Technical information TI 095R/24/ae Nr. 510 06165 Temperature transmitter itemp RTD DIN rail TMT 127 Pt100 transmitter for an economical, high accuracy temperature monitoring. Fixed range measurement, for installation on a DIN rail. Application Economical and technical alternative to direct wiring to DCS or PLC Fixed adjusted temperature Din-rail mounted transmitter for converting various input signals into a scalable 4 to 20 ma analog output signal 2-wire transmitter for a linear temperature proportional analog output Features and benefits High accuracy: 0.08 % of span Breakdown information in event of sensor break or sensor short-circuit enables a quick maintenance intervention Galvanic isolation 2 kv (from the sensor input to the output) Long term stability: < 0.05 %/year Electromagnetic compatibility to IEC 61326 for use in noisy environments Approvals: FM, CSA and ATEX for high safety standards UL recognized component to UL 3111-1 GL German Lloyd marine approval
Function and system design Measuring principle Measuring system Electronic monitoring and conversion of input signals in industrial temperature measurement. The itemp RTD DIN rail TMT 127 DIN rail temperature transmitter is a 2-wire transmitter with analog output, measuring input for Pt100 in 2, 3, or 4-wire connection. Input values Measured variable Measuring range Input type Temperature Depending on the application, different measuring ranges can be ordered (see Product structure ). Input Designation Measuring range limits Min. span Resistance thermometer (RTD) Pt100 as per IEC 751-328 to 1562 F (-200 to 850 C) 18 F (10 C) Type of connection: 2, 3 or 4-wire connection Cable resistance: sensor cable resistance of max. 40 per cable Sensor current: 0.6 ma Output values Output signal Analog 4 to 20 ma Breakdown information Breakdown information to NAMUR NE 43 Breakdown information is created when the measuring information is invalid or not present anymore and gives a complete listing of all errors occuring in the measuring system. Under ranging Standard 3.8 Over ranging Standard 20.5 Signal (ma) Sensor break; sensor short circuit low Sensor break; sensor short circuit high To NAMUR NE 43 3.6 To NAMUR NE 43 21.5 Source impedance Transmission behavior Galvanic isolation Induced current requirement Current limitation Switch-on delay Max. (V Power supply - 12V) / 0.022 A (current output) e. g. (24 V - 12 V)/0.022 A = 545.5 Temperature linear U = 2 kv AC (input/output) 3.5 ma 23 ma 4 s (during switch-on procedure I a 3.8 ma) 2
Power supply Electrical connection Temperature transmitter terminal assignment Supply voltage Residual ripple U b = 12 to 35 V, reverse polarity protection Permitted residual ripple U ss 3 V at U b 15 V, f max. = 1 khz Accuracy Response time Reference operating conditions Measuring error 1 s Calibration temperature: + 73.4 F ± 9 F (+ 23 C ± 5 C) Designation Accuracy 1 Resistance thermometer RTD Pt100 0.36 F (0.2 C) or 0.08% 1) % refer to the set span. The highest value is valid. Influence of supply voltage Influence of ambient temperature (temperature drift) Influence of load Long-term stability ±0.01%/V deviation from 24 V Percentages refer to the full scale value. Pt100 resistance thermometer: T d = ±(8.3 ppm/ F * (full scale value + 200) + 27.8 ppm/ F * of set measuring range) * = deviation of ambient temperature from the reference operating condition (+73.4 F ± 9 F). ± 0.02%/100 Percentages refer to the full scale value. 0.18 F/year ( 0.1 C/year) or 0.05%/year Values under reference operating conditions. % refer to the set span. The highest value is valid. 3
Installation conditions Installation instructions Orientation No limit Environmental conditions Ambient temperature -40 to 185 F (-40 to +85 C) for Ex-area, see Ex-certification or control drawing Storage temperature -40 to 212 F (-40 to +100 C) Climate class as per IEC 60 654-1, Class C Ingress protection NEMA 1 (IP 20) Shock and vibration resistance 4g / 2 to 150 Hz as per IEC 60 068-2-6 Electromagnetic compatibility (EMC) CE Electromagnetic Compatibility Compliance The device meets all requirements listed under IEC 61326 Amendment 1, 1998 and NAMUR NE 21. This recommendation is an uniform and practical way of determining whether the devices used in laboratory and process control are immune to interference with an objective to increase its functional safety. Discharge of static electricity IEC 61000-4-2 6 kv cont., 8 kv air Electromagnetic fields IEC 61000-4-3 80 to 1000 Hz 10 V/m Burst (signal) IEC 61000-4-4 2 kv Transient voltage IEC 61000-4-5 1 kv unsym. / 0.5 kv sym. HF coupling IEC 61000-4-6 0.15 to 80 MHz 10 V Condensation allowed 4
Mechanical construction Design, dimensions Values in inch (mm) Weight approx. 3.2 oz (90 g) Materials Terminals Housing: PC/ABS, UL 94V0 Keyed plug-in screw terminals, core size max. 16 AWG solid, or strands with ferrules Display and operating system Display elements Operating elements Illuminated yellow LED (0.08 in, 2 mm) signals device operation. There are no operating elements available on the transmitter to prevent from manipulation. Certificates and approvals CE-Mark Hazardous area approvals GL The measurement system fulfils the requirements demanded by the EU regulations. Endress+Hauser acknowledges successful unit testing by adding the CE mark. FM IS, Class I, Div. 1+2, Group A, B, C, D CSA IS, Class I, Div. 1+2, Group A, B, C, D ATEX II 2(1)G EEx ia IIC T4/T5/T6 ATEX II 3G EEx na IIC T4/T5/T6 Ship building approval (Germanischer Lloyd) UL Recognized component to UL 3111-1 Other standards and guidelines IEC 60529: Degrees of protection by housing (IP-Code) IEC 61010: Safety requirements for electrical measurement, control and laboratory instrumentation. IEC 61326: Electromagnetic compatibility (EMC requirements) NAMUR Standardization association for measurement and control in chemical and pharmaceutical industries. (www.namur.de) NEMA Standardization association for the electrical industry 5
Ordering information Product structure Temperature transmitter itemp RTD DIN rail TMT 127 for temperature measurement with Pt100; Analog output 4 to 20 ma, 2-wire techn.; Galv. isol., fail. mode to NAMUR NE 43; 22.5 mm wide, for 35 mm top hat DIN rail according to EN 50022; UL recognized, ship building approval GL Certification A Version for non hazardous areas, UL recognized, ship building approval GL B ATEX II2(1)G EEx ia IIC T4/T5/T6 C FM IS, Class I, Div.1+2, Group A,B,C,D D CSA IS, Class I, Div.1+2, Group A,B,C,D E ATEX II3G EEx na IIC T4/T5/T6 Transmitter connection 2 Connection RTD 2-wire 3 Connection RTD 3-wire 4 Connection RTD 4-wire Temperature sensor 1 Configuration Pt100-200 to 850 C, min. sp. 10 C Configuration range 1 LA Range -40 to 140 F LB Range -40 to 200 F MA Range -20 to 400 F NA Range 0 to 100 F NB Range 0 to 200 F NC Range 0 to 300 F ND Range 0 to 500 F NE Range 0 to 750 F NF Range 0 to 900 F NH Range 0 to 1200 F AA Range -100 to 50 C BB Range -50 to 200 C FG Range 0 to 150 C Model A B K Standard model Works calibration certificate (6 test points) Standard model, North America region TMT127 1 Order code (complete) 1 more ranges available on request Accessories No accessories are required for this device. Documentation System information Temperature measurement (SI 008R/24/ae) Operating manual itemp RTD/TC DIN rail TMT 127/128 (BA 157R/24/ae) Short operating manual itemp RTD/TC DIN rail TMT 127/128 (KA 140R/09/a3) Additional documentation for use in explosion-hazardous area: ATEX II2(1)G: XA 013R/09/a3 ATEX II3G: XA 018R/09/a3 Control Drawings: FM IS, NI 510 05062 CSA IS, NI 510 05575 6
For application and selection assistance, in the U.S. call 888-ENDRESS For total support of your installed base, 24 hours a day, in the U.S. call 800-642-8737 Visit us on our web site, www.us.endress.com United States Canada Mexico Endress+Hauser, Inc. 2350 Endress Place Greenwood, IN 46143 Phone: (317) 535-7138 888-ENDRESS FAX: (317) 535-8498 Endress+Hauser Canada Ltd. 1440 Graham s Lane Unit 1, Burlington ON, L7S 1W3 Phone: (905) 681-9292 800-668-3199 FAX: (905) 681-9444 Endress+Hauser Paseo del Pedregal No. 610 Col, Jardines del Pedregal 01900, Mexico D. F. Mexico Phone: (525) 568-2405 FAX: (525) 568-7459 TI 095R/24/ae/04.03 51006165 FM+SGML 6.0 ProMoDo