Enhancement of AC System Stability using Artificial Neural Network Based HVDC System

Similar documents
HVDC Transmission Using Artificial Neural Networks Based Constant Current and Extension Angle Control

Power Flow Control in HVDC-Link Using Artificial Neural Networks

Power Flow Control in HVDC Link Using PI and Ann Controllers

HVDC Control System - Overview

Power Flow Control And Total Harmonic Distortion Reduction In HVDC Link Using PI And ANN Controllers

Effects and Mitigation of Post-Fault Commutation Failures in Line-Commutated HVDC Transmission System

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling

High Voltage DC Transmission 2

Application Of Artificial Neural Network In Fault Detection Of Hvdc Converter

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

ABB Power Systems AB Sweden

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN

Basic Concept, Operation and Control of HVDC Transmission System

BHARATHIDASAN ENGINEERING COLLEGE, NATTRAMPALLI DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING UNIT I

Simulation & Performence Analysis Of HVDC Multigrid Transmission System Using Statcom

Chapter 11. Advanced Controllers 11.1 INTRODUCTION

Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System

Dynamic Performance Evaluation of an HVDC Link following Inverter Side Disturbances

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

The Thyristor based Hybrid Multiterminal HVDC System

1400 MW New Zealand HVDC Upgrade: Introducing Power Modulation Controls and Round Power Mode

Voltage Source Converter Modelling

A new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant alternating voltage

29 Level H- Bridge VSC for HVDC Application

Reactive Power and AC Voltage Control of LCC HVDC System with Digitally Tunable Controllable Capacitors

Modelling and Simulation of Monopolar HVDC Transmission System Feeding a Strong AC Network with Firefly Algorithm based Optimal PI Controller

Koganti Sri Lakshmi, G.Sravanthi, L.Ramadevi, Koganti Harish chowdary

Chapter 4. HVDC Controls 4.1 HISTORICAL BACKGROUND

Identification of Faults in HVDC System using Wavelet Analysis

Steady State Fault Analysis of VSC- HVDC Transmission System

ANALYSIS OF MULTI-TERMINAL HVDC TRANSMISSION SYSTEM FEEDING VERY WEAK AC NETWORKS

IMPORTANCE OF VSC IN HVDC

ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas

Dynamic Performance Comparison of Conventional and Capacitor Commutated Converter (CCC) for HVDC Transmission System in Simulink Environment

Hybrid Simulation of ±500 kv HVDC Power Transmission Project Based on Advanced Digital Power System Simulator

HVDC High Voltage Direct Current

Power Transmission of AC-DC Supply in a Single Composite Conductor

Power Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer

II. RESEARCH METHODOLOGY

Topics in JNTU Syllabus Modules and Sub Modules Lecture. Basic characteristics L21 T1-Ch4, T2-Ch14 Characteristics. Modification of the control

Simulation Study of a Monopole HVDC Transmission System Feeding a Very Weak AC Network with Firefly Algorithm Based Optimal PI Controller

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

POWER QUALITY ENHANCEMENT BY DC LINK SUPPLIED INDUSTRIAL SYSTEM

IDENTIFICATION OF POWER QUALITY PROBLEMS IN IEEE BUS SYSTEM BY USING NEURAL NETWORKS

DEVELOPMENT OF NEURO-FUZZY CONTROLLER FOR A TWO TERMINAL HVDC LINK

New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

INDEPENDENT CONTROL OF MULTI-TERMINAL VOLTAGE SOURCE CONVERTER-BASED HIGH-VOLTAGE DIRECT CURRENT LINK ANALYZING FOR DIRECT CURRENT FAULTS

APPLICATION OF INVERTER BASED SHUNT DEVICE FOR VOLTAGE SAG MITIGATION DUE TO STARTING OF AN INDUCTION MOTOR LOAD

Modelling of the back-to-back converter between Uruguay and Brazil in A.T.P.

ATC s Mackinac Back to Back. Summary

CHAPTER 5 CONTROL SYSTEM DESIGN FOR UPFC

Buck Boost AC Chopper

Damping of Sub-synchronous Resonance and Power Swing using TCSC and Series capacitor

Transient Stability Improvement of Multi Machine Power Systems using Matrix Converter Based UPFC with ANN

Simulative Study into the Development of a Hybrid HVDC System Through a Comparative Research with HVAC: a Futuristic Approach

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 07, 2014 ISSN (online):

Facilitating Bulk Wind Power Integration Using LCC HVDC

II. SINGLE PHASE BOOST TYPE APFC CONVERTER

Introduction to HVDC in GB. Ian Cowan Simulation Engineer 12 March 2018

Voltage Control and Power System Stability Enhancement using UPFC

Development of Multilevel Inverters for Control Applications

Speed Control of Induction Motor using Space Vector Modulation

Harmonic Analysis of Sine PWM and hysteresis current controller

Introduction to HVDC Transmission. High Voltage Direct Current (HVDC) Transmission

Shunt active filter algorithms for a three phase system fed to adjustable speed drive

14. DC to AC Converters

Dynamic performance of an HVDC link based on protection function against commutation failures

International Journal of Advance Engineering and Research Development. Analysis of Power Factor Control Technique for CUK Converter

Investigation of Hybrid Pseudo Bipolar HVDC Performances Supply Power to Passive AC Network

Power System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )

Sensorless Control of BLDC Motor Drive Fed by Isolated DC-DC Converter

ANALYSIS OF RECOVERY FROM COMMUTATION FAILURES IN AN HVDC INVERTER CONNECTED TO A WEAK RECEIVING AC SYSTEM

B4-212 OPERATING EXPERIENCES AND RESULTS OF ON-LINE EXTINCTION ANGLE CONTROL IN KII CHANNEL HVDC LINK

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

A Comparative Study between DPC and DPC-SVM Controllers Using dspace (DS1104)

DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS

Modeling and Simulation of Five Phase Induction Motor Fed with Five Phase Inverter Topologies

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Swinburne Research Bank

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

CHAPTER 6 THREE-LEVEL INVERTER WITH LC FILTER

Volume I Issue VI 2012 September-2012 ISSN

A Predictive Control Strategy for Power Factor Correction

ISSN Vol.04,Issue.16, October-2016, Pages:

International Journal of Advance Engineering and Research Development

Thyristors. In this lecture you will learn the following. Module 4 : Voltage and Power Flow Control. Lecture 18a : HVDC converters.

Control of Wind Power Plant for Cooperation with Conventional Power Generation Unit and HVDC Classic Link

POWER UPGRADATION AND POSSIBILITY OF SMALL POWER TAPPING FROM COMPOSITE AC- DC TRANSMISSION SYSTEM

AN EXPERIMENTAL INVESTIGATION OF PFC BLDC MOTOR DRIVE USING BRIDGELESS CUK DERIVED CONVERTER

MATLAB/Simulink Based Model for 25 kv AC Electric Traction Drive

Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC)

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Open Access Research on Fast Response Characteristic of Magnetic Control Reactor

Modeling and Simulation of Wind Farm with STATCOM in PSCAD/EMTDC Environment

Transcription:

Volume: 02 Issue: 03 June-2015 www.irjet.net p-issn: 2395-0072 Enhancement of AC System Stability using Artificial Neural Network Based HVDC System DR.S.K.Bikshapathy 1, Ms. Supriya Balasaheb Patil 2 1 HOD, Electrical & Electronics engineering, Siddhartha Institute of Engineering Technology, Telangana, India 2 Student, Electrical & Electronics engineering, Siddhartha Institute of Engineering Technology, Telangana, India ---------------------------------------------------------------------***--------------------------------------------------------------------- Abstract - With growing industrialization, power generation and demand are increasing very fast. To handle large bulk amount of power, AC power transmission is not economical over long distances. High Voltage Direct Current (HVDC) transmission is the only alternative to it. The advantages gained by DC power transmission outweigh the complexity of its operation and maintenance. HVDC transmission systems, when installed, often form the backbone of an electric power system. They combine high reliability with a long useful life. Their core component is the power converter, which serves as the interface to the AC transmission system. The conversion from AC to DC, and vice versa, is achieved by controllable electronic switches (valves) in a 3-phase bridge configuration. This paper is concerned with the design and optimization of intelligent controller (particularly ANN) Figure 1: Overall HVDC transmission system for a HVDC system. A MATLAB program has been developed to simulate the system operation. Various simulation results are presented under steady state conditions and performance of ANN and PI controllers is compared. Simulation results obtained shows that the performance of ANN controller is found to be better than PI controller. PWM pattern generation is based on carrier less hysteresis based current control to obtain the switching signals to the Voltage source power converter. Key Words: High voltage direct current, Voltage Dependent Current Order Limiter, Current Control Amplifier, Artificial Neural Network, Voltage Control Amplifier 1. Introduction supplied to each household. Such power transmission method makes it possible to transmit electric power in an economic way through up-conversion of voltage, which is an advantage in existing AC transmission technology and to overcome many disadvantages associated with AC power transmission as well. The overall structure of an HVDC system is shown in Figure 1. Figure 2 represents the overall components of HVDC system used. In this model, two 6-pulse converters are connected in series (bipolar 6-pulse converter) instead of a 12 pulse converter. In a real system, 12 pulse converters are used but bipolar 6-pulse converter is used here for simplicity and ease of computation. HVDC transmission refers to the AC power generated at a power plant is transformed into DC power before its transmission. At the inverter (receiving side), it is then transformed back into its original AC power and then Figure 2: HVDC substation with its basic components 2015, IRJET.NET- All Rights Reserved Page 2321

1.1 HVDC Controller Structure Figure 3 shows the basic control diagram of an HVDC system. An HVDC system can be divided into several levels. Master control determines the power order or frequency order and calculates the current order for both poles. Then, the current order that was received from master control is modified by control functions and limits in pole control. Valve group control consists of a converter control and a valve firing control. The converter control includes the current controller. The valve firing control distributes the firing signal to all thyristors. Figure 4: Steady state - characteristics for a two terminal HVDC system Figure 3: Basic control diagram of an HVDC system 2. CONVERTER CONTROL TECHNIQUES HVDC transmission systems must transport very large amounts of electric power which can only be accomplished under tightly controlled conditions. DC current and voltage is precisely controlled to effect the desired power transfer. It is necessary therefore to continuously and precisely measure system quantities which include at each converter bridge, the DC current, its DC side voltage, the delay angle α and for an inverter, its extinction angle γ. Two terminal DC transmission systems are the more usual and they have in common a preferred mode of control during normal operation. Under steady state conditions, the inverter is assigned the task of controlling the DC voltage. This it may do by maintaining a constant extinction angle γ which causes the DC voltage to droop with increasing DC current as shown in the minimum constant extinction angle γ characteristic A-B-C-D in Figure 4. The weaker the AC system at the inverter, the steeper the droop. Alternatively, the inverter may normally operate in a DC voltage controlling mode which is the constant characteristic B-H-E in Figure 4. This means that the extinction angle γ must increase beyond its minimum setting depicted in Figure 4 as 180. If the inverter is operating in a minimum constant γ or constant characteristic, then the rectifier must control the DC current I d. This it can do so long as the delay angle α is not at its minimum limit. The steady state constant current characteristic of the rectifier is shown in Figure 8 as the vertical section Q-C-H-R, where the rectifier and inverter characteristic intersect, either at points C or H, is the operating point of the HVDC system. The operating point is reached by the action of on-line tap changers of the converter transformers. The inverter must establish the DC voltage U d by adjusting its on-line tap changer to achieve the desired operating level if it is in constant minimum γ control. If in constant U d control, the on-line tap changer must adjust its tap to allow the controlled level of U d be achieved with an extinction angle equal to or slightly larger than its minimum setting of 180 in this case. The on-line tap changers on the converter transformers of the rectifier are controlled to adjust their tap settings so that the delay angle has a working range at a level between approximately 100 and 150 for maintaining the constant current setting. If the inverter is operating in constant DC voltage control at the operating point H, and if the DC current order is increased so that the operating point H moves towards and beyond point B, the inverter mode of control will revert to constant extinction angle γ control and operate on characteristic A-B. DC voltage will be less than the desired value, and so the converter transformer on-line tap changer at the inverter will boost its DC side voltage until DC voltage control is resumed. Not all HVDC transmission system controls have a constant DC voltage control such as is depicted by the 2015, IRJET.NET- All Rights Reserved Page 2322

horizontal characteristic B-H-E in Figure 4. Instead, the constant extinction angle control characteristic A-B-C-D and the tap changer will provide the DC voltage control. 2.1 HVDC Control Normally, HVDC system operates in constant power control mode. Power order is given by the user. Current order () derived from the power controller, which is send to the VDCOL (Voltage Dependent Current Order Limiter) and into the Current Control Amplifier (CCA). The alpha order from the CCA is send to the converter firing control which determines the firing instant of valves. Figure 5 shows HVDC control overview. Figure 6: HVDC control system layout Constant voltage control is normally used under reduced voltage operation; the is set to higher value at normal voltage operation to avoid hunting between alphamax and Voltage controller. But in reduced voltage operation shall be reduced to nominal reduced voltage. Figure 7 shows Overview of HVDC regulator. Figure 5: HVDC control overview The primary function of HVDC controls are: Fast and flexible power control between the terminals under steady state and transient operation. Better stability of AC system. Fast protection of AC and DC system faults. Minimizes over voltage across the valves. Reduces the short circuit current through the valves and lines/cables Reduces the reactive power consumption. Avoids repetitive commutation failures. The above advantages are achieved by varying exact firing instant of valves. The converter firing control determines the firing instants for each valve to obtain the rated DC voltage. The input for the firing control system could be the output of current control, voltage control, minimum alpha control and minimum commutation margin control mode. Figure 7: Overview of HVDC regulator 2.2 Voltage Dependent Current Order Limiter (VDCOL) Figure 8 shows control diagram of Voltage Dependent Current Order Limiter (VDCOL). The layout of HVDC system is shown in the Figure 6 below: Figure 8: Voltage Dependent Current Order Limiter 2015, IRJET.NET- All Rights Reserved Page 2323

The main function of VDCOL control is to reduce the current order to lower value when there is a reduction in DC voltage due to contingencies, in order to prevent the higher consumption of reactive power and valve voltage stress. If the system is operating in constant power control mode, current would be increased to maintain the constant power at low voltage causes higher consumption of reactive power will decrease the AC voltage further and induce commutation failure during the recovery of DC system. The break points for DC voltages are typically between 70% and 30%. These breakpoints could vary relative to the strength of the AC system. Normally, the long lines have same. High breakpoints for both rectifier and inverter but in contrast long cables need different. High break points for charging the cable i.e., 50% for rectifier and 90% for inverter. If there is fault in the inverter end, voltage would decrease greatly, if the VDCOL is not activated, the power control mode will increase the current to keep the power constant. Increased current will increase the reactive power consumption of converter; it will increase the risk of subsequent commutation failures if the AC system is relatively weak. The low pass filter time constants U d_t c_dn and U d_t c_up are down time and up time delay of break point limits. The down time for the inverter should be fast to prevent commutation failures but for rectifier it need not be too fast during inverter fault there is a threshold limit for VDCOL (0.8), if the DC voltage reaches threshold value; current order is decreased very rapidly to predefined lower value to prevent the consecutive commutation failure during inverter side AC fault. The down time constant could be same for both stations. But the up time constant could not be, rectifier should restart before the inverter. So, the up time constant for inverter should be higher than rectifier (mostly depends upon how strong the AC system is). Contrary, if the inverter restarts first, it starts building the counter voltage and thus the DC current, might lose the current margin causing power reversal. This function prevents the commutation failure during the recovery. Obviously the valve stress is reduced. The output of voltage regulator is used as maximum and minimum limits of current control amplifier with respect to converter (rectifier/inverter). In normal voltage operation, the reference voltage of the voltage regulator is set above the operating voltage in order to avoid the hunting between normal tap changer controller and voltage controller. The output from the voltage and angle reference calculation has multiplied by factor of one tap changer step for inverter voltage. This reference voltage is sent as input for voltage regulator. Even higher reference value shall be used in rectifier voltage controller in order to de-activate if it is active at inverter station. Figure 9 shows block diagram of combined CCA and VCA. Figure 9: Combined CCA and VCA 3. Artificial Neural Network Controller Artificial Neural Networks (ANNs) are gaining widespread application in several areas of engineering, especially where, due to non-linearity of the process, it is often too cumbersome to analyze the process or the plant under study. The ANN has the capability to learn and extract information in systems where the non-linearity and time dependency do not permit one to use methods such as frequency or modal analysis. Although it is always possible to linearise such a system around an operating point and conduct such studies, derived models always remain valid only within the limited region. The controller implementation is shown in figure 10. Figure 10: Controller Implementation Figure 11: ANN Network Layers 2015, IRJET.NET- All Rights Reserved Page 2324

Figure 12: ANN network with hidden and output layers The number of hidden neurons in an ANN is one of the main characteristics of the system. The number of neurons in an ANN determines the total number of unknowns in the network. The larger the number of neurons, the more time consuming and lengthy is the learning process. Figure 14: Current response of PI & ANN controllers under No fault condition at the rectifier 4. Simulation & simulation result The system is a mono-polar 500-kV, 1000-MW HVDC link with 12-pulse converters on both rectifier and inverter sides and connected to weak AC system (short circuit ratio of 2.5 at a rated frequency of 50Hz) that provides a considerable degree of difficulty for DC controls. AC filters are added to absorb the harmonics generated by the converter as well as to supply reactive power to the converter. The simulation of CIGRE HVDC Benchmark System is carried out in MATLAB-SIMULINK. Figure 13 shows SIMULINK diagram of HVDC 12-pulse transmission system. Figure 15: Voltage response of PI & ANN controllers under No fault condition at the rectifier Figure 13: SIMULINK diagram of HVDC 12-pulse transmission system 4.1 Simulation Results without Fault Condition Figure 14 and Figure 15 shows the system voltage and current waveforms under no fault condition at the rectifier side using PI and ANN controllers. Figure 16 and Figure 17 shows the system voltage and current waveforms under no fault condition at the inverter side using PI and ANN controllers. Figure 18 shows Power response under no fault condition. Figure 16: Current response of PI & ANN controllers under No fault condition at the inverter 2015, IRJET.NET- All Rights Reserved Page 2325

Figure 17: Voltage response of PI & ANN controllers under No fault condition at the inverter Figure 20: Voltage response of PI & ANN controllers under DC fault condition at the rectifier Figure 18: Power response of PI & ANN controllers under No fault condition Figure 21: Current response of PI & ANN controllers under DC fault condition at the inverter 4.2 Simulation Results with DC Fault Figure 19 and Figure 20 shows the system voltage and current waveforms under DC fault condition at the rectifier side using PI and ANN controllers. Figure 21 and Figure 22 shows the system voltage and current waveforms under DC fault condition at the inverter side using PI and ANN controllers. Figure 23 shows the Power response for DC fault. Figure 20: Voltage response of PI & ANN controllers under DC fault condition at the inverter Figure 19: Current response of PI & ANN controllers under DC fault condition at the rectifier 2015, IRJET.NET- All Rights Reserved Page 2326

[4] L. A. Cabrera, M. E. Elbuluk, and D. S. Zinger, Learning Techniqus to Train Neural Networks as a State Selector for Inverter-Fed Induction Machines using Direct Torque Control, IEEE Transactions on Power Electronics,Vol. 12, No. 5, September 1997, pp. 788-799. [5] A. Ekstrom and G. Liss, "A Refined HVDC Control System," IEEE Transactions on Power Apparatus and Systems, Vol. PAS 89, No. 5, May/June 1970, pp. 723-732. Figure 21: Power response of PI & ANN controllers under DC fault condition [6] N.G.Hingorani, Power Electronnics in Electronic Utilities: Role of Power Electronics in Future Power System, Proceeding of the IEEE, vol.76, no.4, April, 1988, pp. 481-482. 5. CONCLUSIONS A HVDC system is designed to control the power flow between two converter stations with Artificial Neural Networks. For rectifier side, current control is used and for inverter side both current and extinction angle control is implemented. In order to transfer maximum power in the DC link, we have to maintain minimum alpha. The error signal is passed through an Artificial Neural Networks controller, which produces the necessary firing angle order. The firing circuit uses this information to generate the equidistant pulses for the valves in the converter station. Here, Artificial Neural Networks is designed for both rectifier and inverter control and its performance is compared with conventional (PI) controller. REFERENCES [1] Lee Wei Sheng Razani, A. Prabhakaran, N., "Control of High Voltage Direct Current (HVDC) bridges for power transmission systems," Research and Development (SCOReD), 2010 IEEE Student Conference on, Vol. No. pp. 430,435, 13-14 Dec. 2010. [2] Narendra, K. G. Sood, V.K. Khorasani, K. Patel, R.V., "Investigation into an artificial neural network based on-line current controller for an HVDC transmission link," Power Systems, IEEE Transactions on, Vol.12, No.4, pp. 1425, 1431, Nov 1997. [3] Faruque, M.O. Yuyan Zhang Dinavahi V., "Detailed modeling of CIGRE HVDC benchmark system using PSCAD/EMTDC and PSB/SIMULINK," Power Delivery, IEEE Transactions on, Vol.21, No.1, pp. 378, 387, Jan. 2006. BIOGRAPHIES DR.S.K.Bikshapathy ME,PhD,FIE,LMISTE Head of Dept. of Electrical & Electronics Engineering, Siddhartha Inst. of Engineering & Technology, Vinoba Nagar, Ibrahimpatnam, MS. Supriya balasaheb patil M.tech Electrical power System Student in Siddhartha Institute of Engineering & Technology, Vinoba Nagar, Ibrahimpatnam, 2015, IRJET.NET- All Rights Reserved Page 2327