Acquisition of transformer tap positions via an analog measurement transformer

Similar documents
Ground fault supervision of 4 feeders with 7SJ82 or 7SJ85 with 4x I, 4x V

Breaker Pole Discrepancy Function

SIPROTEC 5 Application Note

Line protection with transformer in the protection zone

SIPROTEC 5 Application Note

Impedance protection on power transformer.

SIPROTEC 5 Application. SIP5-APN-025-en: 7UT8 Autotransformer bank with 2 sets of CT inside the delta connection of the compensation side

Fast fault location in medium-voltage cable and overhead line networks siemens.com/short-circuit-indicator

Load Shedding (7RW80)

Application of Low-Impedance 7SS601 Busbar Differential Protection

Enhance operational efficiency with Advanced Process Control (APC) Integration of APC in SIMATIC PCS 7 SIMATIC PCS 7. Answers for industry.

Repair & Retrofit new life for old transformers. Repair and retrofitting through TLM Transformer Lifecycle Management. Answers for energy.

D3 04AD 4-Channel Analog Input

This Errata Sheet contains corrections or changes made after the publication of this manual.

PT100N - Operating instructions

F3 08AD 1 8-Channel Analog Input

Parallel. Parallel. data transmission. Technical Information TR - ECE - TI - GB /05/2016

SINAMICS drives SINAMICS DCM. DC converters from 6 kw to 2500 kw for variable-speed direct-current drives

Temperature Monitoring and Fan Control with Platform Manager 2

The DC Machine Laboration 3

Differential Protection with REF 542plus Feeder Terminal

F3 16AD 16-Channel Analog Input

Overcurrent Protection 7SJ82/7SJ85. Technical Data. Extract from manual C53000-G5040-C017-6, chapter 11. Energy Automation

TD-100 Position Indicator

F4-04ADS 4-Channel Isolated Analog Input

GA A25824 A NEW OVERCURRENT PROTECTION SYSTEM FOR THE DIII-D FIELD SHAPING COILS

Temperature Monitoring and Fan Control with Platform Manager 2

SIPROTEC. Power Supply Transfer Device 7VU68. Preface. Table of contents. Data of the PROFIBUS-DP messages 1. Standard mappings

DIGITAL FILTERING OF MULTIPLE ANALOG CHANNELS

UG0640 User Guide Bayer Interpolation

Tel: Fax:

F4 08DA 2 8-Channel Analog Voltage Output

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Differential Protection Optimal differential protection for phase shifter transformers and special transformers

V7.50 and higher Low-Impedance Busbar Protection 7SS85

Drive System Application

F4 16DA 2 16-Channel Analog Voltage Output

Thermocouple Conditioner and Setpoint Controller AD596*/AD597*

EKT 314/4 LABORATORIES SHEET

Isolated, Linearized RTD Input 7B34 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

NOTICE. (Formulated under the cognizance of the CTA R4 Video Systems Committee.)

PROFINET USER S GUIDE ACSI Servo

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

4413 UPDATING PROGRAMMABLE DISCRIMINATOR 4415A NON-UPDATING PROGRAMMABLE DISCRIMINATOR

Isolated High Level Voltage Output 7B22 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

APPLICATION BULLETIN PRINCIPLES OF DATA ACQUISITION AND CONVERSION. Reconstructed Wave Form

SIPROTEC 5 V7.50 and higher Overcurrent Protection 7SJ82/7SJ85 Technical Data Extract from manual C53000-G5040-C017-8, chapter 12 Energy Automation

Jitter Analysis Techniques Using an Agilent Infiniium Oscilloscope

BCV-1203 Barcode Verification System Users Guide Version 1.2

SIMATIC Vision Sensor SIMATIC VS130-2 and VS 130-2vcr

Portfolio. and ULTRAWATER. Ultrasonic Static Meters. Ultrasonic Meters Residential and District Heating/ Cooling Water Measurement

icwaves Inspector Data Sheet

F2-04AD-2, F2-04AD-2L 4-Channel Analog Voltage Input

F4-08RTD 8-Channel RTD Input

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

F4-04DA-1 4-Channel Analog Current Output

CMOS Micro-Power Comparator plus Voltage Follower

Technical Note. How to Use the Image Studio Software Small Animal Image Analysis. Developed for: Image Studio Software

DT9838 Strain Measurement Module

F4 04DAS 1 4-Channel Isolated 4 20mA Output

Digital Systems Design

xtimecomposer Studio Tutorial

HALL-EFFECT, DIRECTION-DETECTION SENSORS

GE Fanuc IC695ALG600. Rx3i PacSystem

LV-Link 3.0 Software Interface for LabVIEW

Isolated, Linearized Thermocouple Input 7B47 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

XC series PLC expansion module User Manual

Isolated, Thermocouple Input 7B37 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Notes on OR Data Math Function

RS Block A module of RS LabSite Multi-Axis Cyclic Testing with Monitoring and Analysis

Designing in the context of an assembly

technical documentation Requirements CAD-Import GEMOS / Checklist CAD-Drawing GEMOS4

Series SPPM2 Graphical User Interface Panel Meter. Specifications - Installation and Operating Instructions MINI USB PORT

DT9838. Strain- and Bridge-Based Measurement Module. Key Features: Bridge Configurations. Analog Input Features

ma/bcd Converter Model MFC-201 ma/bcd The MFC-201 ma/bcd Converter is a device designed to convert a DC current signal into BCD (8421) signals.

SHF BERT & DAC for NRZ, PAM4 and Arbitrary Waveform Generation

Oscilloscope Measurement Fundamentals: Vertical-Axis Measurements (Part 1 of 3)

JPQ2 PULSE ACCUMULATOR

MFJ ENTERPRISES, INC.

Interfacing Virtex-6 FPGAs with 3.3V I/O Standards Author: Austin Tavares

SIPROTEC 5 V1.1 High-Voltage Bay Control Unit 6MD85/86. Technical Data. Extract from manual C53000-G5040-C015-1, chapter 11.

IP-OptoAD16. Opto-Isolated 16-bit A/D Conversion IndustryPack. User s Manual

12-Bit Successive-Approximation Integrated Circuit ADC ADADC80

V ON = 0.93V V OFF = 0.91V V ON = 2.79V V OFF = 2.73V V ON = 4.21V V OFF = 3.76V V ON = 3.32V V OFF = 2.80V. 45.3k 6.04k 1.62k. 3.09k. 7.68k 1.

Applications & Tools. Sample Blocks for STEP 7 and WinCC flexible - Supplements. WinCC flexible. Application description September 2010

JTY2 PULSE DURATION RECEIVER BEFORE USE... COMPONENT IDENTIFICATION

BPSK_DEMOD. Binary-PSK Demodulator Rev Key Design Features. Block Diagram. Applications. General Description. Generic Parameters

ULTRA-LOW POWER OSCILLATOR 1-26MHz

MFD900. The most industrial ultrasonic test system for flaw detection and thickness measurements

APPLICATION NOTES. This complete setup is available from BIOPAC as Programmable Stimulation System for E-Prime - STMEPM

SIPROTEC. Multi-Functional Generator Protection Relay 7UM61. Preface. Contents. Introduction 1. Functions 2. Mounting and Commissioning 3

GE Fanuc IC695ALG312. Rx3i PacSystem

Rapid Design of FIR Filters in the SDR- 500 Software Defined Radio Evaluation System using the ASN Filter Designer

Agilent ParBERT Measurement Software. Fast Eye Mask Measurement User Guide

VERCISE DIRECTIONAL SYSTEMS* VERCISE NEURAL NAVIGATOR 2.1 PROGRAMMING TUTORIAL

TIP500. Optically Isolated 16 Channel 12 Bit ADC. Version 1.1. User Manual. Issue January 2010

BCD Adder. Lecture 21 1

ADP1043A Evaluation Software Reference Guide EVAL-ADP1043A-GUI-RG

PACSystems* RX3i. Isolated RTD Input Module, 8 Channels, IC695ALG508-CA. Module Features. GFK-2501C November 2012

Model 310H Fast 800V Pulse Generator

Transcription:

Acquisition of transformer tap positions via SIP5-APN-038, Edition 2 www.siemens.com/protection

SIPROTEC 5 Application Note Acquisition of transformer tap positions via SIP5-APN-038, Edition 1 Content 1 Acquisition of transformer tap positions via 3 1.1 Introduction 3 1.2 Configuration of the tap changer 3 1.3 Configuration of the analog input module 4 1.3.1 Hardware configuration 4 1.3.2 Configuration of the analog measurement transducer (MT) 5 1.4 Transformation of the output signal of the measurement transducer into a tap position 6 1.4.1 Principle 6 1.4.2 Handling limit and invalid values 6 1.5 Summary 8 SIP5-APN-038 2 Edition 2

1 Acquisition of transformer tap positions via an analog measurement transformer 1.1 Introduction Usually binary signals such as BCD codes are used to indicate the position of a tap changer. However, an analog DC current can also represent this information. Thanks to SIPROTEC 5 devices from versions 7 onwards, recording the tap changer s position no longer requires any external devices. This is made possible through an analog transducer input, for example the plug-in module ANAI and the expansion module IO 212. With this technology, analog DC currents can be connected directly to the SIPROTEC 5 device. Each tap changer necessitates a separate channel. This application note assumes a DC input current range from 4 ma to 20 ma and a tap position range from 1 to 30 (i.e. 30 tap positions). Settings can be adapted so they correspond with other input currents and tap positions. The application is divided into 3 parts: 1. Configuration of the tap changer function in DIGSI5 2. Configuration of the analog input module 3. Transformation of the transducer s output value transducer (measurement value) into tap position information. 1.2 Configuration of the tap changer The tap changer function can basically be used in two different ways: 1. As a function group tap changer, to acquire the position of the primary tap changer to use this information, for example, for the transformer diff protection or to control the primary tap changer via remote access or CFC. Access the DIGSI5 library and the switching devices folder. This is found below the respective SIPROTEC 5 device folder. After opening the folder, drag and drop the function group (FG) symbol tap changer into the device configuration on the left side. 2. As a part of a voltage control function In this case, the function tap changer is already part of one of the voltage control function groups which can be found in the folder Automatic voltage control. The function group can be added to the device configuration with the drag and drop function. (see fig.1) The possible tap position range must be set in the information routing matrix under the tab properties, which is found in the inspector window on the bottom. Therefore, the signal position of the tap changer must be selected, which can be found in the FG tap changer in the FB (function block) tap changer (see fig. 2). The number of positions must now be entered, as well as an offset value (unless the position range begins with 1.. The smallest and biggest positions are automatically calculated and displayed. The tap coding type setting is irrelevant. Edition 2 3 SIP5-APN-038

Fig.1: Creating a tap changer function Fig.2: Setting the number of tap position and resulting minimum and maximum tap position 1.3 Configuration of the analog input module 1.3.1 Hardware configuration Either the ANAI plug in module or the expansion module IO 212 can be used to acquire the analog DC input signals. Each primary tap changer necessitates one analog input channel. The ANAI has 4 programmable current input channels; the IO 212 has 8 fast analog input channels. These can measure either DC currents or DC voltages. Since the acquisition of tap changer positions is a relatively slow procedure, the ANAI s 200mscycle time generally suffices. The DIGSI5 will automatically add an analog units FG to the configuration after you add the HW in the Hardware and protocols editor. The respective settings can then be found in the project tree under settings and the FG analog units. SIP5-APN-038 4 Edition 2

1.3.2 Configuration of the analog measurement transducer (MT) The MTs of the ANAI-CA-4EL have a signal range from -24mA to 24mA. They are programmable from -20mA to +20mA.A range from e.g. 2mA to 20mA is possible as well. For our use, the Range active box must be checked in order to get 4 more parameters for the scaling of the current-measurement characteristic (see fig.3). Generally lower limit and upper limit correspond with the minimum and maximum input current, (so 4 ma and 20 ma in this example. Lower limit - Sensor and Upper limit - Sensor are the measurement values which the device creates when the input current is at its lower or upper limit (linear characteristic). In our application, measurement value units have no significance and are therefore set to p.u. (per unit).this could be replaced by any other unit. The measurement value resolution is determined by the setting resolution. The measurement resolution is internally converted to an integer value. Thus, a value of 0,1 or smaller is fine. Ideally, the lowest and highest tap position values are set as lower limit sensor and upper limit sensor. By doing this an additional scaling in the CFC can be avoided, for example on account of a division component (DIV_R). This would cost excess function points. In our example we set a value of +1 for the Lower limit Sensor and +30 for the Upper limit Sensor. A DC current of 4 ma then produces a MV value of +1 (p.u.) and a current of 20 ma a MV produces a value of +30 (p.u.). In fig. 2, the information routing displays these two measurements in one channel. TD direct MV is the direct measurement value representing the input current (4 ma to 20 ma). TD scale MV is the output value, ranging from 1 p.u. to 30 p.u. in our example. Using a CFC, MV values will be transformed into transformer tap positions in the subsequent step. Fig.3: Configuration of input currents and measurement value range. Fig.4: Signals of one measurement transducer (MT) channel. Edition 2 5 SIP5-APN-038

1.4 Transformation of the output signal of the measurement transducer into a tap position A new CFC plan can be created by double clicking on add new chart in the project tree. Since the input signal of the CFC chart is a measurement value that changes spontaneously, the task level measurement is selected. It is possible to select all other CFC task levels as well. Fig.4: Selection of the CFC task level and creation of a new CFC chart. 1.4.1 Principle The CFC chart contains the following basic component and signals: Fig.5: Principle of transformation A detailed description of the various CFC components addressed in the following section can be found in the DIGSI 5 help, which is also available as an online PDF on our protection homepage (www.siemens.com/siprotec). BUILD_BSC (1) is a component available from DIGSI V7 onwards and transforms an integer value at its input (POS) into a tap position. This position can then be assigned to the respective tap changer. To do so, the position signal (BSC) of the tap changer must be dragged from the signal catalog to the exit of BUILD_BSC (1). Since many CFC components have a built in signal conversion feature, it is seldom necessary to convert the signal type. In our case the BUILD_BSC component transforms real values or measurement values into integer values for input For this reason we can connect the scaled MV directly to the input of the BUILD_BSC. 1.4.2 Handling limit and invalid values If the input currents are slightly outside of the defined band, the BUILD_BSC (1) in fig. 5 component might output an invalid position instead of the corresponding lower or upper end tap position. As a consequence of the undefined current, the scaled value might fall out of the valid position range. This causes the output of SIP5-APN-038 6 Edition 2

the invalid position. If it cannot be guaranteed that the input signal always lies within the preset range, the CFC plan must be extended. The invalid states are dealt with through two comparisons: LE_R (1) and GE_R (2), and the MUX_R (8) as follows (see fig.6). If the analog input value (TD direct MV) falls within the valid band, both outputs OUT of LE_R (3) and GE_R (4) are logically zero. As a consequence, the output OUT of the NOR (3) and the input of IN2 of BOOL_INT (7) are both logically 1.). Therefore, the output OUT of BOOL_INT (7) has the integer value 2. The scaled MV at IN2 is routed to its output OUT by MUX_R (8). If the analog input value (TD direct MV) is outside its valid band (4mA-20mA) then either IN1 or IN3 of the BOOL_INT (7) logically becomes 1. As a consequence, the inputs IN1 or IN3 of MUX_R (8) are routed to the output OUT. If the value of IN1is set to the real value corresponding to the smallest tap position (1.0) and the value of IN3 is set to the real value corresponding to the highest tap position (30.0), then these values are routed to the output of MUX_R. (8) With this, the end positions are stabilized (see green marking). If the input current is clearly wrong, i.e. significantly outside of the allowed band, the tap position can systematically be set to an invalid value. The input current is verified using 2 stabilized components LIML_R (4) and LIMU_R (5). These components define the maximum tolerable deviation. If the current is below the limit value of LIML_R (4) or above the limit value of LIMU_R (5), the respective output EXC of LIML_R (4) or LIMU_R (5) is 1 and therefore also the output Y of the OR gate (6) and the input IN4 of BOOL_INT (7). In mode 2 of BOOL_INT (7), the integer value of the highest input number, which is logically 1, is put on the output. This means that IN 4 is prioritized over all other inputs. If this is logically 1, then the real value of IN4 of MUX_R (8) is routed to its output. With a well defined value outside the tap position range (e.g. -64), the tap position at the output of BUILD_BSC becomes invalid. The LIML_R and LIMU_R elements are used instead of LE_R and GE_R, since these components provide a hysteresis setting, which prevents their output from jittering if the input current is just below or above the threshold. This would mean that the output jitters invalidly between one of the relative end positions. If a binary signal that indicates an invalid position is required, the output Y on the OR gates could be used, for instance. Edition 2 7 SIP5-APN-038

Fig.6: CFC logic for the transformation including the handling of invalid input signals. 1.5 Summary Thanks to a relatively small CFC logic and an available SIPROTEC 5 device, the tap changer s position can be communicated in the form of an analog input signal without any additional external device. There is no longer a need for an extra device that translates the tap position into a bit pattern. The SIPROTEC 5 analog input transducers are programmable, so that any range between -20mA and 20mA can be used not just the example demonstrated in this manual. With help of the IO 212, even DC voltages can be recognized as tap positions. If you alter the module settings, the MV can be adapted to the tap changer positions. This does not require any scaling in the CFC, and extra function points for a multiplier or divider element in the CFC can be avoided. This application saves costs for external devices, as well as additional wiring and testing. Modular system design in hardware, software, and communication Functional integration of various applications, such as protection, control, and fault recorder SIP5-APN-038 8 Edition 2

Published by and copyright 2016: Siemens AG Energy Management Division Humboldtstr. 59 90459 Nuremberg, Germany www.siemens.com/siprotec For more information, please contact your Siemens Partner or our Customer Support Center. Phone: +49 180 524 70 00 Fax: +49 180 524 24 71 (Charges depending on the provider) Email: support.energy@siemens.com Application Note: SIP5-APN-038, Edition 2 Printed on elementary chlorine-free bleached paper. All rights reserved. Trademarks mentioned in this document are the property of Siemens AG, its affiliates, or their respective owners. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract. For all products using security features of OpenSSL the following shall apply: This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit (www.openssl.org). This product includes cryptographic software written by Eric Young (eay@cryptsoft.com).