RISK MANAGEMENT IN A LOW VOLTAGE NETWORK ON SAFETY ISSUES FROM ASSET MANAGEMENT PERSPECTIVE

Similar documents
ENSURING PUBLIC SAFETY THROUGH PROPER EARTHING IN LOW VOLTAGE NETWORKS

IMPLEMENTING A SYSTEMATIC APPROACH TOWARDS SOLVING POWER QUALITY COMPLAINTS FROM A NETWORK OPERATOR S PERSPECTIVE

TN, TT & IT Earthing Arrangements

Industrial and Commercial Power Systems Topic 7 EARTHING

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING

HV Substation Earthing Design for Mines

Education & Training

Earthing of Electrical Devices and Safety

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Product Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016.

LIMITING THE DANGER OF ELECTRIC CURRENT SHOCK IN RELATION TO THE MEAN OF NEUTRAL POINT EARTHING IN THE MV NETWORKS

Residual Current Operated Circuit-Breakers (RCCBs)

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

2394 EXAM PAPER. 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation

FAQ ON EARTHING STANDARDS 16/08/2018

The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08

Protection of Electrical Networks. Christophe Prévé

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

2 Grounding of power supply system neutral

Arc Flash Analysis Training

Busbars and lines are important elements

Earthing Guidance Notes

Harmonic Distortion Levels Measured at The Enmax Substations

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

Grounding for Power Quality

Les Hampson Cert Ed FSCTE, Chairman CAI Technical Committee

EDS LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Power Systems Modelling and Fault Analysis

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

How to maximize reliability using an alternative distribution system for critical loads

UNBALANCED CURRENT BASED TARRIF

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

ELECTRICAL POWER ENGINEERING

TS RES - OUTSTANDING ISSUES

COUPLING DECOUPLING NETWORK MODEL CDN-AF4

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

7P Series - Surge Protection Device (SPD) Features 7P P P

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

EPG. by Chris C. Kleronomos

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

LV DC DISTRIBUTION NETWORK WITH DISTRIBUTED ENERGY RESOURCES: ANALYSIS OF POSSIBLE STRUCTURES

Adaptive Relaying of Radial Distribution system with Distributed Generation

DC utilization of existing LVAC distribution cables

Fatima Michael college of Engineering and Technology

CP CU1. Coupling unit for line and ground testing

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

Totally Integrated Power SIVACON 8PS LDM busbar trunking system siemens.com/ldm-system

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

Variation in SFRA plot due to design and external parameter

ECE 528 Understanding Power Quality

IMP/007/011 - Code of Practice for the Application of Lightning Protection

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

De allereerste foto van licht als golf én als deeltje (bron: engineersonline.nl ) De foto van licht dat is ingesloten op een nanodraad toont

CONTENTS. 1. Introduction Generating Stations 9 40

Distance Protection for Distribution Feeders. Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng.

NOTE: This paper relates to a closed book exam & therefore candidates should attempt this exam paper with no study-notes or text books.

Hamdy Faramawy Senior Application Specialist ABB Sweden

Residual Current Operated Circuit-Breakers (RCCBs)

GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Chapter B Connection to the MV utility distribution network

ACCURATE SIMULATION OF AC INTERFERENCE CAUSED BY ELECTRICAL POWER LINES: A PARAMETRIC ANALYSIS

Why the IT system is often the best choice for power supply systems of all types

Distribution systems and protection against indirect contact and earth fault

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

Caution - leakage currents! Leakage currents in fault-current protected environments

IP Transport Communications for Power Stations and Other High-Reliability Locations- Challenges and Protection

ESB National Grid Transmission Planning Criteria

Ground Fault Protection

Options to Improve the MEN System into the 21 st Century

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES

Safety earthing. Sector Energy PTI NC. Copyright Siemens AG All rights reserved. Theodor Connor

MAJOR ADVANCES IN MV/LV SUBSTATIONS. Th.Grima et JF.Faltermeier. Groupe CAHORS, France SUMMARY

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

RAPTOR Step and Touch Function

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions

Specialists in HV and MV test and diagnostics. Testing in Substations

G. KOEPPL Koeppl Power Experts Switzerland

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit.

Agenda. Earthing of Telecom Installations using Single Point Earthing. Reference Documents. How many earths? Earthing Issue...

IEEE sion/1547revision_index.html

Back to the Basics Current Transformer (CT) Testing

Calculating AC Line Voltage Drop for S230 Microinverters with Engage Cables

AC Motor Drives EMC Standard Installation Guide EMC Compliance Practice

ELF ELECTRIC AND MAGNETIC FIELDS MEASUREMENTS IN GREECE

3.7 Grounding Design for EAST Superconducting Tokamak

kv AC substation

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

INCREASING NETWORK CAPACITY BY OPTIMISING VOLTAGE REGULATION ON MEDIUM AND LOW VOLTAGE FEEDERS

Earthing for EMC in Installations

Electrical Description

EPR Fundamentals of Calculation of Earth Potential Rise in the Underground Power Distribution Cable Network by Ashok K.

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

The Confusion Surrounding Stray Voltage

Transcription:

RISK MANAGEMENT IN A LOW VOLTAGE NETWORK ON SAFETY ISSUES FROM ASSET MANAGEMENT PERSPECTIVE Sharmistha BHATTACHARYYA Endinet The Netherlands sharmirb@yahoo.com Thijs van DAEL Endinet The Netherlands thijs.van.dael@endinet.nl ABSTRACT The Dutch national regulators ACM ( Autoriteit Consument & Markt in Dutch) have recently announced their visions to various regional network operators in the Netherlands about the minimum safety requirements of public networks. Absence of proper earthing can arise dangerous unsafe situation in the public network or at a customer s installation. In this paper, first a brief summary is given on the recent happenings of national level activities regarding standardization works on electrical network safety needs. Further, different types of low voltage (LV) network configurations in the Netherlands are discussed. Some of them provide better safety during short circuit conditions than the other types. A part of Endinet s LV network is simulated using simulation tool Gaia and the probable areas where risks on safety issues can arise are discussed. As a distribution network operator, Endinet is obliged to guarantee electrical network s safety for its service and operation to the public and associated users. INTRODUCTION The ACM has asked the network operators in the Netherlands to become more transparent about their supply voltage quality, performance and on safety issues of their networks. Also, ACM has recently announced his visions about electrical safety needs for networks, both for old and new networks. In this paper, ACM s vision on safety is discussed briefly. Further, typical earthing configurations of the Dutch LV networks are discussed in this paper. Endinet owns medium voltage (MV) and low voltage (LV) networks in Eindhoven and provides electricity to more than 110.000 customers. Endinet is also obliged to provide reliable and safe electric supply to its customers. Every network operator should provide reliable, safe and good quality electricity to their customers. For safe operation of an electricity network, it is important to ensure proper earthing of its network components. In the Netherlands, the electricity distribution network is mainly fed by underground cables. In the last years, an increasing trend of stealing of copper conductors from the network cables /earth conductors has made the network operators concerned about the vulnerability of their electricity networks to safety issues. Also, maintenance works and digging activities of different facility services (such as water supply, telecom services, etc.) sometimes damage the network cables and earthing system. This affects the safety requirements of the electricity network, potentially leading to unsafe or life-threatening situations. When short circuit occurs in the network, a fault voltage appears in each part of the interconnecting regions. From a safety point of view, it is important to know the touch voltage at an exposed conductive part during an earth fault condition. However, the touch voltage at a node point does not have a unique value. It varies depending on the touching conditions such as people s body weight/ resistance, touching with one or two hands, standing on a dry or a wet surface, with or without shoes, etc. Under a fault condition, an installation located close to a MV/LV substation experiences high fault current which is generally protected by a fuse present in the feeder. However, when a short circuit occurs at a distant point from the source, fault current will be low and therefore the fuse may not operate in time. In that case, fault voltage can still be high because of large feeder impedance. Therefore, there will be a risk for customer or maintenance personnel as they may get an electric shock. The safety regulation for the Dutch LV network specifies to limit the fault voltage within 66V or to restrict the fault clearance time within 5s [1,3], as shown in Fig. 1. Fig. 1: Risk management regulation in Dutch networks To verify Endinet s network s present safety performance, simulations are done using Gaia software tool (developed by Phase to Phase, the Netherlands). A part of Endinet s LV network is simulated to find out fault voltages at various critical nodes of the network. Fault voltages and fault clearing time at different parts of LV networks are found and are compared with the stipulated values mentioned above. This analysis helps to identify relatively unsafe regions of the network and improves asset management activities. CIRED 2015 1/5

THE DUTCH REGULATORS VISION ON NETWORK SAFETY In the recent years, the Dutch regulator ACM is showing more concern about public network safety requirements. The electricity law of the Netherlands (Elektriciteitswet 1998, article 16, section 1b) [2] states about various duties of the network operator regarding their services. One of the most important responsibilities of a network operator is to provide electricity to the customers in a safe way, without endangering any part of public property. The Dutch regulatory body ACM expects that the network operator should fulfil at least some minimum safety requirements for designing and operating their networks. A proper technical standard needs to be developed, stating clearly all the safety requirements in the LV grid. This standard needs to be developed within a year time from the date of approval of the agreement between the regulator and the network operators. After it is developed, the network operators should be obliged to follow these minimum requirement standard. If asked by ACM, the network operators should be in a position to prove that each part of their network meets the standard. Another point which is under discussion is to define and distinguish between a so-called old network and a new network. At present the Dutch network operators follow the guidelines that were developed in 1993 by the work group of distribution network operators from EnergieNed [3]. In the last period, many changes and developments have occurred regarding materials and configurations of the network components. The network operators claim that the new networks have better performance and safety measures than the old networks. However, many of the old networks are still working efficiently and unsafe incidents are seldom registered recorded. They have an opinion that these two generations networks should not be compared and different types of requirements should be applied. ACM has agreed to this point and has asked the network operators to develop the standards for both those types of networks. However, the minimum standard condition is applied for both the cases. ACM has also made a statement that when an existing network does not perform good as per the standard requirements, the network should be modified accordingly so that it can cope up with the minimum safety needs. It is understandable that sometimes the network modification cost is quite high and is not justified from the optimum social cost point of view. Ultimately, all the investments made for the betterment of networks have to be paid back by the customers (as charging higher electricity tariff). In this case, network operators should be absolutely transparent and should be able to justify their arguments about not doing those investments. The network operator should choose an alternative option that is the most suitable under that situation. During this year the network operators and ACM should make a joint agreement regarding various measures to establish the (minimum) safety standard and differentiate the safety needs for an old and a new network. Furthermore, in the coming years, the standard guidelines should be followed and implemented in their networks. TYPES OF EARTHING SYSTEMS All points that generate electricity or changes system voltage must be earthed. Two types of earthing are used at customer s installations: Protective earthing for persons and equipments against electric shock. The purpose of this earthing is to provide a low impedance path to ground during a fault condition, to eliminate step & touch voltage rise and to provide a stable reference voltage. This system must be bounded at some points to the functional earthing system. Functional earthing is used for interference suppression. It is designed mainly to provide a low impedance path to earth for high frequency leakage currents and noise caused by switching and lightning protection. In an installation, there are usually several parallel paths that are connected to earth points. The most common types of earthing system used in the Netherlands for LV public networks are: a) TT-earthed system (Terra-Terra, where the installation is earthed at customer s location), b) TN earthed system (Terra- Neutral, where the network operator provides the earthing as a service via the network). TN system can also be subcategorized in two types: 1) TN-C (combined system, where neutral & protective earth conductors are coupled together), 2) TN-S (separate system, in which neutral conductor and protective earth are separated). Besides these earthing systems, there is another one which is called IT system. It is theoretically an unearthed system, but is connected to the earth by stray capacitance of the network and / or by high impedance. However, the frame at load side is always connected to the earth. Different types of earthing systems are shown in Fig. 2 [4]. a) TN-C system b) TN-S system c) TT system d) IT system Fig. 2: Various earthing methods used in LV networks CIRED 2015 2/5

Endinet has a TN earthing system (both TN-S and TN-C types) for the LV networks. Mainly two types earthing configurations are used: a) an isolated earth-conductor or equivalent (such as water pipelines) that runs parallel to the main cable; b) a neutral conductor of the main cable that serves the purpose of earthing too (called as PEN conductor ). Both these two systems have their own advantages & disadvantages. In a TN-S system, an extra investment is needed for a separate earth conductor. However, it is also a risk that this separate earth conductor might be stolen, as indicated in the beginning of this paper In return, it provides extra protection during fault condition. As the neutral & protective earth (PE) conductors are coupled at several points in the network, it provides also a path for (unbalanced) current to return to the source under normal situation, when neutral conductor is broken. In a TN-C system, as there is no separate earth conductor, it can have relatively higher risk to safety issues when neutral conductor is damaged or broken (during ground digging activity). A survey inside Endinet s service area shows that the customers prefer to have TN-S system as they get the possibility to connect their installation s earthing to the network s PE conductor for enhancing their installation s safety. FAULT AND TOUCH VOLTAGES When a short circuit occurs between a single-phase and the earth connection of an electrical installation, a voltage difference originates between the local earth conductor and the far-off ground. The voltage appears at the fault point is called as fault voltage and is calculated by estimating the fault current (I F ) and the fault impedance (Z F ) at the point. Fault impedance is the impedance of the faulted phase conductor (Z phase ) up to the fault point from the source and the retour path (Z retour ), which includes the impedance of neutral and PE conductors in parallel, where applicable. Under this fault condition, a part of the fault current (I F ) can flow through the body of a person who is touching a grounded piece of an equipment connected to the same network, as shown in Fig. 3. This body current (I B ) causes a rise of voltage between the hand and leg of the person, touching the ground. This is called as touch voltage (U B ). It means that a part of fault voltage will appear as touch voltage to the person, depending on his body resistance (Z Body ), resistance of his shoes (Z Shoe ) that he is wearing and the ground resistance (Z ground ) on which he is standing. The following equations are used to calculate fault voltage (U F ) and body current (I B ) when is touched at the faulted part in the network. I = U / Z F nom F (1) Z = Z + Z F retour phase (2) U = Z * I F retour F (3) I B = U F / (Z Body +Z Shoe +Z ground ) (4) The magnitude of fault current determines the maximum time that a fault condition may continue at that point before the protective fuse can clear it. The standard IEC 60479-1 [5] gives various allowable time for various currents that a human body can tolerate. Fig. 4 gives an indication of the consequences of the amount of currents that can cause various effects on a human body [6]. The curve C1 defines the time-current limit of exposition to an electric shock, which must not be exceeded. Fig. 3: Fault in a TN-S system [6] Fig. 4: Various effects on different body current limits The touch voltage can change significantly depending on the person s body impedance and the surface on which the person is standing. Also, the touching condition defines the amount of tolerable touch voltage. For example, body resistance will be halved when a person touches by two hands on a faulted object than touch by one hand. Normal body resistance is taken as 1300 ohm, and shoe resistance as 500 ohm and ground resistance as zero. These values are used in the simulation of this paper. With the above values of resistance, 37mA body current will cause 66V touch voltage across one hand and feet of the person, touching the faulted object. The values for fault voltage and fault impedance calculated in this section are used as minimum standard safety guidelines for the operation of old as well as new networks in Endinet s service area. ENDINET S LV GRID FOR SIMULATION A part of Endinet s LV network is simulated using software tool Gaia. It has TN-C configuration, therefore neutral conductor serves the purpose of earth conductor too. Only cable junctions and terminals of cable parts are connected by earth conductor as shown in Fig. 5 [7]. CIRED 2015 3/5

Endinet has a mesh connected LV network which means that almost every customer gets supply from two feeding transformers, except some customers who are located in an extended or radial part of a main cable. Every LV feeder is protected by fuse at both ends of the LV distribution box. Z retour / (Z phase + Z retour ) = 0,28. Z phase = 2,57 Z retour or, Z retour 0,39 Z phase (6) By using equations (5) and (6), the maximum value for phase impedance of LV cable is found as 0,165 ohm. The LV cable is of 4x95mm 2 AL conductor which has an impedance of (0,32+j0,082) ohm/km. Hereby, the maximum length of cable is theoretically 500m. This information is needed in the simulation to check if a node point is located in the safe region of Fig. 7 [7]. Fig. 5: Endinet s typical LV cable in TN-C system All the distribution boxes and transformer stations are earthed via the PEN conductor with a resistance of 0,2 ohm (maximum). Also, all the outgoing feeders of the simulated network are protected by fuse of rating 200A. A typical current-response time characteristic for a 200A fuse is shown in Fig. 6. It can be noticed that the fuse will allow 1000A fault current to flow through the feeder for 5s time. This maximum fault current can be bit different for fuses from different manufacturers. Fig. 6: Jean-Muller 200A fuse [6] As found from Fig 6 that maximum of 1000A fault current is allowed to flow through a LV outgoing cable. Therefore, the maximum fault impedance (Z F ) of the circuit is (230/1000 =) 0,23 ohm per phase, when nominal voltage (U nom ) is 230V. Z F = Z phase + Z retour = 0,23 ohm (5) From equations (1) and (3), it is possible to define the relation between phase impedance (Z phase ) and retour impedance (Z retour ). Fault voltage (U F ) at a node point is to be restricted to 66V for safe operation and the fault current (through a human body) should be restricted to 37mA (continuous) for an average person wearing shoe (assuming Z Body +Z Shoe +Z ground = 1800 ohm). Therefore, the following can be calculated using equations (1) to (3): U F = (U nom * Z retour )/ (Z F ), Therefore, [Z retour / Z F ] max = 66/230 = 0,28 Fig. 7: Risk management criteria for Endinet s network As per design rules, most of the main LV cable length in Endinet s service area is restricted to 300m, while the maximum length of a connection cable is 25m. However, to increase the reliability of electrical service to the customers, some distribution boxes are connected by long cables that are fed from different transformers. Endinet follows the philosophy of Fig. 7 to define the risk zone of the LV network. The fuses in an outgoing LV feeder are generally selective while responding to a fault in a LV cable. The connection cables are tapped out from a main LV cable at a cable joint and provides electricity to the customers. The protection of these connection cables are generally not covered by the fuses. When a fault occurs in a connection cable, it is allowed to burn until the cable connection point. In such cases, the service provider of Endinet will repair the burnt cable with a new one. In this way, power outage to that cable is restricted to that specific customer only, not for the other customers connected to the same cable. The network simulation is done for a LV network which has more than 2000 connection points to various household customers and are fed from 9 numbers MV/LV transformers. These transformers are connected together in a ring configuration by a MV cable in the network. The short circuit capacity at the beginning of the MV network is 100MVA (=5.7kA), which can be considered as a relatively strong grid. From the simulation, it is found that majority of the network node points are located in region A of Fig. 7. This region falls under the safest zone of the graph. If the cable length is more than 300m, it is needed that the fault voltage at various points should remain within 66V. CIRED 2015 4/5

The fuse of that specific feeder will mostly not react to that fault and will not be able to clear it with in 5s. Simulations show that approximately 1,6% of the nodes of the simulated network fall in region D of Fig. 7. For those node points, Endinet takes suitable measure (such as placing an extra distribution box with fuse, shortening the cable length, adding extra earth conductor, etc.) to reduce the risk of electric shock. The region B and region C are also accepted as safe zones of operation. At region B, fault voltage is lower than 66V that indicates that the earth retour path is very good at that node point. It helps to keep the fault current lower too that may flow through the body of a person while touching a short circuited object. At region C, the fault voltage is larger than 66V, but the fuse of the cable clears the fault within 5s time. The current during touch condition is also lower than the permissible value. In the simulation tool, every node point is checked to see that the fault voltage, current, fault clearing time, etc. are within the limits discussed in this paper. From simulation, it can be concluded that approximately 5% (among them 1,6% nodes fall in region D and 3,4% in region E) of the node points of the considered network does not fall under the defined safe regions (of A, B, C of Fig. 7). According to the definition of the document [1], region E is also called as safe zone of operation. However, Endinet does not want to take any risk and therefore try to mitigate risk by implementing proper measures for those points too that fall in region E. CONCLUSION In this paper a brief overview is given about the Dutch regulator ACM s vision on low voltage network safety issues. ACM has asked the network operators to develop a minimum standard for safety requirements for all types of network. Also, a proper distinction should be made between a new and old networks and their individual type s safety requirements. If an existing network does not fulfil the standard requirements, the network operator should take proper measure to improve it. However, the optimum choice has to be made by considering the minimum social costs. In all situations, ACM wants the network operators to continue their services in an absolutely transparent manner, and inform their customers about the performance and present condition of their networks openly. In the second part of this paper, various types of earthing systems are discussed. Further the calculation of fault voltage and fault current at a point are described. The safe fault impedance value at a point in a LV network is calculated for Endinet s network. Also, the risk zones are defined where the fault voltage is higher than 66V and the fault clearance time is larger than 5s. Endinet identifies also another region where the fault current passing through a human body may exceed the permissible value. After doing the simulation of a typical LV network of Endinet that has a TN-C earthing system, it is found that most of the node points are fulfilling the safety criteria of fault voltage lower than 66V or fault clearance time lower than 5s. However, approximately 5% node points violate the above conditions because of relatively larger cable length or other reasons such as missing or improper earth conductor connections, or broken PEN conductor. Endinet has a meshed LV network and generally at all end terminals earth conductors are placed and are connected to nearest joints. All LV distribution boxes and transformer stations are also grounded by an earth electrode that has a resistance of lower than 0,2 ohm. Therefore, the LV network is earthed at several points in the network and should have a lower retour impedance. However, when those connections are weak or broken, the earth retour resistance can be higher than the permissible value. Endinet takes necessary measures to improve the safety needs of those points. This type of analysis helps the asset management activities immensely and help Endinet to improve new network s design concepts and also existing network s operation conditions. REFERENCES [1] TIS 10-202a, N11-37a: Veiligheidbepalingen voor nieuwe LS-distributienetten en een minimaal veiligheidsniveau voor bestaande netten, a document proposed by the network operators in the Netherlands, December 2010. (available in Dutch language only) [2] Dutch Grid Code Legislation: Netcode Elektriciteit per 17 december 2009, DTE (Dutch office for Energy Regulation), 2009, (available in Dutch language only). [3] Work group members of EnergieNed (responsible for providing electricity service in distribution network), Aanbevelingen voor distributienetten in verband met het aanbieden van een aardingsvoorziening, Techn 93-945, June 1993. (available in Dutch language only). [4] Schneider Electric document, Earthing systems- Industrial electrical network design guide, T&D, ref.: 6883 427/AE, downloaded from Schneider electric website. (December 2014) [5] IEC 60479-2:1987 standard, Effects of current passing through the human body, IEC standard, 1987. [6] Gaia handbook 6.3, Phase to Phase, 2011. (website: http://www.phasetophase.nl/en_products/vision_lv_n etwork_design.html) [7] Endinet s internal investigation document on network s earthing, Rapport- Aardingsonderzoek, author: S. Bhattacharyya, April 2013. CIRED 2015 5/5