Applicant: Electrical Apparatus: KROHNE Ltd. Measuring converter, type MFC400F Description of equipment The measuring converter, type MFC400F is used as part of a mass flow measuring system to determine display the mass flow rate of flammable non-flammable liquids. The equipment consists of the separately certified components, electronic assembly, type MFC400, measuring converter housing, type MH300, cable gl, type LC-MASS-Ex as well as a mounting bracket with remote junction box. The measuring converter, type MFC400F is designed as associated apparatus may be installed in the hazardous area. The permissible range of the ambient temperature depends on the design of the housing as follows: Aluminium converter housing: T amb = 40 C... + 65 C Stainless steel converter housing: T amb = 40 C... + 60 C Painted versions: T amb = 40 C... + 40 C Electrical data: Auxiliary power (non-intrinsically safe) depending on version U N = 12 24 V DC, +30 % / -10 %, Terminals, PCB power supply (f sht periods -25 %), 12 W X2-A28...A31 (L/L+) internal fuse I N 2 A X2-A23...A26 (N/L-) U m = 253 V X2-A13, A14, A16, A19...A21 (PE) f connection to protective extra low voltage with safe isolation (PELV) U N = 24 V AC/DC, 22 VA/12 W 24 V AC, +10 % / -15 %, 50/60 Hz 24 V DC, +30 % / -25 % internal fuse I N 2 A U m = 253 V f connection to protective extra low voltage with safe isolation (PELV) U N = 100 230 V AC, +10 % / -15 %, 50/60 Hz, 22 VA internal fuse I N 1.6 A Page 1 of 7
Input/output s (non-intrinsically safe) Printed board: Nominal voltage: U N 32 V DC U m = 253 V Basic IO Terminals IO1-A2, B2 Status output, passive I max = 100 ma IO1-A6, B6 Status output, passive I max = 100 ma control input U max = 32 V IO1-A11, B11 Puls output, passive I max = 100 ma IO1-A15, B15, A16 Current output, active/passive HART Modular IO Terminals IO1-A2, B2 Current output, active/passive HART IO1-A11, B11 Status/puls output, active I max = 20 ma Status/puls output, passive I max = 100 ma Modular Carrier + IO Module depending on module (max. 2 modules) Terminals Mod. A: IO2-A11, B11 Current output, active/passive 0(4) 20 ma Mod. B: IO2-A2, B2 Status/puls output, active I max = 20 ma Status/puls output, passive I max = 100 ma Control input active/passive U max = 32 V Control input, active/passive 0(4) 20 ma, U max = 32 V Fieldbus IO Terminals IO1-A2/A11, B2/B11 accding to function Profibus-PA, passive Foundation Fieldbus, passive Nominal voltage 9 V 32 V Profibus DP IO Terminals IO1-A6/B2, A11/B6 IO1-A2, B11 Profibus-DP, active, 12 Mbit/s Termination Modbus IO Terminals IO1-B2, A11, B11 RS 485 Modbus, active Page 2 of 7
Input/output s (intrinsically safe) (depending on PCB IO-function) Printed board: Exi-IO Current output, passive HART communication Ex ib IIC Terminals IO1-A2, B2 Current output, active HART communication Ex ib IIC Terminals IO1-A2, B2 U o = 21 V I o = 90 ma P o = 0.5 W C o 90 nf 110 nf L o 2.0 mh 0.5 mh Puls/Status output Control input, passive Ex ib IIC Terminals IO1-A11, B11 Page 3 of 7
Exi-Option Current output, passive Terminals IO2-A2, B2 Ex ib IIC Current output, active (Terminals IO2-A2, B2 Ex ib IIC U o = 21 V I o = 90 ma P o = 0.5 W C o 90 nf 110 nf L o 2.0 mh 0.5 mh Puls/Status output Control input, passive Ex ib IIC Terminals IO2-A11, B11 Page 4 of 7
Exi-Option 2 Current input, passive Terminals IO2-A2, B2 Ex ib IIC Current input, active Terminals IO2-A2, B2 Ex ib IIC U o = 24.1 V I o = 99 ma P o = 0.6 W C o = 75 nf L o = 0.5 mh Puls/Status output Control input, passive Ex ib IIC Terminals IO2-A11, B11 Page 5 of 7
Fieldbus IO Profibus-PA Foundation Fieldbus Ex ib IIC passive Terminals IO2-A2, B2 IO2-A11, B11 U i = 24 V I i = 380 ma P i = 5.32 W C i = 5 nf L i = 10 µh FISCO-field device accding to EN 60079-27 Driver A (terminals, Ex ib IIC Dubox Connect X5-1...X5-6) I o = 2130 ma P o = 920 mw C o = 500 nf L o = 16 µh 0 when connected infallibly Driver B (terminals, Ex ib IIC Dubox Connect X5-9...X5-14) I o = 1325 ma P o = 530 mw C o = 500 nf L o = 36 µh 0 when connected infallibly Page 6 of 7
Sens (terminals, Ex ib IIC Dubox Connect X3-1 X3-6) I o = 13 ma P o = 39 mw C o = 90 nf L o = 100 mh RTD / DMS- (terminals, Ex ib IIC Dubox Connect X3 7 10) I o = 9 ma P o = 27 mw C o = 310 nf L o = 1 mh The intrinsically safe s are safely electrically isolated from all non-intrinsically safe s up to a peak value of the nominal voltage of 375 V. Special conditions f safe use 1. The flow meters of type series OPTIMASS 1400C, 2400C, 3400C, 6400C, 7400C shall be included in the equipotential bonding system of the hazardous area. 2. Opening the enclosure inside the hazardous area is only permissible in a de-energized state with keeping a subsequent waiting time (warning label!) This waiting time is: 35 minutes f temperature class T6 10 minutes f temperature class T5 No waiting time is required f temperature classes T4... T1. 3. Only certified cable gls may be applied as cable entries. Non-used openings shall be sealed by means of certified blind plugs. 4. The connecting cables shall be installed as fixed wiring in such a way that they are sufficiently protected against damage. Page 7 of 7