Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters

Similar documents
PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Analysis of lightning performance of 132KV transmission line by application of surge arresters

WORLD MEETING ON LIGHTNING Lightning Performance Research on Mexican High Voltage Transmission Lines

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

Including Surge Arresters in the Lightning Performance Analysis of 132kV Transmission Line

Lightning Overvoltage Performance of 110 kv Air-Insulated Substation

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Estimating BFOR on HV Transmission Lines Using EMTP and Curve of Limiting Parameters

Lightning performance of a HV/MV substation

Estimating the Lightning Performance of a Multi- Circuit Transmission Tower

Mitigation of Back-Flashovers for 110-kV Lines at Multi-Circuit Overhead Line Towers

EMTP IMPLEMENTATION OF A MONTE CARLO METHOD FOR LIGHTNING PERFORMANCE ANALYSIS OF TRANSMISSION LINES

Computation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission Lines

Statistical Lightning Simulations for a HV "Mixed" Overhead-Cable Line: Preliminary Studies

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations

Research on Lightning Over-voltage and Lightning Protection of 500kV. HGIS Substation

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

ABSTRACTS of SESSION 6

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

The line-lightning performance and mitigation studies of shielded steelstructure

Analysis of Arrester Energy for 132kV Overhead Transmission Line due to Back Flashover and Shielding Failure

Insulation Coordination Study of 275kV AIS Substation in Malaysia

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS

Study of Tower Grounding Resistance Effected Back Flashover to 500 kv Transmission Line in Thailand by using ATP/EMTP

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

Effective Elimination Factors to the Generated Lightning Flashover in High Voltage Transmission Network

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

INSTALLATION OF LSA ON A 400 KV DOUBLE-CIRCUIT LINE IN RUSSIA

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Lightning overvoltage and protection of power substations

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

Lightning transient analysis in wind turbine blades

Modeling insulation in high-voltage substations

Comparison between Different InstallationLocations of Surge Arresters at Transmission Line Using EMTP-RV

High voltage engineering

TRIGGERED by energy transition towards sustainability,

X International Symposium on Lightning Protection

Lightning Overvoltage performance of 132kV GIS Substation in Malaysia

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Lightning phenomena and its effect on transmission line

Simulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP

Mitigation Methods to Improve the Lightning Performance of Hybrid Transmission Line

Electric Stresses on Surge Arrester Insulation under Standard and

The Effect of High Frequency Model of Tower- Footing Grounding Systems on the Back Flashover Rate of Transmission lines

Journal of Applied Research and Technology 15 (2017)

The Lightning Event. White Paper

Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

Sensitivity Analysis of Maximum Overvoltage on Cables with Considering Forward and Backward Waves

Substation Insulation Coordination Study

The Many Uses of Transmission Line Arresters

Metal-Oxide Surge Arresters Integrated in High-Voltage AIS Disconnectors An Economical Solution for Overvoltage Protection in Substations

Lightning Protection: History and Modern Approaches

University of Zagreb Faculty of Electrical Engineering and Computing

Lightning Performance of Transmission Lines with Tall Sections

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

Accuracy of Lightning Surge Analysis of Tower Surge Response

Guidelines for transmission lines lightning performance improvement using a statistical approach

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

Equipment Rack Grounding. Technical Note

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

Transmission of Electrical Energy

Electrical Power and Energy Systems

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line.

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

B2-301 IMPROVING DOUBLE CIRCUIT TRANSMISSION LINE RELIABILITY THROUGH LIGHTNING DESIGN

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

Analysis of current distribution among long-flashover arresters for 10 kv overhead line protection against direct lightning strikes

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

The impact of recent advances on lightning measurement and detection on the protection of transmission and distribution lines

SCIENCE & TECHNOLOGY

Voltage Sag Index Calculation Using an Electromagnetic Transients Program

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Back-flashover Investigation of HV Transmission Lines Using Transient Modeling of the Grounding Systems

Investigation of Transmission Line Overvoltages and their Deduction Approach

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

Insulation Co-ordination For HVDC Station

Protection against unacceptable voltages in railway systems

ABSTRACT 1 INTRODUCTION

Investigation on the Performance of Different Lightning Protection System Designs

Transformers connected via a cable Overvoltage protection

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

Electric Power Systems Research

Software Development for Direct Lightning Stroke Shielding of Substations

Investigation into Transient SFO, FFO, VFTO Overvoltage Characteristics for Typical Gas Insulated Substations

Utility System Lightning Protection

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

A Study of Lightning Surge on Underground Cables in a Cable Connection Station

Lecture 36 Measurements of High Voltages (cont) (Refer Slide Time: 00:14)

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Transcription:

IEEE PES General Meeting June 23-27, 27, 2007, Tampa Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters Juan A. Martinez Univ. Politècnica Catalunya Barcelona, Spain Ferley Castro-Aranda Universidad del Valle Cali, Colombia

Introduction Surge arresters improve the lightning perfor- mance of lines with a poor shielding or with very high tower footing impedances Arresters must be selected taking into account energy discharge stresses Aim of this paper: analyzing the lightning perfor- mance improvement of a shielded transmission line after installing surge arresters The study will be also aimed at estimating the energy absorption capability of arresters A statistical approach must be used due to the random nature of lightning

Contents Description of the test line Modeling guidelines Features of the Monte Carlo based method Line and lightning parameters Lightning flashover rate without arresters Arrester energy study Lightning flashover rate with arresters

6.75 m 5.25 m 2.11 m A 6.3 m 0.4 m Test line 5.25 m B 6.0 m 43.35 m (33.35) m (400 kv) 6.0 m C 33.02 m (21.02) m 27.87 m (15.87) m 26.1 m 22.62 m (10.62) m 7.05 m

Modeling guidelines Line span model Line termination Insulator strings Towers Footing impedance Power frequency phase conductor voltages Line surge arresters Return stroke Waveform, parameters

Modeling guidelines Shield wire Stroke (ideal current source) Line span Distributed parameter line Line span Distributed parameter line Line termination Resistive matrix Phase conductors Flashover (TACS/MODELS controlled switch) Tower (ideal line) Footing resistance Overvoltages originated by strokes to shield wires

Modeling guidelines Shield wire Line span Distributed parameter line Line span Distributed parameter line Line termination Resistive matrix Phase conductors Flashover (TACS/MODELS controlled switch) Tower (ideal line) Stroke (ideal current source) Footing resistance Overvoltages originated by strokes to conductors

Lightning stroke parameters Return stroke waveform Concave waveform - Heidler model I n p k it k e t / τ 2 () = n η 1+ I p is the peak current η is a correction factor of the peak current n is the current steepness factor k=t/τ 1, (τ 1, τ 2 time constants determining current rise and decay-time, respectively)

Lightning stroke parameters Return stroke waveform ka I 100 I P I 90 I 50 I 30 t 30 t 90 t h time

Lightning stroke parameters Return stroke waveform Parameters used to define this waveform the peak current magnitude, I 100 the rise time, t f (= 1.67 (t 90 t 30 )) the tail time, t h (time interval between the start of the wave and the 50% of peak current on tail) The main difficulty to synthesize a concave waveform is the determination of the parameters to be specified in the current expression from those of the return stroke (I 100, t f, t h )

Insulator strings Based on the leader progression model (LPM) When the applied voltage exceeds the corona inception voltage, streamers propagate along the insulator string; if the voltage remains high enough, these streamers will become a leader channel A flashover occurs when the leader crosses the gap between the cross-arm and the conductor The total time to flashover can be expressed as follows t = t + t + t t c t c is the corona inception time (it is usually neglected) t s is the streamer propagation time t s E50 = 1.25E 0.95E E 50 is the average gradient at the critical flash-over voltage E is the maximum gradient before breakdown s l 50

Insulator strings The leader propagation time, t l, can be obtained from the following equation dl dt V ( t) = klv ( t) El 0 g l V(t) is the voltage across the gap g is the gap length l is the leader length E l0 is the critical leader inception gradient k l is a leader coefficient The leader propagation stops if the gradient in the unbridged part of the gap falls below E l0

Monte Carlo procedure Application of the electrogeometric model Overvoltage calculations Calculation of random values (lightning stroke parameters, leader channel loca- tion,, phase conductor voltages, footing resistance, insulator strength) If a flashover occurs, the counter is incre- ased and the flashover rate updated Convergence of the Monte Carlo method

Line and lightning parameters Models were created using ATP capabilities Line represented by means of 390-m m spans plus a 30-km section as line termination at each side of the point of impact Tower surge impedance calculated according to the expression suggested by CIGRE Parameters of insulator equation k l = 1.3E-6 6 m 2 /(V 2 s) ; E l0 = 570 kv/m Insulator string striking distance 3.066 m Only negative single stroke flashes (represen( represen- ted by the Heidler model) were considered

Line and lightning parameters Probability distributions assumed Stroke parameters determined assuming a log- normal distribution The reference angle had a uniform distribu- tion,, between 0 and 360 degrees Insulator string parameters determined accor- ding to a Weibull distribution, with a standard deviation of 5% for all parameters. The footing resistance had a normal distribu- tion with a mean value of 50 Ω and a standard deviation of 5 Ω (soil resistivity = 200 Ω.m) The stroke location was obtained by assuming a uniform ground distribution of the leader

Flasshover rate without arresters Flashover rates after 20000 runs backflashovers = 1.65 per 100 km-year shielding failures = 0.66 per 100 km-year The total flashover rate was 2.31per 100 km-year Values obtained N g = 1 fl/km 2 -year Too high rate for a transmission line

Simulation results 0.0040 0.0035 0.0030 Probability 0.0025 0.0020 0.0015 0.0010 0.0005 0.0000 80 200 320 440 560 680 Peak Current Magnitude (ka) Strokes to shield wires that caused flashover

Simulation results 0.0025 0.0020 Probability 0.0015 0.0010 0.0005 0.0000 10 30 50 70 90 110 130 150 Peak Current Magnitude (ka) Strokes to phase conductors that caused flashover

Sensitivity analysis Performed to find out the relationship between the flashover rate of the test line and some parameters the median value of the peak current magnitude the rise time of lightning strokes the mean value of the footing resistance at low current and low frequency

Flashover rate vs. peak current magnitude (t f = 2 μs, t h = 77.5 μs, R 0 = 50 Ω, ρ= = 200 Ω.m, N g = 1 fl/km 2 -y) 5 4 Flashover Rate 3 2 1 0 10 20 30 40 50 Peak Current Magnitude (ka)

(I 100 Flashover rate vs. footing resistance 100 = 34 ka, t f = 2 μs, t h = 77.5 μs, ρ= = 200 Ω.m, N g = 1 fl/km 2 -y) 2.5 2.4 Flashover Rate 2.3 2.2 2.1 2 20 30 40 50 60 70 80 90 Footing Resistance (ohm)

Arrester energy studies Modeling guidelines Spans must be represented as multi-phase untrans- posed frequency-dependent distributed-parameter line sections No less than 7 spans at both sides of the point of impact have to be included in the model for arrester energy evaluation The effect of the arrester lead is negligible when strokes hit either a tower or a phase conductor The tail time of the return stroke current has a strong influence; the effect of the rise time very small, or even negligible for low peak current values

Arrester energy studies Arrester model and parameters Model recommended by IEEE Values used to obtain the arrester model: voltage for a 10 ka, 8/20 μs s current, V 10 = 1007 kv switching surge discharge voltage for 1 ka, 30/60 μs s current, V ss = 735 kv height of the arrester, d = 3.72 meters number of parallel columns of MO disks, n = 1 Rated voltage selected for the test arrester is 378 kv

Arrester energy studies B C C A A B Maximum energy discharged by surge arresters Arresters per tower A B C A B Stroke to a tower (1) 96.4 kj 101.2 kj 81.7 kj 90.8 kj 97.3 kj 88.8 kj Stroke to a phase conductor (2) 645.8 kj 645.8 kj 651.7 kj 645.8 kj 645.8 kj 651.7 kj (1) Waveform of the stroke to a tower = 150 ka, 2/50 μs (2) Waveform of the stroke to a conductor = 50 ka, 2/50 μs Footing resistance: R 0 = 50 Ω; ρ = 200 Ω.m

Arrester energy studies Maximum energy discharged by surge arresters 200 Energy (kj) 150 100 50 0 0 50 100 150 200 Peak Current Magnitude (ka) Stroke to a tower - Footing resistance: R 0 = 50 Ω; ρ = 200 Ω.m

Arrester energy studies Maximum energy discharged by surge arresters 3000 2400 Energy (kj) 1800 1200 600 0 0 30 60 90 120 150 Peak Current Magnitude (ka) Stroke to a tower - Footing resistance: R 0 = 50 Ω; ρ = 200 Ω.m

Flashover rate with arresters Goal: estimate the improvement of the flashover rate that can be achieved by installing surge arresters at all towers of the test line, but not at all phases Conclusions derived from the previous results: The line has a poor lightning performance, mainly due to an abnormal shielding failure rate Arrester failures can be caused by a stroke to a phase conductor, unless arresters with a large energy absorption capability were installed The flashover rate of the test line with the different combinations of arresters was estimated; it was as- sumed that arresters with a large enough energy absorption capability were installed

Flashover rate with arresters Flashover rate with arresters (per 100 km-year) Arrester Protection BFOR SFFOR Total flashover rate A B C 0 0 0 A B 0.245 0 0.245 B C 0.670 0.560 1.230 C A 0.505 0.100 0.605 A 0.740 0.105 0.845 B 1.000 0.560 1.560

Conclusions The paper has presented the lightning perfor- mance improvement of a 400 kv line with a poor shielding The study has shown that a different degree of improvement can be achie- ved by installing arresters at all or only some of the line phases the improvement can be very significant when arresters are installed at two phases with the installation of a single arrester per tower, an important reductions of the FR is achieved the installation of arresters with a high energy absorption capability is advisable