Efcon Water. Installation & User Manual Electro Magnetic Flowmeter (EMF) Efcon Water compact Electro Magnetic Flowmeter (EMF) Manual Version UK

Similar documents
SITRANS F flowmeters. SITRANS F M System information MAGFLO electromagnetic flowmeters. 4/18 Siemens FI

WATERFLUX 3000 Quick Start

WATERFLUX 3000 Quick Start

KMS502F. ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products. Electromagnetic Flanged Flowmeters FEATURES: (sizes: 25mm to 200mm)

FLOMID-MX Control unit for electromagnetic flowmeters USERS MANUAL. instrumentación para fluidos. Realitzat: Revisat R+D Electrònic: Aprovat: Data:

Magnetic Inductive Flow Sensor induq

KMS101W. ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products. Electromagnetic Wafer Flowmeters with S100 display

Ambient Conditions. Operating Conditions. Pressure

KMS305W. ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products. Electromagnetic Wafer Flowmeters with S300 display

OPTIFLUX 5000 Technical Datasheet

FMG90 Series Electromagnetic Flow Meter

Pmag. Features. Compact digital system, for conductive liquids (>5µS/cm), even with a limitated content of suspended solids.

Electro-Magnetic Flowmeters COPA-XE

Flow Switch - 2 programmable thresholds. Stand Alone (Battery) - Battery powered, - 2 totalizers display, - Local flow display,

SITRANS F flowmeters. SITRANS F System information MAGFLO electromagnetic flowmeters 4/9

SITRANS F flowmeters SITRANS F M. Transmitter Transmag 2 with sensor 911/E 4/77. Overview

www. otech.com.sg EFS801 ELECTROMAGNETIC FLOWMETER

Magnetic-inductive flow meter. PITe / UMF2. Technical Datasheet. Maintenance-free Nearly no pressure drop Robust design Easy installation and start-up

FLOMID FX Electromagnetic Flowmeter

Electromagnetic Flowmeter Comet F

UFM 800 W, C Ultrasonic flowmeter for water and wastewater

The transducer component converts the measured signal and displays the actual value.

Digital flow transmitter for continuous flow measurement

Type PLC Fitting. Valve for Continuous control. Diaphragm valve. Output

BATCHFLUX 5500 C Technical Datasheet

OPTIFLUX 5000 Technical Datasheet

Magnetic Inductive Flow Sensor

Digital inductive conductivity transmitter

Magnetic-Inductive flow Meter fmi

FMG70B Series Magnetic Inductive Flow Sensor

Electromagnetic Flow Transmitter

Lmag_W803D Battery Powered Electromagnetic Converter. User Manual

J Series induq VMZ MAGNETIC INDUCTIVE FLOW SENSORS. DB_Magnetic_Inductive_Flow_Sensors 05/2016

W803C Battery Powered Electromagnetic Converter. User Manual

UMF. Transmitter for magnetic-inductive flowmeters. Operating Instructions

EN-2018 MAGNETIC FLOW METERS

UNICONT. PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1. pmg4111a0600p_01 1 / 24. ST edition

OPTIFLUX 1000 Technical Datasheet

ProcessMaster / HygienicMaster

Electromagnetic flowmeters and switches DWM 1000/2000

Flow Technologies Overview. For internal use only / Siemens AG All Rights Reserved.

TIDALFLUX 2300 F Technical Datasheet

Digital flowmeter for continuous flow measurement

Digital flowmeter for continuous flow measurement

Electromagnetic flowmeters Transmitter types MAG 5000, MAG 6000

MK372/Ultrasonic Sensor System. Installation & Setting up Instructions. Comprising. MK372 Indicator/Controller Ultrasonic Transmitter

T EK-FLUX 1400A Electromagnetic Flowmeter

WATERFLUX 3070 Technical Datasheet

Operating Instructions. MaxxFlow HTC Measurement of Bulk Solids for High Flow Rates

MS 5000 CIAO SENSOR EXTREMELY EASY TO INSTALL THANKS TO PATENTED WRAPPER FIXING SYSTEM

Target disk flowmeter for liquids and gases

Flow Measurement SITRANS F M

FLOWPET-EG. Description 1 Accumulated total flow (8-digit) 2 Instantaneous flowrate, L/h (mode:b1) and L/min (mode:b2) Selectable with

BATCHFLUX 5500 C Handbook

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL

Instruction Manual TABLE OF CONTENTS 1 PRINCIPLE OF OPERATION Limitations INSTALLATION Mains connection...

Digital conductivity transmitter

Flow Measurement SITRANS F M. Flow sensor MAG /49. Overview

Ultrasonic level transmitter, non-contact

MODEL AT-10 ANALOG TRANSMITTER

Signal converter for electromagnetic flowmeters

IFC 100 Technical Datasheet

KF-510 Series Turbine Flow transducer user's manual

GS.No.GBN062E-5. GENERAL SPECIFICATIONS Sensor unit

Inexpensive PD for Boiler Feed Water and Oil FLOWPET-EG

INSTALLATION AND OPERATION MANUAL

Digital flow ELEMENT transmitter for continuous flow measurement

Section 1, General information Introduction... 3 Description... 3 Specifications... 4 Wiring connections... 5

SITRANS F flowmeters SITRANS F US. SONOFLO SONO 3000 transmitter. 4/152 Siemens FI Overview

ma output signal with transmitter module. - Adjustable frequency output signal with pulse divider module

ph or ORP Transmitter

CX105 Conductivity/Resistivity Transmitter

Rosemount 8700 Series. Magnetic Flowmeter Systems. Rosemount 8700 Series. Product Data Sheet , Rev TA April 2009.

GFL-1000 User Manual Ground Fault Locator

ELECTROMAGNETIC FLOW METER AFLOWT MF

MC 308 CONVERTER MUT SERIES FLOWMETERS

The system (EF-7700) consists out of two parts: the transmitter (EF-7602) and the receiver including wiring (EF-7701).

Field IT Electro-Magnetic Flowmeters Mini-Mag with integral XE converter

SITRANS F flowmeters SITRANS F M. Flow sensor MAG /48 Siemens FI Overview

E l e c t r o m a g n e t i c f l o w m e t e r s

Target disk flowmeters Series DP Metallic flowmeter for liquids and gases

Magnetic Inductive. Flow Sensor. Operating manual (Translation) Series VMM. Operating manual... page SIKA Ba_VMM_en 12/2017.

ProGap Microwave barrier

IFC 010 Signal Converter

Digital flow ELEMENT transmitter for continuous flow measurement

Signal converter for electromagnetic flowmeters

TEMPERATURE CONTROLLER RE21 TYPE

TS-700/1000 INVERTER Instruction Manual

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

Digital batch controller

Flow Measurement SITRANS F M. Transmitter TRANSMAG 2 with sensor 911/E 4/101. Overview

Simplified Operations for TM-3100 Series Digital Tachometer

ITP14. Universal process indicator. User guide

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information

Mobrey Ultrasonic. MSP422, MSP400RH, and MSP900GH Level Transmitters. Product Data Sheet February 2015 IP2045, Rev EA

Smart Electromagnetic Flowmeter Open channel Flowmeter Detector

Flow Measurement SITRANS F M

MaxxFlow HTC Flow Measurement for Dry Bulk Solids

Electromagnetic flowmeter in all metal design Model MIM

USER MANUAL. EPP Intelligent Positioner Control Unit 1/22.

Transcription:

Efcon Water Installation & User Manual Electro Magnetic Flowmeter (EMF) Page 1

Table of content Page 1.1 General 3 1.2 Application area 4 1.3 Transportation 4 1.4 Principle of Operation 4 1.5 Product Description 5 2 Installation 5 2.1 Technical specifications 5 2.2 Measurements 6 2.3 Installation 7 2.3.1 Mechanical installation 7 2.3.2 Electric installation 8 2.5 Maintenance 9 2.6 Trouble shooting 10, 11, 12 3 Commissioning 13 16 3.1 Display & Operation 13 3.2 Programming 13 3.2.1 Basic settings 14 3.2.2 System Settings 14 3.2.2.1 Signal Settings 15 3.2.2.2 Pulse Output settings 15 3.2.2.3 Totalizer settings 16 3.2.3 Calibration settings 16 Page 2

1.1 General Efcon Water compact Electro Magnetic Flowmeter (EMF) Manual Efcon flowmeters are designed for measuring and controlling wastewater flows. Other Products from the Efcon program are: Samplers (several types), level controllers, pump controllers, registration equipment, sample distributor systems, flowmeters industrial and sewers, measurement pits, cool units, mobile systems, etc. BEFORE YOU START: Read the manual before you connect the meter to a power supply or install. In case of illegal use or use in non-defined area s any form of warranty will be denied. The user needs to be informed about the users manual and application dangers. Installing and adjusting parameters of the flowmeter should be done by qualified personnel. Check if the equipment is transported without transport damage. In case of damage directly contact your supplier and do not install the equipment. The equipment is tested in the Efcon factory in Hei- en Boeicop, Netherlands to different quality tests before it is transported. Required maintenance or repair, which will not influence the warranty period, will have to be done by trained Efcon specialists. All equipment returned to Efcon needs to be cleaned, sterilised and transported in a safe enclosure to avoid health-threatening situations. In case of service or repair, the equipment will not be accepted by Efcon if there is no declaration of origin and safety added to the equipment. Extra cleaning can be refused or will be charged! Warranty will be denied if there are mechanical, electronic or software changes in the unit which are not performed by Efcon. BASIC WARRANTY PERIODS: 12 months after delivery for Efcon equipment ex. Works used and installed according specifications, in a non aggressive well ventilated environment. Page 3

1.2 Application area Be aware! Wrong application or misuse can damage the equipment or the surrounding of the unit and is not covered by any form of warranty. Surrounding conditions: Temperature: -15 C / + 50 C avoid large changes Well ventilated space Avoid direct sunlight, especially the liquid crystal display Avoid strong vibration Avoid installation near strong electromagnetic devices, such as large motors, pumps or transformers Use in explosion hazardous environment is prohibited unless mentioned on product and manual! Measured Medium: Especially designed for waste water measurement Minimum fluid conductivity: 50 μs/cm Free of air inclusion Medium temperature range: -40 C / +150 C. 1.3 Transportation For warranty claims send the system packed in the original package and on the supplied pallet. All products should be declared clean and safe to work on. 1.4 Principle of Operation The operation of a magnetic flowmeter or Mag meter is based upon Faraday s Law, which states: A voltage induced across any conductor as it moves at a right angle through a magnetic field is proportional to the velocity of that conductor. Faraday s Formula: E = V x B x D E = Voltage generated in a conductor V = Velocity of the conductor B = The magnetic field strength D = Length of the conductor To apply this principle to flow measurement with a magnetic flowmeter, the fluid being measured should be electric conductive. As applied to the design of the flowmeter, Faraday s Law indicates that the voltage E is dependent if the average liquid velocity (V), the magnetic field (B) and the length of the conductor (distance between electrodes). Page 4

1.5 Product description The Efcon EMF Compact Flowmeter consists out of mainly 2 parts: the sensor tube and transmitter. The sensor tube consist out of the following parts: 1) Junction box / transmitter mounting flange 2) DN Flange connection 3) Insulted Teflon lining 4) SS Electrodes 5) Measuring tube 6) Excitation coil 7) Protective shell The transmitter consist out of the following parts: 1) Sensor tube mounting flange 2) Operation lid 3) Display 4) Cursor buttons 5) Swivels for signal & power lines 6) Connection lid 2.1 Product specifications Sensor Range DN10 DN1000 Flow Range 0,05 m/s 10 m/s Accuracy ±1% >0,5m/s, (pulse calibrated at 0,1 0,5 1 2 5 m /s) Repeatability ± 0,5% Medium Conductivity >50μS/cm Power supply 230VAC ±2% Power rating 10VA Protection grade IP65 Pulse Output Open collector, maximum load 24VDC / 50mA Current Output 4-20mA, maximum load <750Ω Display language English Control buttons 3 Low flow cut off % 0,0%... 9,9% adjustable (for display or output) Damping Time 0,1s 99,9s adjust (for display Auto Trim Current output self-calibration, empty/full trim. Zero trim Self test function Current frequency output self test Page 5

Measurements DN (mm) max work pressure (bar) L* (mm) D (mm) K (mm) Weight (kg) 10 90 60 15 95 65 4 20 105 75 150 25 115 85 5 32 25 140 100 7 40 150 110 8 50 165 125 10 65 200 185 145 80 200 160 15 100 220 180 20 250 125 10 250 210 22 150 300 285 240 33 200 350 340 295 43 250 400 395 350 82 300 445 400 100 500 350 505 460 121 400 565 515 145 450 615 565 207 6 600 500 670 620 210 600 780 725 250 700 700 895 840 350 800 800 1015 950 460 900 900 1115 1050 550 1000 1000 1235 1120 680 * BEWARE: Gaskets & ground rings are not included in the measurements. Page 6

2.3 Installation Efcon Water compact Electro Magnetic Flowmeter (EMF) Manual Installation, commissioning and service should be carried out by qualified and authorized personnel. 2.3.1 Mechanical: When installing a flowmeter in a pipe system beware of the following : The sensor tube should always be 100% filled with liquid medium. Minimum fluid conductivity: 50 μs/cm The Free of air inclusion Temperature range medium: -40 C / +150 C Use proper gaskets when making the flange connection. Use proper grounding Don t install: In a downward flow At the highest point in a pipe system In pipe systems not free of air inclusion Avoid vibrations Page 7

Grounding: Steel/conducting piping: Connect the supplied yellow/green ground lines(a) on both sides of the flowmeter to the piping. Ensure the piping is properly grounded. Plastic or non-conducting piping: Install the flowmeter with the supplied grounding rings(b), connect these with the ground lines (A) on both sides. Ensure the rings are placed in the centre so the flow isn t interrupted by the ground rings. 2.3.2 Electric: Before connecting the power supply, check the name plate and connection terminals, to avoid misoperation and damage the instrument. To access and connect the wires to the terminals remove/open the screw-lid. Ensure when removing the lid the tread doesn t damage. A damage tread can make the lid get stuck. Feed the power line cable and output signal cable through separate cavities. Power Supply Connect the ground line to the transmitter to screw with ground symbol Connect the 230VAC line to the L & N terminals Current Output The current output creates an active 4-20mA signal powered from the transmitter, with 4 ma stands for a flow of 0 m3/h and 20mA stands for full scale value or Qmax. The maximum current output load is 750Ω. Connect the signal cable (shielded recommended) to terminals I+ and I-. Page 8

Pulse Output Direct connection to PLC input Connect the 24VDC wire to the F+ connection of the transmitter, connect the F- connection of the transmitter to the desired digital PLC-input (<50mA load). Pulse Output Connecting to a relay Use solid state relay and normal relay (Efcon uses Omron G3R-ODX02SN) to create a potential free contact from the pulse output. See the diagram to the left how to wire the relays. 2.4 Maintenance BE AWARE! Before maintenance or revision switch off power supply, remove pressure and medium from piping. Maintenance and reparations should be done by qualified personnel. Avoid direct contact with wastewater. Wear protective gloves during use, maintenance and reparation. Check the inside of the sensor tube regularly and inspect the SS electrodes inside the tube. Clean inside with a soft cloth. Page 9

2.5 Trouble shooting No flow data shown in display Page 10

Instrument shows flow data inconsistent with actual flow. Page 11

Zero point instability Efcon Water compact Electro Magnetic Flowmeter (EMF) Manual 50 50 Page 12

3.1 Display & Operation After the first power up the display will show the following: 0,0m 3 /h + 0,0m 3 0 %! * Current flow (upper row) * Totalizer positive flow * Percentage flow (100% = full range scale) * Blinking Exclamation mark (= alarm signal) ------ALARM------- PIPE LINE EMTY Press to check the Alarm message display Press again to check the totalizer display 0,0m3-0,0m3 PV_S 0,000 m/s E108-4S13-E4NNO * Cumulative total positive direction (upper row) * Cumulative total negative direction * Current flow velocity * Software version 3.2 Programming To access the programming open the display lid. Programming and setting changements should be done by qualified personnel. Ensure when removing the lid the tread doesn t damage. A damage tread can make the lid get stuck. Press to enter the menu. By pressing or to change the cursor and press to select. Basic System Calibration Basic System Calibration Basic settings; change the Pulse value unit, number of pulse value decimals, totalizer units, number of totalizer decimals and damping System settings; change signal settings, Pulse output settings, clear totalizers, load settings, load settings Calibration settings; Zero trim, tube trim, loop trim & calibration factor (don t change!) Page 13

3.2.1 Basic settings Press to enter the menu, press again to enter the basic settings menu. PV Units PV Decimal Total units Total Decimal PV Units PV Decimal Total Units Total Decimal Damping Pulse Value units, select which SI unit to use Select unit with or (L/s, L/m, L/h, m3/s, m3/m, m3/h G/s, G/m or G/h) and press to select and press again to confirm, (or to cancel) Pulse Value decimals, select how many decimals to use for the pulse value setting, Press or to select how many decimals are used and press to select and press again to confirm, (or to cancel) Total Units, select which SI unit to use Select unit with or (L/s, L/m, L/h, m 3 /s, m 3 /m, m 3 /h G/s, G/m or G/h) and press to select and press again to confirm, (or to cancel) Total decimals, select how many decimals to use for the totalizers in the display. Press or to select how many decimals are used and press to select and press again to confirm, (or to cancel) Damping time, for display & output Move cursor with and change value with or and press to select and press again to confirm, (or to cancel). 3.2.2 System settings Press to enter the menu, press to select System, press to enter the basic settings menu. Signal Pulse Output Total Set Load Settings Signal Pulse Output Total Set Load Settings Signal settings, Q max (full scale value), low flow cut off (%), Direction and indication Pulse output settings, maximum frequency (Hz), Liters/pulse, Pulse width and pulse level Clear totalizers, or preset totalizers. Load factory default settings, Press or to change from YES or NO, press to select and press again to confirm, (or to cancel). Page 14

3.2.2.1 Signal settings Press to enter the menu, press to select System, press to enter Signal settings menu. Qmax (m3/h) Low Cutoff% Direction Indication Qmax (m3/h) Low Cutoff% Direction Indication Q max, full scale value, 20mA current flow value. The maximum and minimum value are bound to the flowmeter diameter size. Move cursor with and change value with or and press to select and press again to confirm, (or to cancel). Low flow cut off, Fill at what percentage of the Qmax the flowmeter should keep the flow at 0. Move cursor with and change value with or and press to select and press again to confirm, (or to cancel). Flow direction, choose flow direction. Press or to select Fwd. (forward) or Rev. (reverse) press to select and press again to confirm, (or to cancel) Flow indication, select which direction to display Press or to select Forward or Reverse, press to select and press again to confirm, (or to cancel) 3.2.2.2Pulse Output settings Press to enter the menu, press to select System, press to select Pulse Output, press to enter the Pulse Output settings menu. Freq Max (hz) Liter/Pulse PulseWidth(ms) Pulse Level Freq Max (Hz) Liter/Pulse PulseWidth(ms) Pulse Level Maximum pulse frequency, fill in the maximum pulse frequency Move cursor with and change value with or and press to select and press again to confirm, (or to cancel). Liter / Pulse value, enter the desired volume per pulse measured by the flowmeter. Move cursor with and change value with or and press to select and press again to confirm, (or to cancel). Pulse Width, enter how long the pulse output remains active when active. Move cursor with and change value with or and press to select and press again to confirm, (or to cancel). Pulse Level Press or to Active H or active L or Rev. (reverse) press to select and press again to confirm, (or to cancel) Page 15

3.2.2.3 Totalizer settings Press to enter the menu, press to select System, press 2x to select Total Set, press to enter the Totalizer settings menu. Clear Total FWD Preset (m3) REV Preset (m3) Clear Total FWD Preset (m3) REV Preset (m3) Clear Totalizer, clear the totalizer Press or to No or Yes, press to select and press again to confirm, (or to cancel) Forward Preset, enter a value to change the forward totalizer. Move cursor with and change value with or and press to select and press again to confirm, (or to cancel). Reverse Preset, enter a value to change the reverse totalizer. Move cursor with and change value with or and press to select and press again to confirm, (or to cancel). Zero Trim Tube Trim Loop Trim K Character 3.2.3 Calibration settings Press to enter the menu, press to select System, press 3x to select Calibration, press to enter the Pulse Output settings menu. Before Zero Trim, the flowmeter sensor tube needs to be filled with medium and be in quiescent state. The flowmeter needs to be powered for more than 15 minutes (warm-up time). Zero Trim Fast Calibration method, to correct the flow measurement. Press or to select Yes press to select and press again to confirm, (or to cancel) Tube Trim Tube Trim manual calibration method, trim empty pie, full pipe & Tube region-%. Loop Trim Loop trim, adjust the 4-20mA output signal, for 4mA and 20mA K Character Don t change keep on 1.00000 Page 16