PI144H - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

Similar documents
PI734F - Winding 28. Technical Data Sheet APPROVED DOCUMENT

PI734E - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734C - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734B - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734F - Winding 07. Technical Data Sheet APPROVED DOCUMENT

PM734D - Winding 312. Technical Data Sheet APPROVED DOCUMENT. Generator Solutions AS

PM734F - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734C - Technical Data Sheet

PI734A - Technical Data Sheet

WDG 12 - Technical Data Sheet

WDG 71 - Technical Data Sheet

WDG 12 - Technical Data Sheet

WDG 07 - Technical Data Sheet

WDG 13 - Technical Data Sheet

WDG 61 - Technical Data Sheet

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet

WDG 51 - Technical Data Sheet

WDG 83 - Technical Data Sheet

PM734B - Technical Data Sheet. Generator Solutions AS

AS440 AUTOMATIC VOLTAGE REGULATOR (AVR)

S4L1D-G41 Wdg Technical Data Sheet

S4L1S-D4 Wdg.17 - Technical Data Sheet

Rotek AS440 compatible VOLTAGE REGULATOR (AVR)

S0L1-J1 - Technical Data Sheet

SPECIFICATION, CONTROLS AND ACCESSORIES

SPECIFICATION, CONTROLS AND ACCESSORIES

PARTNER ALTERNATORS LSA 40-4 Pole

SPECIFICATION, CONTROLS AND ACCESSORIES

440 (12) 416 (12) 416 (12) 440 (12)

Low Voltage alternators - 4 pole LSA 47.2

LSA Pole. R 726 Mains paralleling

Low Voltage alternators - 4 pole LSA 46.2

PARTNER ALTERNATORS LSA Pole

LSA R & LSA H 49.1 Low Voltage Alternators - 4 pole

TAL 049 Low Voltage Alternator - 4 pole

HCM634G - Technical Data Sheet

TAL 047 Low Voltage Alternator - 4 pole

Time constants ( s ) Resistance. Other data - Class H /6600 V kva. Efficiencies ( % )(3 phase - Classe H V kva)

TAL 044 Low Voltage Alternator - 4 pole

AGN 124 AVR Power Supplies

Spec Information. Reactances Per Unit Ohms

Packaged Generators: New Kato Engineering Packaged Generator Line: Over 75 Years of Experience: Conformity: Service: Quality Standards:

Spec Information. Reactances Per Unit Ohms

GENERATOR DATA JANUARY 30, 2015

ALTERNATOR TECHNICAL DESCRIPTION 1. LSA 53.2 XL13 / 4p. Chargé d'affaire : Karthikeyan GN 1 Moteurs Leroy-Somer +33 (0) xx

McPherson Voltage Regulators 4501 NW 27 Ave Miami FL

Using the VR448 in place of the Marathon DVR 2000

R180. AVRs. Installation and maintenance

GX 340 SERIES (AUTOMATIC VOLTAGE REGULATOR)

AGN 124 AVR Power Supplies

R448 & R448 V50 A.V.R. Installation and maintenance R 448 ST5 ST3 ST10. Armature + 6- Field X2 Z1 X1 Z2 E+ E- 0V Slow fuse 250V 10 A

R1 Q2 Q1 F2 F1 N A1 A2 FUSE V AC S UF OE SL UF OE R150 R150. AVRs. Installation and maintenance

Generator Advanced Concepts

VOLTAGE REGULATOR R 449. Installation and maintenance. This manual must be sent to the end user R 449 X2 Z1 X1 Z2 E+ E- (12V - 10A)

AGN 034 Alternator Reactance

Instructions AVC125-10: Voltage Regulator. Voltage Range. Maximum Continuous Burden. Voltage Range. Nominal Frequency

R438 A.V.R. Installation and maintenance. This manual is to be given to. the end user CALL US TODAY POWER-58. SHOP ONLINE

R448 & R448 V50 A.V.R.

M40FA640A/A - Mark I. User Manual SIN.NT Automatic Voltage Regulator for Three-phase Synchronous Generators. (Issued: 04.

R1 Q2 Q1 F2 F1 N A1 A2 FUSE V AC S UF OE SL UF OE R150 A.V.R. R150. Installation and maintenance

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

ADVR-053. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

V S UF OPEN IN 60Hz OE UF SL R120 V N1 U N F1 F2 A.V.R. R120. Installation and maintenance

r 450 Installation and maintenance This manual is to be given to the end user R 450 VOLT. STAB. I EXC STAT. AREP PMG FUSIBLES / FUSES

Orbital GFI Inverter Series

AGN 005 Fault Currents and Short Circuit Decrement Curves

Class 300 Equipment CBS 305, 320 Current Boost Systems FEATURES. DESCRIPTION Page 2. SPECIFICATIONS Pages 2 through 4.

R 450. AVRs. Installation and maintenance. This manual is to be given to. the end user R 450 VOLT. STAB. I EXC STAT. LEDS PMG

Power Processor - Series 700F 10KVA to 150KVA

DLVP A OPERATOR S MANUAL

GX 600 SERIES (AUTOMATIC VOLTAGE REGULATOR)

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

TOSHIBA International Corp

Phoenix DX Clean Power (18 Pulse) AC Drive

Variable Transformers Product Design & Engineering Data

APPENDIX 1 to LGIP INTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY

R438 A.V.R. R438. Installation and maintenance X2 Z1 X1 Z2 E+ E- 0V REQUEST A QUOTE

The new Yaskawa Varispeed G7 Inverter

Ametek, Inc. Rotron Technical Products Division. 100 East Erie St., Suite 200 Kent, Ohio User's Guide. Number Revision F

TDA Power Factor Controller. IC for High Power Factor and Active Harmonic Filtering

INTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY

1525-BRS INFORMATION MANUAL SERV O D YN A M ICS. D y n ad r iv e Ave Crocker Suite 10 Valencia, CA

Type KLF Generator Field Protection-Loss of Field Relay

CAT BOARD A CONTROL AND TRIGGER BOARD FOR 3-PHASE POWER SUPPLIES

DynaDrive INFORMATION MANUAL SDFP(S)

D I G I T A L V O L T A G E R E G U L A T O R

PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY

AGN 022 Conditions for Parallel Operation

Application Guidance Notes: Technical Information from Cummins Generator Technologies

Sizing Generators for Leading Power Factor

R / 8000 RAPIDE FAST RAPIDE 3 PAHASES SENSING SHUNT / AREP SERIES PMG NORMAL NORMAL NORMAL NORMAL 5000 / 6000 LSA 46 / 47

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

A cost effective, compact and reliable PWM drive for 1/4 through 1 HP DC applications

M16FA655A - Mark V. User Manual SIN.NT Automatic Voltage Regulator for Three-phase Synchronous Generators

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

1. SUMMARY 2. SPECIFICATION 3. WIRING. 3.3 Power Input Voltage Selection. 3.1 A to C: Sensing Input. 3.2 B to C: Power Input

A Subsidiary of Regal-Beloit Corporation. AC Inverter Terminology

ELECTRONIC CONTROL OF A.C. MOTORS

Transcription:

PI144H - Winding 311 Technical Data Sheet

PI144H SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA C22.2-100, AS1359. Other standards and certifications can be considered on request. VOLTAGE REGULATOR AS480 AVR fitted as STANDARD TERMINALS & TERMINAL BOX Standard generators are 3-phase reconnectable with 12 ends brought out to the terminals, which are mounted at the non-drive end of the generator. Dedicated single phase generators are also available. A sheet steel terminal box contains provides ample space for the customers' wiring and gland arrangements. Alternative terminal boxes are available for customers who want to fit additional components in the terminal box. SHAFT & KEYS With this self-excited system the main stator provides power via the AVR to the exciter stator. The high efficiency semi-conductors of the AVR ensure positive build-up from initial low levels of residual voltage. The exciter rotor output is fed to the main rotor through a three-phase full-wave bridge rectifier. The rectifier is protected by a surge suppressor against surges caused, for example, by short circuit or out-of-phase paralleling. The AS480 will support limited accessories, RFI suppession remote voltage trimmer and for the P1 range only a 'droop' Current Transformer (CT) to permit parallel operation with other ac generators. The AVR is can be fitted to either side of the generator in its own housing in the non-drive end bracket. Excitation Boost System (EBS) (OPTIONAL) The EBS is a single, self-contained unit, attached to the non-drive end of the generator. The EBS unit consists of the Excitation Boost Controller (EBC) and an Excitation Boost Generator (EBG). Under fault conditions, or when the generator is subjected to a large impact load such as a motor starting, the generator voltage will drop. The EBC senses the drop in voltage and engages the output power of the EBG. This additional power feeds the generator s excitation system, supporting the load until breaker discrimination can remove the fault or enable the generator to pick up a motor and drive the voltage recovery. WINDINGS & ELECTRICAL PERFORMANCE All generator stators are wound to 2/3 pitch. This eliminates triplen (3rd, 9th, 15th ) harmonics on the voltage waveform and is found to be the optimum design for trouble-free supply of non-linear loads. The 2/3 pitch design avoids excessive neutral currents sometimes seen with higher winding pitches, when in parallel with the mains. A fully connected damper winding reduces oscillations during paralleling. This winding, with the 2/3 pitch and carefully selected pole and tooth designs, ensures very low waveform distortion. All generator rotors are dynamically balanced to better than BS6861:Part 1 Grade 2.5 for minimum vibration in operation. Two bearing generators are balanced with a half key. INSULATION / IMPREGNATION The insulation system is class 'H'. All wound components are impregnated with materials and processes designed specifically to provide the high build required for static windings and the high mechanical strength required for rotating components. QUALITY ASSURANCE Generators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001. The stated voltage regulation may not be maintained in the presence of certain radio transmitted signals. Any change in performance will fall within the limits of Criteria 'B' of EN 61000-6-2:2001. At no time will the steady-state voltage regulation exceed 2%. DE RATES All values tabulated on page 9 are subject to the following reductions 5% when air inlet filters are fitted. 3% for every 500 metres by which the operating altitude exceeds 1000 metres above mean sea level. 3% for every 5 C by which the operational ambient temperature exceeds 40 C. Note: Requirement for operating in an ambient exceeding 60 C must be referred to the factory. 5% For reverse rotation (Standard rotation CW when viewed from DE) NB Continuous development of our products entitles us to change specification details without notice, therefore they must not be regarded as binding. Front cover drawing typical of product range. 2

PI144H WINDING 311 CONTROL SYSTEM VOLTAGE REGULATION SUSTAINED SHORT CIRCUIT CONTROL SYSTEM SUSTAINED SHORT CIRCUIT STATOR WINDING WINDING PITCH WINDING LEADS STATOR WDG. RESISTANCE ROTOR WDG. RESISTANCE EXCITER STATOR RESISTANCE EXCITER ROTOR RESISTANCE STANDARD AS480 AVR (SELF EXCITED) ± 1.0 % SELF EXCITED MACHINES DO NOT SUSTAIN A SHORT CIRCUIT CURRENT AS480 AVR WITH OPTIONAL EXCITATION BOOST SYSTEM (EBS) REFER TO SHORT CIRCUIT DECREMENT CURVE (page 8) DOUBLE LAYER CONCENTRIC TWO THIRDS 12 0.179 Ohms PER PHASE AT 22 C SERIES STAR CONNECTED 0.89 Ohms at 22 C 22.9 Ohms at 22 C 0.21 Ohms PER PHASE AT 22 C EBS STATOR RESISTANCE R.F.I. SUPPRESSION WAVEFORM DISTORTION MAXIMUM OVERSPEED BEARING DRIVE END BEARING NON-DRIVE END 12.9 Ohms at 22 C BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0% 1 BEARING WEIGHT COMP. GENERATOR 172.5 kg 170.8 kg 175.5 kg 173.8 kg WEIGHT WOUND STATOR 75 kg 75 kg 75 kg 75 kg WEIGHT WOUND ROTOR 65.63 kg 63.93 kg 67.34 kg 65.64 kg WR² INERTIA 0.2541 kgm 2 0.2524 kgm 2 0.2545 kgm 2 0.2528 kgm 2 SHIPPING WEIGHTS in a crate 191 kg 189.3 kg 200 kg 198.3 kg PACKING CRATE SIZE 85 x 51 x 67 (cm) 85 x 51 x 67 (cm) 50 2250 Rev/Min BALL. 6310-2RS. (ISO) BALL. 6306-2RS. (ISO) 2 BEARING WITH EBS WITHOUT EBS WITH EBS WITHOUT EBS TELEPHONE INTERFERENCE COOLING AIR THF<2% 0.135 m³/sec 286cfm TIF<50 0.165 m³/sec 340 cfm VOLTAGE SERIES STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277 VOLTAGE PARALLEL STAR 190/110 200/115 208/120 220/127 208/120 220/127 230/133 240/138 VOLTAGE SERIES DELTA 220/110 230/115 240/120 254/127 240/120 254/127 266/133 277/138 kva BASE RATING FOR REACTANCE VALUES 35 35 35 33.3 38.5 41.1 42.4 43.8 Xd DIR. AXIS SYNCHRONOUS 1.85 1.67 1.55 1.31 2.20 2.10 1.98 1.88 X'd DIR. AXIS TRANSIENT 0.17 0.15 0.14 0.12 0.20 0.19 0.18 0.17 X''d DIR. AXIS SUBTRANSIENT 0.12 0.11 0.10 0.09 0.15 0.14 0.14 0.13 Xq QUAD. AXIS REACTANCE 0.89 0.80 0.74 0.63 1.05 1.00 0.95 0.90 X''q QUAD. AXIS SUBTRANSIENT 0.19 0.17 0.16 0.13 0.23 0.22 0.21 0.20 XL LEAKAGE REACTANCE 0.07 0.06 0.06 0.05 0.08 0.08 0.07 0.07 X2 NEGATIVE SEQUENCE 0.16 0.14 0.13 0.11 0.19 0.18 0.17 0.16 X0 ZERO SEQUENCE 0.08 0.07 0.07 0.06 0.09 0.09 0.08 0.08 REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED T'd TRANSIENT TIME CONST. T''d SUB-TRANSTIME CONST. T'do O.C. FIELD TIME CONST. Ta ARMATURE TIME CONST. SHORT CIRCUIT RATIO 0.026 s 0.007 s 0.6 s 0.007 s 1/Xd 60 3

50 PI144H Winding 311 THREE PHASE EFFICIENCY CURVES 4

60 PI144H Winding 311 THREE PHASE EFFICIENCY CURVES 5

30 50 PI144H Winding 311 AS480 AVR Without EBS Locked Rotor Motor Starting Curves 346V 380V 400V 415V 440V 25 PER CENT TRANSIENT VOLTAGE DIP. 20 15 10 5 0 30 25 0 10 20 30 40 50 60 70 80 LOCKED ROTOR kva 60 380V 416V 440V 460V 480V PER CENT TRANSIENT VOLTAGE DIP. 20 15 10 5 0 0 10 20 30 40 50 60 70 80 90 LOCKED ROTOR kva 6

30 50 PI144H Winding 311 AS480 AVR With EBS fitted Locked Rotor Motor Starting Curves 346V 380V 400V 415V 440V 25 PER CENT TRANSIENT VOLTAGE DIP. 20 15 10 5 0 30 25 0 10 20 30 40 50 60 70 80 LOCKED ROTOR kva 60 380V 416V 440V 460V 480V PER CENT TRANSIENT VOLTAGE DIP. 20 15 10 5 0 0 10 20 30 40 50 60 70 80 90 100 LOCKED ROTOR kva 7

PI144H WITH EBS FITTED Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed Based on star (wye) connection. 50 1000 SYMMETRICAL CURRENT (Amps) 100 ASYMMETRICAL 60 Sustained Short Circuit = 153 Amps 10 0.001 0.01 TIME (secs) 0.1 1 10 1000 CURRENT (Amps) 100 SYMMETRICAL ASYMMETRICAL 10 0.001 0.01 TIME (secs) 0.1 1 10 Sustained Short Circuit = 191 Amps Note 1 The following multiplication factors should be used to adjust the values from curve between time 0.001 seconds and the minimum current point in respect of nominal operating voltage : Note 2 The following multiplication factor should be used to convert the values calculated in accordance with NOTE 1 to those applicable to the various types of short circuit : 50 60 3-phase 2-phase L-L 1-phase L-N Voltage Factor Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30 380v X 1.00 416v X 1.00 Minimum x 1.00 x 1.80 x 3.20 400v X 1.05 440v X 1.06 Sustained x 1.00 x 1.50 x 2.50 415v X 1.09 460v X 1.10 Max. sustained duration 10 sec. 5 sec. 2 sec. 440v X 1.16 480v X 1.15 All other times are unchanged The sustained current value is constant irrespective Note 3 of voltage level Curves are drawn for Star (Wye) connected machines. For other connection the following multipliers should be applied to current values as shown : Parallel Star = Curve current value X 2 Series Delta = Curve current value X 1.732 8

PI144H Winding 311 / 0.8 Power Factor RATINGS Class - Temp Rise Cont. F - 105/40 C Cont. H - 125/40 C Standby - 150/40 C Standby - 163/27 C 50 Series Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440 Parallel Star (V) 190 200 208 220 190 200 208 220 190 200 208 220 190 200 208 220 Series Delta (V) 220 230 240 254 220 230 240 254 220 230 240 254 220 230 240 254 kva 32.0 32.0 32.0 30.4 35.0 35.0 35.0 33.3 37.5 37.5 37.5 35.6 38.5 38.5 38.5 36.6 kw 25.6 25.6 25.6 24.3 28.0 28.0 28.0 26.6 30.0 30.0 30.0 28.5 30.8 30.8 30.8 29.3 Efficiency (%) 87.7 87.9 88.0 88.2 87.1 87.4 87.6 87.9 86.6 87.0 87.2 87.7 86.4 86.8 87.0 87.5 kw Input 29.2 29.1 29.1 27.6 32.1 32.0 32.0 30.3 34.6 34.5 34.4 32.5 35.6 35.5 35.4 33.5 60 Series Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480 Parallel Star (V) 208 220 230 240 208 220 230 240 208 220 230 240 208 220 230 240 Delta (V) 240 254 266 277 240 254 266 277 240 254 266 277 240 254 266 277 kva 35.2 37.6 38.8 40.0 38.5 41.1 42.4 43.8 41.3 44.1 45.5 46.9 42.4 45.2 46.7 48.1 kw 28.2 30.1 31.0 32.0 30.8 32.9 33.9 35.0 33.0 35.3 36.4 37.5 33.9 36.2 37.4 38.5 Efficiency (%) 88.0 88.0 88.1 88.1 87.5 87.5 87.6 87.7 87.1 87.1 87.2 87.3 86.9 86.9 87.0 87.1 kw Input 32.0 34.2 35.2 36.3 35.2 37.6 38.7 39.9 37.9 40.5 41.7 43.0 39.0 41.7 43.0 44.2 DIMENSIONS 9

Head Office Address: Barnack Road, Stamford Lincolnshire, PE9 2NB United Kingdom Tel: +44 (0) 1780 484000 Fax: +44 (0) 1780 484100 www.cumminsgeneratortechnologies.com Copyright 2010, Cummins Generator Technologies Ltd, All Rights Reserved Stamford and AvK are registered trade marks of Cummins Generator Technologies Ltd Cummins and the Cummins logo are registered trade marks of Cummins Inc. PI144H-311-TD-EN-SG-A

AS480 AUTOMATIC VOLTAGE REGULATOR (AVR) SPECIFICATION INSTALLATION AND ADJUSTMENTS General description Technical specification The AS480 is a half wave phase controlled AVR which forms part of the excitation system of the brushless generator. The design employs Surface Mount Technology (SMT), custom mouldings and heatsinks to produce a compact AVR assembly. The AVR also incorporates an interface to the optional Excitation Boost System (EBS) for use where short-circuit current maintenance is required. The AVR is linked with the main stator windings and the exciter field windings to provide closed loop control of the output voltage with load regulation of +/- 1.0%. The AVR voltage sensing terminals continuously sample the output windings for voltage control purposes. In response to this sample voltage, the AVR controls the power fed to the exciter field, and hence the main field, to maintain the machine output voltage within the specified limits, compensating for load, speed, temperature and power factor of the generator. Positive voltage build up from residual levels is ensured by the use of efficient semiconductors in the power circuitry of the AVR. A frequency measuring circuit continually monitors the generator output frequency and provides under-speed protection of the excitation system. This is done by reducing the output voltage proportionally with speed below a pre-settable threshold. A manual adjustment is provided for factory setting of the under frequency roll off point, (UFRO). This can be changed to 60 (or 50) in the field by push-on link selection. SENSING and POWER INPUT Voltage 100-264 V ac 1 phase Frequency 50-60 nominal OUTPUT Voltage 82 V d.c. @ 200 Va.c power input. Voltage 45 V d.c. @ 110 Va.c power input. Current continuous 5A (see note 1). transient 7.5A for 10 secs. Resistance 15 ohms min REGULATION +/- 1.0% (see note 2) THERMAL DRIFT 0.03% per deg. C change in AVR ambient (see note 3) TYPICAL SYSTEM RESPONSE AVR response Field current to 90% Machine Volts to 97% 20ms 80 ms 300ms EXTERNAL VOLTAGE ADJUSTMENT +/-10% with 1 k ohm 1 watt trimmer (see note 4) Increasing resistance lowers voltage. Fixed 15kOhm resistor enables 110V sensing UNDER FREQUENCY PROTECTION Set point 94-98% (see note 5) UNIT POWER DISSIPATION 12 watts maximum A wide range of stability settings are available to compensate for machine sizes and applications. A slow setting is available for applications involving single/twin cylinder engines and where lamp-flicker could be a problem. Provision is made for the connection of a remote voltage trimmer, allowing the user fine control of the generator s output voltage. Operation with 110Vac sensing is possible, replace the hand trimmer link with fixed resistor. The hand trimmer option cannot be used in this configuration. The generator overload capability is reduced in 110V operation. The AVR has the facility for droop CT connection, to allow parallel running with other similarly equipped generators. Over excitation conditions are limited to a safe period by a protection circuit within the AVR. Once activated by a sustained over-excitation condition, the generator voltage is reduced to a low level until reset. Stopping the generator or removing power from the AVR will perform the necessary reset. Connections are provided to interface to the optional Excitation Boost System. This incorporates a small externally mounted rotary power supply which provides excitation power in the event of heavy overloads or short circuits. The EBS is short term rated and responds to signals from the AVR to deliver excitation power when required. A separate overload protection system within the EBS electronic module protects the generator against sustained overloads. BUILD UP VOLTAGE 4 Volts @ AVR terminals QUADRATURE DROOP INPUT 10 ohms burden Max. sensitivity: 0.07 A for 5% droop 0PF Max. input: 0.33 A OVER EXCITATION PROTECTION Set point 67 Vdc +/-3% (fixed) Time delay 10-15 seconds (fixed) ENVIRONMENTAL Vibration 20-100 50mm/sec 100 2k 3.3g Operating temperature -40 to +70C (note 6) Relative Humidity 0-70C 95% (note 7) Storage temperature -55 to +80C NOTES 1. De-rate by 20% if mounted external to generator. 2. Inclusive of 4% engine governing. 3. After 2 minutes warm-up. 4. Generator de-rate may apply. Check with factory. 5. Factory set, semi-sealed, jumper selectable. 6. De-rate output current by 5% per deg. C above 60C. 7. Non condensing. Cummins 2008 TD_AS480 AVR_04.08_02_GB A043Y698 (Issue 1)

AS480 AVR Block Diagram Generator Output Winding Voltage Sensing Sensing Voltage Divider / Adjust Droop C.T. Input Droop Adjust + + + Hand Trimmer Hand Trimmer Connection Precision Rectifier + - - Low Detect Reference Voltage Amplifier Stability Circuit Synchronising Circuit Ramp Generator Over Excitation Detector Low-Pass Filter Level Detector Voltage Divider Power Supply EBS Interface Level Shifter Input Power Suppression AVR Output Power Control + Exciter Field Windings - Excitation Boost Controller Connections EB DR F1 F2 The AVR Circuit Description The main functions of the AVR are: Sensing Voltage Divider / Adjust takes a proportion of the generator output voltage and attenuates it. The potential divider is adjustable by the AVR Volts potentiometer and external hand trimmer (when fitted). The output from the droop CT is also added to this signal. A Precision Rectifier converts the a.c. input signal into d.c. for further processing. The Amplifier compares the sensed voltage to the Reference Voltage and amplifies the difference (error) to provide a controlling signal for the power devices. The Ramp Generator and Level Detector and Level Shifter infinitely control the conduction period of the AVR Output Power Control devices. This provides the exciter field windings with the variable power necessary to maintain the generator voltage within specified limits. The Stability Circuit provides adjustable feedback to ensure good steady state and transient performance of the control system. The Low Detector measures the period of each electrical cycle and causes the reference voltage to be reduced approximately linearly with speed below a presettable threshold. A Light Emitting Diode gives indication that the circuit is activated by the low-speed running condition. The Synchronising circuit is used to keep the Ramp Generator and Low Detector locked to the generator waveform period. The Low Pass Filter prevents distorted waveforms affecting the operation of the AVR control circuit. AVR Output Power Control devices vary the amount of exciter field current in response to the error signal produced by the Amplifier. Input Power Suppression components are included to prevent load generated voltage transients from damaging the AVR components and also to reduce the amount of conducted radio-frequency noise on the generator terminals. The Over Excitation Detector continuously monitors the exciter field voltage and provides the signal required to collapse the output voltage. This protection circuit triggers only if an over excitation condition persists for a specific amount of time. The Power Supply provides the required voltages for the AVR circuitry. The EBS Interface provides the signals necessary to control the excitation boost generator (EBG). The EBG responds to the level of excitation provided by the AVR and supplies additional power as it is needed to support the overload. Cummins 2008 TD_AS480 AVR_04.08_02_GB A043Y698 (Issue 1)

AS480 AVR Links and Adjustments refer to the generator wiring diagram for all connection details Operation at 110Vac (optional) - remove link(*) before fitting - connect the 15k/1W sensing link - the hand trimmer cannot be used in this mode - Overload performance is limited in this mode. Link BC Stability Linking > 100kW < 100kW Slow connections for excitation boost unit Link BD < 100kW Fast No Link VOLTS DROOP DR EB F2 F1 2 1 S2 S1 F2 * F1 7 8 Hand Trimmer (optional) 1k / 1W Raise 50 60 UFRO Linking D C B 50 HZ 60 LED STABILITY UFRO Droop C/T (optional) * Remove link before fitting Control Function Direction VOLTS Generator output voltage setting Clockwise raises voltage STABILITY Output voltage stability Clockwise increases stabilisation effect DROOP Voltage droop for paralleling Clockwise increases drooping effect UFRO Under-frequency 'Knee' point Clockwise decreases 'Knee' point Refer to the Generator Wiring Diagrams for all Connection detail Cummins 2008 TD_AS480 AVR_04.08_02_GB A043Y698 (Issue 1)

ADJUSTMENT OF AVR CONTROLS VOLTAGE ADJUSTMENT The generator output voltage is set at the factory but can be altered by adjustment of the VOLTS control on the AVR board or by the external hand trimmer if fitted. Before adjusting the generator output voltage, note the following warnings. WARNING! Do not increase the voltage above the rated generator voltage shown on the rating plate mounted on the generator case. WARNING! Do not ground any of the external hand trimmer terminals. Failure to observe this could cause equipment damage. To adjust the generator output voltage, proceed as follows: 1. Before running the generator set, turn the [VOLTS] control fully anti-clockwise. Turn the [STABILITY] control to its midway position and the external hand trimmer (if fitted) to its midway position. 2. Connect a suitable voltmeter (0-300Vac) across Line and Neutral of the generator. 3. Start the generator set, and run on no load at nominal frequency e.g. 50 (or 60). 4. If the red Light Emitting Diode (LED) is illuminated, refer to the section on Under-Frequency-Roll-Off adjustment. 5. Carefully turn the [VOLTS] control clockwise until the required voltage is reached. 6. If instability is present at rated voltage, refer to the section on Stability adjustment.7. Voltage adjustment is now completed. STABILITY ADJUSTMENT The AVR includes an optimised stability circuit to provide good steady state and transient performance of the generator. Links are provided to change the response of the stability circuit to suit different frame size generators and applications. A slow response setting is more appropriate on small generator sets and will prove helpful in reducing lamp flicker. The correct setting of the Stability adjustment can be found by running the generator at no load and slowly turning the stability control anti-clockwise until the generator voltage starts to become unstable. The optimum position for the control is slightly clockwise from this point (i.e. where the machine volts are stable but close to the unstable region). UNDER-FREQUENCY-ROLL-OFF ADJUSTMENT: (UFRO) The AVR incorporates an under-speed protection circuit which produces a volts/ characteristic when the generator frequency falls below a preset threshold - known as the "knee" point. The red Light Emitting Diode (LED) gives indication that the UFRO circuit is operating in the low frequency region. The UFRO adjustment is preset and sealed and only requires the selection of 50 or 60 operation using the jumper link. For normal operation, the LED should illuminate as the frequency falls just below 95% of nominal. i.e. 47 on 50 systems or 57 on 60 systems. DROOP ADJUSTMENT Generators intended for parallel operation should be fitted with a quadrature droop C.T. The C.T. is connected to S1, S2 on the AVR and provides a power factor dependent signal for the AVR voltage sensing circuit. This allows the control of generator reactive current when two or more generators are operated in parallel. The DROOP adjustment is normally preset in the works to give 5% voltage droop at full load zero power-factor. Clockwise increases the amount of C.T. signal injected into the AVR and increases the amount of voltage droop. With the control fully anti-clockwise there is no droop. OVER EXCITATION TRIP The over-excitation trip level is set at the works at 65Vdc and cannot be altered. An over excitation condition is indicated on the LED (which also indicates under speed running). The over-excitation is allowed to exist for approximately eight seconds to prevent nuisance tripping and to support normal transients and shortterm overloads. The generator voltage falls to low levels when the trip is activated. The generator must be stopped to reset an over-excitation shutdown condition. EXCITATION BOOST SYSTEM There are no user adjustments on the EBS module just connect the unit and it is ready for use. Cummins 2008 TD_AS480 AVR_04.08_02_GB A043Y698 (Issue 1)

EBC ( Excitation Boost Controller ) Block Diagram PMG Output Winding Excitation Boost Controller Connections Power Supply Input Rectifier EB Level Shifter Full Output Power Control DR Micro - controller Level Shifter Mid Output Power Control Level Shifter Low Output Power Control F1 + Exciter Field Windings F2 - EBS - Circuit description: The EBS comprises an add-on permanent magnet generator (EBG) with embedded control electronics (the EBC module). The main functions of the EBC are as follows: need for excitation power support. As this support is required it is delivered at low, medium or high levels to the exciter field. The AVR control function maintains generator voltage within broad limits until both AVR and EBS are fully conducting. The Input Rectifier and Power-Supply provides supplies to the internal control parts of the EBC. The Micro-controller measures the drive signal (DR) generated by the AVR and determines the The micro processor contains three timer functions: to prevent activation on generator run up, operation below 30 and to disconnect the booster power after a period of boost operation i.e. preventing the generator from overheating. This function is designed to follow the approximate thermal state (temperature) of the machine windings. Cummins 2008 TD_AS480 AVR_04.08_02_GB A043Y698 (Issue 1)

The output characteristic of the EBS is as shown below. The high-speed interaction between the EBS output and AVR demand is effectively smoothed by the connected generators excitation component time-constants. EBS Output Characteristic POWER INPUT Voltage Frequency OUTPUT Voltage Current Resistance 90-130 Vac 3 phase 100-120 nominal 120 Vd.c. @ 100 Va.c power input. continuous 6A 15 ohms min Excitation Level AVR output Level #2 Level #3 TYPICAL SYSTEM RESPONSE EBC response INTERNAL TIMERS 20ms Level #1 EBS output Start-up timer Overload protection timer 5sec nominal 5sec nominal Full Load AVR demand Output Short Circuit UNIT POWER DISSIPATION 12 watts maximum Barnack Road Stamford Lincolnshire PE9 2NB Tel: 00 44 (0)1780 484000 Fax: 00 44 (0)1780 484100 Cummins 2008 TD_AS480 AVR_04.08_02_GB A043Y698 (Issue 1)