AN APPLICATION OF MS-EXCEL FOR COMPUTATION OF VARIOUS TRANSFORMER PARAMETERS

Similar documents
86 chapter 2 Transformers

PROBLEMS on Transformers

Module 7. Transformer. Version 2 EE IIT, Kharagpur

Chapter 2: Transformers

Hours / 100 Marks Seat No.

Development of power transformer design and simulation methodology integrated in a software platform

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.

Methods of secondary short circuit current control in single phase transformers

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

RESONANT TRANSFORMER

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad ELECTRICAL AND ELECTRONICS ENGINEERING

Active Smart Wires: An Inverter-less Static Series Compensator. Prof. Deepak Divan Fellow

Open Circuit (OC) and Short Circuit (SC) Tests on Single Phase Transformer

3-phase short-circuit current (Isc) at any point within a LV installation

MV network design & devices selection EXERCISE BOOK

148 Electric Machines

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Ferroresonance Experience in UK: Simulations and Measurements

ISSN: [IDSTM-18] Impact Factor: 5.164

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Short-Circuit Current Calculations

Maintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems

Chapter 2-1 Transformers

VALLIAMMAI ENGINEERING COLLEGE

Table of Contents. Table of Figures. Table of Tables

Design optimization of distribution transformers based on mixed integer programming methodology

Rarely used, problems with unbalanced loads.

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

EN Assignment No.1 - TRANSFORMERS

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

SUBSTATION MONITORING AND CONTROL SYSTEM

INTRODUCTION...xiii Author s Comments...xiii Exam Preparation...xiii Difficult Concepts...xiv Textbook Errors and Corrections...xv Internet...

Transformer & Induction M/C

500 kva Dry-type Isolation Transformer V-Delta to 208Y/120V 3PH - NEMA 1/Indoor

Vallabh Vidyanagar, Anand, INDIA

Spotlight on Modern Transformer Design

Transformer circuit calculations

TRANSFORMER OPERATION

Practical Transformer on Load

AUTO-TRANSFORMER. This is having only one winding; part of this winding is common to both primary and secondary.

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

Performance of high voltage transducers for measurement of power quality disturbances modeling and simulation

How to maximize reliability using an alternative distribution system for critical loads

Transformer Protection

Benefits of SFRA - Case Studies

Alternative Testing Techniques for Current Transformers. Dinesh Chhajer, PE Technical Support Group MEGGER

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Decriminition between Magnetising Inrush from Interturn Fault Current in Transformer: Hilbert Transform Approach

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 4, OCTOBER

An Example Distance Protection Application with Complicating Factors.

Tap Changer Analyzer & Winding Ohmmeter RMO60TT

Regional Technical Seminar TAP CHANGERS

1. THREE-PHASE TRANSFORMER. SHORT CIRCUIT TEST

The Reactances as Voltage Divider

Comparison of Leakage Impedances of Two Single-phase Transformers

Part Number I s (Amps) n R s (Ω) C j (pf) HSMS x HSMS x HSCH x

Rony Parvej s EEE. Lecture 3 & 4: Transformer. Update: 30 April, fecabook.com/ronyiut

QUESTIONNAIRE for Wind Farm Power Stations only

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Chapter 1: DC circuit basics

A COMPLEX CURRENT RATIO DEVICE FOR THE CALIBRATION OF CURRENT TRANSFORMER TEST SETS

Alternating Current Study Guide. Preface. This module is DIFFICULT.

A Resonant Tertiary Winding-Based Novel Air-Core Transformer Concept Pooya Bagheri, Wilsun Xu, Fellow, IEEE, and Walmir Freitas, Member, IEEE

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

Core Technology Group Application Note 1 AN-1

Tap Changer Analyzer & Winding Ohmmeter RMO-TD Series

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

UNIVERSITY OF TECHNOLOGY By: Fadhil A. Hasan ELECTRICAL MACHINES

Tap Changer Analyzer & Winding Ohmmeter RMO-TT

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS

6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV

Optimization of power transformers based on operative service conditions for improved performance

Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation

ISSN: Page 298

Power Factor & Harmonics

Research Article Transformer Winding Deformation Profile using Modified Electrical Equivalent Circuit

Tap Changer Analyzer & Winding Ohmmeter RMO-TT

PIONEER RESEARCH & DEVELOPMENT GROUP

Comparison of Internally Parallel Secondary and Internally Series Secondary Transgun Transformers

How to Analyze and Test the Location of Partial. Discharge of Single-winding Transformer Model

Question Paper Profile

1 Introduction

Spring 2000 EE361: MIDTERM EXAM 1

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Code No: RR Set No. 1

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

Contents. Core information about Unit

Maximum Allowable PV Penetration by Feeder Reconfiguration Considering Harmonic Distortion Limits

Transformers handling and transport

Application Guidance Notes: Technical Information from Cummins Generator Technologies

ANALYSIS OF OPERATION MODE AND PERFORMANCE INDICATORS OF A TRANSFORMER WHEN CONTROLLING ITS VOLTAGE WITH AN ALTERNATING MAGNETIC FLUX

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

, ,54 A

Adaptive Relaying of Radial Distribution system with Distributed Generation

Transcription:

AN APPLICATION OF MS-EXCEL FOR COMPUTATION OF VARIOUS TRANSFORMER PARAMETERS Prof. Manan M. Desai 4 Assistant Professor DegreeElectrical Engineering Dr. Subhash Technical Campus, Junagadh Ghadiya Kishan S. 1 Gohel Tushar M. 2 Baraiya Yogesh 3 Dr. Subhash Technical Campus Dr. Subhash Technical Campus Dr. Subhash Technical Campus Junagadh Junagadh Junagadh ABSTRACT Transformer is a very important part of any substations, which affects overall costing of transmission and distribution budgets. So, it is necessary to design economical, viable, low weight, small size efficient transformer.the design of transformer depend to large extent on the specific requirement of the customer. The main objective of our project is to develop a program for transformer design using Excel sheet. This Programming has ability to execute many difficult and reiterative calculations and step-wise procedure leading to a design that satisfies all input specification.with the Calculation technologies in the power industry, new references addressing new technologies are coming to the market. Based on this fact, there is an urgent need to keep track of international experiences and activities taking place in the field of modern transformer design. The complexity of transformer design demands reliable and rigorous solution methods. A survey of current research reveals the continued interest in application of advanced techniques for transformer design optimization. This paper conducts a literature survey and reveals general backgrounds of research and developments in the field of transformer design and optimization for the past 30 years, based on more than 200 published articles, 25 transformer books, and 50 standards.[1] Keywords :-Microsoft excel, visual basic, power system analysis, equivalent circuits, experimental methods, numerical techniques, standards, survey, transformer books, transformer design optimization. 1. Introduction Transformer design is a complex task in which engineers have to ensure that compatibility with the imposed specifications is met, while keeping manufacturing costs low. Moreover, the design methodology may vary significantly according to the transformer type (distribution or power transformer) and its operating frequency (ranging between 50/60 Hz and a few MHz), while many alterations according to the core constructional characteristics, the cooling method, or the type of the magnetic material may be encountered. This paper provides an overview of research, development and application of various computational methods for transformer design, based on an extensive number of published papers. The review is divided into two major sections: research efforts focusing on the prediction and/or optimization of specific transformer characteristics (mainly losses and short-circuit impedance) and techniques adopted for global transformer design optimization, taking into account all the relevant performance parameters.[2] 2. Methodology Design With the rapid development of the digital computer, designers are no longerassist to their performance of the routine calculations. Computer is widely use in optimized of transformer designwithintheir matter of the seconds. We have make an excel sheet that includes transformer parameter calculation easily. 43 Prof. Manan M. Desai, Ghadiya Kishan S., Gohel Tushar M., Baraiya Yogesh

These are the input parameters of transformer :- KVA rating of Transformer Primary voltage Secondary voltage No load losses No load current Full load losses Impedance voltage LV resistance in mili ohms HV resistance in ohms Amb temperature Total Connected Load on Transformer Above transformer data include in excel sheet and we got the calculation of transformer parameters. 3. CASE STUDY This section presents the mathematical formulation of the objective function, design variables, and design constraints for distribution transformer design optimization. This technique is integrated in excel environment, using suitable graphical user interface. The transformer inputs involves design parameters, such as rated power, voltages, etc., comprises of the upper/lower limits and the initial value of the design. For optimizing the transformer design is based on the minimization of the overall transformer cost function. 3.1Formula HV Full load current = VA / (1.732xVolt) LV Full load current = VA / (1.732xVolt) HV Side I2R losses = I²R x1.5 LV Side I²R losses = I²R x0.5x3 Total I² R losses @ Amb temp = Hv losses + Lv losses Total Stray losses @ Amb temp = Measured losses -I² R losses I² R losses @75 c temp = ((225+75) x losses) / (225+ Amb temp) Stray losses @ 75 c temp = ((225+Amb temp)(stray losses at amb)) / 300 Total Full load losses at @75 c = I²R losses at 75 c+stray losses at 75 c Total Impedance at ambient temp = (Imp voltage x 1.732) / Full load current Total Resistance at ambient temp = I²R losses / I² Total Reactance (X) = SQRT(Impedance ²- Resitance ²) Resistance at@ 75 c = (300 x resistance at ambient ) /(225+Amb temp) Impedance at 75 c = SQRT(R² at 75 + X²) Percentage Impedance = (Z at 75 c x I x 100)/V1 Percentage Resistance = ( R 75 c x I x 100)/V1 Percentage Reactance = (X x I x 100) / V1 Regulation at Unity P.F = (%R cosø+%xsinø) Regulation at 0.8 p.f. =(%R cosø+%xsinø)+1/200(%r sinø-%xcosø)2" Efficiency at Unity P.F o At 125 % of Transformer Loading = (Kva x 1.25 x 100)/((kva x 1.25)+(I²R losses x 1.25²)+(No Load Losses)) Efficiency at 0.8 P.F o At 125 % of Transformer Loading = (Kva x 1.25xp.f x 100)/((kvaxp.fx 1.25)+(I²R losses x 1.25²)+(No Load Losses)) 3.2 Parameter Caculations I 2 R Losses :- 1. LV Full load current = (KVA rating of Transformer)/( Secondary voltage*1.732) 44 Prof. Manan M. Desai, Ghadiya Kishan S., Gohel Tushar M., Baraiya Yogesh

= (16000)/(11000*1.732) = 0.84 Amps 2. LV Full load current = (KVA rating of Transformer)/( Secondary voltage*1.732) = (16000)/(433*1.732) = 21.33 Amps 3. HV Side I²R losses = (HV Full Load Current) ^2* HV resistance*1.5 = (0.84*0.84)*215*1.5 = 227.80 Watts 4. LV Side I²R losses = (LV Full Load Current) ^2* LV resistance*1.5 = (21.33*21.33)*219.16mΩ*1.5 = 149.56 Ohms 5. Total I² R losses @ Amb temp = HV Side I²R losses + LV Side I²R losses = (227.80)+(149.56) Ω = 377.43 Ohms 6. Total Stray losses @ Amb temp= (LV Side resistance in mili Ω) - Total I² R losses @ Amb temp = (219.16mili ohm s) (377.43 watts) = 16.57watts 7. Total I² R losses @75`C Amb temp = ((225+75) total I²R losses) / (225+ Amb temp) = ((225+75) x337.43) / (225+ 30) = 441.52Watts 8. Stray losses @ 75 c temp = ((Total Stray losses @ Amb temp)*(235+ Amb temperature))/(310) = ((16.57watts)*(235+ 30))/(310) = 14.16Watts 9. Total Full load losses at @75 c = =( Total I² R losses @75`C Amb temp)+( TotalStray losses @ 75 c temp) = (441.52Watts)+(14.16Watts) = 455.9 Watts 10. Total Impedance at ambient temp = ( Impedance voltage*1.732)/( HV Full load current) = 480*1,732)/(0.84) = 989.54 Ohms 11. Total Resistance at amb temp = ( Total I²R losses @ Amb temp)/((hv Full Load Current) 2 ) = ( 377.43)/(0.84) 2 = 535.15 Ohms 12. Total Reactance (X) = SQRT(Impedance ²- Resistance ²) = SQRT((989.94) ²- (535.15) ²) = 832.82Ω 13. Resistance at@ 75 c = (310 *total resistance at ambient ) /(225+Amb temp) = (310 *535.15) /(225+30) = 625.03Ω 14. Impedance at@ 75 c = SQRT(R² at 75 + X²) = SQRT((625) 2 + (832.82) 2 ) = 1041.88Ω 15. Percentage Impedance = (Impedance*0.5774*HV Load Current*100)/(Primary Voltage) = (1041.88*0.5774*0.84*100)/(11000) =4.59% 16. Percentage Resistance = (Resistance at 75 c*0.5774*hv Load Current*100)/(Primary Voltage) = (535.15*0.5774*0.84*100)/(11000) =2.76% 17. Percentage Reactance = (Total Reactance *0.5774* HV Load Current *100)/(Primary Voltage) = (832.82Ω *0.5774* 0.84*100)/(11000) =3.67% 45 Prof. Manan M. Desai, Ghadiya Kishan S., Gohel Tushar M., Baraiya Yogesh

Regulation Calculation:- 1. Regulation at Unity P.F = (%R cosø+%xsinø) = ((2.75*0.8)+ (3.67*0.6)) = 2.76 2. Regulation at 0.8 P.F = (%R cosø+%xsinø)+1/200(%r sinø-%xcosø) 2 =( 2.75 0.8 + (3.67 0.6)) + 0.005((2.75 0.6) + (3.67 0.8)) 2 = 4.43% Efficiency Calculation:- 1. Efficiency at Unity P.F = (KVA*1.25*100)/((KVA* 1.25)+(I²R losses*1.25²)+(no Load Losses)) = (16000*1.25*100)/((16000*1.25)+(377.45*1.25²)+(72)*100 = 96.80% 2. Efficiency at 0.8 P.F = = (KVA x 1.25xp.f x 100)/((KVA xp.fx 1.25)+(I²R losses x 1.25²)+(No Load Losses = (16000*1.25*.8*100)/((16000*1.25*0.8+(377.45*0.8*1.25²)+(72)*100 = 99.52% 4. RESULT Now a day to calculate transformer parameters method is very lengthy, hard and it take a so much time of operators. So, we make this project to calculate transformer parameter and it is very easy and give output within there matter of seconds. I²R losses Calculation:- Theoretical Calculation Practical Calculation HV Full load current :- 0.83 A HV Full load current :- 0.84 A LV Full load current :- 21 A LV Full load current :- 21.33 A HV Side I²R losses :- 225 W HV Side I²R losses :- 227.80 W LV Side I²R losses:- 150 W LV Side I²R losses:- 149.63 W Total I² R losses @ ambient temp:- 376 W Total I² R losses @ ambient temp:- 377.43 W Total Stray losses @ ambient temp:- 15 W Total Stray losses @ ambient temp:- 16.57 W I² R losses @75 c temp:- 441 I² R losses @75 c temp:- 441.52 W Stray losses @ 75 c temp:- 15 W Stray losses @ 75 c temp:- 14.16 W Total Full load losses at @75 c :- 455 W Total Full load losses at @75 c :- 455.69 W Total Impedance at ambient temp:- 989 Ω Total Impedance at ambient temp:- 989.94 Ω Total Resistance at ambient temp:- 535 Ω Total Resistance at ambient temp:- 535.15 Ω Total Reactance (X):- 831 Ω Total Reactance (X):- 832.82 Ω Resistance at@ 75 c:- 626.35 Ω Resistance at@ 75 c:- 626.03 Ω Impedance at 75 c :- 1041.20 Ω Impedance at 75 c :- 1041.88 Ω Percentage Impedance:- 4.60 % Percentage Impedance:- 4.59 % Percentage Resistance :- 2.65 % Percentage Resistance :- 2.67 % Percentage Reactance :- 6.66 % Percentage Reactance :- 3.67 % 46 Prof. Manan M. Desai, Ghadiya Kishan S., Gohel Tushar M., Baraiya Yogesh

Regulation Calculation :- Theoretical Calculation Practical Calculation Regulation at P.F of unity :- 2.75 % Regulation at P.F of unity :- 2.76 % Regulation at P.F of 0.8 :- 4.43 % Regulation at P.F of 0.8 :- 4.43 % Efficiency Calculation :- Efficiency at P.F of Unity:- Efficiency at P.F of Unity:- At Transformer Loading 125% :- 96.75 % At Transformer Loading 125% :- 96.80 % Efficiency at P.F of 0.8 Efficiency at P.F of 0.8 At Transformer Loading 125% :- 99.50 % At Transformer Loading 125% :- 99.52 % 5. CONCLUSION In this projectwe got the information and practical knowledge about Transformer. We got the knowledge about different type of transformer testing, I² R loss, efficiency, regulation, outer and inner part of transformer like core, winding, relay etc. We have make an excel sheet that includes transformer parameter calculation easily. Because all calculations is done by there programming, by human errors is eliminated which turn eliminate cost associated by these.these project are very useful for industrial and power supplier. by use this software they not need any external document require. 6. REFERENCES [1] Eleftherios I. Amoiralis, Marina A. Tsili,and Antonios G. Kladas,IEEETransactions on Power Delivery. November 2009 DOI:10.1109/TPWRD.2009.2028763. Source: IEEE Xplore [2] Eleftherios I. Amoiralis, Marina A. Tsilia, Pavlos S. Georgilakis,Journalof optoelectronics and advanced materials Vol. 10, No. 5, May 2008, p. 1149 1158 [3] K. Zakrzewski, B. Tomczuk, and D. Koteras, Simulation of forces and 3-D field arising during power autotransformer fault due to electric arc in HV winding, IEEE Trans. Magn., vol. 38, no. 2, pp. 1153 1156, Mar. 2002. [4] American Journal of Engineering Research (AJER) e-issn : 2320-0847 p-issn : 2320-0936 Volume-4, Issue-2, pp- 133-145 47 Prof. Manan M. Desai, Ghadiya Kishan S., Gohel Tushar M., Baraiya Yogesh