CLU Arrester. Certified Test Report. IEEE Standard C

Similar documents
Effective February 2017 Supersedes January 2012 (CP1122)

Eaton s Cooper Power Series DEADFRONT ARRESTERS

UltraSIL Polymer-Housed VariSTAR Normal-Duty, Heavy-Duty and Riser Pole Distribution-Class Arresters

UltraSIL Polymer-Housed Evolution Distribution Class Surge Arrester Certified Test Report

ANSI DESIGN TEST REPORT Report No. EU1295-H-00 Type PVN Station Class Surge Arrester

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

VariSTAR Type AZU heavy-duty distribution-class under-oil MOV surge arrester

VariSTAR Type AZL heavy-duty distribution-class MOV arrester

Tab 8 Surge Arresters

COOPER POWER. UltraSIL Polymer-Housed VariSTAR Type U2Surge Arrester for Systems through 275 kv IEC 10-kA; Line Discharge Class 2 SERIES

IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4

POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

35 kv Class M.O.V.E. DirectConnect elbow arrester

Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

ArresterFacts-002. Field Testing Arresters ArresterWorks.com. ArresterFacts are information modules pertaining to the arrester world.

Surge Arresters. VariSTAR Type AZS Normal Duty Distribution Class MOV Arrester

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

Under-Oil ARRESTERS Page 1 July 2016

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

A SIMPLIFIED LIGHTNING MODEL FOR METAL OXIDE SURGE ARRESTER. K. P. Mardira and T. K. Saha s: and

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet

Energy Division. Bowthorpe LV/MV Surge Arresters

Electric Stresses on Surge Arrester Insulation under Standard and

Insulation Co-ordination For HVDC Station

New Modeling of Metal Oxide Surge Arresters

EE 1402 HIGH VOLTAGE ENGINEERING

Arrester 2050 JONATHAN WOODWORTH

Evaluating the Response of Surge Arresters

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

INTERNATIONAL STANDARD

Modeling insulation in high-voltage substations

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv

CVVOZE Power Laboratories (CVVOZEPowerLab)

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Howard Smart Transformer Specification Guide

Overvoltage Protection of Light Railway Transportation Systems

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

3EK8 distribution class surge arresters. Catalogue HP-AR Version siemens.com/arresters

PEAK OUTPUT CURRENT 1. MAP V 4.7V to 5.8V 8A 11A 0.2% ±1% 1% 4.9V to 5.1V PEAK OUTPUT CURRENT 4 LINE REGULATION

SURGE ARRESTERS AND TESTING. Keith Hill Doble Engineering Company

This convection-cooled series is designed for use in commercial and industrial environments in temperatures up to 50 C.

ArresterFacts 024. Separation Distance for Substations. ArresterFacts 024 Separation Distance for Substations. September 2014 Rev 7 Jonathan Woodworth

SURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES

What is the Value of a Distribution Arrester

The Many Uses of Transmission Line Arresters

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

MEDIUM & HIGH VOLTAGE

Selection of MO surge arresters Overvoltage protection

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

HIGH VOLTAGE Insulation Coordination

Single-output models feature wide-range output adjustability to meet a wide variety of standard and user-specific output voltage requirements.

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

Semiconductor (AC) fuses

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

SPECIFICATION SWITCHING POWER SUPPLY SINGLE POWER 250W BEST POWER SOLUTIONS, INC. 9F, NO.196-7, SEC.3, TA-TUNG RD SHI CHIH, TAIPEI, TAIWAN, R.O.C.

The VSX3622, a 1.5 kw X-Band GaN Power Amplifier for Radar Application

Vacuum Interrupters for Medium Voltage

SPECIFICATION SWITCHING POWER SUPPLY BPS-300SP/2U 6-OUTPUT WITH ACTIVE PFC FUNCTION SINGLE POWER 300W BEST POWER SOLUTIONS, INC.

Description. Features. Continuous BA Series BB Series Units Steady State Applied Voltage: AC Voltage Range (V M(AC)RMS

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

ISOLATING TRANSFORMERS FOR TLC PLANTS

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

Substation Insulation Coordination Study

Transformers connected via a cable Overvoltage protection

International Journal of Advance Engineering and Research Development. Analysis of Surge Arrester using FEM

TFI V DRM V DSM V RRM V RSM

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

Distribution Transformers

Transient Voltage Suppressor Diodes

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

(2) New Standard IEEE P (3) Core : (4) Windings :

7. INSPECTION AND TEST PROCEDURES

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

Construction zglass passivated collar zaluminum termination for pressure contact

Continuous C-III Series Units. ) 2ms Rectangular Wave 40 to 530 J Operating Ambient Temperature Range (T A

Errata to IEEE Standard Test Specification for Thyristor Diode Surge Protective Devices

60Hz Ratings. Typical Applications. Features & Characteristics. Ratings

Chip Varistor LVS B DESCRIPTION APPLICATIONS FEATURES ORDERING INFORMATION. Capacitance 030 = 3pF 300 = 30pF 301 = 300pF

G5NB. A Miniature Relay with 1-pole 3A/5A Switching Capability and 10 kv Impulse Withstand Voltage. Application Examples. Model Number Legend

TECHNICAL SPECIFICATION

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Chapter 1. Overvoltage Surges and their Effects

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

AS/NZS :2013 (IEC , , MOD)

Table 1: Results with standard impluse current 8/20 s applied to check for the residual voltage of V-MOV-ZnO

Electrical Measurement Safety. Sponsored By:

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

POWER TRANSFORMERS CATALOGUE

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

Transcription:

CP No.: CP0605 Page 1 of 8 CLU Arrester Certified Test Report IEEE Standard C62.11-1999 CERTIFICATION Statements made and data shown are, to the best of our knowledge and belief, correct and within the usual limits of commercial testing practice. Michael M Ramarge Chief Engineer Jonathan J Woodworth Arrester Engineering Manager October 2006 New Issue Cooper Power Systems, Inc.

CP No.: CP0605 Page 2 of 8 INTRODUCTION This test report certifies that the VariSTAR arresters CLU were successfully tested to IEEE C62.11-1999 Metal-Oxide surge arresters for a.c. circuits (>1kV). TEST PROGRAM OBJECT To demonstrate that the VariSTAR CLU Arrester meet all performance requirements. PROCEDURE The following design tests were performed on a sufficient number of samples to demonstrate all performance requirements are met. TYPE TESTS A. Insulation Withstand Test. Per IEEE C62.11 Section 8.1.1 B. Discharge-Voltage Characteristics a) Discharge-voltage Current Characteristics.... Per IEEE C62.11 Section 8.3.1 b) Discharge-voltage Time Characteristics Per IEEE C62.11 Section 8.3.2 C. Accelerated Aging Procedure. Per IEEE C62.11 Section 8.5 D. High Current, Short Duration... Per IEEE C62.11 Section 8.10.1 E. Low Current, Long Duration Per IEEE C62.11 Section 8.10.2 F. Operating Duty Cycle Test.. Per IEEE C62.11 Section 8.11 G. Power Frequency Voltage vs. Time. Per IEEE C62.11 Section 8.12.2 H. Failure Mode Test for Liquid-immersed Arresters a) Test for fail-open mode.. Per IEEE C62.11 Section 8.16.2.2 b) Test for fail-short mode.. Per IEEE C62.11 Section 8.16.2.3 RESULTS The VariSTAR CLU arresters met all performance requirements of IEEE C62.11-1999.

CP No.: CP0605 Page 3 of 8 TEST A: INSULATION WITHSTAND Test Report Number: 13-7351-20-05-039 To demonstrate the voltage withstand capability of the external insulation of the arrester housing. The test samples were mounted in mineral oil, meeting ASTM D3487-88 (1993), at room temperature. The samples were subject to positive and negative 1.2 X50 μs voltage impulses which were larger than the minimums in Table 4, IEEE C62.11-1999. These samples were also subject to 60 Hz withstand voltages higher than the minimums in Table 4, IEEE C62.11-1999. None of the samples flashed over during any of the above tests in accordance with requirements. TEST B: DISCHARGE-VOLTAGE CHARACTERISTICS Test Report Number: 13-7351-20-05-035 To determine the maximum discharge voltage for each discharge current. Discharge-Voltage Current Characteristics The sample arresters were impulsed using an 8 X 20 μs wave shape at 1.5, 3, 5, 10, 20, and 40kA crest. The discharge voltage crest was measured. Discharge-Voltage Time Characteristics A classifying current of 5kA crest was used to determine the equivalent front-of-wave protective level. The arresters were impulsed using front times of 8 μs, 2 μs, and 1 μs. The maximum discharge voltage and the time to voltage crest were measured. The voltage/time measurements were plotted on linear voltage versus log time paper and the maximum voltage at 0.5 μs was determined and recorded.

CP No.: CP0605 Page 4 of 8 Duty Cycle Voltage Rating (kv) Result: COV (kv) Front-of- Wave Protective Level (kv, crest) Maximum Discharge Voltage (kv, peak) 8/20 μs Current Wave Switching Surge (kv, peak) 30/60 μs Current Wave 1.5 ka 3 ka 5kA 10kA 20kA 40kA 500A 1.5 ka 3 2.55 10.5 8.6 9.2 9.9 10.8 12.4 14.4 7.5 8.1 6 5.10 20.9 17.1 18.5 19.8 21.6 24.7 28.7 15.0 16.2 9 7.65 31.5 25.8 27.8 29.8 32.6 37.2 43.2 22.6 24.3 10 8.40 33.4 27.4 29.5 31.6 34.5 39.4 45.9 24.0 25.8 12 10.2 42.0 34.4 37.0 39.7 43.4 49.5 57.6 30.1 32.4 15 12.7 50.8 41.6 44.8 48.0 52.5 59.9 69.6 36.4 39.2 18 15.3 63.1 51.6 55.6 59.6 65.1 74.4 86.5 45.2 48.7 21 17.0 66.9 54.7 59.0 63.2 69.1 78.9 91.7 48.0 51.6 24 19.5 77.3 63.3 68.2 73.1 79.9 91.2 106 55.5 59.7 27 22.0 89.8 73.5 79.2 84.9 92.8 106 123 64.4 69.4 30 24.4 97.8 80.0 86.2 92.4 101 115 134 70.1 75.5 33 27.0 111 90.9 98.0 105 115 131 152 79.7 85.8 36 29.0 117 96.1 104 111 121 139 161 84.2 90.7 TEST C: ACCELERATED AGING PROCEDURE Test Report Number: 13-7351-20-04-072 To verify K C (MCOV Ratio) and K R (Duty Cycle Ratio) of the arresters. MOV valve elements were placed in mineral insulating oil, meeting ASTM D3487-88 (1993), and energized at MCOV for a period of 7000 hours. The watts loss was measured at the MCOV and duty cycle voltage levels within two to five hours after the start of the test. The watts loss was re-measured at 7000 hours at MCOV and duty cycle voltage levels. Power ratios for both measurements were equal to or less than 1 for the 7000 hr test procedure in standard transformer oil (mineral oil based).

CP No.: CP0605 Page 5 of 8 TEST D: HIGH CURRENT, SHORT DURATION Test Report Number: 5A4-13-1 Cooper Power Systems, Olean, NY To demonstrate the ability of the arrester to meet the high current, short duration test requirements. The samples were tested in mineral oil meeting ASTM D3487-88 (1993) with a temperature 75 + 5 o C. The samples were subject to two 4/10 μs impulse current waves having 40kA crest amplitude. The samples were allowed to cool between impulses. Within five minutes of the second discharge each arrester was energized at the thermal recovery voltage for 30 minutes minimum. The samples achieved thermal stability and were not physically damaged. TEST E: LOW CURRENT, LONG DURATION Test Report Number: 5A4-12-1 To demonstrate the ability of the arrester to meet the low current, long duration test requirements. The samples were tested in mineral oil meeting ASTM D3487-88 (1993) with a temperature 20 + 5 o C. The samples were subject to twenty 2000 μs rectangular current waves having 75kA crest amplitude. The first eighteen impulses were applied in three groups of six operations and cool between groups of operations. Prior to the nineteenth impulse the arrester temperature was equilibrated at 120 o C. Within five minutes of the twentieth impulse the arrester was energized at the thermal recovery voltage for 30 minutes minimum. The samples met test requirements with less than 10% change in residual voltage, achieving thermal stability, and no physical damage.

CP No.: CP0605 Page 6 of 8 TEST F: OPERATING DUTY CYCLE TEST Test Report Number: 13-7351-20-05-034 To demonstrate the ability of the arrester to meet the duty cycle test requirements. The samples were tested in mineral oil meeting ASTM D3487-88 (1993). The samples were each energized at K R times the duty cycle voltage (K R = 1), for the duration of the time needed to allow 20 impulses. Each sample was impulsed with a 5kA crest surge of 8X 20 μs wave shape. The impulse occurred at approximately 60 o before the crest on the power frequency wave with 50-60 seconds between impulses. After the twentieth impulse the samples were heated to 120 + 5 o C. Once at temperature, the samples were impulsed at 5kA. Samples remained energized at the thermal recovery voltage for 30 minutes minimum. The samples met test requirements with less than 10% change in residual voltage, achieving thermal stability, and no physical damage.

CP No.: CP0605 Page 7 of 8 TEST G: POWER FREQUENCY VOLTAGE VS. TIME Test Report Number: 13-7351-20-05-033 To determine the over voltage values and time durations for the arrester design. The sample was placed in mineral oil meeting ASTM D8347-88 (1993) and heated to the temperature 120 o +5 o C. The sample was then subject to each over voltage at each specified time range. The recovery voltage was applied to the sample for thirty minutes.

CP No.: CP0605 Page 8 of 8 TEST H: FAILURE MODE TEST FOR LIQUID-IMMERSED ARRESTERS TEST FOR FAIL-OPEN MODE: Test Report Number: 13-7351-19-05-012 To verify the fail-open current rating above which the arrester is claimed to evolve into an open circuit upon failure. The samples tested were three of both the highest and lowest ratings available. The samples were mounted in mineral oil meeting ASTM 8347-88 (1993). Samples were prekilled using an over voltage applied less than 5 minutes. The arresters failed open above 1250 Amps. TEST FOR FAIL-SHORT MODE: Test Report Number: 13-7351-19-05-009 To verify the fail-open current rating below which the arrester is claimed to evolve into a short circuit upon failure. The samples tested were three of both the highest and lowest ratings available. The samples were mounted in mineral oil meeting ASTM 8347-88 (1993). Samples were prekilled using an over voltage applied less than 5 minutes. The arresters failed short up to 5kA.