SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

Similar documents
Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents

International Journal of Advance Engineering and Research Development. Short-circuit analysis of Industrial plant

ETAP PowerStation 4.0

Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

MV network design & devices selection EXERCISE BOOK

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

CONTENTS. 1. Introduction Generating Stations 9 40

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Short Circuit Current Calculations

PROTECTION of electricity distribution networks

3Ø Short-Circuit Calculations

Electrical Power Systems

Electrical Protection System Design and Operation

TABLE OF CONTENT

Impact Assessment Generator Form

How to maximize reliability using an alternative distribution system for critical loads

A Guide to the DC Decay of Fault Current and X/R Ratios

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

Notes 1: Introduction to Distribution Systems

Preface...x Chapter 1 Electrical Fundamentals

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

ESB National Grid Transmission Planning Criteria

Digital Fault Recorder Deployment at HVDC Converter Stations

Power Plant and Transmission System Protection Coordination Fundamentals

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Fast Protection of Strong Power System With Fault Current Limiters and PLL - Aided Fault Detection

Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC)

INVESTIGATION INTO THE POWER QUALITY AND RELIABILITY OF SUPPLY IN THE INDUSTRIAL NETWORKS WITH DISTRIBUTED GENERATION

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Appendix D Fault Levels

Short-circuits in ES Short-circuit: cross fault, quick emergency change in ES the most often fault in ES transient events occur during short-circuits

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

THREE-PHASE SHORT-CIRCUIT TESTING OF HIGH-VOLTAGE CIRCUIT-BREAKERS USING SYNTHETIC CIRCUITS

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

In Class Examples (ICE)

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device

Modelling of Phasor Measurement Unit and Phasor Data Realisation with 2 Bus System

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

Impact of Thyristor Controlled Series Capacitor on Voltage Profile of Transmission Lines using PSAT

Electrical Engineering. Power Systems. Comprehensive Theory with Solved Examples and Practice Questions. Publications

Power Systems Modelling and Fault Analysis

Determination of Optimal Account and Location of Series Compensation and SVS for an AC Transmission System

International Journal of Advance Engineering and Research Development

System grounding of wind farm medium voltage cable grids

ELECTRICAL POWER ENGINEERING

Bruce L. Graves /01/$ IEEE. IEEE Industry Applications Magazine PhotoDisc, Inc.

Single Line Diagram of Substations

Substation Testing and Commissioning: Power Transformer Through Fault Test

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

Embedded Generation Connection Application Form

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

I. INTRODUCTION IJSRST Volume 3 Issue 2 Print ISSN: Online ISSN: X

Cause, Effect & Mitigation Strategies

HIGH VOLTAGE CIRCUIT BREAKERS

1 Introduction General Background The New Computer Environment Transmission System Developments Theoretical Models and Computer Programs

Fixed Series Compensation

Fault Current Limiter Selection Considerations for Utility Engineers

Poly Canyon Cogeneration System

This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor.

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Central or Local Compensation of Earth-Fault Currents in Non- Effectively Earthed Distribution Systems

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

ARC FLASH HAZARD ANALYSIS AND MITIGATION

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

Smart Grid Where We Are Today?

EH2741 Communication and Control in Electric Power Systems Lecture 2

Lightning test in lab. Symmetrical fault and protection. Olof Samuelsson

Bus Protection Fundamentals

EDS FAULT LEVELS

Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

Utility Interconnection and System Protection

9 Overcurrent Protection for Phase and Earth Faults

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software

2 Grounding of power supply system neutral

ECET 211 Electric Machines & Controls Lecture 3-1 (Part 1 of 2) Motor Transformers and Distribution Systems

Unit 2. Single Line Diagram of Substations

Power System Stability. Course Notes PART-1

Distribution System Development & Preliminary Studies

Switching and Fault Transient Analysis of 765 kv Transmission Systems

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

Embedded Generation Connection Application Form

Electrical Arc Hazards

Electrical PIP ELEGL03 Guidelines for Power Systems Analysis

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Wind Power Facility Technical Requirements CHANGE HISTORY

Voltage Unbalance Mitigation Using Positive Sequence Series Compensator

Adaptive Relaying of Radial Distribution system with Distributed Generation

Transcription:

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP Kiran V. Natkar 1, Naveen Kumar 2 1 Student, M.E., Electrical Power System, MSS CET/ Dr. B.A.M. University, (India) 2 Electrical Power System, MSS CET/ Dr. B.A.M. University, (India) ABSTRACT Modern power system is different from older system. The character of load is drastically changed now days. As most of the load is controlled and operated by using digital electronics controller. It is also important to focus on protection of the modern power system. For healthy operation of electrical power generation, transmission and distribution, it is important that system should be balanced and fault current should be in design limits. This paper deals with the simulation of 220/132 kv substation fault current calculation. The analysis is done by using advance software Electrical Transient Analyzer Program (ETAP) with detailed short circuit analysis. All the data used for analysis is real time and collected from 220/132 KV substation under M.S.E.T.C.L. Keywords: ETAP, Fault studies using ETAP, Fault Studies on Software, Short Circuit Analysis using ETAP, Substation Fault Analysis. I. INTRODUCTION Recent advances in engineering sciences have brought a revolution in the field of electrical engineering after the development of powerful computer based software. This research work high- lights the effective use of Electrical Transient Analyzer Program (ETAP) software for Short Circuit Studies. Transmission networks of present power systems are becoming progressively more stressed because of increasing demand and limitations on building new lines. One of the consequences of such a stressed system is the risk of losing stability following a disturbance. Transients occur due to various disturbances like sudden change in the load, switching of the power electronics devices and capacitor banks, loss of the synchronous generators. The short circuit fault can occurs due to any reason. In electrical devices unintentional short circuits are usually caused when a wire's insulation breaks down, or when another conducting material is introduced, allowing charge to flow along a different path than the one intended. In mains circuits, short circuits may occur between two phases, between a phase and neutral or between a phase and earth (ground). Such short circuits are likely to result in a very high current and therefore quickly trigger an over current protection device. However, it is possible for short circuits to arise between neutral and earth conductors, and between two conductors of the same phase. Such short circuits can be dangerous, particularly as they may not immediately result in a large current and are therefore less likely to be detected. Possible effects include unexpected energisation of a circuit presumed to be isolated. A short circuit fault current can, within milliseconds, be thousands of times larger than the normal operating current of the system. Damage from short circuits can be reduced or prevented by employing fuses, circuit 415 P a g e

breakers, or other overload protection, which disconnect the power in reaction to excessive current. Overload protection must be chosen according to the current rating of the circuit. In this work there are out Short circuit analysis of 220 kv substation. The actual ratings of Power Transformers, Circuit Breakers, Current Transformers, Potential Transformers and Isolating switches are taken and modeled accordingly in ETAP. This 220 kv substation is located in Maharashtra State Electricity Transmission Corporation Limited (MSETCL) which comprises of 4 Power Transformers, 25 Circuit Breakers, 21 Current Transformers, 4 Potential Transformers and 55 Isolating switches. II. ABOUT ETAP ETAP is Electrical Transient Analyzer Program. This software provides engineers, operators, and managers a platform for continuous functionality from modeling to operation. ETAP s model-driven architecture enables Faster than Real-Time operations - where data and analytics meet to provide predictive behavior, preemptive action, and situational intelligence to the owner-operator. ETAP offers a suite of fully integrated electrical engineering software solutions including arc flash, load flow, short circuit, transient stability, relay coordination, cable capacity, optimal power flow, and more. Its modular functionality can be customized to fit the needs of any company, from small to large power systems. Here we are focusing on load flow studies of 220 kv/132 kv/33 kv substation. III. DETAILS OF COMPONENTS COMPONENT TYPE RATINGS Power Transformer Circuit Breaker Transformer 1 Transformer 2 Transformer 3 Transformer 4 CB 1-11 CB 12-19 CB 20-25 50 MVA 25 MVA 150 MVA 100 MVA 33kV/1600A 145kV/3150A 245kV/3150A Primary Secondary CT 1-3 800A 1A Current Transformer CT 4-11 200A 1A CT 12-18 800A 1A CT 19-22 400A 1A 416 P a g e

PT 1 220kV 120V Potential Transformer PT 2,3 33kV 120V PT 4 132kv 120V SW 1-20,45,47,49 33kV/1500A Isolating Switches SW 21-37,50 SW 38-44,46-48 SW 51-55 Load 1 132kV/1250A 220kV/1000A 220kV/1000A 175A Load 2 262.4A Load 3 175A Feeders Load 4 140A Load 5 209.9A Load 6 122.5A Load 7 157.5A Load 8 140A Load 9 349.9A Load 10 306.2.A Feeders Load 11 43.74 Load 12,13,14 0A (FUTURE) IV. SHORT CIRCUIT SIMULATION OF 220 kv SUBSTATION IN ETAP Fig. 1 shows the Power Grid which supplies power to the 220 kv Bus 6 and Bus 7. Transformer 1 and Transformer 2 are 220kV/33kV supply power to Bus 1 and Bus 2 respectively. Four feeders are emanating from Bus 1 and four feeders are emanating from Bus 2. On the other side Transformer 3 and Transformer 4 is 220kV/132kV supply power to Bus 4 and Bus 5 respectively. Three feeders are emanating from Bus 4 and three feeders are emanating from Bus 5. 417 P a g e

V. SHORT CIRCUIT ANALYSES Fig.1. Simulated diagram of 220 kv substation using ETAP Fig. 2 shows the sectional view of short circuit current flow Analysis of the 220kV substation carried out using ETAP. It is observed that at the Bus 4 and Bus 5 there is fault at that bus which can be clearly seen from Fig. 2 showing the sectional view of the feeders. At Bus 4 and Bus 5 the current is 6.67kA. That is when 3 phase short circuit happened on this bus the fault current will flow from them is 6.67kA. Both the buses are connected with the help of tie breaker. The voltage level of 132 kv bus is decreased to 71.93 kv. This short circuit is done with reference of IEC60909. The manual calculation of this fault current is time consuming, but as ETAP software work on the both standards either ANSI or IEC the results are more accurate and according to standard which we consider for analysis. Similarly from fig 3 it is observed that at the Bus 1 and Bus 2 there is under voltage which can be clearly seen from the sectional view of the feeders. At Bus 1 and Bus 2 the voltage level shown in red color indicating 19.81 kv and the fault current is 14.16 ka. These values give us the components rating which can be used to design condition as well as current condition of the protection system for the substations. Fig -2 Sectional view of Substation 418 P a g e

Fig -3 Sectional view of Substation VI. GENERAL DESCRIPTION OF CALCULATION METHODOLOGY In IEC short-circuit calculations; an equivalent voltage source at the fault location replaces all voltage sources. A voltage factor c is applied to adjust the value of the equivalent voltage source for minimum and maximum current calculations. All machines are represented by their internal impedances. Transformer taps can be set at either the nominal position or at an operating position, and different schemes are available to correct transformer impedance and system voltages if off-nominal tap setting exists. System impedances are assumed to be balanced 3-phase, and the method of symmetrical components is used for unbalanced fault calculations. Zero sequence capacitances of transmission lines, cables and shunt admittances can be considered for unbalanced fault calculations (LG and LLG) if the option in the study case is selected to include branch Y and static load. This means that the capacitances of static loads and branches are considered based on IEC 60909-0 2001. Calculations consider electrical distance from the fault location to synchronous generators. For a far-fromgenerator fault, calculations assume that the steady-state value of the short-circuit current is equal to the initial symmetrical short-circuit current and only the DC component decays to zero. However, for a near-to-generator fault, calculations count for decaying in both AC and DC components. The equivalent R/X ratios determine the rates of decay of both components, and different values are taken for generators and loads near the fault. VII. FORMULAS AND EQUATIONS The short circuit current for a circuit in which the pre-load current can be ignored is: Where, (1) (2) 419 P a g e

Ɵ= impedance angle α= initial phase displacement (or offset) angle of the source voltage, v (t) The time constant, T, for the circuit is given by, (3) (4) For a three phase fault, L and R are the positive sequence inductance and resistance of the system. For an earth fault, L and R are derived from Z TOT = R TOT + jx TOT = Z 1 + Z 2 + Z 0. The maximum possible offset occurs when, α Ɵ = ±90 i.e. or (5) The asymmetrical R.M.S. equivalent of the transient current, I R.M.S., is given by, (6) K is called the asymmetry factor. The asymmetrical r.m.s. fault current varies from 3 I AC when t = 0 to I AC when t is large where I AC = Init Sym RMS. Note that the asymmetrical rms current does not form part of IEC60909. The peak current, I p, as per IEC 60909 is given by The limit for both is when X/R approaches giving i p(max) =2* 2*Ik" or i p(max) = 2*2* I AC. (7) VIII. SIMULATION RESULT OF FAULTS AT VARIOUS BUSES 8.1 Faults at Bus 1 and Bus 2 FAULT 3 Phase L G L L L L G Initial Symmetrical Current (ka, rms) 14.954 14.162 12.951 14.763 Peak Current (ka), 37.980 35.969 32.892 37.494 Breaking Current (ka, rms, symm) 14.162 12.951 14.736 Steady State Current (ka, rms) 3.260 14.162 12.951 14.763 Table 2 Fault Current at Bus 1&2 420 P a g e

8.2 Faults at Bus 4 and Bus 5 FAULT 3 Phase L G L L L L G Initial Symmetrical Current (ka, rms) 5.728 6.666 4.961 6.463 Peak Current (ka), 14.384 16.739 12.457 16.230 Breaking Current (ka, rms, symm) 6.666 4.961 6.463 Steady State Current (ka, rms) 0.985 6.666 4.961 6.463 Table 3 Fault Current at Bus 4&5 8.3 Faults at Bus 8 and Bus 9 FAULT 3 Phase L G L L L L G Initial Symmetrical Current (ka, rms) 3.056 1.377 2.646 2.689 Peak Current (ka), 7.798 3.514 6.753 6.862 Breaking Current (ka, rms, symm) 1.377 2.646 2.698 Steady State Current (ka, rms) 0.656 1.377 2.646 2.689 Table 4 Fault Current at Bus 8&9 IX. REFERENCE FOR RELAY CO-ORDINATION Relay co-ordination plays an important role in the protection of power system. For proper protection, proper coordination of relays with appropriate relay settings is to be done. Relay settings are done in such a way that proper co-ordination is achieved along various series network. However the review of Co-ordination is always essential since various additions / deletion of feeders and equipments will occur after the initial commissioning of plants. As power can be received from generators of captive power plant, the analysis becomes complex. So this study can be a base reference for relay as well as circuit breaker ratings and plug setting of the protective devices. X. CONCLUSIONS Short circuit studies are important for planning future expansion of power systems as well as in determining the best operation of protective systems. In this paper design analysis of 220/132 kv substation using ETAP software is carried out with an approach to calculate short circuit current of complex substation. Short circuit Studies using ETAP software is an excellent tool for system planning and its protection. A number of operating procedures is analyzed such as line to line fault, line to ground fault, line-line to ground fault and three phase fault. This can be used to determine the optimum size and location of relays and circuit breaker. Also, it is useful in determining the system voltages under conditions of different faults. REFERENCES [1] Kiran Natkar, Naveen Kumar, Design Analysis of 220/132 KV Substation Using ETAP, ISSN: 2395-0072, Volume: 02 Issue: 03 (June-2015) [2] ETAP Operations Technology, Inc., Available: http://www.etap.com. 421 P a g e

[3] P. Kundar, Power System Stability and Control. New York: McGraw-Hill, 1994. [4] P.K. Iyambo, R. Tzonova, Transient Stability Analysis of the IEEE 14- Bus Electrical Power System, IEEE Conf. 2007. [5] P. M. Anderson and A. A. Fouad, Power System Control and Stability. New York: IEEE Press,1994. [6] Rana A. Jabbar Khan, Muhammad Junaid, Muhammad Mansoor Asgher, Analysis and Monitoring of 132 grid using ETAP software. [7] Hadi Saadat (2002) Power System Analysis, Edition, Tata Mc Graw Hill. 422 P a g e