Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

Similar documents
Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques

Power Measurements and Basic Electrical Diagnostic Tests

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC.

Chapter 7 Conclusion 7.1 General

Transformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

Matz Ohlen Director Transformer Test Systems. Megger Sweden

Transformer Factory Testing

7. INSPECTION AND TEST PROCEDURES

Power Transformer Condition Assessment Based on Standard Diagnosis

Power Factor Insulation Diagnosis: Demystifying Standard Practices

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

Benefits of SFRA - Case Studies

Substation Preventive Maintenance

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

Regional Technical Seminar TAP CHANGERS

Hands-On Transformer Testing and Maintenance

Transformers handling and transport

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Power Transformers Basics

ELECTRICAL TESTING PLANS AND PROCEDURES FOR TRANSFORMERS-DRY TYPE, AIR-COOLED

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Vallabh Vidyanagar, Anand, INDIA

DELTA Reference Manual Applications Guide. 12 kv Insulation Diagnostic System ZM-AH02E

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

Specialists in HV and MV test and diagnostics. Testing in Substations

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Transformer condition assessment with an integrated test van

Primary Test Manager (PTM) Testing and management software for primary assets

Variation in SFRA plot due to design and external parameter

TECHIMP Power Transformer Monitoring

EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY

Advanced Diagnostic Testing Services. Provides detailed and reliable results

TECHNIQUES AND STANDARD

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

SERVICE OFFERINGS FOR POWER SYSTEM STUDY & CONDITION MONITORING FOR STATIC EQUIPMENT

SAMPLE. Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs.

We can classify test failure modes in power transformers according to transformer components

CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW

EFFECETIVE TRANSFORMER CONDITION ASSESSMENT

DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER

Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

RESONANT TRANSFORMER

Effective maintenance test techniques for power transformers

Doble Test Procedures

(2) New Standard IEEE P (3) Core : (4) Windings :

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

MEDIUM & HIGH VOLTAGE

The measurement and normalisation of dielectric dissipation factor for diagnostics of transformer insulation

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

CDAX 605 High Precision Capacitance & Dissipation Factor Test Set

OMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES

Dielectric analysis of high-voltage power transformers DIAGNOSIS ABSTRACT KEYWORDS. 1. Introduction

Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission

Test description for dry-type transformers chapter for special tests

Phase Shifting Transformers. Presented by

ISSN: [IDSTM-18] Impact Factor: 5.164

Shunt Reactor Switching

Regional Technical Seminar SHORT CIRCUIT FORCES

Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC)

86 chapter 2 Transformers

Transformer Installation, Assembly & Testing

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

4. CAPACITIVE VOLTAGE TRANSFORMERS AND COUPLING CAPACITORS Oil-paper insulation

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

Impact Assessment Generator Form

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

Field Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis

Are snubbers required with Eaton s Cooper Power series liquid-filled hardened transformers?

Performing reliable and reproducible frequency response measurements on power transformers

- Continuous real-time measurement and PD trend analysis; not multiplexed data collection.

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

2013 Applied Power Electronics Conference (APEC) Page 1 of 8

Power Transformer Testing

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Diagnostic testing of cast resin transformers

Onsite Mobile AC High Voltage Test System

Martin Stoessl R&D Manager Siemens Transformers Austria - Weiz

Condition-based maintenance of power transformers Complete three-phase system Turns Ratio: Recovery Voltage: Winding Resistance:

Regional Technical Seminar

+ 24V 3.3K - 1.5M. figure 01

Transformers: Basics, Maintenance, and Diagnostics

Mitigating Murphy s Law While Test. Frédéric Dollinger

Transcription:

Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser - OMICRON

Transformers

Diagnostic Testing - OVERALL DGA Oil Screen Power Factor / Capacitance Exciting Current Transformer Turns Ratio Leakage Reactance DC Winding Resistance SFRA (Sweep Frequency Response Analysis) DFR (Dielectric Frequency Response) Thermal Imaging Insulation Resistance Partial Discharge

Transformer Tests Dielectric Thermal Mechanical DGA DGA SFRA Oil Screen Oil Screen Leakage Reactance PF/TD CAP IR PF/TD CAP Exciting Ima DC Winding RES Exciting Ima Turns Ratio Tests DC Winding RES DFR Insulation Resistance

Transformer Test Protocol 1. Overall Power Factor and Capacitance 2. Bushings (C1, C2, Hot Collar) 3. Exciting Current 4. Surge Arresters 9. IR 10. DFR 11. SFRA 12. DC Winding Resistance 5. Insulating Fluids 6. Leakage Reactance 7. Turns Ratio Test 8. Insulation Resistance

Diagnostic Tests 1. Overall Power Factor and Capacitance 2. Bushing Power Factor and Capacitance 3. Exciting Current Test 4. TTR Transformer Turns Ratio 5. Leakage Reactance (3-Phase Equivalent and Per Phase) 6. DC Winding Resistance

Industry Guides and Standards IEEE C57.152-2013, "IEEE Guide for Diagnostic Field Testing of Fluid-Filled Power Transformers, Regulators, and Reactors". ANSI/NETA MTS-2015, "Standard for Maintenance Testing Specifications for Electrical Power Equipment and Systems". IEEE C57.149-2012, "IEEE Guide for the Application and Interpretation of Frequency Response Analysis for Oil-Immersed Transformers".

Delta-Wye (Dyn1)

Two-Winding Transformer Model Windings are short-circuited to remove unwanted inductance CH, CL and CHL insulation systems CH includes H-C1 CL includes X-C1

Overall Power Factor - Test Preparation 1) Ensure that the transformer tank and core are solidly grounded, also connect both the test instrument and power source ground to this point. We will refer to this point as the GROUND node. 2) Ensure that all bushing surfaces are clean and dry. 3) Completely isolate the transformer terminals; remove external connections and buswork from H1, H2, H3, X1, X2, X3 and X0. 4) Bond/short the H1, H2, and H3, making sure that they are isolated. We will refer to this point as the HV node. 5) Bond/short the X1, X2, X3, and X0 making sure that they are isolated. We will refer to this point as the LV node. 6) Document tap-positions, temperatures, humidity, fluid levels, and pressures.

Overall Power Factor - Test Procedure The test voltages will be limited and should not exceed the line-toground rating of the insulation system. When convenient, Variable Frequency Power Factor Tests will be performed on CH, CL, and CHL insulation components, along with Power Factor Tip-Up measurements. Test Insulation Test Voltage * Test Mode Energize Red LV Lead 1 CH + CHL 10 kv GST HV LV 2a CH 10 kv GST-gA HV LV 2b CH(f) 2 kv (15-400 Hz) GST-gA HV LV 3a CHL 10 kv UST-A HV LV 3b CHL(f) 2 kv (15-400 Hz) UST-A HV LV 4 CL + CLH 7 kv GST LV HV 5a CL 7 kv GST-gA LV HV 5b CL(f) 2 kv (15-400 Hz) GST-gA LV HV 6a CLH 7 kv UST-A LV HV 6b CLH(f) 2 kv (15-400Hz) UST-A LV HV

Overall Power Factor - Expected Results IEEE C57.152 PF < 0.5% at 20 C for new liquid filled power transformers rated under 230kV PF < 0.4% at 20 C for new liquid filled power transformers rated over 230kV PF < 1.0% at 20 C for service aged liquid filled power transformers PFs between 0.5% and 1.0% at 20 C warrant additional testing and investigation NETA MTS PF < 1.0% for liquid filled power transformers PF < 2.0% for liquid field distribution transformers PF < 2.0% for dry-type power transformers (CHL insulation) PF < 5.0% for dry-type distribution transformers (CHL insulation) PF Tip-Up for dry-type insulation should be < 1.0% Note: Measured values should also be compared to the manufacturer s published data.

Bushing Power Factor Condenser Bushing with Potential Tap Condensers Bushing with Test Tap Non Condenser Visual Inspection Visual Inspection Visual Inspection C1 Power Factor (60 Hz) C1 Power Factor (60 Hz) Energize Collar Test C1 Capacitance (60 Hz) C1 Capacitance (60 Hz) Infrared Test C2 Power Factor (2.0 kv) C2 Capacitance (2.0 kv) Advance Power Factor Measurements Power Factor Tip Up Test C2 Power Factor (0.5 kv) C2 Capacitance (0.5kV) Advance Power Factor Measurements Power Factor Tip Up Test Infrared Test Infrared Test

Bushing Power Factor Test Connections C1 C2 Hot Collar

Bushing Power Factor - Expected Results Bushings shall remain shorted, similar to the overall power factor test. Failure to short the bushing terminals, may result in compromised measurements. Hot Collar tests are optional; they will not be performed if test taps or potential taps are available. Test taps and potential taps can be identified, based on the bushing rating, as follows: Test Taps <= 350 kv BIL Potential Taps > 350 kv BIL C2 tests must be performed carefully, ensuring that the hook is in the clear, completely. The C1 results should compare well with the nameplate data. C1 Power Factor values should not exceed 1.5X to 2.0X nameplate data. C1 capacitance should not exceed +/- 5% of nameplate data. C2 values should compare well with the nameplate or amongst similar bushings. The hot collar results are analyzed from watts loss. We expect less than 100 mw loss.

Transformer Exciting Current Test Vs 1. Apply Voltage Vs on on primary phase, secondary winding left floating 2. Measure currurent I ex 3. The current required to force ``transformer action (the use of one winding to induce a voltage in the second winding).

Exciting Currents - Analysis Strategy Confirm Expected Phase Pattern Confirm Expected LTC Pattern (For load tap changing transformers) Compare to Previous Results

Exciting Current - Analyzing Results Confirming the Expected Phase Pattern: 1. High Low High (HLH) Pattern Expected for a 3-legged core type transformer. Expected for a 5-legged core (or shell) type transformer with a Delta connected secondary winding. 2. Low High Low (LHL) Pattern Will be obtained on a 3-legged core type transformer if the traditional test protocals are not followed. Neutral on high side Wye-configured transformer is inaccessible Forget to ground 3 rd terminal on a Delta-connected transformer Expected for a 4-legged core type transformer. 3. All 3 Similar Pattern Expected for a 5-legged core (or shell) type transformer with a nondelta secondary winding.

Exciting Current Test Results Transformer: Delta Wye (Dyn1) H2 X2 X1 X0 H1 H3 X3 Test HV Lead LV Lead Ground Float Mode Measure Result 1 H1 H3 H2, X0 X1,X2,X3 UST H1-H3 63.8 ma 2 H2 H1 H3, X0 X1,X2,X3 UST H2-H1 48.6 ma 3 H3 H2 H1, X0 X1,X2,X3 UST H3-H2 64.2 ma

Turn Ratio - Expected Results

Turn Ratio - Expected Results The turn ratio measurement results should be within 0.5% of nameplate markings.

Leakage Reactance

Leakage Reactance Short circuit LV winding or winding pairs Inject 0.5-1.0% of rated current 60 Hz (Line-to-Line) A variable 280 VAC source is recommended Measure Series Current and Terminal Voltage RESULT - ZΩ, RΩ, and XΩ There are two ways to perform the measurement 1. 3 Phase Equivalent 2. Per Phase

Leakage Reactance - Example Nameplate: 6.85% 69 kv 12.5 MVA Phase V I Z R X L H1-H3 55.22 1.05 51.59 4.38 51.41 136.4 H2-H1 54.68 1.05 51.15 4.37 50.96 135.2 H3-H2 54.46 1.05 50.96 4.46 50.76 134.2

DC Winding Resistance - Failure Modes A change greater than the criteria mentioned can be indicative of the following: 1. Shorted Circuited Turns 2. Open Turns 3. Defective DETC or LTC (contacts) 4. A Poor Connection Between Terminals Measured

DC Winding Resistance - Case Study

Conclusion When performed properly, electrical diagnostic testing can provide useful and in depth information regarding the condition of the power transformer. Dielectric, thermal, and mechanical incipient failure modes can be identified. Care should be taken to ensure useful results. The test data is only as good as the technician performing the tests. The technician should always know what to expect; utilizing invalid test data can lead to an undesired result in the decision-making process. NETA and IEEE standards and guides provide comprehensive information regarding test plans test procedures test preparations, and analysis of the results.