Ferroresonance Experience in UK: Simulations and Measurements

Similar documents
Modeling Ferroresonance Phenomena on Voltage Transformer (VT)

FERRORESONANCE SIMULATION STUDIES USING EMTP

Sensitivity studies on power transformer ferroresonance of a 400 kv double circuit

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

TECHNICAL BULLETIN 004a Ferroresonance

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Research Article Resistive Ferroresonance Limiter for Potential Transformers

Electrical Power and Energy Systems

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Simulation and Analysis of Ferroresonance in Power System

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

A Study on Ferroresonance Mitigation Techniques for Power Transformer

ELECTRICAL POWER ENGINEERING

Parameter Study of Ferro-Resonance with Harmonic Balance Method

Effect of Circuit Breaker Shunt Resistance on Chaotic Ferroresonance in Voltage Transformer

ABSTRACT 1 INTRODUCTION

STUDY ON THE NON LINEAR CHARACTERISTIC OF POWER TRANSFORMER AND THEIR EFFECT FERRORESONANCE SALIZAWATI BT HJ. SHAMSUDDIN

Ferroresonance Elimination in 275kV Substation

Analysis of Electromagnetic Transients in Secondary Circuits due to Disconnector Switching in 400 kv Air-Insulated Substation

Spectral analysis of voltages and currents during different modes of ferroresonance in switchgear

Effect of Metal Oxide Surge Arrester on Ferroresonance in Voltage Transformer Including Nonlinear Core Losses

GIS Disconnector Switching Operation VFTO Study

FERRORESONANCE - its Occurrence and Control in Electricity Distribution Networks

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Innovative Science and Technology Publications

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

DEVELOPMENT OF NUMERICAL ALGORITHMS FOR FERRORESONANCE MONITORING

Power Systems Modelling and Fault Analysis

Modeling insulation in high-voltage substations

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

Simulation of Ferroresonance Phenomena in Power Systems

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

(2) New Standard IEEE P (3) Core : (4) Windings :

The study of ferroresonance effects in electric power equipment

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software

SATURATION ANALYSIS ON CURRENT TRANSFORMER

Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

of the improved scheme is presented. Index Terms Inrush current, power quality, transformer.

Analysis of a 405 km transmission line with series compensation

Tab 2 Voltage Stresses Switching Transients

Ferroresonances during Black Starts - Criterion for Feasibility of Scenarios

Ferroresonance Signal Analysis with Wavelet Transform on 500 kv Transmission Lines Capacitive Voltage Transformers

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Core Technology Group Application Note 1 AN-1

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

Power Quality enhancement of a distribution line with DSTATCOM

Power Quality and Reliablity Centre

Current Transformer Performance study Using Software Tools.

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

ACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

Look over Chapter 31 sections 1-4, 6, 8, 9, 10, 11 Examples 1-8. Look over Chapter 21 sections Examples PHYS 2212 PHYS 1112

A SPECIAL CASE OF FERRORESONANCE INVOLVING A SERIES COMPENSATED LINE

UNDERSTANDING SUB-HARMONICS

Keywords: Transformer modeling, saturation, hysteresis, MATLAB. Introduction

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Frequency domain analysis of a power transformer experiencing sustained ferroresonance

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

Impact of the system parameters on the ferroresonant modes

Transformer Inrush and Voltage Sag P28 Studies. August 2017

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

Module 1. Introduction. Version 2 EE IIT, Kharagpur

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

Operating principle of a transformer

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Transformers and power quality Part II. Modelling and researching generation of higher harmonics in small three-phase transformers

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Protection of Electrical Networks. Christophe Prévé

Burdens & Current Transformer Requirements of MiCOM Relays. Application Notes B&CT/EN AP/B11. www. ElectricalPartManuals. com

INFLUENCE OF INSTRUMENT TRANSFORMERS ON POWER SYSTEM PROTECTION. A Thesis BOGDAN NAODOVIC

Three-Phase/Six-Phase Conversion Autotransformers

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Resonances in Collection Grids of Offshore Wind Farms

Long lasting transients in power filter circuits

Generator Advanced Concepts

System grounding of wind farm medium voltage cable grids

Class XII Chapter 7 Alternating Current Physics

Electromagnetic Interference in the Substation Jose up 400/115 kv

Frequency Domain Analysis of Capacitor Transient Overvoltages

Study of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T.

Alternative Testing Techniques for Current Transformers. Dinesh Chhajer, PE Technical Support Group MEGGER

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

A Guide to the DC Decay of Fault Current and X/R Ratios

Analysis of Indirect Temperature-Rise Tests of Induction Machines Using Time Stepping Finite Element Method

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

RESONANT TRANSFORMER

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

HARMONIC distortion complicates the computation of. The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

2 Grounding of power supply system neutral

Transcription:

Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey KT22 7ST UNITED KINGDOM Abstract - Ferroresonance is a complex non-linear electrical phenomenon that can cause dielectric & thermal problems to the transmission plant and switchgear. Electrical systems exhibiting ferroresonant behaviour are nonlinear dynamical systems. The application of conventional linear mathematics is therefore not fully appropriate for the study of ferroresonance. The prediction of ferroresonance is achieved by detailed modelling using a digital computer transient analysis program such as the EMTP/ATP. This paper presents the analyses performed with ATP and compares them with system measurements to identify the crucial factor in ferroresonance. Keywords: Ferroresonance, electromagnetic voltage transformer, traction supply transformer, ATP, nonlinear dynamics. I. INTRODUCTION Ferroresonance or nonlinear resonance is a complex electrical phenomenon, which may cause overvoltages and overcurrents in an electrical power system thus endanger the transmission plant, switchgear and the operational personnel. Ferroresonant overvoltages on electrical power systems were recognised and investigated as early as 1930s [1]. It occurs when a nonlinear inductor is fed from a series capacitor. The nonlinear inductor can be due to the magnetic core of a wound type voltage transformer or it may be due to the complex structure of a 3 or 5 limb threephase power transformer. The circuit capacitance can be due to a number of elements, such as the circuit-to-circuit capacitance or parallel lines, conductor to earth capacitance, circuit breaker grading capacitance, busbar capacitance, bushing capacitance, etc. Ferroresonance should not be confused with linear resonance that occurs when inductive and capacitive reactances of a circuit are equal. In linear resonance the current and voltage are linearly related in a manner which is frequency dependent. In the case of ferroresonance it is characterised by a sudden jump of voltage or current from one stable operating state to another one. The relationship between voltage and current is dependent not only on frequency but also on a number of other factors such as the system voltage magnitude, initial magnetic flux condition of transformer iron core, the total loss in the ferroresonant circuit and the point on wave of initial switching. Although analytical methods, such as the principle of harmonic balance, can be employed to model and analyse ferroresonant systems, they do not provide an overall picture of the behaviour of the system. This is mainly because of the characteristic of the analyses of forced nonlinear systems where even relatively simple nonlinear differential equations lead to algebraic equations of considerable complexity. Conventional linear mathematics is therefore inappropriate in this situation and researchers are applying nonlinear dynamics and/or chaos theory to describe the phenomenon [2, 3]. II. SYSTEM DESCRIPTION AND ATP MODELLING Current studies related to ferroresonance in electromagnetic wound voltage transformers (VT) and single-phase traction supply transformers. A Voltage Transformer Ferroresonance[5,6] During voltage transformer ferroresonance an oscillation occurs between the nonlinear inductance of the VT and the capacitance of any network remaining connected to the VT. In this case, energy is coupled to the nonlinear core of the voltage transformer via the open circuit breaker grading capacitance to sustain the resonance. The VT can be driven into saturation resulting in high currents at sub-harmonic or fundamental frequency. For the latter, very high voltage of up to 4 pu can theoretically arise in worst case conditions. Electromagnetic voltage transformers have a relatively low thermal capacity and overheating can result in insulation failure very quickly. Fig.1 shows the single line diagram of the most commonly encountered system arrangement that can give rise to VT ferroresonance. Ferroresonance can occur upon opening of disconnector 3 with circuit breaker open and either disconnector 1 or 2 closed. Alternatively it can also occur upon closure of either disconnector 1 or 2 with circuit breaker and disconnector 3 open. Disconnector 1 Disconnector 2 C Disconnector 3 Main Busbar Reserve Busbar Circuit Breaker Fig. 1 System arrangement resulting to VT ferroresonance VT

The system arrangement shown in Fig. 1 can effectively be reduced to an equivalent circuit as shown in Fig. 2. C series Circuit Breaker 1 Circuit Breaker 2 E i V C shunt R Single-phase Traction Supply Transformer Fig. 3 Traction supply transformer ferroresonance arrangement III. FIELD MEASUREMENTS vs SIMULATION RESULTS Fig. 2 Reduced equivalent ferroresonant circuit In Fig. 2, E is the rms supply phase voltage, C series is the circuit breaker grading capacitance and C shunt is the total phase-to-earth capacitance of the arrangement. The resistor R represents voltage transformer core losses that has been found to be an important factor in the initiation of ferroresonance [4,8,9]. The circuit of Fig.2 is modelled in ATP [7]. Transformer magnetisation characteristic supplied by the manufacturer was used in a type-93 true nonlinear inductor to simulate the magnetic core of the VT. The VT itself is a low thermal capacity, 400kV/110V, 100VA wound voltage transformer. C series and C shunt were represented as lumped parameters. The resistance R was represented dynamically based on R R OS MS R = + a B 1+ B S R MS In (1) R OS =60Ω, R MS =20Ω, B S =1.7T and a=9.5. At every integration time-step of ATP then the value of R is recalculated depending on the value of B. B Traction Supply Transformer Ferroresonance Fig. 3 shows the single line diagram of a traction supply transformer arrangement. The single phase transformer is fed from two phases of the three-phase system. Ferroresonance occurs upon opening of circuit breakers 1 and 2 to de-energise the line and the transformer. Energy is coupled to the de-energised network from the adjacent live parallel circuit via the inter-circuit coupling capacitance, i.e. C series in the equivalent ferroresonant circuit. The equivalent C shunt in the ferroresonant circuit is the phase-to-earth capacitance of the line and the transformer winding and bushing capacitance. Simulation of traction supply transformer can be carried out on a complex 3-phase network. Both the measurements and simulation results are given in figure 9. Nevertheless digital computer modelling of the traction supply transformer configuration can be simplified using the single-phase ferroresonant equivalent circuit given in Fig. 2. (1) A Voltage Transformer Ferroresonance Fig. 4 (a) and (b) show the measured and simulated VT secondary voltages respectively. The measured test waveform of Fig. 4 (a) was obtained after opening disconnector 3 in Fig. 1. As it can be seen from the graphs the VT did not go into ferroresonance. Although the simulated waveform does not match the measured test waveform exactly, its general appearance is a very close fit. It can be said that the ATP model employed in this study is capable of predicting possible ferroresonance modes as long as the parameters of the system are known or can be estimated. In the study C series was set to 514pF and C shunt to 1137pF to give the waveform of Fig. 4 (b). Primary current waveforms for the field measurement and the simulation study are given in Fig. 5 (a) and (b), respectively. When the same system is tested for a second time the response is totally different to the above in that it is driven into sub-harmonic ferroresonance. Prediction of this response with digital simulation proved to be hard as the system is very sensitive to parameter changes. The measured and simulated VT secondary voltage waveforms are shown in Fig. 6 (a) and (b) and the corresponding primary current waveforms are given in Fig. 7 (a) and (b), respectively. The shape of measured and simulated waveforms in Figs. 6 & 7 (a) and (b) are of a good match. The minute difference is believed was due to the numerical and actual saturation around the knee point of the magnetisation curve. The bifurcation diagram of Fig. 10 shows the sensitivity of the model to applied voltage E. Bifurcation diagrams provide information about the dynamics of the system for range of parameter values. In the diagram of Fig. 10 all system parameters except E were constant. Values of E from 0.8pu to 1.15pu result to a normal response while at 1.15pu and onwards a fundamental ferroresonant response is present. B Traction Supply Transformer Ferroresonance Figs. 8 and 9 show the results of a full scale measurement and simulation of a traction supply transformer which ferroresonated at 50Hz, the fundamental system frequency. The phase voltages and current on the de-energised transformer are presented. Clearly, the two phases feeding the transformer are in sustained fundamental frequency mode ferroresonance.

(a) field measurement VT Secondary Voltage 1.2 0.6 0.0-0.6-1.2 0.0 0.2 0.4 0.6 0.8 1.0 Fig. 4 VT secondary voltages (values in p.u.) showing normal response (a) field measurement VT Primary Current (ma) 150 100 50 0-50 -100-150 0.0 0.2 0.4 0.6 0.8 1.0 Fig. 5 VT primary currents showing normal response

(a) field measurement VT Secondary Voltage 1.5 1.0 0.5 0.0-0.5-1.0-1.5 0.0 0.2 0.4 0.6 0.8 1.0 Fig. 6 VT secondary voltages (values in p.u.) showing sub-harmonic (16.6Hz) ferroresonance (a) field measurement VT Primary Current (ma) 150 100 50 0-50 -100-150 0.0 0.2 0.4 0.6 0.8 1.0 Fig.7 VT primary currents showing sub-harmonic (16.6Hz) ferroresonance

Fig. 8 Field measurements of a fundamental frequency ferroresonance in a traction supply transformer system Fig. 9 Digital simulation results for the system tests shown in Fig. 8

VI. REFERENCES transformer voltage (p.u.) 2 1 0-1 -2 0.8 0.9 1.0 1.1 1.2 E (p.u.) Fig. 10 Bifurcation diagram showing sensitivity of model to E (all other parameters kept constant) IV. CONCLUSIONS A reliable prediction of the ferroresonant voltage and current in advance can provide valuable information to planners to design the system, engineers to specify the equipment and operators to run the transmission plant within all the design and tested criteria and capabilities. This comprehensive understanding can be achieved if all the parameters of the system and plant in question are available or can be estimated with reasonable accuracy. Although the model used in this study provided comparable result with those of field measurements, many more questions, such as the effect of magnetisation hysteresis and remnance and the Point-on-Cycle switching etc are still to be examined. Boundary approach can be adopted to establish the interaction between the system and the plant, and subsequently bringing forward an operating window with the lowest ferroresonance risk. V. ACKNOWLEDGEMENT The work was carried out at National Grid Engineering & Technology and the paper is published with the permission of The National Grid Company. [1] P.H. Odessey and E. Weber, Critical conditions in ferroresonance, AIEE Trans. Vol. 57, 1938, pp. 444-452. [2] C. Kieny, Application of the bifurcation theory in studying the global behaviour of a ferroresonant electric power circuit, IEEE Trans. on Power Delivery, Vol. 6, No. 2, April 1991, pp. 866-872. [3] Z. Emin, B.A.T. Al Zahawi, D.W. Auckland and Y.K. Tong, Ferroresonance in Electromagnetic Voltage Transformers: A Study Based on Nonlinear Dynamics, IEE Proc. on Generation, Transmission, Distribution, Vol. 144, No. 4, July 1997, pp. 383-387. [4] Z. Emin, B.A.T. Al Zahawi and Y.K. Tong, Core Loss Effects on the Ferroresonant Behavior of Wound Voltage Transformers, 10 th International Symposium on High Voltage Engineering, August 25-29, Montreal. [5] Tong Y K, NGC Experience on Ferroresonance in Power Transformers and Voltage Transformer on HV transmission Systems IEE Colloquium 1997. [6] NGC Technical Guidance Note TGN86, Control of Ferroresonance. [7] EMTP Rule Book and Theory Book. [8] B.A.T. Al Zahawi, Z. Emin and Y.K. Tong, Chaos in Ferroresonant Wound Voltage Transformers: Effect of Core Losses and Universal Circuit Behaviour, IEE Proc. on Science, Measurement, Technology, Vol. 145, No. 1, January 1998, pp. 39-43. [9] Z. Emin, B.A.T. Al Zahawi and Y.K. Tong, Voltage Transformer Ferroresonance in 275kV Substation, 11 th International Symposium on High Voltage Engineering, August 23-27, London.