Application Note on Power Point Tracking for Conext Core XC and XC-NA Series Inverters

Similar documents
Application Note: Grid Settings by Utility Region for the Conext Core XC Series

Conext CL-60 Inverter Active and Reactive Power Control and LVRT

Conext CL125 Inverter - Active and Reactive Power Control and LVRT/HVRT

Application Note: String sizing Conext CL Series

Conext Core XC Series Inverter, 0G-XC-BB: Thermal Derating Application Note

Conext Core XC-NA Series Grid Tie Photovoltaic Inverter and DC Recombiner

RenConnectLite. Version 3.0. Software User Guide.

Conext Core XC-NA ES Series Energy Storage Inverter

Conext Core XC and XC-NA Series Grid Tie Photovoltaic Inverter

Conext Core XC ES and XC-NA ES Series Energy Storage Inverters

AccuSine SWP A. Operation. Active Harmonic Filter 02/

Conext CL Three Phase Grid Tie Inverters Conext CL NA Conext CL NA

JBus/Modbus Communication Card

SPECIFICATION, CONTROLS AND ACCESSORIES

Technical information SUNNY TRIPOWER CORE1-US

AN Programming the PCA200x family of watch ICs. Document information

CP /240-MC4 User Manual

SPECIFICATION, CONTROLS AND ACCESSORIES

How do I Implement Hybrid Solutions for LV Dynamic Power Factor Correction

Aluminum Electrolytic Capacitors Power Ultra High Ripple Current Snap-In for Solar

Elgar ETS TerraSAS. 1kW-1MW V. Standalone TerraSAS Photovoltaic Simulator

Technical information SUNNY BOY 3.0-US / 3.8-US / 5.0-US / 6.0-US / 7.0-US / 7.7-US

SSR-150xxx-40VL-12P-xC-xxxCS

CHAPTER 7 MAXIMUM POWER POINT TRACKING USING HILL CLIMBING ALGORITHM

BC145 SIGNAL ISOLATOR BOARD

Technical information Grid Support Utility Interactive Inverters for Sunny Central-US and Sunny Central Storage-US

Single Phase Rectifier Bridge, 1.9 A

Mini Receiver. Off Peak System Control. Operation & Installation Guide for Power Line Carrier WARRANTY. (Applicable to Software Version

C-Bus 8 Channel Low Voltage Relay

IEC compliance and ION meters

Model 532 ma/v Loop Calibrator with Loop Diagnostic Operating Instructions

Capacitor protection relay

ISOlinear Architecture. Silicon Labs CMOS Isolator. Figure 1. ISOlinear Design Architecture. Table 1. Circuit Performance mv 0.

Advanced Test Equipment Rentals ATEC (2832)

MC33PF8100, MC33PF8200

Power-One Aurora PLUS and PLUS-HV Series Inverters: guide to the sizing of photovoltaic generators with Aurora Designer and PowerOne String Tool

AN NHS3xxx Temperature sensor calibration. Document information

Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA

Is Now Part of To learn more about ON Semiconductor, please visit our website at

HG G B. Gyroscope. Gyro for AGV. Device Description HG G B. Innovation through Guidance. Autonomous Vehicles

TEST REPORT DIN V VDE V :2006 Automatic disconnecting device

High Bay Occupancy Sensor for Use with Electronic Ballast HID Luminaires

CCE Image may differ from the actual product By Martin Labbé, eng., Jasmin Goupil & Louis Perreault

Power One Aurora String Inverter: energy absorption

Galaxy VM. Kit for IP32. Installation 06/

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

Aluminum Electrolytic Capacitors Power Miniaturized General Purpose - Snap-In

APS M1P Single-phase Micro-inverter Installation and User Manual

CMOS Micro-Power Comparator plus Voltage Follower

Single Phase Rectifier Bridge, 1.9 A

Dual 4-bit static shift register

TIMING CIRCUIT SEMICONDUCTOR TECHNICAL DATA ORDERING INFORMATION. Figure Second Solid State Time Delay Relay Circuit

SPECIFICATION, CONTROLS AND ACCESSORIES

MC Low Voltage Rail-To-Rail Sleep Mode Operational Amplifier

Power Meter. Measurement Guide. for Anritsu RF and Microwave Handheld Instruments BTS Master Site Master Spectrum Master Cell Master

CONTENTS OF THE BOX. *PIR sensor only **Dual Technology and PIR sensors only. Description PIR Ultrasonic Dual Technology

SSR VL-12P-xC-NCS

LM339S, LM2901S. Single Supply Quad Comparators

FLEX 5000 High-speed Counter I/O Modules

Single Phase Rectifier Bridge, 2 A

DUAL TIMING CIRCUIT SEMICONDUCTOR TECHNICAL DATA PIN CONNECTIONS ORDERING INFORMATION. Figure Second Solid State Time Delay Relay Circuit

NCP304A. Voltage Detector Series

Electrical Multimeter

APS M1P Single-phase Micro-inverter Installation and User Manual

Certificate of Compliance

Harmony XB5R. Expert Instruction Sheet 11/ EIO

AND8388/D. Input Dynamic Range Extension of the BelaSigna 300 Series

Installation and Operating Instructions. Power IT Power Factor Controller RVC

XDC 6000 Watt and Watt Series Digital Programmable DC Power Supply. Operating Manual

Functional Safety Application Guide

Surface Mounted Power Resistor Thick Film Technology

Single Phase Rectifier Bridge, 2 A

Low-Pressure Sensing Using MPX2010 Series Pressure Sensors

74HCT138. Description. Pin Assignments. Features. Applications 3 TO 8 LINE DECODER DEMULTIPLEXER 74HCT138

Quad 2-input NAND Schmitt trigger

MC3456 DUAL TIMING CIRCUIT

Hex non-inverting precision Schmitt-trigger

Sliding-Mode Control Based MPPT for PV systems under Non-Uniform Irradiation

Optimizing Magnetic Sensor Power Operations for Low Data Rates

Conext CL-60E Inverter

Aluminum Electrolytic Capacitors Radial, High Temperature, Low Impedance, High Vibration Capability

Single Phase Rectifier Bridge, 1.2 A

3M Dynatel Far End Device III

CBCT TM CIRCUIT BREAKER COIL TESTER

PIECAL Model 541 Frequency Calibrator with Totalizer Operating Instructions

Push Button Minute Timer Programmable between 1 minute and 30 minutes with built in multi-way control

Solectria Renewables Modbus Level 6 For models SGI 500XT

Single Phase Bridge Rectifier, 2 A

MBC Bipolar Microstep Driver. User s Guide E. Landon Drive Anaheim, CA

IEEE sion/1547revision_index.html

Grid Radar Installation Manual

312, 316, 318. Clamp Meter. Users Manual

Dual non-inverting Schmitt trigger with 5 V tolerant input

Single Phase Rectifier Bridge, 3 A, 6 A

Aluminum Electrolytic Capacitors Axial High Temperature, High Ripple Current

Taking the Nuisance Tripping out of AFCI - Useful Changes to Testing of PV Inverters

AN12165 QN908x RF Evaluation Test Guide

High-Voltage Switchmode Controller

600A Clamp Meters w/tightsight Display

Independent Technology Service Inc Independence Ave. Chatsworth, California Toll Free:

Transcription:

Application Note on Power Point Tracking for Conext Core XC and XC-NA Series Inverters AP-XC-007-EN Revision D DANGER RISK OF ELECTRIC SHOCK, EXPLOSION, ARC FLASH, AND FIRE This Application Note is in addition to, and incorporates by reference, the relevant product manuals for each product in the Schneider Electric Conext Core XC and XC-NA Series Grid-Tied Photovoltaic Inverters. Before reviewing this Application Note you must read the relevant product manuals. Unless specified, information on safety, specifications, installation, and operation is as shown in the primary documentation received with the product. Ensure you are familiar with that information before proceeding. Failure to follow these instructions will result in death or serious injury. Introduction The Schneider Electric Conext Core XC and XC-NA Series inverters are designed to help optimize the drawing of power from photovoltaic (PV) arrays. The relationship between the inverter, PV array, and grid is shown in Figure 1. The inverter firmware uses a series of algorithms with preset default values to monitor the power production of the PV array and determine when to connect to the PV array, when to begin maximum power point tracking (MPPT), and when to disconnect from the PV array. Figure 1 Inverter relationship to PV array and grid

The default parameter values that are set in the factory will work for any photovoltaic panel, but they are not always optimal for a particular PV array. In these cases, the default parameters can be changed to meet the custom requirements of the inverter-pv configuration. This document describes and illustrates how an inverter transitions between its online and offline states and how it tracks power points to establish the optimal PV voltage at which to transfer power. Tips are provided about changing the default parameters. Operating Modes The Conext Core XC and XC-NA Series inverter monitors the PV array and goes online (connects to the PV array and grid) when the PV array generates a voltage level that is higher than the PV OC Start Voltage parameter. This normally occurs soon after sunrise. The inverter operates throughout the day in the following modes, as illustrated in Figure 2: At the beginning of the day, PV power levels are low and the inverter harvests energy in a low power (passive MPPT) mode. When the power level exceeds the preset Low Power Threshold parameter, the inverter leaves low power mode and enters active MPPT mode. As evening approaches, the PV power level drops below the Low Power Threshold parameter value and the inverter returns to low power mode. When the power level drops below the preset PV nop Disconnect Threshold parameter, the inverter goes offline (disconnects from the PV array and grid). The following sections discuss the parameters that define each mode and the transitions between the modes. Figure 2 Inverter to PV array operating modes 2 AP-XC-007-EN Revision D

Offline to Online Transition at Daybreak The following parameters are used for the inverter transition from an offline state to an online state at daybreak, as illustrated in Figure 3 on page 4: PV OC Start Voltage The PV voltage threshold at which the inverter, if offline, will prepare to go online (OC = open circuit). This voltage must be greater than or equal to the LP PV Voltage Reference that is, the voltage must always drop when the inverter goes online. The PV OC Start Voltage parameter has the following constraints: PV OC Start Voltage LP PV Voltage Reference Min Tracking Volt PV OC Start Voltage Max OC Voltage (1000 V) The PV OC Start Voltage parameter has the following default value: PV OC Start Voltage = LP PV Voltage Reference = Dynamic minimum tracking voltage For information about setting the PV OC Start Voltage parameter to achieve the best MPPT performance, see Optimizing MPPT Performance on page 11. PV Reconn Delay The length of time, in seconds, that the inverter waits before going online. This wait is to confirm that PV voltage is continuously above the PV OC Start Voltage threshold. Default Values for Offline to Online Transition The following settings are the factory default values for the offline to online transition, as illustrated in Figure 4 on page 5: Table 1 Default values for the offline to online transition Parameter Default Value PV OC Start Voltage LP PV Voltage Reference PV Reconn Delay LP Threshold LP Transition Delay 400 VDC 400 VDC 1200 s 5% of P nominal 300 s AP-XC-007-EN Revision D 3

Figure 3 Inverter offline to online transition 4 AP-XC-007-EN Revision D

Figure 4 Default offline to online settings AP-XC-007-EN Revision D 5

Power Point Tracking Power point tracking is a technique to obtain maximum power from the PV array as the environmental conditions change. The two MPPT regimes are low power MPPT (also known as passive MPPT) and active MPPT. Low Power (Passive MPPT) Mode When output power is low that is, less than LP Threshold the system is considered to be in low power (LP) mode. This mode is a passive MPPT regime where PV voltage is maintained at a fixed level ( LP PV Voltage Reference ). The following parameters are used for low power mode: LP PV Voltage Reference The PV voltage level which the inverter maintains while in low power (LP) mode. This voltage is always equal to or less than the PV OC Start Voltage. The LP PV Voltage Reference parameter has the following constraints: LP PV Voltage Reference PV OC Start Voltage Active MPPT Mode Min Tracking Volt < LP PV Voltage Reference < Max Tracking Volt (800 V) For information about setting the LP PV Voltage Reference parameter to achieve the best MPPT performance, see Optimizing MPPT Performance on page 11. LP Threshold The level of PV power above which the inverter operates in active MPPT mode and below which the inverter operates in low power (passive MPPT) mode. LP Transition Delay The length of time, in seconds, that the inverter waits before changing between low power (passive MPPT) mode and active MPPT mode. This delay confirms that the PV power is above (or equal to) LP Threshold. These settings are illustrated in Figure 3 on page 4 (offline to online transition) and Figure 9 on page 13 (online to offline transition). When output power is above LP Threshold, the system is considered to be in active MPPT mode. Maximum power point tracking begins, using a Perturb and Observe method designed to improve tracking performance in the presence of dynamic insolation conditions. The procedure is cyclic, and the period of each cycle is called the perturb interval. The following parameters are used for active tracking of maximum power point using perturb steps, as illustrated in Figure 5 on page 8: 6 AP-XC-007-EN Revision D

MPPT Type The method used for trend prediction (how external factors affect dynamic power). Type 1 is the default method. Type 0 = No trend prediction Type 1 = 1st order (linear) trend prediction Type 2 = 2nd order (quadratic) trend prediction Min Tracking Volt The minimum PV voltage that can be maintained during power point tracking. This setting defines the tracking range and cannot be at a level below the system-calculated minimum tracking voltage. For details, see Min Tracking Volt Limitation on page 9. Max Tracking Volt The maximum PV voltage of the tracking range. Perturb Voltage Step The PV voltage delta in each perturbation. Perturb steps determine the granularity of the power point search algorithm. Smaller steps result in a more accurate search result, while larger steps allow for a more robust and reliable search process. MPPT Sampling Interval PV power. The length of time, in ms, between two samplings of MPPT Occurrence Factor The number of MPPT Sampling Intervals between two PV voltage perturbations. MPPT Offset Factor A relative comparator hysteresis. This hysteretic element is used to determine the perturbation direction. A smaller offset factor results in more accurate tracking and a larger offset factor results in more robust tracking. MPPT Offset Maximum MPPT Offset Minimum The maximum offset voltage allowed. The minimum offset voltage allowed. MPPT Reset Factor The factor used to equalize the initial conditions of the MPPT algorithm during extended power point shifting regimes. A higher reset factor results in faster equalization and a lower reset factor results in slower equalization. AP-XC-007-EN Revision D 7

Figure 5 MPPT perturbations 8 AP-XC-007-EN Revision D

Min Tracking Volt Limitation Min Tracking Volt is a key parameter that defines the tracking range. This parameter sets the minimum PV voltage that can be maintained and is limited by the grid voltage amplitude, as shown in Figure 6. Figure 6 Minimum tracking voltage in relation to grid voltage The Min Tracking Volt parameter is represented as V trackmin. When reactive power is zero ( ), V trackmin is defined as: Q = 0 V trackmin = 15 V + grid voltage amplitude Grid voltage amplitude = 2 V rms Example: If V grid = 300 V rms, then grid voltage amplitude = 2 300 V rms = 424 V With reactive power at zero ( Q = 0 ), then: V trackmin = 15 + 424= 439 V For information about calculating V trackmin when the reactive power is not zero (>0 or <0), see the next section. AP-XC-007-EN Revision D 9

Dynamic Minimum Tracking Voltage (System-Calculated) The system-calculated minimum tracking voltage is also called dynamic minimum tracking voltage. The dynamic minimum tracking voltage is represented as V* trackmin, as shown in the following equations: Capacitive mode (Q > 0) 15 V + 2 Vgrid 2 + 3.0 f grid Q V* track min = (1) Inductive mode (Q < 0) V* track min = (2) f = grid frequency in Hz Q = reactive power level in kvar 15 V + 2 Vgrid 2 + 1.0 f grid Q Actual Minimum Tracking Voltage The actual minimum tracking voltage is whichever value is greater: the user-set voltage V trackminuser or the system-calculated voltage V* track min, as shown in the following equation: max{ V trackmin, V trackminuser } Actual V track min = (3) The inverter constantly monitors V grid and updates the V* track min parameter. If a user sets the minimum tracking voltage below the system-calculated level (per equations 1 and 2), the inverter overrides the user setting. An example of this scenario is shown in Figure 7 on page 11. The inverter does not allow the PV voltage to drop below the dynamic minimum tracking voltage. 10 AP-XC-007-EN Revision D

Figure 7 Calculating the actual min tracking voltage Optimizing MPPT Performance When power point tracking is optimized, the energy harvest in low power (passive MPPT) mode is optimized, as shown in Figure 8. Figure 8 Unused energy when power point tracking is not optimized AP-XC-007-EN Revision D 11

In order to get the best MPPT performance from the Conext Core XC and XC-NA Series inverter, we recommend that the PV OC Start Voltage and LP PV Voltage Reference parameters be adjusted as described in the following procedure. To optimize MPPT: 1. Determine the maximum power point voltage of the PV strings at standard test condition (STC). 2. Using the front panel user interface on the inverter, adjust the PV OC Start Voltage and LP PV Voltage Reference settings according to the following table: Maximum Power Point of PV Strings at Standard Test Condition (STC) Parameter Value PV OC Start Voltage (defined on page 3) 650 VDC 400 VDC (default) > 650 VDC 650 VDC LP PV Voltage Reference (defined on page 6) 650 VDC 400 VDC (default) > 650 VDC 650 VDC Note: The maximum power point of the PV strings must not exceed 800 VDC, Online to Offline Transition at Nightfall The following parameters are used for the inverter transition from an online state to an offline state, as illustrated in Figure 9 on page 13: PV nop Disconnect Threshold The power level at which the PV array is considered to be generating no power and the inverter prepares to go offline. PV nop Disconnect Delay The length of time that the inverter waits before going offline, to confirm that the PV power is constantly below the PV nop Disconn Threshold. 12 AP-XC-007-EN Revision D

Figure 9 Inverter online to offline transition AP-XC-007-EN Revision D 13

Default Values for Online to Offline Transition The following settings are the factory default values for the online to offline transition: Table 2 Default values for the online to offline transition Parameter Default Value LP Threshold LP Transition Delay LP PV Voltage Reference PV nop Disconn Threshold PV nop Disconn Delay 5% of P nominal 300 s 400 VDC 1% of P nominal 3000 s The following relationship is also a factory default: LP PV Voltage Reference = Dynamic minimum tracking voltage For information about dynamic minimum tracking voltage, see Dynamic Minimum Tracking Voltage (System-Calculated) on page 10. Diagnostic Parameters Sweep The configurable parameters described in this section are used for diagnostic purposes. The Fast Sweep technology is used to help identify the global maximum power point in a system. The following parameters are used for performing a userinitiated sweep, as illustrated in Figure 10 on page 15: Sweep Enable Enable periodic sweeping. When sweeping is enabled, power point tracking is interrupted periodically and PV power is swept. Sweep Occurrence The length of time, in seconds, between each sweep. Sweep Duration The length of time, in seconds, that the sweep event lasts. Sweep Start Voltage Sweep Stop Voltage The PV voltage at which sweeping starts. The PV voltage at which sweeping stops. Sweep Range Voltage A voltage range between which sweeping occurs. The range occurs around a preset voltage reference in the system (not configurable). When Sweep Range Voltage = 0, the sweep starts at Sweep Start Voltage and stops at Sweep Stop Voltage. MPPT Sweep Trigger Initiates a single sweep event. 14 AP-XC-007-EN Revision D

Figure 10 Sweep settings AP-XC-007-EN Revision D 15

User PV Voltage Reference Negative Current The User PV Voltage Ref parameter enables a user to set their own PV voltage reference to override the active MPPT settings. User PV Voltage Ref The user s desired PV voltage reference. When this reference is set to zero, the inverter is in active MPPT mode. The default User PV Voltage Ref is 0. If current flows in the opposite direction and into the PV generator for any reason, the following parameters will trigger an error and prevent potential damage to the PV strings: PV Neg Disconn Threshold an error is triggered. The threshold value of PV negative current before PV Neg Disconn Delay The length of time that the inverter waits before triggering an error due to PV Neg Disconn Threshold. Copyright 2014 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Exclusion for Documentation UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER (A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION; (B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S RISK; AND (C) REMINDS YOU THAT IF THIS DOCUMENTATION IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION WHICH IS POSTED AT www.schneider-electric.com. Date: March 2014 Revision: Revision D Document Number: AP-XC-007-EN Contact Information www.schneider-electric.com For other country details please contact your local Schneider Electric Sales Representative or visit the Schneider Electric website at: http://www.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page 16 AP-XC-007-EN Revision D