KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 3M TO DETERMINE THE SHEAVE CRITERIA FOR 774 KCMIL 3M TM COMPOSITE CONDUCTOR

Similar documents
AEOLIAN VIBRATION TEST ON 1572 KCMIL BITTERN ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION

KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 3M COMPANY TO COMPARE THE LIGHTNING PERFORMANCE OF ACCR TO ACSR CONDUCTORS

SEQUENTIAL MECHANICAL TESTING OF 1020 KCMIL DRAKE ACCC/TW CONDUCTOR. Kinectrics North America Inc. Report No.: K RC-0001-R00.

SELF DAMPING TEST ON 1020 KCMIL ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION

Optical Ground Wire Fiber Optic Cable. Design Qualification Testing IEEE solutions. for the real world

Page 1 of 5 Application Engineering Note Proc. 001 Interlock Armor and Corrugated Steel Tape Cables Pulling Grip Installation Procedure Rev.

Slack Span Dead-end. Slack Span Dead-end GENERAL RECOMMENDATIONS NOMENCLATURE 14-23

Structural Strength of Lapped Cold-Formed Steel Z-Shaped Purlin Connections with Vertical Slotted Holes

MESP TECHNICAL SPECIFICATION FOR BARE FLEXIBLE ANNEALED COPPER JUMPER WIRE 37/7/ mm 2

Copyright. Michael Joseph Gilroy. May 1997

INCH-POUND. MIL-DTL June 2008 DETAIL SPECIFICATION WIRE ROPE, 1.5 INCH DIAMETER, GALVANIZED, COMPACTED STRAND, FOR AIRCRAFT ELEVATOR

Industrial Solutions & Innovation, LLC. Watts Specialties

MEGA MOUTH HEAVY DUTY 3 WHEEL SLICKLINE MEASUREMENT DEVICE WITH COMBINED DEPTH AND TENSION CERTIFIED FOR USE IN A ZONE 2 ENVIRONMENT

TUTORIAL 4: Combined Axial and Bending Problem Sketch Path Sweep Initial Project Space Setup Static Structural ANSYS

APPENDIX E INSTRUMENT VERIFICATION STRIP REPORT. Final Remedial Investigation Report for the Former Camp Croft Spartanburg, South Carolina Appendices

Pow-R-Feed Systems Service Manual

Installation Instructions for OPGW Bolted Dead End

2. CONDUCTORS. 2.1 Strand Types. 2.2 Coatings Tensile Strength of Copper Wire Copper Strand Properties. 2.5 Aluminum Strand Properties

Rejuvenate An Old Tinius Olsen Machine with Computer Data Acquisition Using Its Existing Hardware and LabVIEW

Fluid Sealing Association

Machining Titanium. Losing the Headache by Using the Right Approach (Part 2)

Drawing. Fig. 1 Drawing

RUS Accepted NOMENCLATURE GENERAL RECOMMENDATIONS (440) EN-CA

Coated Dead-end NOMENCLATURE GENERAL RECOMMENDATIONS

1/2/2016. Lecture Slides. Screws, Fasteners, and the Design of Nonpermanent Joints. Reasons for Non-permanent Fasteners

Installation Guidelines, 10Gig SFP+ Direct Attach Copper Cable Assembly PN533A

Total Ionizing Dose (TID) Radiation Testing of the RH1016MW UltraFast Precision Comparator for Linear Technology

Product Information Report Maximizing Drill Bit Performance

Products contained in this shipment may be subject to ITAR regulations.

INCREASING INTERLAMINAR STRENGTH IN LARGE SCALE ADDITIVE MANUFACTURING

Copyright 2013 Boart Longyear. All Rights Reserved. XQ WIRELINE CORING ROD. Technical Overview

INSTRUCTION MANUAL TRI-PLATE LINE MODEL EM-7310

MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2

BigBore IIe. 15,000 psi 20,000 psi SUBSEA WELLHEAD SYSTEMS

Optical Ground Wires (OPGW)

Buttress Thread Machining Technical Report Summary Final Report Raytheon Missile Systems Company NCDMM Project # NP MAY 12, 2006

Dowel connections in laminated strand lumber

Precision Double Row Cylindrical Roller Bearings With Tapered Bore

LAB #5: Measurement of Strain

Total Ionizing Dose (TID) Radiation Testing of the RH1009MH 2.5V Voltage Reference for Linear Technology

Certificate of Accreditation

MECHANICAL PROPERTY OF CARBON NANOTUBE YARN REINFORCED EPOXY

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z

Enhanced Low Dose Rate Sensitivity (ELDRS) Radiation Testing of the RH1814MW Quad Op Amp for Linear Technology

Arc Sensor User Manual

BRACE ASSEMBLIES FOR WIRE FENCES. What They Are - How They Work - How To Construct Them

NORMATIVE REFERENCES

TESTING EQUIPMENT SHEAR STRENGTH PARAMETERS SOIL. established in 1972

MIL-STD-883E METHOD BOND STRENGTH (DESTRUCTIVE BOND PULL TEST)

Engineering Policy & Procedure

J O I N T I N D U S T R Y S T A N D A R D. Requirements for Soldering Pastes J Standard 005A. December 2011

Radiation Lot Acceptance Testing (RLAT) of the RH1016MW UltraFast Precision Comparator for Linear Technology

Radiation Lot Acceptance Testing (RLAT) of the RH1013MJ8 Dual Precision Operational Amplifier for Linear Technology

Implementation of an Acoustic Emission Proximity Detector for Use in Generating Glass Optics. M. A. Piscotty, J. S. Taylor, K. L.

Use the arrow keys to easily navigate through the course.

TECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2

COPPERCLAD STEEL WIRE. Dead Soft Annealed Jacketed High Strength. Extra High Strength Composite Conductors Guy Wire

Accredited Laboratory

Enhanced Low Dose Rate Sensitivity (ELDRS) Radiation Testing of the RH1086MK Low Dropout Positive Adjustable Regulator for Linear Technology

General catalog. BESMAK Servo-hydraulic Medium-Capacity fatigue test System with Furnace. 1 BESMAK Material Testing Machines

Low Voltage AIRGUARD. A proven, rugged product for harsh environments

Orbital Test Stand. Operations and Assembly Manual. Department of Mechanical Engineering Northern Arizona University Flagstaff, AZ 86011

Radiation Lot Acceptance Testing (RLAT) of the RH1009MH 2.5V Voltage Reference for Linear Technology

Data Sheet. AEDx-8xxx-xxx 2- or 3-Channel Incremental Encoder Kit with Codewheel. Description. Features. Assembly View. Housing.

An experimental investigation of vibration characteristics in the diamond wire sawing of granite

What is Wire Rope? Understanding the Specifications and Construction

Experimental investigation of the influence of burnishing tool passes on surface roughness and hardness of brass specimens

ICC-ES Evaluation Report

INSTRUCTIONS FOR THE SAFE APPLICATION OF CABLES

Geosteering Resistivity Tool

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z

The Tracking and Trending Module collects the reduced data for trending in a single datafile (around 10,000 coils typical working maximum).

UTC. Engineering 329. Frequency Response for the Flow System. Gold Team. By: Blake Nida. Partners: Roger Lemond and Stuart Rymer

Enhanced Low Dose Rate Sensitivity (ELDRS) Radiation Testing of the RH117H-Positive Adjustable Regulator for Linear Technology

Radiation Lot Acceptance Testing (RLAT) of the RH1014MW Quad Precision Operational Amplifier for Linear Technology

Division of Custom Mold & Design

RR-F-191/1D 14 May SUPERCEDING RR-F-191/1C July 22, 1981 FEDERAL SPECIFICATION SHEET

Radiation Lot Acceptance Testing (RLAT) of the RH1014MW Quad Precision Operational Amplifier for Linear Technology

AN, MS, NAS Bolts. AN3 20 bolts are identified by a multi-part code:

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2017 & ANSI/NCSL Z

National Radio Astronomy Observatory Socorro, NM EVLA Memorandum 41 Lightning Protection for Fiber Optic Cable. T. Baldwin June 05, 2002

M-RAIL Sismet Road, Mississauga, L4W 1V6 TEST REPORT FOR MLEVEL GUARD SYSTEMS

Testing and Results of a New, Efficient Low-Profile AM Medium Frequency Antenna System

14 AWG 2 AWG: 600 Volt

MESP TECHNICAL SPECIFICATION FOR FLEXIBLE DROPPER WIRE TIN-BEARING COPPER 7/7/ mm 2

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005. NORTHSTAR CALIBRATION, INC th Place NW Owatonna, MN John Moorhouse Phone:

Enhanced Low Dose Rate Sensitivity (ELDRS) Radiation Testing of the RH118W Op-Amp for Linear Technology

Parametric Optimization of Ball Burnishing Process Parameter for Hardness of Aluminum Alloy 6061

Selective Soldering for Interconnection Technology Used in Enterprise Communication Apparatuses

Radiation Lot Acceptance Testing (RLAT) of the RH137H Negative Adjustable Regulator for Linear Technology

Load Cell Accessories and Services

CONTINUOUS COUNTERPOISE ON POLES

Products contained in this shipment may be subject to ITAR regulations.

Proposal for new standard. Determination of interface friction between painted parts. Orientation. p. 1 (15) Draft1, Revised

ERECTION & CONSTRUCTION

15,000 psi 20,000 psi. BigBore IIe HPHT SUBSEA WELLHEAD SYSTEMS

CH # 8. Two rectangular metal pieces, the aim is to join them

Enhanced Low Dose Rate Sensitivity (ELDRS) of the RH1078MJ8 Dual Precision Op Amp for Linear Technology

Technical Information

Transcription:

To: Colin McCullough 3M Composite Conductor Program 3130, Lexington Ave. So. Eagan MN 55121-2239 USA KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 3M TO DETERMINE THE SHEAVE CRITERIA FOR 774 KCMIL 3M TM COMPOSITE CONDUCTOR Kinectrics North America Inc. Report No.: K-422132-RC-0001-R00 March 2, 2006 C.J. Pon, M. Colbert, M.J. Kastelein Transmission and Distribution Technologies Department INTRODUCTION 3M contracted with Kinectrics under PO # 1600000 to conduct a series of investigative tests on their 774 kcmil Aluminum Conductor Composite Reinforced (ACCR) Conductor. These tests are part of a larger series of tests to demonstrate the viability of ACCR conductors for use on overhead electric power transmission lines. 3M owns all data and copyright to this information. The tests were performed from May 9 to October 11, 2005 by Kinectrics North America Inc. personnel at 800 Kipling Avenue, Toronto, Ontario, M8Z 6C4, Canada. SUMMARY Under conditions of combined tension and bending of the ACCR conductor, it is possible to overstress the conductor. These tests probe the relations between sheave diameter, tension and break-over angle (that may occur for example during field installation) to determine the correct combinations that should be used with the ACCR conductor. The 36 inch root diameter sheave showed smaller break-over angles can support higher tensions for double-pass tests. Specifically, at 45 per sheave and 5% RTS, at 33 per sheave and 7.5% RTS and at 25 per sheave and 15% RTS, the conductor behaves well. The 7x7 inch roller array sheave showed smaller break-over angles can support higher tensions for double-pass tests. Specifically, at 60 per sheave and 10% RTS, 33 per sheave and 15% RTS, the conductor behaves well. 1 K422132-RC-0006-R00

The 774 kcmil ACCR conductor successfully completed 20 passes over the 7x7 inch roller array at the two selected break-over angles and tensions combinations of 33 degrees/15.0% RTS, and 60 degrees/10.6% RTS. TEST OBJECTIVE AND STANDARD The objective of the tests were to determine, in an indoor laboratory, the threshold combination(s) of sheave size(s), conductor angle(s) over sheave, and conductor tension(s) that cause breakage of the core wires on 774 kcmil 3M TM Composite Conductor during double-pass and multi-pass sheave tests. The set-ups and procedures for the tests were based on the IEEE Std 1138-1994, IEEE Standard Construction of Composite Fiber Optic Overhead Ground Wire (OPGW) for Use on Electric Utility Power Lines, Paragraph 4.1.1.6. TEST CONDUCTOR The ACCR 774-T53, 46/37 conductor is manufactured by 3M and is constructed of 46 aluminum alloy wires in 2 layers surrounding the core wires. The aluminum alloy wires contain a small quantity of zirconium for heat resistance (resistance to annealing). The 37 core wires of the ACCR are made from a fiber-reinforced metal matrix composite material. The outside diameter is 1.254 inches (31.852 mm). The RTS (Rated Tensile Strength) of the conductor is 71,010 lbf. A data sheet on the ACCR conductor used in the sheave tests is contained in Appendix A. PURPOSE OF TESTS The ACCR conductor contains a core that exhibits no plasticity unlike traditional metals and alloys. It stress-strain behavior is linear-elastic to the failure stress. Thus there exists a bending radius at which the failure stress is reached. Furthermore combinations of axial tension and bending loads can lead to an overstressed condition. The purpose of the testing is to understand the interactions of tension, angle, and sheave size, and to understand which combinations do not overstress the conductor. Understanding the angle per sheave that may be tolerated is useful in designing and selecting the correct sheave size (or multi-sheave configuration) for conductor installation. This particular construction of 774 ACCR contains a very high core fraction and is especially stiff and requires extra attention be paid to it s bending characteristics. Two separate tests were performed : a double-pass test and a multi-pass test. The double-pass tests were performed on a 36 inch root diameter sheave and a 7x7 inch roller array sheave. The tests were performed to determine the threshold combination of tension and conductor angle over sheave that could be used for the multi-pass tests. The conditions that produced no broken core wires were used for the multi-pass tests. The multi-pass tests were performed on the 7x7 inch roller array sheave only. The tests were performed to determine the threshold combination of tension and conductor angle over sheave that could be used during installation in the field. 2 K422132-RC-0006-R00

TEST SET-UP Double-Pass and Multi-Pass Tests A schematic of the set-up for the Double and Multi-Pass Sheave Tests is shown in Figure 1a. Typical photos of the set-up for the 36 inch sheave are shown in Figures 1b and 1c. Typical photos of the set-up for the 7x7 inch Roller Array sheave are shown in Figures 1d, and 1e. The Roller Array consists of 7 small sheaves each 7 inches in diameter with a 1 inch bottom groove radius. They are arrayed along an arc that sweeps a 60 angle and maintains a 60 inch radius. The Roller Array was built and supplied by Sherman & Reilly Inc. of Chattanooga, TN. Test Apparatus Double-Pass and Multi-Pass Tests The test conductor was strung over the sheave assembly and tensioned using pulling grips and/or dead-end grips. Both ends were attached to a motor driven, chain link loop system. The conductor was passed back and forth over the sheave at a speed of about 0.515 ft/sec (0.157 m/sec). The sheave was fixed at the appropriate height to produce the desired break over angle over the sheave. A hydraulic piston was used to tension the conductor. A load cell was used to measure the conductor tension. The test was carried out in a temperature-controlled laboratory at 21ºC ± 2ºC. Instrumentation and Data Acquisition The load cell was monitored on a data acquisition system. The unaided ear was used to listen for possible breaking core wires. A digital inclinometer was used to measure the break-over angle. The measuring instruments used in this test are listed in Appendix B. 3 K422132-RC-0006-R00

Adjustable support structure Angle A Angle B Dead-end pulling grip Sheave Break-over angle (degrees), Angle A + B Dead-end pulling grip 774 kcmil ACCR Conductor 3 K422132-RC-0006-R00 Motor drive and gearbox chain drive 18 meters Hydraulic Piston (to tension chain loop) Data aquisition Figure 1a: Schematic of Set-up for Double and Multi-Pass Sheave Tests Load cell

4 K422132-RC-0006-R00 Figure 1b: Typical Set-up for 36 Sheave Test Figure 1c: Typical Set-up for 36 Sheave Test

Figure 1d: Typical Set-up for 7x7 Roller Array Sheave Test (60 degree break-over angle shown in photo) Figure 1e: Typical Set-up for 7x7 Roller Array Sheave Test 5 K422132-RC-0006-R00

TEST PROCEDURE Double-Pass Test - 36 Inch Root Diameter Sheave A 13 ft (4 m) length of test conductor was setup in the test apparatus. The test parameters were: Sheave diameter: 36 inch root diameter Break-over Angle: 45, 33, and 25 Tension: 2.5, 5.0, 7.5, 10.0, 12.5, 15% of conductor RTS (71,010 lbf, 32,210 kgf) The test sequence was based on the most to least severe condition for break-over angle. The starting tension was 2.5% of RTS (71,010 lbf, 32,210 kgf). A double pass of the conductor over the sheave was completed. A double pass is defined as two forward and backward movements of the conductor. The portion of conductor that actually passed over the sheave was about 6.5 feet (2 meters). During the pass if there was no audible indication of broken core wires, then the tension was increased by 2.5%, and the test repeated. If there was an audible indication of broken core wires, the conductor was dissected and the core wires were visually examined over the test section for breaks or damage. After completion of one test a new sample was installed in the facility, the break-over angle was decreased and the procedure was repeated. Double-Pass Test - 7x7 Inch Diameter Roller Array Sheave A 13 ft (4 m) length of test conductor was setup in the test apparatus. The test parameters were: Sheave diameter: 7x7 inch roller array Break-over Angle: 60, 52, 45, and 33 Tension: 2.5, 5.0, 7.5, 10.0, 10.56, 12.05, 12.5, 13.8, 15% of conductor RTS (71,010 lbf, 32,210 kgf) Sheave Specifications: Manufacturer: Sherman and Reilly Inc. Model: 261-030-03 Size: 60R Maximum Working Load: 7,500 lbs, 60 degree The Maximum Working Load (7,500 lbs) of the roller array limited the amount of tension that could be applied at the various break-over angles. The following are the tension limits for each break-over angle, based on the calculated total vertical load on the roller array not exceeding 7,500 lbs. For 33 degree : 15.0 % RTS For 45 degree : 13.8 % RTS 6 K422132-RC-0006-R00

For 52 degree : 12.05 % RTS For 60 degree : 10.56 % RTS The test sequence was based on the most to least severe condition for break-over angle. The starting tension was 2.5% of RTS (71,010 lbf, 32,210 kgf). A double pass of the conductor over the sheave was completed. A double pass is defined as two forward and backward movements of the conductor. The portion of conductor that actually passed over the sheave was about 6.5 feet (2 meters). During the pass if there was no audible indication of broken core wires, then the tension was increased by 2.5%, and the test repeated. If there was an audible indication of broken core wires, the conductor was dissected and the core wires were visually examined over the test section for breaks or damage. After completion of one test a new sample was installed in the facility, the break-over angle was decreased and the procedure was repeated. Multi-Pass Test - 7x7 Inch Diameter Roller Array Sheave A 13 ft (4 m) length of test conductor was setup in the test facility. Based on the results from the double pass tests, the test parameters were: Sheave diameter: 7x7 inch roller array Break-over Angle: 60 and 33 Tension: 10.56% and 15% of conductor RTS (71,010 lbf, 32,210 kgf) The portion of conductor that passed over the sheave was about 6.5 ft (2 m) in length. The multi-pass test consisted of 20 passes of the conductor over the sheave. The tested conductor was dissected after each test and the individual wires were visually examined over the test section for breaks or damage. TEST RESULTS Double-Pass Test - 36 Inch Root Diameter Sheave The results for the various combinations of break-over angles and tensions are summarized in Table 1. Figure 2 shows a graph plotting break-over angle versus tension. This provides a double-pass threshold curve for the 36 inch sheave. The curve is based on the test results from Table 1 that had no broken wires after a double-pass. 7 K422132-RC-0006-R00

Table 1: Double-Pass Test Results for 36 Inch Root Diameter Sheave (May 9-18, 2005) Conductor Break-over Angle Tension (% of RTS) 25 degree 33 degree 45 degree 2.5 No broken wires No broken wires No broken wires 5.0 No broken wires No broken wires No broken wires 7.5 No broken wires No broken wires 10.0 No broken wires One Broken wire on outer layer One Broken wire on outer layer - 12.5 No broken wires - - 15.0 No broken wires - - Break-over Angle, degrees 50 45 40 35 30 25 20 15 10 0 5 10 15 20 Tension, % of RTS Figure 2: Threshold Curves for the 36 Inch Root Diameter Sheave Double Pass Test, May 9-18, 2005 (Results from Tables 1 based on a double pass with no broken core wires) 8 K422132-RC-0006-R00

Double-Pass Test 7x7 Inch Roller Array Sheave The results for the various combinations of break-over angles and tensions are summarized in Table 2. Figure 3 shows a graph plotting break-over angle versus tension. This provides a double-pass threshold curve for the 7x7 inch roller array sheave. The curve is based on the test results from Table 2 that had no broken wires after a double-pass. Table 2: Double-Pass Test Results for 7x7 Inch Roller Array Sheave (July 5-15, 2005) Conductor Break-over Angle Tension (% of RTS) 33 degree 45 degree 52 degree 60 degree 2.5 No broken wires No broken wires No broken wires No broken wires 5.0 No broken wires No broken wires No broken wires No broken wires 7.5 No broken wires No broken wires No broken wires No broken wires 10.0 No broken wires No broken wires N/A No broken wires 10.56 N/A N/A N/A No broken wires 12.05 N/A N/A No broken wires N/A 12.5 No broken wires No broken wires N/A N/A 13.8 N/A No broken wires N/A N/A 15.0 No broken wires N/A N/A N/A N/A not part of the tension test parameters. Break-over Angle, degrees 70 60 50 40 30 20 10 0 2.5 5 7.5 10 12.5 15 17.5 Tension, % of RTS Figure 3: Threshold Curves for the 7x7 Inch Roller Array Sheave Double Pass Test, July 5-15, 2005 (Results from Tables 2 based on a double pass with no broken core wires) 9 K422132-RC-0006-R00

Multi-Pass Test 7x7 Inch Roller Array Sheave Two test conditions were chosen for multi-pass testing that produced no broken core wires in double-pass testing. The results for the two break-over angles and tensions are summarized in Table 3. Figure 4 shows a graph plotting break-over angle versus tension. This provides a multi-pass threshold curve for the 7x7 inch roller array sheave. The curve is based on the test results from Table 3 that had no broken wires after a 20 passes. Table 3: Multi-Pass Test Results for 7x7 Inch Roller Array Sheave (October 6 & 11, 2005) Conductor Break-over Angle Tension (% of RTS) 33 degree 60 degree 10.56 N/A 15.0 No broken wires after 20 passes. No broken wires after 20 passes. N/A N/A not part of the tension test parameters. Break-over Angle, degrees 70 60 50 40 30 20 10 0 2.5 5 7.5 10 12.5 15 17.5 Tension, % of RTS Figure 4: Threshold Curves for the 7x7 Inch Roller Array Sheave Multi Pass Test, October 6 & 11, 2005 (Results from Tables 3 based on a 20 passes with no broken core wires) 10 K422132-RC-0006-R00

Dissection Observations 36 Inch Sheave Double-Pass Test - 36 inch Sheave, 45 degree angle, 7.5% RTS tension Aluminum Outer Layer inner surface had fret marks. Aluminum 2 nd Layer outer surface had fret marks. Aluminum 2 nd Layer inner surface had fret marks. Core Wires no observations made. Double-Pass Test - 36 inch Sheave, 33 degree angle, 10.0% RTS tension There were no visual observations made for fretting between the aluminum wires or the composite core wires. Double-Pass Test - 36 inch Sheave, 25 degree angle, 15% RTS tension There were no visual observations made for fretting between the aluminum wires or the composite core wires. Dissection Observations 7x7 Roller Array Sheave Double-Pass Test 7x7 Roller Array Sheave, 60 degree angle, 10.56% RTS tension 1 st Layer Aluminum (26) inner surface had fret marks see photo 1a. 2 nd Layer Aluminum (20) outer surface had fret marks see photo 1b. 2 nd Layer Aluminum (20) inner surface had fret marks see photo 1c. 3 rd Layer Core Wires (18) outer surface had fret marks see photo 1d. 2 nd Layer Core Wire (12) outer surface had fret marks see photo 1e. 1 st Layer Core Wire (6) outer surface had fret marks see photo 1f. Center Core Wire had fret marks see photo 1g. 1 st Layer Aluminum (26) noticed some fretting between adjacent wires (side to side), see photo 1h. All fret marks were more noticeable (larger or deeper) on the bottom side of the conductor. i.e. the side in contact with the sheave wheel. Unless otherwise labelled, all the photos taken were the most severe fretting observed, generally on the bottom side of the conductor. The fret marks on the core wires looked more like indentations or impressions. The fret marks for the aluminum and the core wires became longer in length for each layer into the conductor (i.e. as the lay-length became longer). The fret marks for the core wires generally became lighter for each layer into the conductor. 11 K422132-RC-0006-R00

Photo 1a: 1 st Layer Aluminum inner surface Photo 1b: 2 nd Layer Aluminum outer surface 12 K422132-RC-0006-R00

Photo 1c: 2 nd Layer Aluminum inner surface Photo 1d: 3 rd Layer Core outer surface 13 K422132-RC-0006-R00

Photo 1e: 2 nd Layer Core outer surface Photo 1f: 1 st Layer Core outer surface 14 K422132-RC-0006-R00

Photo 1g: Center Core Wire Fret marks between adjacent wires (side to side) Photo 1h: 1 st Layer Aluminum side to side fretting 15 K422132-RC-0006-R00

Dissection Observations 7x7 Roller Array Sheave Double-Pass Test 7x7 Roller Array Sheave, 52 degree angle, 12.05% RTS tension 1 st Layer Aluminum (26) inner surface had fret marks see photo 1a. 2 nd Layer Aluminum (20) outer surface, top side had fret marks see photo 1b. 2 nd Layer Aluminum (20) outer surface, bottom side had fret marks see photo 1c. 2 nd Layer Aluminum (20) inner surface had fret marks see photo 1d. 3 rd Layer Core Wires (18) outer surface had fret marks see photo 1e. 2 nd Layer Core Wire (12) outer surface had fret marks. 1 st Layer Core Wire (6) had fret marks. Center Core Wire had fret marks. 1 st Layer Aluminum (26) noticed some fretting between adjacent wires (side to side), see photo 1f. All fret marks were more noticeable (larger or deeper) on the bottom side of the conductor. i.e. the side in contact with the sheave wheel. Unless otherwise labelled, all the photos taken were the most severe fretting observed, generally on the bottom side of the conductor. The fret marks on the core wires looked more like indentations or impressions. The fret marks for the aluminum and the core wires became longer in length for each layer into the conductor (i.e. as the lay-length became longer). The fret marks for the core wires generally became lighter for each layer into the conductor. 16 K422132-RC-0006-R00

Photo 1a: 1 st Layer Aluminum inner surface Photo 1b: 2 nd Layer Aluminum outer surface, top side 17 K422132-RC-0006-R00

Photo 1c: 2 nd Layer Aluminum outer surface, bottom side Photo 1d: 2 nd Layer Aluminum inner surface 18 K422132-RC-0006-R00

Photo 1e: 3 rd Layer Core outer surface Fret marks between adjacent wires (side to side) Photo 1f: 1 st Layer Aluminum side to side fretting 19 K422132-RC-0006-R00

Dissection Observations 7x7 Roller Array Sheave Double-Pass Test 7x7 Roller Array Sheave, 45 degree angle, 13.80% RTS tension 1 st Layer Aluminum (26) inner surface had fret marks see photo 1a. 2 nd Layer Aluminum (20) outer surface, top side had fret marks see photo 1b. 2 nd Layer Aluminum (20) outer surface, bottom side had fret marks see photo 1c. 2 nd Layer Aluminum (20) inner surface had fret marks. 3 rd Layer Core Wires (18) outer surface had fret marks see photo 1d. 2 nd Layer Core Wire (12) outer surface had fret marks see photo 1e. 1 st Layer Core Wire (6) outer surface had fret marks see photo 1f. Center Core Wire had fret marks. All fret marks were more noticeable (larger or deeper) on the bottom side of the conductor. i.e. the side in contact with the sheave wheel. Unless otherwise labelled, all the photos taken were the most severe fretting observed, generally on the bottom side of the conductor. The fret marks on the core wires looked more like indentations or impressions. The fret marks for the aluminum and the core wires became longer in length for each layer into the conductor (i.e. as the lay-length became longer). The fret marks for the core wires generally became lighter for each layer into the conductor. The outer rollers on each end of the roller array were barely in contact with the conductor during the sheave test. 20 K422132-RC-0006-R00

Photo 1a: 1 st Layer Aluminum inner surface Photo 1b: 2 nd Layer Aluminum outer surface, top side 21 K422132-RC-0006-R00

Photo 1c: 2 nd Layer Aluminum outer surface, bottom side Photo 1d: 3 rd Layer Core outer surface 22 K422132-RC-0006-R00

Photo 1e: 2 nd Layer Core outer surface Photo 1f: 1 st Layer Core outer surface 23 K422132-RC-0006-R00

Dissection Observations 7x7 Roller Array Sheave D ouble-pass Test 7x7 Roller Array Sheave, 33 degree angle, 15.0% RTS tension 1 st Layer Aluminum (26) inner surface had fret marks see photo 1a. 2 nd Layer Aluminum (20) outer surface, had fret marks see photo 1b. 2 nd Layer Aluminum (20) inner surface had fret marks see photo 1c. 3 rd Layer Core Wires (18) outer surface had fret marks. 2 nd Layer Core Wire (12) outer surface had fret marks. 1 st Layer Core Wire (6) outer surface had fret marks. Center Core Wire had fret marks. All fret marks were more noticeable (larger or deeper) on the bottom side of the conductor. i.e. the side in contact with the sheave wheel. Unless otherwise labelled, all the photos taken were the most severe fretting observed, generally on the bottom side of the conductor. The fret marks on the core wires looked more like indentations or impressions. The fret marks for the aluminum and the core wires became longer in length for each layer into the conductor (i.e. as the lay-length became longer). The fret marks for the core wires generally became lighter for each layer into the conductor. The outer rollers the sheave test. on each end of the roller array were not in contact with the conductor during 24 K422132-RC-0006-R00

Photo 1a: 1 st Layer Aluminum inner surface Photo 1b: 2 nd Layer Aluminum outer surface 25 K422132-RC-0006-R00

Photo 1c: 2 nd Layer Aluminum inner surface 26 K422132-RC-0006-R00

Dissection Observations 7x7 Roller Array Sheave Multi-Pass Test 7x7 Roller Array Sheave, 60 degree angle, 10.56% RTS tension, 20 passes 1 st Layer Aluminum (26) outer surface, no fret marks see photo 1a. 1 st Layer Aluminum (26) inner surface, top side had fret marks see photo 1b. 1 st Layer Aluminum (26) inner surface, bottom side had fret marks see photo 1c. 2 nd Layer Aluminum (20) outer surface, top side had fret marks see photo 1d. 2 nd Layer Aluminum (20) outer surface, bottom side had fret marks see photo 1e. 2 nd Layer Aluminum (20) inner surface, top side had fret marks see photo 1f. 2 nd Layer Aluminum (20) inner surface, bottom side had fret marks see photo 1g. 3 rd Layer Core Wires (18) outer surface, top side had fret marks see photo 1h. 3 rd Layer Core Wires (18) outer surface, bottom side had fret marks see photo 1j. 2 nd Layer Core Wire (12) outer surface, had fret marks see photo 1k. 1 st Layer Core Wire (6) outer surface, had fret marks see photo 1m. Center Core Wire had fret marks see photo 1n. All fret marks were more noticeable (larger or deeper) on the bottom side of the conductor. i.e. the side in contact with the sheave wheel. Unless otherwise labelled, all the photos taken were the most severe fretting observed, generally on the bottom side of the conductor. The fret marks on the core wires looked more like indentations or impressions. The fret marks for the aluminum and the core wires became longer in length for each layer into the conductor (i.e. as the lay-length became longer). The fret marks for the core wires generally became lighter for each layer into the conductor. The outer rollers on each end of the roller array were barely in contact with the conductor during the sheave test. 27 K422132-RC-0006-R00

Photo 1a: 1 st Layer Aluminum outer surface Photo 1b: 1 st Layer Aluminum inner surface, top side 28 K422132-RC-0006-R00

Photo 1c: 1 st Layer Aluminum inner surface, bottom side Photo 1d: 2 nd Layer Aluminum outer surface, top side 29 K422132-RC-0006-R00

Photo 1e: 2 nd Layer Aluminum outer surface, bottom side Photo 1f: 2 nd Layer Aluminum inner surface, top side 30 K422132-RC-0006-R00

Photo 1g: 2 nd Layer Aluminum inner surface, bottom side Photo 1h: 3 rd Layer Core outer surface, top side 31 K422132-RC-0006-R00

Photo 1j: 3 rd Layer Core outer surface, bottom side Photo 1k: 2 nd Layer Core outer surface 32 K422132-RC-0006-R00

Photo 1m: 1 st Layer Core outer surface Photo 1n: Center Core Wire 33 K422132-RC-0006-R00

Multi-Pass Test 7x7 Roller Array Sheave, 33 degree angle, 15.0% RTS tension, 20 passes 1 st Layer Aluminum (26) outer surface, no fret marks see photo 1a. 1 st Layer Aluminum (26) inner surface, bottom side had fret marks see photo 1b. 2 nd Layer Aluminum (20) outer surface, bottom side had fret marks see photo 1c. 2 nd Layer Aluminum (20) outer surface, bottom side had fret marks see photo 1d. 2 nd Layer Aluminum (20) inner surface, bottom side had fret marks see photo 1e. 3 rd Layer Core Wires (18) outer surface, top side had fret marks see photo 1f. 3 rd Layer Core Wires (18) outer surface, bottom side had fret marks see photo 1g. 2 nd Layer Core Wire (12) outer surface, had fret marks see photo 1h. 1 st Layer Core Wire (6) outer surface, had fret marks see photo 1j. Center Core Wire had fret marks see photo 1k. All fret marks were more noticeable (larger or deeper) on the bottom side of the conductor. i.e. the side in contact with the sheave wheel. Unless otherwise labelled, all the photos taken were the most severe fretting observed, generally on the bottom side of the conductor. The fret marks on the core wires looked more like indentations or impressions. The fret marks for the aluminum and the core wires became longer in length for each layer into the conductor (i.e. as the lay-length became longer). The fret marks for the core wires generally became lighter for each layer into the conductor. The outer rollers on each end of the roller array were not in contact with the conductor during the sheave test. 34 K422132-RC-0006-R00

Photo 1a: 1 st Layer Aluminum outer surface Photo 1b: 1 st Layer Aluminum inner surface, bottom side 35 K422132-RC-0006-R00

Photo 1c: 2 nd Layer Aluminum outer surface, top side Photo 1d: 2 nd Layer Aluminum outer surface, bottom side 36 K422132-RC-0006-R00

Photo 1e: 2 nd Layer Aluminum inner surface, bottom side Photo 1f: 3 rd Layer Core outer surface, top side 37 K422132-RC-0006-R00

Photo 1g: 3 rd Layer Core outer surface, bottom side Photo 1h: 2 nd Layer Core outer surface 38 K422132-RC-0006-R00

Photo 1j: 1 st Layer Core outer surface Photo 1k: Center Core Wire 39 K422132-RC-0006-R00

SUMMARY Double-Pass Test The 36 inch root diameter sheave showed smaller break-over angles can support higher tensions for double-pass tests. Specifically, at 45 per sheave and 5% RTS, at 33 per sheave and 7.5% RTS and at 25 per sheave and 15% RTS, the conductor behaves well. The 7x7 inch roller array sheave showed smaller break-over angles can support higher tensions for double-pass tests. Specifically, at 60 per sheave and 10% RTS, 33 per sheave and 15% RTS, the conductor behaves well. Multi-Pass Test The 774 kcmil ACCR conductor successfully completed 20 passes over the sheave at the two selected break-over angles and tensions combinations of 33 degrees/15.0% RTS, and 60 degrees/10.6% RTS. The dissections showed there was fretting evident on all aluminum layer cross-over interfaces and all the core wires cross-over interfaces. All fret marks were more noticeable (larger or deeper) on the bottom side of the conductor. i.e. the side in contact with the sheave wheel. The fret marks for the core wires generally became lighter for each layer into the conductor. The fretting appears to become more severe at the higher conductor tensions and/or conductor angle over the sheave. The degree of fretting appears to increase with increased passes over the sheave. The fret marks for the aluminum and the core wires became longer in length for each layer into the conductor (i.e. as the lay-length became longer). The heavy fret-marks in some instances suggest more support is required for the conductor (e.g. larger sheaves), so as to reduce the point loads at the cross-over points. Understanding the angle per sheave that may be tolerated is useful in designing and selecting the correct sheave size (or multi-sheave configuration) for subsequent tests. Thus, this data will be used as a starting point in selecting sheave (and multi-sheave) configurations for outdoor installation experiments while using full installation rigging. 40 K422132-RC-0006-R00

Prepared by: M. Colbert Technologist Transmission and Distribution Technologies Department M. J. Kastelein Technologist Transmission and Distribution Technologies Department C.J. Pon Principal Engineer Transmission and Distribution Technologies Department Approved by: J. Kuffel Manager Transmission and Distribution Technologies Department CJP:MJK:MC:JK DISCLAIMER Kinectrics North America Inc. has prepared this report in accordance with, and subject to, the terms and conditions of the contract between 3M, dated August 9, 2004. This material is based upon work supported by the U.S. Department of Energy under Award No. DE-FC02-02CH11111. Any opinions, findings, and conclusions or recommendations expressed in this material are those of the author(s) and do not necessarily reflect the views of the Department of Energy. 41 K422132-RC-0006-R00

APPENDIX A DATA SHEET FOR 3M 774 KCMIL ACCR COMPOSITE CONDUCTOR (see Product Data and Specification at www.3m.com/accr) A-1 K422132-RC-0006-R00

ISO-9001 Form: QF11-1 Rev 0, 97-10 APPENDIX B INSTRUMENT SHEET 3M SHEAVE TESTS on 774 kcmil ACCR CONDUCTOR Test Description: 3M Sheave Tests on 774 kcmil ACCR Conductor Test Start Date: May 9, 2005 Project Number: 422132 Test Finish Date: October 11, 2005 TEST DESCRIPTION EQUIPMENT DESCRIPTION MAKE MODEL ASSET # or SERIAL # ACCURACY CLAIMED CALIBRATION DATE CALIBRATION DUE DATE TEST USE B-1 K422132-RC-0006-R00 Sheave A/D Board Load Cell Load Conditioner Load Cell Load Conditioner National Instruments PCI-6034E CA1C1A ±0.1% of reading January 7, 2005 January 7, 2006 Eaton Daytronics Aries Daytronics 3124 3170 1000 TRC 3170 17952-0 11148-0 ±1% of reading December 21, 2004 December 21, 2005 11137-0 10718-0 ±1% of reading February 10, 2005 February 10, 2006 Digital Protractor Mitutoyo Pro 3600 19693-0 0 to -0.1 degree February 15, 2005 February 15, 2006 Data Acquisition Conductor Tension for Double-Pass Tests Conductor Tension for Multi-Pass Tests Conductor Angle

DISTRIBUTION Colin McCullough (2) 3M Composite Conductor Program 3130, Lexington Ave. So. Eagan MN 55121-2239 USA Mr. C.J. Pon Transmission and Distribution Technologies, KB104