SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section

Similar documents
TABLE OF CONTENTS. 1.0 Scope. 2.0 References. 3.0 Definitions. 4.0 Submission and Design Requirements. 5.0 Materials 5.1 General 5.

SIG-032-B TRAFFIC SIGNAL MAST ARM POLE AND MAST ARM DETAILS - CATEGORY III LUMINAIRE ARM (SEE CONTRACT) 6'-0", 8'-0", 10'-0" NOMINAL SPREAD

SIG-030-B TRAFFIC SIGNAL MAST ARM POLE AND MAST ARM DETAILS - CATEGORY I LUMINAIRE ARM 6'-0", 8'-0", 10'-0" NOMINAL SPREAD (SEE CONTRACT) POLE CAP

SECTION METAL FABRICATIONS

Bol FEATURES: SPECIFICATIONS: 8' 24' Round Tapered and Straight Wood Poles STRUCTURA INC. FIXTURE TYPE: PROJECT NAME:

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

1. ANSI/ASME Standard B , Square and Hex Bolts and Screws, Inch Series

SECTION TRAFFIC SIGNAGE

ROUND STEEL POLE STRAIGHT

SECTION STRUCTURAL STEEL. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

1.1 RELATED DOCUMENTS

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

Section COUPLINGS AND COUPLING ADAPTERS. This Section covers couplings and coupling adapters for ductile iron and steel pipe.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

EMMEGI ARCHITECTURAL FENCING MASTER SPECIFICATION SECTION METAL FENCING, GATES & RAILING SYSTEM PART 1 GENERAL

SECTION 58 PRECAST CONCRETE BOX CULVERT. This work consists of furnishing and installing Pre-cast Concrete Box Culverts.

SECTION CHAIN LINK FENCING AND GATES

SQUARE STEEL POLE STRAIGHT

PART MATERIALS. Section Fencing Materials. Description

STEEL PIPE GUIDERAIL 01/01/

Standard Specifications

ALUMINUM PIPE GUIDERAIL 01/01/

TENANT IMPROVEMENT 16 FEBRUARY WEST 27TH STREET, 4TH FLOOR 100% CD OWNER/BID ADD 1-03/08/2018

APPENDIX FENCE GENERAL NOTES

SECTION STRUCTURAL STEEL FRAMING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SPECIAL SPECIFICATION LIGHTNING PROTECTION SYSTEM

D. Thermally Sprayed Metallic Coating (Flame Spray): STD SPEC

SECTION CABLE TRAYS

A. Deviation from this standard must be approved by the Project Architect.

SECTION HELICAL PILES AND HELICAL ANCHORS

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1.

DOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410

Project: # Solano Community College District

TYPE J (20 FT - 40 FT) MICHIGAN DEPARTMENT OF TRANSPORTATION 10-0" 7-6" NOTE: sheet 5 & 6 of 10) DEPARTMENT DIRECTOR. Kirk T.

Item 550 Chain Link Fence

SECTION BULLET- RESISTANT DOORS

1.1 SUMMARY. A. This Section includes the following: 1. Loose steel lintels. 2. Shelf angles. 3. Metal floor plate. 4. Pipe bollards.

Procedure for Testing Direct Tension Indicators (DTI) Assemblies

SPECIFICATIONS FOR THE MANUFACTURE AND DESIGN OF PRECAST THREE SIDED ARCH STRUCTURES, WINGWALLS AND HEADWALLS

TECHNICAL CORRECTION October Process Industry Practices Structural. PIP STF05121 Fabrication and Installation of Anchor Bolts

MEDIUM DUTY CAST IRON SLIDE GATES SERIES 20-10C

Testing. Material testing will be according to applicable AASHTO, ASTM or Department methods as specified.

SECTION CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP

CITY OF PITTSBURG ENGINEERING DEPARTMENT CONTRACT NO A WATER TREATEMENT PLANT CAPITAL IMPROVEMENTS PHASE 1A ADDENDUM #1 FENCE AND DITCH AUGUST

Collins Engineers Palmetto Islands County Park Boardwalk Repairs 03/28/2014 SECTION ROUGH CARPENTRY

6o ft (18.3 m) Southwest Windpower, Inc West Route 66 Flagstaff, Arizona USA Phone: Fax:

SECTION SITE FURNISHINGS FOR CFCRT. 1. American Society for Testing and Materials (ASTM).

BRIDGE RAILING, 4 TUBE B-26-F POST DETAILS MICHIGAN DEPARTMENT OF TRANSPORTATION

SECTION CABLE TRAYS FOR ELECTRONIC SAFETY AND SECURITY

A. Extent of structural precast concrete work is shown on drawings and in schedules.

COMMERCIAL ITEM DESCRIPTION RODS, GROUND (WITH ATTACHMENTS)

SECTION CHAIN LINK FENCING

SECTION PRECAST CONCRETE STRUCTURES

SECTION FUEL OIL SYSTEM (PLUMBING)

Foundation Specifications for 5.6-Meter Modular Earth Station Antennas

HSAF Era Stepped Aluminum Fluted Pole revision 10/6/15 kl_hasf_spec.pdf

Attachment of Residential Deck Ledger to Side of Metal Plate Connected Wood Truss Floor Ladder. Installation Instructions Revised 9/2/2016

Foundation Specifications for 7.6-Meter Modular Earth Station Antennas

SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

STRUCTURAL STEEL AND ALUMINUM PART 1 - GENERAL 1.01 SCOPE:

Square Straight Steel - 4 Bolt Base Light Poles

AMPCO PRODUCTS, INC. TECHNICAL SPECIFICATIONS SOLID PHENOLIC CORE TOILET COMPARTMENTS

5/16" Flange nut. Bolt Keeper Plate (8" Sq. SYS.) (3) 1/2" x 3" Hex head connector zinc plated bolt w/ washers and nut. Anchor 3" sq. 7 Ga.

ESR-2024* Reissued September 1, 2011 This report is subject to renewal September 1, 2013.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Product Guide Specification

SECTION PANELBOARDS

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT

SIGNALS AND LIGHTING FIELD GUIDE

(50 FT FT) MICHIGAN DEPARTMENT OF TRANSPORTATION 10-0" 7-6" 8-0" 6-0" Truss Depth. 3" sheets 5 & 6 of 10) DEPARTMENT DIRECTOR. Kirk T.

CHAPTER 10 MICHIGAN DESIGN MANUAL BRIDGE DESIGN (SI) SHOP DRAWING REVIEW TYPES OF SHOP DRAWINGS Structural Steel

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Section 914. JOINT AND WATERPROOFING MATERIALS

LOW PRESSURE STEEL DUCTWORK Mechanical Systems Insulation Outlets (HVAC) Testing and Balancing.

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

FUEL GAS PIPING SECTION A. The provisions of SECTION 15010, MECHANICAL GENERAL REQUIREMENTS, apply to this section.

Structural Bolting. Notice the Grade 5 has a much smaller head configuration and a shorter shank then the grade A325 structural bolt.

1. Show the following information with additional information necessary to indicate shop compliance with the requirements of this section.

DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS

ESR-2648 Reissued May 1, 2012 This report is subject to renewal June 1, 2013.

Versai Evolution of Versatile Fencing

BUILDING PLANS. BUILDING INSPECTIONS DEPARTMENT

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.

Special Provision No. 999F29 March 2018 REQUIREMENTS FOR INSTALLATION OF METALLIC DOWELS INTO CONCRETE

Heckmann Building Products Inc. DOVETAIL SLOT AND ANCHORS SPECIFICATION SECTION MASONRY ANCHORS AND ACCESSORIES PART 1 GENERAL

SURFACE FINISH. A galvanized finish is MnDOT s standard on new traffic control signal poles, mast arms, transformer bases, and luminaire extensions.

Section 808. FENCING

Tenons Adaptors

INSTRUMENT MOUNTING STANDS PRODUCT CATALOG Continuous Tray Support System for Instrumentation and Controls

2016 Specification Treads, Base, Stringers and other Amenities Wausau Tile Precast Epoxy Terrazzo

The Manitoba Water Services Board SECTION Standard Construction Specifications September 2013 Page 1 of 8

OHIO DEPARTMENT OF TRANSPORTATION CENTRAL OFFICE, 1980 W. BROAD ST., COLUMBUS, OHIO

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

SPECIFICATION: ALUMINUM SLIDE GATES

SHEET METAL FLASHING AND TRIM Christ on the Mountain

ADDENDUM NO. 1 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO.

WADE 2-1. Universal Carrier. Exclusive Features of 400 Series Universal Carrier for Lavatories, Urinals, Drinking Fountains.

SIGN STRUCTURE BOLT TESTING AND INSPECTION! WHAT HAVE WE FOUND AND WHAT ARE WE DOING

DIVISION 12 - FURNISHINGS. Section General Discussion. Introduction

Transcription:

02760-1 of 5 SECTION 02760 STEEL LIGHTING STANDARDS 02760.01 GENERAL A. Description Steel lighting standards shall include, but not necessarily be limited to, furnishing and installing steel lighting poles, bracket arms, and reinforced concrete foundations as shown and detailed on the Plans and in accordance with the Contract Documents or as directed by the Engineer. B. Related Work Included Elsewhere 1. Electrical conduit and fittings; Section 02731. 2. Concrete foundations; Section 02734. 3. Luminaries; Section 02762. C. Quality Assurance 1. General 2. Tests D. Submittals The Engineer will inspect all materials and work to ensure compliance with the Contract Documents. In addition to the requirements specified in Section 05100.01, all 100% welds shall be ultrasonic tested, all other welds may be either visual or magnetic particle inspected as determined by the Engineer. 1. Shop Drawings Shop drawings shall be submitted as specified in the "General Provisions" for all steel lighting standards. The shop drawings shall show the overall dimensions of the poles, details of construction, and include bolt circle data. 2. Certificates of Compliance Certificates of compliance shall be submitted as specified in the "General Provisions" for all steel lighting standards stating that the lighting standards meet the NEMA test requirements specified in Section 02760.03.

STEEL LIGHTING STANDARDS 02760-2 of 5 3. Design Computations The Contractor shall submit complete pole wing loading calculations based on the following: a. P = 0.0025 (V) 2 b. gust factor = 30% c. height coefficient = 0.79 02760.02 MATERIALS A. Materials Furnished by the County The County will not furnish any materials for steel lighting standards. B. Contractor's Options Not applicable. C. Detailed Material Requirements 1. Steel Castings Carbon steel castings shall meet the requirements of ASTM A 27, Grade 65-35. 2. Iron Castings Iron castings shall meet the requirements of ASTM A 48, Class 30B. 3. Galvanization Galvanization shall meet all the requirements of ASTM A 123. 4. Hardware a. Steel Bolts, Nuts, and Washers Machine bolts, drift pin bolts, and similar threaded fasteners shall be mechanically or hot-dip galvanized. The coating shall meet the thickness, adherence, and quality requirements of ASTM A 153.

STEEL LIGHTING STANDARDS 02760-3 of 5 b. Bolts Machine bolts, turn bolts, and drift bolts shall meet the requirements of ASTM A 307. The grade will be specified on the plans or in the "Special Provisions". c. Drift Pins 5. Conduit Bolts used as drift pins shall be made of carbon tool steel having a Rockwell Hardness of C50 to C53 on the shank and C30 to C37 on the head. Conduit shall meet all the requirements of Section 02731.02. 6. Pole Shaft The pole shaft shall meet the requirements of ASTM A 595, Grade A. After forming and welding, the shaft shall have a smooth finish with only one longitudinal and no transverse welds. Poles shall be galvanized meeting the requirements of ASTM A 123 or ASTM A 153. 7. Bracket Arm and Mounting Bracket The bracket arm and mounting bracket shall meet the requirement of ASTM A 531, Schedule 40 and galvanized to meet the requirements of ASTM A 123 or ASTM A 153. 8. Steel Base Plate The base plates shall be fabricated from steel meeting the requirements of ASTM A 588. 02760.03 EXECUTION A. General All fabrication and welding shall be in accordance with Division 5. The overall height dimension shall be achieved by a combination of shop welding and/or telescoping of one section into another. B. Fabrication 1. Poles Poles shaft shall be secured to the foundation by a steel base plate welded to the shaft. The shaft shall telescope the base and be welded by two continuous electric arc

STEEL LIGHTING STANDARDS 02760-4 of 5 welds, with one weld on the inside of the base plate at the end of the shaft and the other weld on the outside of the top of the base plate. 2. Welding a. All traverse welds, those joining one section to another, shall be 100% penetration. b. Longitudinal welds shall have a penetration of 60% except that portion that makes up the slip joint areas, plus 1 foot each side of the traverse welds, shall be 100% penetration. 3. Handhole All poles shall be equipped with a reinforced handhole approximately 6 inches above the base. 4. Grounding Connection A grounding connection capable of receiving a 1/2 inch x 13NC bronze threaded bolt shall be 12 inches above the base. 5. Bracket Arms and Lighting Standards C. Installation The bracket arms shall be secured to the shafts in accordance with the manufacturer's recommendations. Each bracket arm shall be oriented as shown on the Plans. Lighting standards and brackets shall meet the NEMA test requirements for metals. Each lighting standard shall be capable of withstanding a 500 pound transverse load applied 18 inches from the top of the shaft without fracture and with maximum deflection of not ore than 4.0% of shaft length. After removal of the load, the shaft shall have taken a permanent set of not more than 1/2 inch. Each bracket arm when attached to the shaft shall withstand a vertical load of 100 pounds and transverse load of 50 pounds applied to the luminaire end of the bracket arm without fracture or apparent deformation after the load is removed. Lighting standards shall be installed as detailed on the Plans. Each lighting standard when fully assembled shall be installed in such a manner that the shaft shall be vertical. 02760.04 METHOD OF MEASUREMENT Measurement for steel lighting standards with bracket arms and reinforced concrete foundations will be made on a per each assembly basis in each bracket arm length category.

STEEL LIGHTING STANDARDS 02760-5 of 5 02760.05 BASIS OF PAYMENT Payment for steel lighting standards with bracket arms will be made at the price bid per each assembly for the various bracket arm lengths specified, complete in place. The price bid shall include furnishing all materials, labor, equipment, reinforced concrete foundations, including excavation, backfill, conduit elbows, and incidentals necessary to complete this item of work as shown and specified in strict accordance with the Contract Documents.