Relay-assisted commissioning

Similar documents
Verifying Transformer Differential Compensation Settings

Relay-Assisted Commissioning

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Catastrophic Relay Misoperations and Successful Relay Operation

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS

Event Analysis Tutorial

Tom Ernst GE Digital Energy Craig Talbot Minnesota Power

Testing Numerical Transformer Differential Relays

Forward to the Basics: Selected Topics in Distribution Protection

Substation Testing and Commissioning: Power Transformer Through Fault Test

Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications

Generator Protection GENERATOR CONTROL AND PROTECTION

Transformer Protection

Differential Protection Optimal differential protection for phase shifter transformers and special transformers

g GE POWER MANAGEMENT

EASUN REYROLLE LIMITED

Back to the Basics Event Analysis Using Symmetrical Components

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

148 Electric Machines

Considerations and Experiences in Implementing Ground Differential Protection for Transformer Protection at TVA

Tutorial on Symmetrical Components

Solution for Effect of Zero Sequence Currents on Y-Y Transformer Differential Protection

System Protection and Control Subcommittee

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

Transformer Fault Analysis Using Event Oscillography

ATP modeling of internal transformer faults for relay performance testing

SIPROTEC 5 Application. SIP5-APN-025-en: 7UT8 Autotransformer bank with 2 sets of CT inside the delta connection of the compensation side

Overcurrent Elements

Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Differential Protection with REF 542plus Feeder Terminal

Distance Relay Response to Transformer Energization: Problems and Solutions

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner

Introduction. Principle of differential relay operation

Protection of a 138/34.5 kv transformer using SEL relay

Negative-Sequence Differential Protection Principles, Sensitivity, and Security

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

IMPROVEMENTS IN PROTECTION AND COMMISSIONING OF DIGITAL TRANSFORMER RELAYS AT MEDIUM VOLTAGE INDUSTRIAL FACILITIES

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

Pinhook 500kV Transformer Neutral CT Saturation

Impedance protection on power transformer.

Modern Protection of Three-Phase and Spare Transformer Banks

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

Power Distribution: Protection Analysis

Electric Circuits II Three-Phase Circuits. Dr. Firas Obeidat

Parallel tap-changer controllers under varying load conditions (Part 1)

Transformers 3: connections

Table of Contents. Introduction... 1

Unit Protection Differential Relays

Rarely used, problems with unbalanced loads.

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Relaying 101. by: Tom Ernst GE Grid Solutions

Hands-On-Relay School 2015 Distribution Event Analysis. Randy Spacek Protection Engineer Manager

Problems connected with Commissioning of Power Transformers

Summary Paper for C IEEE Guide for Application of Digital Line Current Differential Relays Using Digital Communication

ANALYSIS OF A DIFFERENTIAL AND OVERCURRENT OPERATION ON A 345KV HIGH VOLTAGE LINE REACTOR

PROTECTION OF TRANSFORMERS M-3311A TEST PLAN

Directional STANDARDS: Overcurrent Relaying

R Distribution Transformers. Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections. Reference Data

Distance Element Performance Under Conditions of CT Saturation

Transformer Protection Principles

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

POWER SYSTEM II LAB MANUAL

Power systems Protection course

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Harmonic Distortion Evaluations

Transformer Trainer. Electrical Power Systems PSL20. Learning Outcomes. Key Features. Key Specifications

Using a Multiple Analog Input Distance Relay as a DFR

Directional Elements in L-PRO 4000

Beyond the Knee Point: A Practical Guide to CT Saturation

Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS

Optimizing HV Capacitor Bank Design, Protection, and Testing Benton Vandiver III ABB Inc.

Specifications. S&C BankGuard Plus Controls. For Substation Capacitor Banks and Shunt Reactors. Conditions of Sale

Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC)

Automated Phase Identification System for Power Distribution Systems

Thermal Imaging, Power Quality and Harmonics

Performance Analysis of Traditional and Improved Transformer Differential Protective Relays

Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer

The power transformer

In Class Examples (ICE)

Company Directive STANDARD TECHNIQUE: SD1E/2. Technical Requirements for Customer Export Limiting Schemes

EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER

CHAPTER 11. Balanced Three-Phase Circuits

Visualization and Animation of Protective Relay Operation

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

Protecting power transformers from common adverse conditions


EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY

NERC Protection Coordination Webinar Series July 15, Jon Gardell

function block description to the differential protection and restricted earth-fault protection functions for autotransformers

CONTROL OF A FOUR LEG INVERTER FOR UNBALANCED POWER NETWORKS 1

Earth Fault Protection

Using Event Recordings

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

Evaluating the Impact of Increasing System Fault Currents on Protection

Transcription:

Relay-assisted commissioning by Casper Labuschagne and Normann Fischer, Schweitzer Engineering Laboratories (SEL) Power transformer differential relays were among the first protection relays to use digital technology. These new relays offered improvements such as automatic calculation of TAP values, and the use of calculations instead of current transformer (CT) connections. This allows immediate and conclusive confirmation of the correctivness of relay wiring, and the integrity of differential element configuration settings. This paper describes an algorithm that checks for correct CT polarities, consistent CT ratios, and the existence of any crossed phase wiring errors, provided minimum, balanced load current flows. Other algorithms [2, 3] describe systems that test for similar wiring errors, but fail to calculate an alternate vector-group compensation setting if the existing setting is incorrect. The algorithm includes a vector-group compensation calculation. After verifying CT connections, the algorithm calculates the correct CT compensation connections for the particular vector group. Commissioning protection equipment involves verification of physical connections (cabling, wiring, etc.), relay settings, and proper operation of the complete system. To verify the complete system, a number of measurements are taken during injection testing and compared against expected values. Differences in excess of predetermined margins indicate errors, and further tests are performed to determine their cause. The operating current of the current differential element is used to determine whether commissioning errors exist. However, using this as a catchall method can result in ambiguous conclusions. For example, both incorrect CT polarity and a CT connected to the incorrect CT tap result in the presence of operating current which can also exist in an error-free installation [3]. Although numerical relays compensate for most unbalances, TAP compensation can result in operating current. Because standard CT ratios seldom match the full load current of the transformer, relays adjust each phase current to compensate for the mismatch. To determine the adjustment for each phase current, the relay uses either Eqn. 1 or Eqn. 2 to calculate a scaling factor called TAP. (1) (2) Although excessive operating current indicates commissioning errors, it cannot indicate the specific cause of the unbalance, and other measurements are needed to identify this. Table 1 shows the measurement methods used in the algorithm. Measurement quantities The relay uses operating current to select the correct vector group compensation. Because the selection resulting can be applied as a relay setting, all possible ambiguities and error sources must be eliminated. To avoid errors resulting from primary or secondary current injection, at least 250 ma (for a 5 A secondary relay) of balanced-load current is required (approximately 5% of full load) instead of injected current. 250 ma load current is specified, as CT characteristics can var y significantly among phases at low current values. For greater current magnitudes, CTs operate where the CT characteristics are substantially similar to each other, and the secondary currents from the CTs are balanced. It is important to have balanced load current, as symmetrical components are used in some of the tests (see Table 1), and unbalanced load current can distort test results. The value of 250 ma also ensures that relay errors do not obscure proper compensation Error Insufficient load current Two crossed phases CT connected to the incorrect tap Incorrect CT polarity Vector-group compensation selection Measuring method selection. Table 2 shows the various differential current values for each 30 phase shift.with the correct compensation selection on both windings, the differential current is (ideally) zero. With 250 ma secondary current flowing, differential current resulting from a 30 phase error (150 instead of 180, for example) is ± 130 ma which is substantially larger than any relay error, and the relay can make correct compensation selections. Current compensation Current compensation consists of three parts: vector group compensation (phase-angle correction); zero-sequence removal; and scaling (TAP). Vector-group compensation and zero-sequence removal can be achieved either by appropriate CT connections or by mathematical calculations. In numerical relays, actual compensation transformer taps do not exist, and calculations are used to determine TAP (Eqn. 1 or Eqn. 2). E l e c t r o m e c h a n i c a l r e l a y s r e q u i r e delta-connected CTs to compensate for wye-connected power transformer windings, whereas wye-connected CTs generally provide more information. Because numerical relays compensate for input currents mathematically, deltaconnected CTs are no longer necessary. The algorithm this paper describes assumes that all CTs are wye-connected, regardless of the transformer vector group. Current magnitude measurement Negative-sequence current measurement Expected current to measured current magnitude comparison; negative sequence current measurement Angular comparison between a reference phase and all other phases Operating current and phase angle measurement Table 1: Measurement methods to identify various causes of operating current. where: MVA = transformer rating in MVA kv = nominal system line-to-line rated voltage in kv CTR = CT ratio (normalized) If measurements are taken at a transformer tap position that does not correspond with the rated voltage of the network, operating current can be present, although there may be no setting or commissioning errors at the installation. Angular error A-phase HV A-phase LV Differential current No error 250 0 ma 250 180 ma 0,0 0 ma 30 error 250 0 ma 250 150 ma 129,4 75 ma 60 error 250 0 ma 250 120 ma 250,0 60 ma 90 error 250 0 ma 250 90 ma 353,6 45 ma 120 error 250 0 ma 250 60 ma 433,0 30 ma 150 error 250 0 ma 250 30 ma 482,9 15 ma 180 error 250 0 ma 250 0 ma 500 0 ma Table 2. Differential current for 30 phase shifts. energize - Jan/Feb 2009 - Page 35

(6) (7) (8) (9) Fig. 1: Phase shift between HV and LV sides of a YDAB (YNd11) transformer. within the differential zone. All CTs are wyeconnected, and the zero sequence currents must be removed mathematically in the relay. One way is by means of the delta matrices used for phase-angle correction. For a DAB delta, connecting a b, b c, and c a phases forms the delta connection. Of these three groups, consider the I a I b connection. Eqns 6 and 7 express I a and I b in terms of symmetrical components, A-phase being the customary reference. where: α is the alpha operator, i.e., 1 120 Fig. 2: System fault on the Wye-connected winding of a YDAB transformer. Phase-angle compensation Phase angle differences come about when the vector group of one set of power transformer windings differs from the group for another set of power transformer windings. For example, consider the YDAB (YNd11) connection shown in Fig. 1. Taking the A-phase of the HV winding as reference, the a-b delta connection causes the A-phase of the LV winding to differ by 30 with respect to the A-phase HV winding. With electromechanical relays, CTs from wye-connected windings are connected in delta, and CTs from delta-connected windings are connected in wye to compensate for the 30 phase shift. When both HV and LV CTs are wye-connected, CT connections cannot compensate for this 30 phase difference, and the secondary current from the HV winding and the secondary current from the LV winding are phase-shifted by 30. For correct differential operation, it is necessary to correct for the phase shift of wye-delta transformers in the relay software, and the relay software calculates the appropriate delta connection. Eqns. 3-5 show the line current for the YDAB transformer connection. (3) (4) (5) Writing Eqns. 3 to 5 in matrix format, the placeholders for the current vectors are as follows: I ab can be renamed to I ACOMP and the current relationships of the YDAB transformer completed in matrix form as follows :(divide b y to scale the magnitude) In the same manner, delta matrices for transformer vector groups that require integer multiples of 30 phase-shift correction can be formed Zero-sequence elimination Fig. 2 shows a wye-delta transformer with the wye winding grounded. Ground faults on the HV side of the transformer result in current flowing in the wye-connected windings and hence the HV CTs. This current distribution is different in the LV windings. Fault current for ground faults on the HV side circulate in the delta-connected windings, but no zero-sequence current flows in the LV lines or CTs. Because fault current flows in the HV CTs only, the differential protection is unbalanced and can misoperate. Zero-sequence currents must be eliminated from CTs connected to all grounded, wyeconnected windings,or where a grounding transformer is installed on the delta winding Eqn 8 shows the I a I b connection in terms of symmetrical components. From Eqn. 9, we see that the zero sequence currents cancel, and only positive-sequence and negative- sequence currents flow. Although delta connections effectively eliminate zero sequence currents, they also create phase shifts. This phase shift is needed in wye-delta transformers, but not in autotransformers or wye-wye connected transformers, where the HV and LV currents are in phase with each other (or 180 out of phase). Use of a delta connection to remove zero-sequence current introduces an unnecessary 30 phase shift between the HV and LV currents. Numerical relays make it possible to remove zero-sequence currents mathematically. The following calculation is used to remove zero sequence current from the A-phase current: Similarly for the B and C phases: Arranging the results in matrix form yields: energize - Jan/Feb 2009 - Page 36

Matrix 0 is the identity matrix; it does not alter the currents: Adding the even matrices (M2, M4,.. M12, see Appendix 2) brings the total number of available matrices to 13 (including the identity matrix). Even with all CTs connected in wye configuration, there are 13 4 or approximately 30 000 possible matrix combinations for a four-winding installation. With so many combinations, it is easy to make an error in selecting the correct matrix combination. The following discussion describes an algorithm that automatically selects the correct matrices. Automatic vector-group selection Overview Fig. 3 shows a typical two-winding transformer installation. Both HV CTs (CT2) and LV CTs (CT3) are wye connected. The differential protection obtains three phase current inputs from current transformers CT2 and CT3. There are three restraint differential elements inside the differential relay, one element per phase; each calculates operate current (IOP1 through IOP3) and restraint current (IRT1 through IRT3). The vector-group selection algorithm reverses the process usually followed, where the setting engineer selects relay settings and the commissioning engineer takes suitable measurements to verify their correctness. With the vector- group selection algorithm, first do the measurement, then select the relay settings. The algorithm is in two parts: one that checks for correct CT wiring (single contingency, balanced conditions) and the other that calculates vector group compensation, two windings at a time. Both parts require that 250 ma balanced, load current flows through the transformer. Part I: CT checks The algorithm checks for correct CT polarities, consistent CT ratios, and for crossed-phase wiring errors. The occurrence of one of the following CT errors can be identified using balanced load current (wyeconnected CTs): CT secondary wire connected to the incorrect tap on the CT Crossed phases Incorrect CT polarity Fig. 4 shows a CT secondary connected to the incorrect tap on the CT, as well as a connection that results in an incorrect CT polarity. Fig. 5 shows the crossing of two phases. Incorrect CT polarity To check for correct CT polarities, the relay uses the Aphase current as a reference. Fig. 3: Typical two-winding transformer installation. Fig. 4: Incorrect CT ratio or CT polarity A-phase B-phase C-phase IA<0 IB< 120 IC<120 Table 3: Angular relationship for correct ct polarities. A-phase B-phase C-phase *IA<0 IB<60 IC< 60 IA<0 *IB<60 IC<120 IA<0 IB< 120 *IC< 60 *Incorrect polarity Table 4: Angular relationship for incorrect ct polarities. energize - Jan/Feb 2009 - Page 38

calculates the positive and negativesequence current of a test winding, and detects a crossed-phase condition when the positive-sequence current is less than 10% of the negative-sequence current. Incorrect CT tap position The fact that the LV current is a scaled version of the HV current is used. When the transformer is on the nominal tap, the lineto-line voltage ratio can be used instead of the transformer turns ratio. Eqn. 12 is used to calculate the scaling factor N. Table 3 shows the angular relationship between phases when the polarities of all three CTs are correct in an ABC phasesequence system. Table 4 shows the three-phase angular relationships for incorrect polarity of each of the three phases. Because A-phase is the reference, its angle remains at 0. Fig. 5: Crossed phases. Fig. 6: Logic to detect the phase with incorrect CT tap connection. (10) (11) where: I1 REF = Positive-sequence current of the reference winding I2 REF = Negative-sequence current of the reference winding IA = A-phase current of the reference winding IB = B-phase current of the reference winding IC = C-phase current of the reference winding Crossed phases The relay considers the relay phase rotation setting (ABC or ACB) and uses Eqn. 10 to calculate the positive sequence current of the reference winding, and Eqn. 11 to calculate the negative-sequence current of the reference winding for an ABC phase rotation. α = alpha-operator (1<120 ) In a separate calculation, the relay Fig. 6 shows the logic to detect an incorrect CT tap connection. The relay scales the measured HV current (IAW1 N) for each HV phase and compares this result to the measured LV current (IAW2) of the corresponding LV phase. If the difference exceeds 0,04 pu, the relay detects an incorrect CT tap connection. To determine the location the relay calculates the negative- sequence currents from the HV side and from the LV side, and identifies the side with the greater as the side with the CT on the incorrect tap. To avoid possible misleading results from unbalanced loading, the relay provides an alarm independent of the negativesequence calculation. When one of the wiring errors, is detected the algorithm reports the error and suspends the selection process, providing the opportunity to correct the wiring error before continuing with the selection process. Part II. Calculation of vector-group compensation After verifying the CT connections, the correct CT compensation for the particular vector group within the transformer is calculated. The relay accepts the new setting only if the tester confirms the setting change. Calculating the correct vector group consists of two parts: vector-group selection through use of operate current, and vectorgroup selection through use of relative phase angles. Fig. 7 shows vector-group selection through use of operate current for a two-winding transformer. Selection using the operate current To correct an angular difference of 30 between two windings, the CT secondary current phasors of one winding are rotated by 30 with respect to the CT secondary current phasors of the other winding (assuming wye-wye connected CTs). For example, consider the YDAB vector group shown in Fig. 8. Taking the HV winding as reference, the LV current resulting from the a-b connection leads the A-phase HV energize - Jan/Feb 2009 - Page 39

Fig. 7: Vector-group selection for a two-winding transformer. Fig. 8: YDAB transformer with the HV winding as reference Fig. 9 YDAB transformer with the LV winding as reference. Fig. 10 A-phase vector-group selection angular verification. current by 30. To correct for this, the LV current is rotated clockwise by 30. Taking the HV winding as reference is arbitrary. Fig. 8 shows the same YDAB vector group, but with the LV winding as reference. With the LV winding as reference, the HV currents must be rotated counterclockwise to correct for angular difference. To compensate for the angular difference of the YDAB transformer, an HV/LV matrix combination of M12/M11 is equally correct as an M1/M12 combination or as an M2/M1 combination. Clearly, it is not necessary to know the actual transformer vector group; to correct for an angular difference, one set of secondary current phasors is used as reference and the other set of secondary current phasors rotated either clockwise or counterclockwise by the appropriate amount. After selecting the reference winding (WDG1 in Fig. 11), the vector-group compensation algorithm assigns Matrix 12 to the reference winding. Assume for this example that WDG2 is the test winding. With Matrix M12 assigned to the reference winding, starting from Matrix M1, all 12 matrices are assigned to the test winding, with the object of finding the combination of matrices that produces an operate current that is (ideally) zero (see Table 2). The existing relay settings can be the correct matrix combination, and the relay calculates the operate current and restraint current with existing settings before assigning matrices to any of the windings. If the operate current is less than 0,05 pu, the existing settings are correct and the relay records the numbers of the two matrices. The relay still assigns all 12 matrices to the test winding, and records all calculated values. If the operate current is greater than 0,05 pu with the present settings, the relay assigns matrix M1 to the test winding. By keeping the reference winding at matrix M12 and assigning all 12 matrices in succession to the test winding, the algorithm finds the correct matrix combination. Fig. 11 shows a flow diagram of the selection process. At the conclusion of the test, the relay displays the recorded, calculated values from the 12 calculations in a commissioning report. Table 5 summarises the operated current vector group solution process. Selection using relative phase angles As the selected matrix can be permanently assigned as the relay setting, a further test is necessary. Relative angle selection provides a second, independent method for determining the correct matrix combination. Results can be confirmed by checking that the reference winding and test winding current phasors are in phase (± 5 ) with each other. Fig. 10 shows the logic to compare the HV winding A-phase phasor with the LV winding A-phase phasor. Because of the CT polarity connections, the HV and LV phasors are 180 out of phase. Arbitrarily selecting the HV phasors as reference, 180 is added to the LV phasors and the HV phasors and LV phasors are tested to be in phase with each other (± 5 ). When both selection processes agree, the relay considers the present calculated matrix combination to be correct. To provide visual confirmation, the relay displays a commissioning report showing the operate currents and the restraint currents for each of the 12 matrix combinations. Conclusion The relay uses balanced, minimum load current to detect single-contingency CT errors such as crossed phase, incorrect CT polarity, and incorrect CT ratio. Although the algorithm can be used for delta-connected energize - Jan/Feb 2009 - Page 40

Steps Activity Comment Step 1 Step 2 Step 3 Step 4 Step 5 Calculate IOP, the operating current, and IRT, the restraint current. Read the existing matrix setting of the reference winding. Assign matrix 1 as the initial matrix for the test winding. Calculate IOP, the operating current, and IRT, the restraint current. If IOP is less than 0,05 pu, record the matrix number, and assign the next matrix to the test winding. If IOP is greater than 0,05 pu of IRT, do not record the matrix number and assign the next matrix to the test winding. Evaluated the existing relay settings Use the existing matrix setting. Table. 5: Vector-group selection process. Assign the existing matrix setting - M1 matrix combination. Get the data to evaluate in step 5 and data for the commissioning report. If IOP is less than 0,05 per unit, the present matrix combination is the correct combination. However, we continue to evaluate the remaining combinations. Phase rotation: ABC Reference Winding: Winding S Matrix assigned to Winding S: Matrix 12 Test winding: Winding T Matrix auto-selected for Winding T: Matrix 1 With the present matrix, the differential measurements are: 0,12 0,12 0,12 0,47 0,47 0,47 Matrix auto-selected for Winding T: Matrix 1 With the auto-selected matrix, the differential measurements are: 0,00 0,00 0,00 0,47 0,47 0,48 A-Phase Values from all matrices (Winding S Matrix: Matrix 12) Matrix 1 0,00 0,00 0,00 0,47 0,47 0,48 Matrix 2 0,12 0,12 0,12 0,47 0,47 0,47.. Matrix 12 0,12 0,12 0,12 0,47 0,47 0,48 Fig. 12: Commissioning report. CTs, this increases the risk for undetected doublecontingency errors. The vector-group compensation algorithm uses two independent compensation selection methods to calculate the correct transformer differential protection matrix combination, making, commissioning transformer differential protection much easier. With the commissioning report, personnel can immediately and conclusively confirm the correctness of relay wiring (balanced test) and the integrity of differential element configuration settings. When relays assist commissioning personnel during commissioning, increased relay complexity need not mean increased complexity to protection personnel. Acknowledgment This paper was presented at the Southern African Power System Protection Conference 2008 and is reprinted with permission. References Fig. 11 Algorithm for IOP-Matrix selection. [1] W A Elmore, Ways to Assure Improper Operation of Transformer Differential Relays, in 1991 44th Annual Conference for Protective Relay Engineers Proceedings. [2] M Young, J Horak, Commissioning Numerical Relays, in 2003 30th Annual Western Protective Relay Conference Proceedings. [3] M Thompson, J R Closson, Using IOP Characteristics to Troubleshoot Transformer Differential Relay Misoperation, in 2001 International Electric Testing Association Technical Conference Proceedings. Contact Rudolf van Heerden, SEL, Tel 012 664-5930, rudovanh@selinc.com v energize - Jan/Feb 2009 - Page 42