtracted and the difference u X is the reactive component of the total system voltage. The u R is the active or real component and the phasor sum of these voltages is the total voltage U. The cosine of the angle ϕ between total voltage U and the active voltage u R is the Power Factor of an ideal system, which is known as cosϕ. If U and u R have one single, fundamental frequency, cosϕ is sometimes called displacement Power Factor. To understand, power factor is sometimes visualized with a horse pulling a railroad car down a railroad track. Because the railroad ties are uneven, the horse must pull the car from the side of the track. The horse is pulling the railroad car at an angle to the direction of car s travel. The power required to move the car down the track is the real power. The effort of the horse is the total (apparent) power. The car will not move sideways. Therefore the sideways pull of the horse is wasted effort or reactive power. These three different power vectors are shown in Fig. 3. Apparent Power = 100 kva Reactive Power = 60 kvar Active (Real) Power = 80 kw Power Factor = 80/100 = 0.8 Figure 3. The Power factor definition by using power vectors In summary:! Power Factor (PF) is the Real Power divided by Apparent Power! Power Factor of the system with sinusoidal current and voltage is cosϕ

! In both cases, the value of PF is from 0 to 1, sometimes given as 0 to 100%! The real-world PF is influenced by harmonic disturbances and other non linearity s! The real-world PF is therefore lower than with sinusoidal current and voltage When Should the Power Factor be improved? Power plant generators usually are designed for PF = 0.8 to 0.9. Therefore, if the actual demand-side Power Factor is lower than the designed (0.8), either the generator current increases above the rated current or the active power output has to be limited. For that reason, the power companies put limits on reactive power consumed by the customers. The limits usually are set for large industrial or public customers only. Customers have to pay a power factor penalty if power factor falls below a certain limit. The limits can vary widely from 0.8 to 0.97. Electric motors connected to the power line is the main reason for reduced power factor. The rated power factor of a standard motor depends on its rated power and, typically, is around 0.85 but can be much lower if the motor is lightly loaded. This topic will be studied in the next section. Why Do Electric Motors Cause Low Power Factor? The use of AC induction motors is essential for industry and utilities. AC induction motors consume more than 50 per cent of the energy used in industry. As compared to other type of loads, motor loads have relatively poor power factor. Poor power factor causes higher line currents, which causes additional heat in line cables and transformers. The power factor is especially low in cases when the motors are oversized and are running with a light load. Figure 4. Line current and power factor of a 55 kw AC induction motor as function of the motor load.

To produce the required rotating torque and speed, the induction motor takes both active current and reactive current from the power supply. The rotating torque of the motor is created as an interaction between the active current component and the magnetic field. The field is produced by the reactive current component. Light load takes less active current but the magnetic field, as well as the reactive current, stays constant. This means that the power factor decreases with decreasing load, as shown in the Fig. 4. At the full load, the current is mainly active but, at the light load, the current is mainly reactive. How to Improve the Power Factor? There are many different methods to improve the power factor or compensate for the reactive power:! At the power plant, the excessive reactive power can be compensated by increasing the excitation of synchronous generators; or, by using separate rotating synchronous compensators.! At transmission or transformer stations, the reactive power can be compensated by power- factor-correction capacitors. The capacitors can be installed to improve the power factor for a single load or an entire power system.! At the plant level, the power factor correction can be accomplished by using power-factor-correction capacitors, or by using variable speed AC drives. When AC drives are used, power-factor-correction capacitors should not be used, because it is usually unnecessary, and because drive harmonics could damage power factor capacitors. See the next section. The principle of Variable Speed AC Drives On a so-called PWM (Pulse Width Modulated) drive with a diode bridge converter input, the Power Factor to the AC line is near unity (see Fig. 5). The output may have an inductive (lagging) power factor, due to the motor s inductive reactance. However, the motor s reactive current is circulated between the motor and the inverter bus capacitors and not to the input line. Line Rectifier AC to DC L C + U d Inverter DC to AC V1 V3 V5 Motor V4 V6 V2 - Output Power Factor = 0.8 to 0.9 Figure 5. A Variable speed AC drive input consists of a rectifier bridge that converts the line AC voltage to DC voltage. The smoothing of the DC voltage is made via an inductor (L) and capacitor (C). The DC voltage (Ud) then is converted in the inverter to variable frequency and variable voltage AC that is connected to the AC motor. The switches V1 to V6 in the inverter are very fast semiconductors, usually IGBT s (Insulated Gate Bipolar Transistors) M

in modern drives. Because of the fast switching inside the AC drive, there is a risk of electromagnetic emissions. Emissions can be both conductive and radiating interference. International regulations set limits on both low- and high-frequency emissions. With the use of filters, screening and suitable mechanical construction inside the drive cabinet, it is possible to meet the Electromagnetic Compatibility (EMC) standards. How Variable Speed AC Drives improve Power Factor Let s study the currents of the above mentioned 55 kw/400v motor and drive system: Motor: Motor Mechanical Power = 55 kw, Input U = 400 V, efficiency = 94.4% and power factor = 0.89 Motor Electrical Input Power= 55 kw/0.944 = 58.3 kw Motor Electrical KVA = kw/pf = 65.5 58.3 * 1000 I 2 = = 94.5 A 3 * 400 * 0.89 AC drive: Output P = 58.3 kw, 94.5 A Input U = 400 V, efficiency = 98% and power factor = 0.96 Drive Input Power = 58.3 kw/0.98 = 59.5 kw Drive Input KVA = 62.0 One can see that the drive input current from the supply is 5 amps, or more than five percent (94.5 versus 89.5 amps), lower than the drive output current to the motor. The active power input, instead, is 1.2 kw (58.3 versus 59.5 kw) higher than the output from the drive. The difference in drive input and output power factor is how the variable speed AC drive can improve the Power Factor and how the drive output current can be greater than the input current! What Does This Mean in Reduced Losses and Saved Money? The power losses in the power line, transformers and cables are proportional to the square of the current. We can estimate the following:

Assume the average load on the 55 kw motor is 35 kw. From Fig. 4, the motor current at 35 KW is 65 amps; the AC drive input current under these conditions is 60 amps. The AC drive reduces the input current from 65 A to 60 A. The reduction of losses when operating the motor from an AC drive is then: P p 60 = 100 65 2 *100 = 15% If total losses on the supply side are 5% of the average load, the AC drive can reduce the losses to about 4%. The reduction on the total power consumption, as well as reduction on money spent, is one per cent. (Note: The original reason to install an AC drive is not the power factor improvement but better process controls, energy savings in the process, and/or reduced wear of the machinery. PF improvement is a positive side effect.) Power Factor Comparison Between AC and DC Drives The main difference between standard AC and DC drives is that PWM AC drives have a diode rectifier on the front end while DC drives have SCR rectifier. The control principle of the SCR rectifier is based on phase control with line commutation, causing a phase shift between voltage and current. The lower the speed, the larger the phase shifts. This reduces the power factor of DC drives, especially in the lower speed ranges (as shown in Fig. 6). Figure 6. Power factor of AC and DC drives as function of motor speed.

Conclusions The power factor topic is interesting and important for a number of parties within the power generation and consumption marketplace:! Industrial, commercial and domestic customers have a desire to get the most cost effective electrical installation to serve their machinery. Low power factor can mean extra losses and penalty payments to the utility for excessive reactive power.! Power production and transmission companies want to sell as much active power as possible to their customers. Low power factor can reduce the generating and transmission capacity.! Manufacturers of power-factor-correction equipment are willing to sell capacitor banks and automation equipment to help improve the power factor.! Consultants have an interest to help the power companies, consumers and other interest groups with audits and plans for better energy economy and achieving higher power factors.! Drives and motors manufacturers can also help to improve the power factor with variable speed drives. VSDs help solve the power factor problem -- while improving process control, saving electrical energy, and reducing machinery wear. # # # Sidebar: Why is Power Factor Important? In the mid 90 s, a large semi-conductor manufacturer built a new production plant in New Mexico. A few years later, they built another, nearly identical, plant in Arizona. After operating the new Arizona plant for one year, the user noticed that the Arizona plant s electrical bill was approximately 30% higher than the New Mexico sister plant. The only discernable difference between the two plants was the method of controlling the Clean Room Recirculating Air Handlers (RAH) Units. In the New Mexico plant, PWM AC Drives were used on the (RAHs). In the Arizona plant, the RAH OEM provided variable-width fans and constant-speed AC Motors instead of PWM Drives. When the variable-width fan closed off (less CFM), the AC Motor unloaded, and the PF dropped drastically. The Arizona Utility had a poor PF penalty charge. The 30% increase in the electrical bill cost of the Arizona plant was due to the RAH motor s poor PF at reduced loads!

For more information please contact: ABB Power Factor Mike Olson 262-785-2815 phone 262-785-8501 fax mike.olson@us.abb.com ABB Media Relations Ken Graber 262-780-3873 phone 262-785-8501 fax ken.j.graber@us.abb.com