Power Calculation Algorithm for Single-Phase Droop-Operated Inverters Considering Nonlinear Loads

Similar documents
Micro-grid Inverter Parallel Droop Control Method for Improving Dynamic Properties and the Effect of Power Sharing

Shunt Active Filters (SAF)

Design of Shunt Active Filter for Harmonic Compensation in a 3 Phase 3 Wire Distribution Network

Figure.1. Basic model of an impedance source converter JCHPS Special Issue 12: August Page 13

antenna antenna (4.139)

Fuzzy Logic Controlled Shunt Active Power Filter for Three-phase Four-wire Systems with Balanced and Unbalanced Loads

Control of Parallel-connected Inverters to Achieve Proportional Load Sharing

To: Professor Avitabile Date: February 4, 2003 From: Mechanical Student Subject: Experiment #1 Numerical Methods Using Excel

Walsh Function Based Synthesis Method of PWM Pattern for Full-Bridge Inverter

Uncertainty in measurements of power and energy on power networks

An Improved Active Filter Technique for Power Quality Control under Unbalanced Dynamic Load Condition

Rejection of PSK Interference in DS-SS/PSK System Using Adaptive Transversal Filter with Conditional Response Recalculation

Evaluation and Implementation of Three Phase Shunt Active Power Filter for Power Quality Improvement

Low Switching Frequency Active Harmonic Elimination in Multilevel Converters with Unequal DC Voltages

A Novel Reference Current Generation Algorithm for Harmonic and Reactive Power Compensation in Non Ideal Three-phase Systems

Comparison of Reference Compensating Current Estimation Techniques for Shunt Active Filter

INSTANTANEOUS TORQUE CONTROL OF MICROSTEPPING BIPOLAR PWM DRIVE OF TWO-PHASE STEPPING MOTOR

Control of Venturini Method Based Matrix Converter in Input Voltage Variations

Improved P-f/Q-V and P-V/Q-f Droop Controllers for Parallel Distributed Generation Inverters in AC Microgrid

A method to reduce DC-link voltage fluctuation of PMSM drive system with reduced DC-link capacitor

Control of Chaos in Positive Output Luo Converter by means of Time Delay Feedback

Aalborg Universitet. Published in: Proceedings of the IEEE Energy Conversion Congress and Exposition 2012

Improvement of the Shunt Active Power Filter Dynamic Performance

Simulation of Distributed Power-Flow Controller (Dpfc)

Voltage Quality Enhancement and Fault Current Limiting with Z-Source based Series Active Filter

THE application of distributed generation (DG) has been

High Speed, Low Power And Area Efficient Carry-Select Adder

Dual Functional Z-Source Based Dynamic Voltage Restorer to Voltage Quality Improvement and Fault Current Limiting

Harmonic Balance of Nonlinear RF Circuits

Published in: Proceedings of the 11th International Multiconference on Systems, Signals & Devices, SSD 2014

Modeling and Control of a Cascaded Boost Converter for a Battery Electric Vehicle

Calculation of the received voltage due to the radiation from multiple co-frequency sources

TECHNICAL NOTE TERMINATION FOR POINT- TO-POINT SYSTEMS TN TERMINATON FOR POINT-TO-POINT SYSTEMS. Zo = L C. ω - angular frequency = 2πf

IEE Electronics Letters, vol 34, no 17, August 1998, pp ESTIMATING STARTING POINT OF CONDUCTION OF CMOS GATES

Passive Filters. References: Barbow (pp ), Hayes & Horowitz (pp 32-60), Rizzoni (Chap. 6)

NATIONAL RADIO ASTRONOMY OBSERVATORY Green Bank, West Virginia SPECTRAL PROCESSOR MEMO NO. 25. MEMORANDUM February 13, 1985

Journal of Engineering Science and Technology Review 5 (2) (2012) Research Article. P.M.Balasubramaniam 1,* and G.

CHAPTER 4 INSTANTANEOUS SYMMETRICAL COMPONENT THEORY

An Improved Droop Control Strategy for Reactive Power Sharing in Islanded Microgrid Han, Hua; Liu, Yao; Sun, Yao; Su, Mei; Guerrero, Josep M.

Three-Phase Grid-Connected PV System With Active And Reactive Power Control Using dq0 Transformation

Improved PLL Tuning of Shunt Active Power Filter for Grid Connected Photo Voltaic Energy System

Closed Loop Topology of Converter for Variable Speed PMSM Drive

Controller Design Using Coefficient Diagram Methods for Matrix Converter Based Unified Power Flow Controllers

Th P5 13 Elastic Envelope Inversion SUMMARY. J.R. Luo* (Xi'an Jiaotong University), R.S. Wu (UC Santa Cruz) & J.H. Gao (Xi'an Jiaotong University)

Study on Shunt Active Power Filter with Improved Control Method Yaheng Ren1,a*, Xiaozhi Gao2,b, Runduo Wang3,c

Power Quality Improvement in an Autonomous Microgrid under Nonlinear Load using Control Strategies

Aalborg Universitet. Published in: I E E E Transactions on Industry Applications. DOI (link to publication from Publisher): /TIA.2016.

An Optimal Control Load Demand Sharing Strategy for Multi-Feeders in Islanded Microgrid

PRACTICAL, COMPUTATION EFFICIENT HIGH-ORDER NEURAL NETWORK FOR ROTATION AND SHIFT INVARIANT PATTERN RECOGNITION. Evgeny Artyomov and Orly Yadid-Pecht

Graph Method for Solving Switched Capacitors Circuits

Development of a High Bandwidth, High Power Linear Amplifier for a Precision Fast Tool Servo System

A Novel Soft-Switching Two-Switch Flyback Converter with a Wide Operating Range and Regenerative Clamping

Hybrid Power Line Conditioner Based on Two Parallel Converters Topology

A Single-Phase Dual-Stage PV-Grid System with Active Filtering

ACTIVE RESISTANCE EMULATION IN THREE-PHASE RECTIFIER WITH SUBOPTIMAL CURRENT INJECTION

Mitigation of Harmonics in Micro Grid using Photo Voltaic cell interfaced Shunt Active Power Filter

Latency Insertion Method (LIM) for IR Drop Analysis in Power Grid

An Adaptive Over-current Protection Scheme for MV Distribution Networks Including DG

Efficient Large Integers Arithmetic by Adopting Squaring and Complement Recoding Techniques

Static Voltage and Frequency Regulation of Standalone Wind Energy Conversion System

Parameter Free Iterative Decoding Metrics for Non-Coherent Orthogonal Modulation

Dynamic Optimization. Assignment 1. Sasanka Nagavalli January 29, 2013 Robotics Institute Carnegie Mellon University

The Effect Of Phase-Shifting Transformer On Total Consumers Payments

Hassan II University, Casablanca, Morocco

Digital Differential Protection of Power Transformer Using Matlab

Control of Drivetrain Boost DC DC Converter

Chapter 13. Filters Introduction Ideal Filter

Three Phase Active Conditioner for Harmonics Mitigation

Aalborg Universitet. Published in: I E E E Transactions on Industrial Electronics. DOI (link to publication from Publisher): /TIE.2014.

Interharmonic Mitigation Using Boost Converter In Variable Speed Drives

A MODIFIED DIFFERENTIAL EVOLUTION ALGORITHM IN SPARSE LINEAR ANTENNA ARRAY SYNTHESIS

Microgrids. Microgrid

Figure 1. DC-DC Boost Converter

Priority based Dynamic Multiple Robot Path Planning

High Speed ADC Sampling Transients

Comparison of V I c control with Voltage Mode and Current Mode controls for high frequency (MHz) and very fast response applications

Unified Power Quality Conditioner (UPQC) During Voltage Sag and Swell

BI-DIRECTIONAL EDGE-RESONANT SWITCHED CAPACITOR CELL-ASSISTED SOFT-SWITCHING PWM DC DC CONVERTER FOR RENEWABLE ENERGY APPLICATIONS

A High-Sensitivity Oversampling Digital Signal Detection Technique for CMOS Image Sensors Using Non-destructive Intermediate High-Speed Readout Mode

熊本大学学術リポジトリ. Kumamoto University Repositor

Realization of Unified Power Quality Conditioner for Mitigating All Voltage Collapse Issues

Power Factor Correction with AC-DC Buck Converter

ANALYTICAL DESIGN AND SIMULATION OF A STATCOM FOR COMPENSATING OF REACTIVE POWER CONNECTED TO NON- LINEAR LOADS IN POWER SYSTEMS

Probable Optimization of Reactive Power in distribution systems, in presence of distributed generation sources conjugated to network and islanding

A Current Differential Line Protection Using a Synchronous Reference Frame Approach

AC-DC CONVERTER FIRING ERROR DETECTION

Chapter 2 Two-Degree-of-Freedom PID Controllers Structures

Time-frequency Analysis Based State Diagnosis of Transformers Windings under the Short-Circuit Shock

A Facts Device: Distributed Power-Flow Controller (DPFC)

An Efficient Bridgeless PFC Cuk Converter Based PMBLDCM Drive

Application of Intelligent Voltage Control System to Korean Power Systems

Power quality enhancement using cascaded multilevel inverter based shunt hybrid active power filter

On the Use of Harmonic Detection Algorithms for Active Power Filtering Control

Implementation of Fan6982 Single Phase Apfc with Analog Controller

PERFORMANCE OF SHUNT ACTIVE FILTER IN ALL-ELECTRIC SHIP (AES)

STUDY OF MATRIX CONVERTER BASED UNIFIED POWER FLOW CONTROLLER APPLIED PI-D CONTROLLER

Title Power electronic interfaces in Micro grids. Dejene

Research of Dispatching Method in Elevator Group Control System Based on Fuzzy Neural Network. Yufeng Dai a, Yun Du b

Selective Harmonic Mitigation Technique for Cascaded H-Bridge Converters with Equal DC Link Voltages

A High-Speed Multiplication Algorithm Using Modified Partial Product Reduction Tree

Transcription:

Internatonal Conference on Renewable Energes and Power Qualty (ICREPQ 18) Salamanca (Span), 1 th to 3 th March, 018 eçãtuä XÇÜzç tçw céãü dâtä àç ]ÉâÜÇtÄ (RE&PQJ) ISSN 17-038 X, No.16 Aprl 018 Power Calculaton Algorthm for Sngle-Phase Droop-Operated Inverters Consderng Nonlnear Loads J. El Marachet*, J. Matas **, Helena Martín, Abdullah Abusorrah** * Department of Electronc Engneerng, Unversdad Poltécnca de Cataluña (UPC), Barcelona, Span. Department of Electrc Engneerng, Unversdad Poltécnca de Cataluña (UPC), Barcelona, Span. **Renewable Energy Research group, Kng Abdulazz Unversty (KAU), Jeddah, Saud Araba. Abstract The average actve and reactve powers, P av and Q av, are crucal parameters that have to be calculated when sharng common loads between parallelzed droop-operated sngle-phase nverters. However, low-pass flters () wth very low cut-off frequency should be used to mnmze the dstorton mpact n the ampltude and frequency references proded by the droop equatons. Ths forces the control to operate at a very low dynamc velocty, degradng the stablty of the parallelzed system. For ths reason, dfferent solutons had been proposed to ncrease the droop operaton velocty n lterature, but wth the consderaton of only sharng lnear loads. The ssues derved from the sharng of nonlnear loads had not been properly consdered. Ths paper proposes a method to calculate P av and Q av usng second order generalzed ntegrators (SOGI) that ncrease the velocty of the droop control algorthm consderng nonlnear loads as the desgn worst case scenaro. Then t s employed a double SOGI (DSOGI) approach to flter the current non-snusodal waveform and prode the fundamental component, whch results n a faster transent response and mproves the system's stablty. The proposed calculaton method shows to be faster than other approaches when consderng nonlnear loads. Smulatons are proded to valdate the proposal. Keywords-component; Actve and reactve power calculaton, sngle-phase nverters, nonlnear loads, nverter parallelzaton, droop method, trade-off speed and accuracy. I. INTRODUCTION The calculaton of the averaged actve, P av, and reactve, Q av, powers s an mportant aspect n the droop based local control algorthm used to parallel sngle-phase nverters wthout ntercommuncaton, snce t has a crtcal nfluence on the transent response speed of the nverter and n the system stablty [1]-[3]. The calculaton of P av and Q av had been usually performed by the multplcatons of the nverter delvered output current, o, wth the nverter output ltage, v o, and wth ts π/ phase shfted verson, v o, for obtanng the actve and reactve nstantaneous powers, p and q, respectvely. A should be appled to acheve the averaged values of p and q and for remong the double frequency component resultng for the multplcaton of these snusodal sgnals [4], [5] and [6]-[1]. In ths operaton, v o can be obtaned by dfferent approaches such as a transport delay (TD) n [13] and [14], an etended three-phase dq SRF approach appled to sngle-phase systems n [15] and [16], and a method usng the quadrature output of a SOGI flter n [17]. In [18] a method based on SOGI for calculaton of powers and later cancellng the double frequency component smlarly to [6] had been proposed. Although the calculaton tme was reduced n one order of magntude aganst lnear loads, ths method employed also a for obtanng P av and Q av, whch slows down the transent response. Moreover, a proposal based on a dscrete Fourer transform (DFT) was presented n [19] for etractng averaged values, but t ntroduced a severe delay that makes t unsutable when abrupt changes of load occur. For ths reason, n [0] a method was presented for calculatng the actve and reactve powers through optmzng a cost functon of P and Q by means of LMS adaptve algorthm. However, appromatons acheved n the P and Q epressons are only possble n steady state and aganst lnear loads. In general, all these proposals have n common the objectve of tryng to enhance somehow the droop-operated system stablty by means of acheng a fast and accurate calculaton of the averaged powers for the droop references. However, the valdty of these approaches s only partal when sharng nonlnear loads. Ths paper proposes a modfcaton n the power evaluaton scheme proposed n [6] and [18], usng a DSOGI approach for obtanng the fundamental component of the nverter output current, of, whch s used n the power calculaton aganst a RC rectfed nonlnear load wth a 15% total harmonc dstorton (THD). The flterng capablty of the DSOGI s determned by ts dampng factor parameter, ξ, that wll be desgned for keepng the rpple n the calculated powers below a predefned desred value. The use of the DSOGI allows the remong of the from the ntal calculaton scheme and reduces the tme for obtanng the averaged powers. Ths https://do.org/10.4084/repqj16.00 19 RE&PQJ, Vol.1, No.16, Aprl 018

DSOGI structure must be desgned wth a proper value of ξ for gng a lower settlng tme durng transents. The proposal s then compared wth the classcal droop approach and wth [6] and [18] under the assumpton of causng the same ampltude rpple at the obtaned powers for a gven RC rectfed nonlnear load. The obtaned responses show to be faster when abrupt load changes occur and determne to whch pont the speed and stablty of the system can be enhanced. In Secton II the calculaton block n a droop based local control structure s contetualzed and descrbed, for a snglephase nverter. In Secton III, an advanced method for calculatng P-Q based on [18] s shown. Secton IV proposes the novel calculaton of actve and reactve powers based on a DSOGI flter approach and also shows the smulaton results for valdatng the proposal. II. POWER CALCULATION IN SINGLE-PHASE DROOP- OPERATED INVERTERS Ths secton deals wth the power calculaton of a sngle-phase nverter when sharng a common load wth another parallelzed nverter usng the droop method. Ths secton and the rest of the paper s focused on the power calculaton dynamcs of one of the nverters n attempt to ew the problems when sharng a nonlnear load, to propose a soluton to deal wth the dstorted currents, and to see the relatonshp between the transent speed and the flterng capablty of the power calculaton, whch wll mprove the stablty of the system and the accuracy of power sharng. Fg. 1 represents a basc scheme of a sngle-phase nverter that s operated wth the droop method. In ths fgure t can be seen that the control scheme s composed by a P-Q power calculaton block, a droop method block, and nverter's control nner loops plus pulse wdth modulaton block (PWM). The P- Q block uses the nverter's output ltage and current, v o and o, to delver the averaged powers, P av and Q av, to the droop block that uses them to generate the nverter's reference ltage, v ref, to command the nverter power swtches through the nner loops plus PWM control block. Sngle-Phase Power Inverter (Inv. #1) Power Swtches PWM CTRL L vref L DROOP Method C o o v o P-Q Power CALC v o Load (Inv. #) Fg. 1. Droop-based control scheme of a sngle-phase nverter. Fg. shows the tradtonal power calculaton that obtans the averaged powers, after the multplcatons between ltages and current to produce an nstantaneous actve, p, and reactve, q, powers. Then, s are used to obtan the respectve averaged powers [17]. -π/ p q Flterng Flterng o Averaged Power products powers Fg. Block dagram of conventonal P-Q power calculaton prodng averaged powers. The droop control method determnes the operatng frequency and ampltude ltage of the nverter through the followng equatons, when lne mpedance and output nverter s mpedance are consdered to be manly nductve: = (1) = () where m and n are the droop coeffcents, ω n and V n are the nomnal frequency and ampltude and ω * and V * are the proded frequency and ampltude references. These references are used to generate the followng snusodal ltage reference for the nverter's nner control loops to follow. = ( ) (3) Assumng that the output ltage and current of the nverter are [15] ( )= ( ) (4) ( )= ( ) (5) where V and I are the ltage and current ampltudes, s the fundamental frequency and o s the phase angle between v o and o. The quadrature ltage, wth a π/ delay, s defned as ( )= sn( ) (6) So, the nstantaneous actve and reactve powers could be formulated as = ( ) ( )= ( ) = = (7) And, n a smlar way, = ( ) ( )= ( ) = = (8) where P av and Q av are the average actve and reactve powers and and are the oscllatng components at twce of the fundamental operatng frequency proded by the droop method. The s used to flter these nstantaneous powers, see Fg., should have a low cut-off frequency value, fc, n order to flter properly the double frequency components, and. Ths value s typcally of one or two order of magntude lower than the nverter's operatng frequency [1], []. The fc value fnally determnes the speed of the droop method, whch s too slow. Moreover, fc should be reduced more to be able to handle the sharng of nonlnear loads. Also, nonlnear loads may ntroduce strong dstortons n the nverter current, [3], whch are drectly conveyed to the nstantaneous powers. Therefore, calculaton of powers become much more comple and not only the double frequency power components shall be removed. In sngle phase parallelzed nverters the man concern when sharng nonlnear loads s to ad the ecessve power rpple nduced by these loads. The power rpples cause https://do.org/10.4084/repqj16.00 0 RE&PQJ, Vol.1, No.16, Aprl 018

strong dstortng swngs n the proded droop frequency and ampltude references, ω * and V *, whch, n turn, cause dstorton n nverter's ltage reference, v ref, and prokes a bad droop operaton of the system. In fact, the value of fc should be desgned to be typcally less than 1Hz n order to ad the mpact of nonlnear loads. III. ADVANCED P-Q POWER CALCULATION METHOD A SOGI s a specal lnear flter wth one nput, v n, and two outputs, v d and v q, one n-phase and the other π/ delayed wth respect to the nput, respectvely. These outputs have the followng band-pass flter (BPF) and transfer functons relatonshps regardng to the nput n ( s) ξω s Hd ( s) = = (9) v ( s) s ξ ω s ω n v q( s) ξ Hq( s) = = (10) v ( s) s ξ ω s ω where ξ s the flter dampng factor and ω ts tunng center frequency. These two parameters determne the settlng tme of the transent response of ths flter, whch s (11) Fg. 3 shows the proposed P-Q calculaton method n [18] for acceleratng the calculaton of the actve and reactve powers. o -π/ p q SOGI1 SOGI p q Fg. 3. P-Q calculaton block scheme based on [18]. The SOGI1 and SOGI n Fg. 3 are used for etractng the pulsatng double frequency power components, and, respectvely. These SOGI are tuned both at ω o and ξ 1 =ξ =1. The s are used for a better flterng and prode the averaged powers P av.and Q av. Fg. 3 do not show the method for generatng the π/ delay snce t s not mentoned n [18]. Therefore another SOGI, SOGI0, tuned at ω o and ξ=0.707, s used for generatng ths delay as shown n Fg. 4, for adng delay ssues reported n [13], [14], [19]. ξ SOGI0 ξ o vq p q SOGI1 SOGI p q Fg. 4. P-Q calculaton block scheme of Fg. 3 usng an addtonal SOGI for generatng the -π/ delay. Fg. 5 shows the smulatons results after usng the P-Q scheme of Fg. 4 when sharng a lnear load that produces a current perturbaton from 4A to 8A at tme 1s. For sake of smplcty Fg. 5 only shows the actve power, P av. The dynamcs are compared wth the obtaned by the conventonal droop method depcted n Fg., named as P droop, usng a wth fc=1hz. The P av power of Fg. 4 s named as P adv to dfferentate t, from now on, from the other methods. The cut-off frequency for the advanced power calculator was desgned to be 10Hz. Lnear current (A) Actve Power P (W) 8 4 0-4 -8 0.98 0.99 1 1.01 1.0 1.03 1.04 1.05 1300 100 1100 1000 900 800 700 600 1 1. 1.4 1.6 1.8 Fg. 5. P droop and P adv transent response for a lnear load current perturbaton from 4A to 8A at 1s: up) Detal of the perturbaton; down) P droop and P adv calculated powers. As shown n Fg. 5, the P adv dynamcs remove the double frequency component and s much faster than the P droop, whch stll contans a small double frequency component. These results are compatble wth those reported n [18]. However, the perfect dynamc behaor depcted n Fg. 5 vanshes when a nonlnear load that nduces dstorton n current s shared. Fg. 6 shows the dynamcs of the system when a nonlnear load s used. In ths case, the load s a rectfer supplyng a RC load that draws a hghly dstorted current wth 4A peak and that suffers a perturbaton that pushes the peak to 8A. The smulaton parameters are shown n Table I. TABLE I. SIMULATION PARAMETERS FOR FIG. 4. V n 311V ω n π50(rad/s) R at t <1s; R at t >1s 1100Ω;37 Ω C 470µF Current THD 15% 0.7, 1 fc droop; fc adv 1Hz; 10Hz Padv (10Hz) As shown n Fg. 6, the dynamcs of the proposed method n [18] were never consdered usng a nonlnear load, smlarly to other proposals mentoned n Secton I. Thus, n the presence https://do.org/10.4084/repqj16.00 1 RE&PQJ, Vol.1, No.16, Aprl 018

of nonlnear loads the method has ecessve steady state rpple that corrupts the calculated powers, oppostely to the stated n [18]. Fortunately, the flterng capabltes of the n Fg. 4 can be mproved by reducng fc to.hz. Therefore, the rpple of P adv s dmnshed untl the same level than the produced by the conventonal droop method. Fg. 7 shows ths stuaton and also shows how the advanced method s stll faster calculatng P adv than the conventonal droop controller. Note that both methods have been compared under the same dynamcal and dstorton-attenuaton condtons, beng better the advanced one but wth less effectty than ntally argued. Nonlnear current (A) Actve Power P (W) Actve Power P (W) Fg. 6. P droop and P adv transent response for a nonlnear rectfer-type load perturbaton n current from 4A peak to 8A peak at 1s: up) Detal of the dstorted load current perturbaton from 4A peak to 8A peak; mddle) P droop and P adv calculated powers; down) Detal of the calculated powers showng ther rpple. Actve Power P (W) 8 4 0-4 -8 0.98 0.99 1 1.01 1.0 1.03 1.04 1.05 300 80 60 40 0 00 180 160 140 10 100 80 300 80 60 40 Padv (10Hz) 1 1. 1.4 1.6 1.8 0 1.96 1.965 1.97 1.975 1.98 1.985 1.99 1.995 60 40 0 00 180 160 140 10 100 80 Padv (10Hz) Padv (.Hz) 1 1. 1.4 1.6 1.8 Actve Power P (W) 60 55 50 45 Fg. 7. P droop and P adv transent response for a nonlnear rectfer-type load perturbaton from 4A peak to 8A peak at 1s: up) P droop and P adv calculated powers, for P adv wth a wth fc=.hz; down) Detal of the calculated powers showng ther rpple. Note also that there s a postve offset n the calculated actve power at steady state, snce the mean value of P adv s slghtly hgher than ths of P droop, see lower plot of Fg. 7. IV. PROPOSED P-Q DSOGI POWER CALCULATION METHOD Fg. 8 shows the proposed power calculaton method that conssts n a modfcaton of Fg. 4 to enhance the dynamcal response when sharng nonlnear loads. ξ SOGI0 ξ vq OF DSOGI SOGI3 SOGI4 o d d ξc ξ ξ OF p' q' SOGI1 SOGI p q Padv (.Hz) 40 1.96 1.965 1.97 1.975 1.98 1.985 1.99 1.995 Fg. 8. Proposed P-Q calculaton method for dealng wth nonlnear loads and usng a DSOGI approach. When the proposed nonlnear load s connected, the output current of the nverter can be epressed as [3]: ( ) = ( ) (h ) (1) where the sub nde h represents the harmonc number, N the mamum set of harmoncs, I DC the DC component, and are the ampltudes of the fundamental and harmonc components, respectvely. The fundamental frequency s and h represents ts harmonc multples. Fnally, and are the phase-shft of the fundamental and of each harmonc component, respectvely. Then, the nstantaneous powers should be redefned as: = ( ) h h h (13) = ( ) h h h (14) Consequently (13) and (14) contan the DC, double frequency and hgher harmonc order components of the powers and the subtracton of only the double frequency component s not enough for the proper calculaton of P av and Q av. Then, t becomes necessary the flterng of the measured current, o, n order to reject ts harmoncs components preously for resultng n a smpler and faster calculaton of powers as n (7) and (8). For ths purpose, n Fg. 8, the DSOGI, formed by SOGI3 & 4, s used to flter the non-snusodal output current and to prode ts fundamental component. Then, t s obtaned the product wth the n-phase and the quadrature ltages and https://do.org/10.4084/repqj16.00 RE&PQJ, Vol.1, No.16, Aprl 018

generate nstantaneous powers wth only the double frequency components and wthout thrd or hgher order harmoncs. Later, SOGI1 and SOGI are used for only remong the double frequency components wth the help of the subtractng blocks. The resultng value s named as P DSOGI for the actve power, and Q DSOGI for the reactve one. In Fg. 8, the DSOGI BPF flterng acton s so strong that allows to remove the from the scheme, whch accelerates further the P-Q dynamc response. Also, the subharmonc components of current are rejected due to the BPF behaor of the SOGI flter. In ths case, because the DSOGI s used n the current, the transent response speed s determned by (11) and t relays manly n ξc, snce the frequency proded by the droop method, ω*, vares n a small range around the nomnal ω n. Therefore, the DSOGI dampng factor s tuned to flter the non-snusodal current to a pont n whch the produced power rpple s dentcal n ampltude as the conventonal droop controller. In ths case, ths s acheved for ξc=ξ 3 = ξ 4 =0.1. Fg. 9 shows the smulaton results, whch yeld that the proposed method s faster calculatng the actve power and acheves a lower steady state rpple. Actve Power P (W) Actve Power P (W) 60 40 0 00 180 160 140 10 100 80 60 55 50 45 Padv (.Hz) P DSOGI (ch=0.1) 1 1. 1.4 1.6 1.8 Padv (.Hz) P (ch=0.1) DSOGI 40 1.96 1.965 1.97 1.975 1.98 1.985 1.99 1.995 Fg. 9. Actve power transent responses for a nonlnear rectfer-type load perturbaton from 4A peak to 8A peak at 1s: up) Fundamental current of proded by the DSOGI flter; mddle) P DSOGI, Padv and Pdroop calculated powers; down) Detal of calculated powers at steady-state. Note that the calculated P DSOGI power has not postve offset error n steady state n contradstncton wth P adv. Ths means that the proposed method s also more accurate than proposed n [18]. Table II yelds the measured rse tme for the transent responses depcted n Fg. 9, whch shows that the proposed method mples a 60.00% and a 79.69% reducton n the rse tme regardng P adv and P droop, respectvely. TABLE II. RISE TIME MEASUREMENTS FROM FIG. 9. Measurements 35ms P droop P adv 165ms P DSOGI 66ms Improvements Improvement P DSOGI vs P adv 60.00% Improvement P DSOGI vs P droop 79.69% V. CONCLUSIONS In ths work a P-Q calculaton method has been proposed for sngle-phase parallelzed nverters wth the purpose of mprong the speed and accuracy of the power calculaton when they are sharng nonlnear loads. The dynamc response of the power calculaton used n the conventonal droop method and n another advanced method s analyzed frst to show ther lmtatons n speed and accuracy when sharng a RC-rectfed type nonlnear load. For ths reason a novel calculaton method has been proposed and compared wth the preous ones. The smulatons results, under the same dstortng condtons n current, show how the proposed method obtans the P-Q powers at a 76.69% faster than the proposed one for the conventonal droop controller. Also t obtans also the P-Q powers at a 60.00% faster than the advanced one based on [18]. Ths mprovement supposes an enhancement n the droop speed operaton under nonsnusodal condtons n current that may lead to a better dynamc performance of non-herarchcally controlled nverters n mcrogrds. Further works wll be carred out to determne the mprovements n load sharng dynamcs for the paralleled systems and n ts stablty. REFERENCES [1] E. A. A. Coelho, P. C. Cortzo and P. F. D. Garca, "Small sgnal stablty for sngle phase nverter connected to stff AC system," Conf. Record of the 1999 IEEE Industry Applcatons Conf. 3th IAS Annual Meetng (Cat. No.99CH36370), pp. 180-187 l.4, 1999. [] M. Soshnskaya, W. H. J. Graus, J. M. Guerrero, J. C. Vasquez, "Mcrogrds: eperences barrers and success factors", Renew. Sustan. Energy Rev., l. 40, pp. 659-67, 014. [3] L. S. Araújo, D. I. Narváez, T. G. Squera and M. G. Vllalva, "Modfed droop control for low ltage sngle phase solated mcrogrds," 016 IEEE Int. Conf. on Automatca (ICA-ACCA), pp. 1-6, 016. [4] "IEEE Standard defntons for the measurement of electrc power quanttes under snusodal, nonsnusodal, balanced or unbalanced condtons, IEEE Standard 1459-010", Mar. 010. [5] J. Lu, Y. Wen, Yngchao Zhang and W. Wen, "A novel power calculaton method based on second order general ntegrator," 016 IEEE 8th Int. Power Electroncs and Moton Control Conf. (IPEMC- ECCE Asa), Hefe, pp. 1975-1979, 016. [6] E. T. Andrade, P. E. M. J. Rbero, J. O. P. Pnto, C. L. Chen, J. S. La and N. Kees, "A novel power calculaton method for droop-control mcrogrd systems," 01 7 th Annual IEEE Appled Power Electroncs Conf. and Ep., (APEC), pp. 54-58., 01. [7] Z. Ren, M. Gao, Q. Mo, K. Lu, W. Yao, M. Chen and Z. Qan "Power Calculaton Method Used n Wreless Parallel Inverters Under Nonlnear Load Condtons," n Proc. of APEC, pp. 1674-1677, 010. [8] E.C. Furtado, L.A. Agurre and L.A.B. Torres, "UPS Parallel Balanced Operaton Wthout Eplct Estmaton of Reactve Power - A Smpler Scheme," IEEE Trans. on Crcuts and Systems II: Epress Brefs, l.55, no.10, pp. 1061-1065, Oct. 008. [9] J.M. Guerrero, J. Matas, L. G. Vcuna; M. Castlla and J. Mret, "Decentralzed Control for Parallel Operaton of Dstrbuted Generaton https://do.org/10.4084/repqj16.00 3 RE&PQJ, Vol.1, No.16, Aprl 018

Inverters Usng Resstve Output Impedance," IEEE Trans. on Industral Electroncs, l.54, no., pp. 994-1004, Apr. 007. [10] S. A. O. Slva, R. Nochadlo and R.A. Modesto, Sngle-phase PLL structure usng modfed p-q theory for utlty connected systems, n Proc. of IEEE PESC, pp. 4706-4711, 008. [11] H. Wang, X. Yue, X. Pe and Y. Kang, A new method of power calculaton based on parallel nverters, n Proc. of IEEE EPE-PEMC, pp. 1573-1576, 009. [1] Yu, D. Xu and K. Ma, A Novel Accurate Actve and Reactve Power Calculaton Method for Paralleled UPS System, n Proc. of APEC, pp. 169 175, 009. [13] Zheng Ren; Mngzh Gao; Qong Mo; Kun Lu; We Yao; Mn Chen; Zhaomn Qan, "Power calculaton method used n wreless parallel nverters under nonlnear load condtons," Appled Power Electroncs Conf. and Ep., (APEC), 010 5 th Annual IEEE, pp.1674,1677, 1-5 Feb. 010. [14] We Yu; Dehong Xu; Kuan Ma, "A Novel Accurate Actve and Reactve Power Calculaton Method for Paralleled UPS System," Appled Power Electroncs Conf. and Ep., 009. (APEC 009). 4 th Annual IEEE, pp.169,175, 15-19 Feb. 009 [15] H. Akag, E.H. Watanabe, M. Aredes, "Instantaneous Power Theory and Applcaton to Power Condtonng," Pscataway, NJ: John Wley & Sons, Inc., 007, pp. 5-8 [16] Mngzh Gao; Shangda Yang; Cheng Jn; Zheng Ren; Mn Chen; Zhaomng Qan, "Analyss and epermental valdaton for power calculaton based on p-q theory n sngle-phase wreless-parallel nverters,"appled Power Electroncs Conference and Eposton (APEC), 011 6 th Annual IEEE, pp.60,64, 6-11 March 011 [17] J. Matas, M. Castlla, L. G. d. Vcuña, J. Mret and J. C. Vasquez, "Vrtual Impedance Loop for Droop-Controlled Sngle-Phase Parallel Inverters Usng a Second-Order General-Integrator Scheme," n IEEE Trans. on Power Electroncs, l. 5, no. 1, pp. 993-300, Dec. 010. [18] S. Tolan and P. Sensarma, "An mproved droop controller for parallel operaton of sngle-phase nverters usng R-C output mpedance," 01 IEEE Int. Conf. on Power Electroncs, Drves and Energy Systems (PEDES), Bengaluru, 01, pp. 1-6. [19] Y. Yang, F. Blaabjerg and H. Wang, "Low ltage rde-through of sngle-phase transformerless photoltac nverters," 013 IEEE Energy Converson Congress and Eposton, Denver, CO, 013, pp. 476-4769. [0] Y. Yang and F. Blaabjerg, "A new power calculaton method for snglephase grd-connected systems," 013 IEEE Internatonal Symposum on Industral Electroncs, Tape, Tawan, 013, pp. 1-6. [1] J. M. Guerrero, N. Berbel, J. Matas, L. G. de Vcuna and J. Mret, "Decentralzed Control for Parallel Operaton of Dstrbuted Generaton Inverters n Mcrogrds Usng Resstve Output Impedance," IECON 006-3nd Annual Conference on IEEE Industral Electroncs, Pars, 006, pp. 5149-5154. [] H. Song and K. Nam, Dual current control scheme for PWM converter under unbalanced nput ltage condtons, IEEE Trans. Ind. Electron., l. 46, no. 5, pp. 953-959, Oct. 1991. [3] IEEE Standard Defntons for the Measurement of Electrc Power Quanttes Under Snusodal, Nonsnusodal, Balanced, or Unbalanced Condtons - Redlne," n IEEE Std 1459-010 (Reson of IEEE Std 1459-000) - Redlne, l., no., pp.1-5, March 19 010. https://do.org/10.4084/repqj16.00 4 RE&PQJ, Vol.1, No.16, Aprl 018