SIPROTEC 5 Application. SIP5-APN-025-en: 7UT8 Autotransformer bank with 2 sets of CT inside the delta connection of the compensation side

Similar documents
SIPROTEC 5 Application Note

SIPROTEC 5 Application Note

Line protection with transformer in the protection zone

Impedance protection on power transformer.

Ground fault supervision of 4 feeders with 7SJ82 or 7SJ85 with 4x I, 4x V

function block description to the differential protection and restricted earth-fault protection functions for autotransformers

Breaker Pole Discrepancy Function

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

Transformer protection IED RET 670

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Acquisition of transformer tap positions via an analog measurement transformer

Application of Low-Impedance 7SS601 Busbar Differential Protection

Transformer Protection

Relay-assisted commissioning

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

2015 Relay School Bus Protection Mike Kockott March, 2015

Line Protection Roy Moxley Siemens USA

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

Bus Protection Fundamentals

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

ELECTRICAL POWER ENGINEERING

Repair & Retrofit new life for old transformers. Repair and retrofitting through TLM Transformer Lifecycle Management. Answers for energy.

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

The Advantages and Application of Three Winding Transformers

Differential Protection with REF 542plus Feeder Terminal

Transformer Protection Principles

Earth Fault Protection

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

Catastrophic Relay Misoperations and Successful Relay Operation

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

Restricted earth-fault protection function block description

Stabilized Differential Relay SPAD 346. Product Guide

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Busbars and lines are important elements

Medium-voltage in-phase regulator system Energy Management

~=E.i!=h. Pre-certification Transformers

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Transformer Fault Categories

Differential Protection Optimal differential protection for phase shifter transformers and special transformers

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

ELECTRICAL POWER TRANSMISSION TRAINER

IVE(TY) Department of Engineering. Electrical Machines 1. Electrical Machines 1. Hour 13. slide 1

EASUN REYROLLE LIMITED

VOLTAGE OPTIMIZATION FOR INDUSTRY, TRADE, BUSINESS AND LOCAL NETWORKS

Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources

ReliabilityFirst Regional Criteria 1. Disturbance Monitoring and Reporting Criteria

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

g GE POWER MANAGEMENT

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

, ,54 A

Ground Fault Detection using Zigzag Grounding Transformer in Ungrounded System

Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content

Transformer Trainer. Electrical Power Systems PSL20. Learning Outcomes. Key Features. Key Specifications

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Testing Numerical Transformer Differential Relays

Protection of Electrical Networks. Christophe Prévé

RESTRICTED EARTH FAULT RELAY

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management

Electrical Engineering. Power Systems. Comprehensive Theory with Solved Examples and Practice Questions. Publications

TS RES - OUTSTANDING ISSUES

Introduction. Principle of differential relay operation

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

TABLE OF CONTENT

Pinhook 500kV Transformer Neutral CT Saturation

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

Power systems 2: Transformation

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER

Problems connected with Commissioning of Power Transformers

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL)

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

SPAE 010, 011 High Impedance Protection Relay

Convincing technology creates compact performance

SPAD 346 C Stabilized differential relay

Solution for Effect of Zero Sequence Currents on Y-Y Transformer Differential Protection

EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

NEW DESIGN OF GROUND FAULT PROTECTION

QUESTIONNAIRE for Wind Farm Power Stations only

148 Electric Machines

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

एस.आर.प.स 40व प र ट क शनउप सम त क ब ठकक मऱएएज ड Additional Agenda Points for 40 th meeting of Protection Sub-Committee of SRPC

Modern Protection of Three-Phase and Spare Transformer Banks

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

ELECTRICAL POWER ENGINEERING

MV network design & devices selection EXERCISE BOOK

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Babak Enayati National Grid Thursday, April 17

Preventing transformer saturation in static transfer switches A Real Time Flux Control Method

Unit Protection Differential Relays

Transmission System Phase Backup Protection

Transcription:

www.siemens.com/protection SIPROTEC 5 Application SIP5-APN-025-en: 7UT8 Autotransformer bank with 2 sets of CT in the delta connection of the compensation Answers for infrastructure and cities.

Autotransformer bank with 2 sets of CT in the delta connection of the compensation SIPROTEC 5 - Application: Autotransformer bank with 2 sets of CT on the delta connected compensation Contents: 1 Autotransformer bank with 2 sets of CT on the delta connected compensation 3 1.1 Introduction 3 1.2 Differential Protection for Auto Transformer 87-T1 4 1.3 Differential Protection for the compensation 87-T2 5 1.4 Complete current transformer connection diagram 6 1.5 Functiongroup connections 7 1.6 Settings (Extract) 7 1.6.1 Power system 7 1.6.2 (87-T1) Auto transformer compensation 8 1.6.3 (87-T1) Auto transformer diff. 1 8 1.6.4 (87-T2) Transformer 1 9 1.6.5 (87-T2) Transformer 2 9 1.7 Fault examples (without load current) 10 1.7.1 External fault L1-L2 on 34.5 kv 10 1.7.2 External fault L1-E on the 230 kv 11 1.7.3 Internal fault L1-E on 230 kv 12 1.7.4 Internal fault L1-L2 on 34,5 kv (out the delta connection) 13 1.7.5 Internal fault L1-LE on the 34,5 kv (out the delta connection) 14 SIP5-APN-025-de 2

1 Autotransformer bank with 2 sets of CT on the delta connected compensation 1.1 Introduction Autotransformers are often applied in high voltage transmission networks. In most cases these transformers include a so called compensation (tertiary delta). This winding ensures symmetrical magnetization of the three limbs even under adverse conditions. In addition it may be used for the auxiliary supply of the sub-station. The rating of this tertiary delta is generally substantially less than the rating of the actual auto-transformer. The basis for the differential protection across the entire auto-transformer is the rating of the actual primary windings. Such a protection cannot always detect faults in the compensation. This depends on the plant data, the number of connected CTs and their configuration! This situation can be significantly improved by applying two sets of CTs in the delta of the compensation. Two differential protection functions are configured in the 7UT87: - Differential protection for the auto transformer 87-T1 (Figure 1) - Differential-protection for the compensation 87T-2 (Figure 2) 87-T1 (Base: MVA of the auto transformer winding) protects the auto transformer winding and the 3 windings of the compensation, however not or only partially the delta connection of the tertiary winding of the auto transformer bank. Fault detection is phase selective. This is more frequently required, as it reduces the time required to find the fault in the 3 individual transformers of the bank. 87-T2 (Base: MVA of the compensation winding) protects the compensation winding including the terminal connections up to the current transformer 5. On the 34,5 kv delta connected compensation, a neutral earthing transformer is installed for this application. As a result a corresponding current also flows in the tertiary windings during a single phase fault in this zone. Selective tripping is possible. (If required, a restrictive earth fault protection (REF) can be applied; this is however not gone into further here). The fault detection on the compensation is NOT phase selective in this zone! A single phase fault is fed via two limbs and a 2-phase fault via 3 limbs. 3 SIP5-APN-025-de

1.2 Differential Protection for Auto Transformer 87-T1 In this application the zero sequence current from all three s of the auto transformer bank, including the circulating current in the tertiary winding are measured. Elimination of the zero sequence current is therefore not required! Figure 1: Differential protection for the auto transformer (87T-1) The current transformers CT 3 and CT 4 are in the tertiary connection of the compensation. The measured current therefore corresponds to only I/ 3. This may be compensated for by means of the voltage setting 3 34,5 kv. Under normal operation the currents from CT 3 and CT 4 are identical are summated. Consequently the ultimate setting value for the voltage 3 = ( 3 34,5 kv)/2 = 29,88 kv. Advantage of this solution: Increased sensitivity as the zero sequence current is not eliminated Increased sensitivity for faults in the delta connected tertiary winding. Unambiguous fault condition, only differential current in the faulted phase. SIP5-APN-025-de 4

1.3 Differential Protection for the compensation 87-T2 The base for the differential protection is the 125 MVA of the compensation (and not the 500 MVA). This results in a (significantly) higher sensitivity during internal faults. Figure 2: Differential protection for the compensation (87T-2) Setting as for the 2-winding transformer YNd11 In the event of a short circuit on the 230 kv or 400 kv, a zero sequence current will flow via the current transformers CT 3 and CT 4. With the setting transformer 1 starpoint = earthed, this zero sequence current is eliminated from the differential current component. For the restraint component, the zero sequence current is however used (new in the 7UT8). 5 SIP5-APN-025-de

1.4 Complete current transformer connection diagram Figure 3: Complete current transformer connection diagram CT 3 and CT 4 are used both for the auto transformer differential protection 87T-1 as well as for the differential protection of the tertiary winding 87T-2 (transformer 1 1). In figure 3 the starpoint of CT3 for 87-T1 is not in direction of the object. For the 87-T2 however, the starpoint is in direction of the object! As there is only one setting address for the CT starpoint, it is necessary to invert the measuring point allocation for I-3ph 3 and I-3ph 4 by setting "I" under "function- group connections" for the transformer 1. SIP5-APN-025-de 6

1.5 Functiongroup connections Auto trf. auto 1 Auto trf. auto 2 Auto trf. comp. Circuit breaker 1 Circuit breaker 2 Circuit breaker 3 Transformer 1 Transformer 2 Transform. neut.p 1 Meas. point I-3ph 1 X X Meas. point I-3ph 2 X X Meas. point I-3ph 3 X X I *) Meas. point I-3ph 4 X I *) Meas. point I-3ph 5 Meas. point I-1ph 1 *) Polarity inverted 1.6 Settings (Extract) X X 1.6.1 Power system Meas.point I-3ph 1 CT 3-phase 11.931.8881.101 Rated primary current 1000.0 A 11.931.8881.102 Rated secondary current 1 A 11.931.8881.116 Neutr.point in dir.of ref.obj: yes Meas.point I-3ph 2 CT 3-phase 11.932.8881.101 Rated primary current 1500.0 A 11.932.8881.102 Rated secondary current 1 A 11.932.8881.116 Neutr.point in dir.of ref.obj: yes Meas.point I-3ph 3 CT 3-phase 11.933.8881.101 Rated primary current 1500.0 A 11.933.8881.102 Rated secondary current 1 A 11.933.8881.116 Neutr.point in dir.of ref.obj: no Meas.point I-3ph 4 CT 3-phase 11.934.8881.101 Rated primary current 1500.0 A 11.934.8881.102 Rated secondary current 1 A 11.934.8881.116 Neutr.point in dir.of ref.obj: no 7 SIP5-APN-025-de

Meas.point I-3ph 5 CT 3-phase 11.935.8881.101 Rated primary current 2000.0 A 11.935.8881.102 Rated secondary current 1 A 11.935.8881.116 Neutr.point in dir.of ref.obj: yes Meas.point I-1ph 1 General 11.951.2311.101 Rated primary current 1000.0 A 11.951.2311.102 Rated secondary current 1 A 11.951.2311.116 Term. 1,3,5,7 in dir. of obj.: yes 1.6.2 (87-T1) Auto transformer compensation 1.6.3 (87-T1) Auto transformer diff. 1 With the setting " Neutral point = isolated" no zero sequence current elimination is carried out for the s 1 and 2 SIP5-APN-025-de 8

1.6.4 (87-T2) Transformer 1 With the setting Neutral point = grounded zero sequence current is eliminated from the differential current component 1.6.5 (87-T2) Transformer 2 9 SIP5-APN-025-de

1.7 Fault examples (without load current) 1.7.1 External fault L1-L2 on 34.5 kv The stabilizing current with the 87-T2 (125 MVA) is 4 times greater than with the 87-T1 (500 MVA). SIP5-APN-025-de 10

1.7.2 External fault L1-E on the 230 kv A zero sequence current circulates in the tertiary winding. This has a stabilizing effect on the 87-T2. 11 SIP5-APN-025-de

1.7.3 Internal fault L1-E on 230 kv 87-T1 only trips the faulted phase L1 unambiguous! A zero sequence current circulates in the tertiary winding, similar as with the external fault. Here again the zero sequence current has a stabilizing effect on the 87-T2. SIP5-APN-025-de 12

1.7.4 Internal fault L1-L2 on 34,5 kv (out the delta connection) This is an external fault for the 87-T1, the 87-T2 on the other hand trips. The trip is issued on all three phases. Although there is no zero sequence current, there is fault current in-feed on all three limb windings during the fault L1-L2. 13 SIP5-APN-025-de

1.7.5 Internal fault L1-LE on the 34,5 kv (out the delta connection) This is an external fault for the 87-T1, the 87-T2 on the hand trips. Due to the neutral grounding transformer, a fault current which results in tripping in this case is also present during the single phase fault. This fault current is fed via two limb windings (no zero sequence current). SIP5-APN-025-de 14

15 SIP5-APN-025-de

Fehler! Verweisquelle konnte nicht gefunden werden. Published by and copyright 2013: Siemens AG Infrastructure & Cities Sector Smart Grid Division Humboldtstr. 59 90459 Nuremberg, Germany Siemens AG Infrastructure & Cities Sector Smart Grid Division Energy Automation Humboldtstr. 59 90459 Nuremberg, Germany www.siemens.com/protection Printed on elementary chlorine-free bleached paper. All rights reserved. If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights. Drawings are not binding. All product designations used are trademarks or product names of Siemens AG or other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract. For more information, please contact our Customer Support Center. Tel.: +49 180 524 8437 Fax: +49 180 524 24 71 (Charges depending on provider) E-mail: support.ic@siemens.com Application note: SIP5-APN-025 SIP5-APN-025-de 16