OCPS CLAY SPRINGS ES SUBMITTAL DETAILS: SUBJECT: BUILDING REFERENCE: DATE RECIEVED: Jun 01, 2015 DISCIPLINE: Mechanical PRIORITY STATUS: 2-STANDARD SPECIFICATION REF: 23 25 00 REVIEWER DUE DATE: 6/11/2015 DWG REF. DWG TITLE: RETURNED ITEMS: HVAC WATER TREATMENT CHILLED WATER PIPING TR NONE NO OF ITEMS: ITEM DESCRIPTI CONTRACTOR/CM: SUBMITTAL TRANSMITTAL SUBMITTAL NUMBER: 232500-02.00 : WILLIAMS COMPANY : BRAD KUBIN 2301 SILVER STAR RD. (407) 295-2530 FAX:(407) 297-0459 DATE RETURNED TO CM: 1 Product Literature(s) REVIEW STATUS: REVIEWED REVIEWERS: PRIMARY: SECONDARY: COMMENTS: KEVIN KING PHN: (407) 740-5020 FAX: (407) 740-0365 kking@matern.net NO SECOND REVIEWER ASSIGNED cc: OWNER : CALVIN WOOLFOLK 6501 MAGIC WAY, BLDG. 200 (407) 317-3700 FAX:(407) 317-3768 R+B FILE: : 13017-0001.X6 RHODES + BRITO ARCHITECTS INC. : 605 E. ROBINSON STREET, SUITE 750 : ORLANDO, FL. : 32801 : 407.648.7288 : FAX.648.7289 PAGE 1 OF 1
OCPS CLAY SPRINGS ES SUBMITTAL DETAILS: SUBJECT: DATE RFI RECIEVED: Jun 01, 2015 DISCIPLINE: Mechanical PRIORITY STATUS: 2-STANDARD SPECIFICATION REF: 23 25 00 REVIEWER DUE DATE: 6/11/2015 DWG REF. DWG TITLE: SUBMITTAL CONTENTS: HVAC WATER TREATMENT CHILLED WATER PIPING TR NONE NO OF ITEMS: ITEM DESCRIPTION 1 SERVICE REPORT REVIEWERS: PRIMARY: SECONDARY: SUBMITTAL ASSIGNMENT MEMO KEVIN KING PHN: (407) 740-5020 FAX: (407) 740-0365 kking@matern.net SCOTT BURCHFIELD SUBMITTAL NUMBER: 23250002.00 PHN: FAX: sburchfield@matern.net REVIEW STATUS: REVIEWED FURNISHED AS MARKED REVISE AND RESUBMIT RE-SUBMIT WITH ITEMS NOT REVIEWED REJECTED THIS SUBMITTAL IS ISSUED TO YOU FOR YOUR REVIEW. PLEASE RESPOND AND RETURN...WITH THIS COMPLETED SAM TRANSMITTAL...TO MICHELE BUDAY-URDANETA NO LATER THAN: 6/11/2015. PLEASE COMPLETE REVIEW STATUS AT RIGHT COMMENTS: THIS SUBMITTAL WAS REVIEWED BY : (please print) cc: OWNER : CALVIN WOOLFOLK 6501 MAGIC WAY, BLDG. 200 CONTR/CM: : WILLIAMS COMPANY : BRAD KUBIN 2301 SILVER STAR RD. R+B FILE: : 13017-0001.X6
Submittal Approval Form PROJECT: CLAY SPRINGS ELEMENTARY SCHOOL DATE: 6/1/15 SUBCONTRACTOR NAME: DHR Mechanical Services SUBCONTRATOR ADDRESS: NUMBER AND TITLE OF SPECIFICATION SECTION: 23 25 00 - HVAC Water Treatment Chilled Water Piping TR Contractor s Submittal Stamp Architect/ Engineer s Submittal Stamp 6/1/15
SUBMITTAL DATA REVIEW COMMENTS Date: June 12, 2015 MPE Project No: 2013-224 Project: By: Submittal: OCPS-Clay Springs ES J. Walden for Kevin King Water Treatment Data No.: 23 25 00 Submittal No.: 002 Contractor s I.D.: DHR Class: Basis of Design (1) Equal (2) Substitution (3) X A No exceptions taken. B Make corrections noted. C Revise and Resubmit. D Submit Specified Item. E Rejected. N Review not required. ACTION CODE THE FOLLOWING COMMENTS SHALL BE CONSIDERED AN INTEGRAL PART OF THE SUBMITTAL DATA REVIEW. REVIEW OF THIS DATA IS ONLY FOR CONFORMANCE WITH THE DESIGN CONCEPT AS GIVEN IN THE CONTRACT DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR: QUANTITIES, FUNCTIONS, DIMENSIONS AND COORDINATION OF THE WORK WITH OTHER TRADES. 1.Preliminary water test report. END OF SUBMITTAL DATA REVIEW COMMENTS Corporate Office: 130 Candace Drive, Maitland, Florida 32751-3331 Phone: 407.740.5020 Orlando Fort Myers Jacksonville Tampa www.matern.net Registered: FLORIDA * GEORGIA* LOUISIANA * NORTH CAROLINA * SOUTH CAROLINA * TEXAS * TENNESSEE * VIRGINIA
WATER TREATMENT SERVICE REPORT Company: DHR Mechanical Date: 06/01/15 Address: Plant Clay Springs Elementary City: Apopka State: FL Zip: Country: Attention: Billy Walton Copy to: NALCO Copy to: WP106 FILES PURPOSE: To perform an inspection visit, and issue a preliminary report. Check the chemical parameters of your chilled water loop and provide recommendations to assure the specified performance goals are being met. OBSERVATIONS: Cleaning agent was introduced in the system on and flushed for over 48 hours. System water was tested on 05-21-15. We tested the conductivity, iron and ph levels of the closed loop. All parameters were within recommended settings, the results were 301 us/cm, 0.34 ppm and 8.01 respectively and are tabulated below. We recommended the inhibitor to be added once the system is free of leaks so product is not wasted. We returned to test for inhibitor on 06-01-15 and it tested At 1000 ppm. Conductivity ph Iron Nitrite 301.00 us/cm 8.01 00.34 ppm 1000 ppm Conductivity ph Iron Recommen ded Iron Record Record < 1 ppm < 600 ppm Your input on today s visit matters to us, and will help improve our service. Feel free to contact us with any questions or concerns. Jesus Morfa, B.S.M.E., M.S.E.M District Representative. Nalco an Ecolab Company 813-394-1730 Alex Pichardo, Technical Service Representative. Nalco an Ecolab Company. 407-936-4497 Signed: Jesus Morfa Title: District Representative. District: WP106 NALCO COMPANY 2622 Cypress Ridge Blvd., Suite 102 Wesley Chapel, FL 33544