Micro Motion Model 5700 Transmitter ATEX Zone 2/22 Installation Instructions II 3 G or II 3 (2) G/EPL Gc & II 3 D/EPL Dc

Similar documents
Micro Motion Model 5700 Transmitter IECEx Zone 2/22 Installation Instructions EPL Gc and EPL Dc

Installation Instructions P/N MMI , Rev. AA July ATEX Installation Instructions for Micro Motion Model 3500 Transmitters

ATEX Installation Instructions for Micro Motion CMF400 Sensors with Booster Amplifier

Installation Instructions P/N MMI , Rev. AA July ATEX Installation Instructions for Micro Motion Model RFT9739 Transmitters

Rev ECN Description Approval Date AA Release to Approvals RCS 10/9/12

Rev ECN Description Approval Date AA Release to Approvals RCS 10/9/12

ATEX Installation Drawings and Instructions

Power supply. Calibration. Surface finishing. Seal. Process connection

IECEx Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers

DPharp Differential Pressure and Pressure Transmitters

Certificate of Compliance

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

Micro Motion Specific Gravity Meters (SGM)

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

Emerson (Appleton Group ATX)

Micro Motion Specific Gravity Meters (SGM)

Annex 1 to Certificate of Conformity IECEx KEM X Issue No. 8 Rota Yokogawa Rotamass 3 Series Coriolis Mass Flowmeter

2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER

Product manual wire programmable RTD transmitter

CSA Hazardous Area Approvals Fisher FIELDVUE DVC6005 Series Remote Mount Digital Valve Controllers

Ex instruction manual. Rotamass Coriolis mass flow meter ATEX. IM 01U10X01-00EN-R_002, 2nd edition,

D1035S INSTRUCTION MANUAL. Frequency-Pulse Isolating Repeater DIN Rail Model D1035S. D Frequency-Pulse Isolating Repeater

Isolators A3/1. Ex i Power Supply Field Circuit Ex i Series

CERTIFICATE OF COMPLIANCE

CSA Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers

Ex instruction manual. Rotamass Coriolis mass flow meter. IECEx. IM 01U10X02-00EN-R_002, 2nd edition,

FM Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers

Attachment to Certificate IECEx PTB X

Description. Annexe to: IECEx CML X Issue 1. Isolating Amplifier D461

General Specifications

A9000Px Power/Signal Adapter Installation Drawing for Emerson Transmitters

Micro Motion LF-Series Low Flow Sensor and Transmitter

User's Manual. ROTAMASS Total Insight Coriolis Mass Flow and Density Meter Explosion Proof Type Manual IECEx IM 01U10X02-00EN-R

Micro Motion Series 1000 and Series 2000 Transmitters with MVD Technology

Certificate of Conformity

Isolators A3/1. Vibration Transducer Supply Unit Series

IP26 Series Current to Pneumatic Converter

Inductive sensor slot-type SI2-K08-AP7

Rosemount 848L Logic Transmitter with FOUNDATION Fieldbus

D1061S INSTRUCTION MANUAL. RS422/RS485 Fieldbus Isolating Repeater Din-Rail Model D1061S. D RS422 / RS485 Fieldbus Isolating Repeater

Certificate of Conformity

Remote I/O. 74 Remote I/O. Remote I/O System

STT 3000 Smart Temperature Transmitter Series STT170 Specifications

Rosemount 148 Temperature Transmitter

R88000 T (including ATEX)

TÜV NORD CERT. TÜV NORD CERT GmbH & Co. KG Am TÜV 1 D Hannover. Annexe to IECEx TUN , issue No. 0 Page 1 of 5.

INSTRUCTION MANUAL (ATEX / IECEx)

Sicherheit, auf die Sie sich verlassen können

INSTRUCTION MANUAL. SIL 3 - SIL 2 Digital Output Loop/Bus Powered DIN-Rail Models D1040Q, D1041Q, D1042Q, D1043Q, D1040Q - D1041Q - D1042Q - D1043Q

INSTRUCTION MANUAL. SIL 3 - SIL 2 Digital Output Loop/Bus Powered DIN-Rail Models D1040Q, D1041Q, D1042Q, D1043Q, D1040Q - D1041Q - D1042Q - D1043Q

Specifications. Specifications. Transfer Characteristics Accuracy at 20 C (68 F) Temperature Drift

IECEx Certificate of Conformity

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.

MODEL: B6U-B B6-UNIT. [2] LCD DISPLAY 0: Without 1: With

Micro Motion Fork Viscosity Meters

Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

... for hydraulic and general applications in hazardous areas

IECEx Certificate of Conformity

Operating Manual. isolate501

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5.

Micro Motion Compact Density Meter (CDM)

Binary Output Series 9175

SOLENOID TYPE, CERTIFICATION & PROTECTION CONCEPTS

D1061S INSTRUCTION MANUAL. RS422/RS485 Fieldbus Isolating Repeater Din-Rail Model D1061S. D RS422 / RS485 Fieldbus Isolating Repeater

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

Binary Output without Power Supply Series 9176

[ Rosemount 648 Wireless Temperature Transmitter. Rosemount 648 Wireless. Quick Installation Guide , Rev CA August 2011

Installation guide 873 SmartRadar Control Unit & Antenna Unit

Product Manual wire HART transmitter

Head mounted Temperature Transmitter TF02/TF02-Ex

Micro Motion Model 2400S Transmitters with MVD Technology

Safety Instructions Nivotester FTC625, FTC325

OPTIMASS / 300 / 010 Guidelines for the use of Coriolis meters in hazardous areas

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F

Intrinsic Safety Control Drawing

Fieldbus Isolating Repeater Series 9185/11

Intrinsically Safe Compact Controller CTR 210i. Intrinsically Safe Bargraph Indicator. BGI 210i

Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters

Fisher LCP100 Local Control Panel

IECEx Certificate of Conformity Annexe

SEM210 SERIES. Programmable In-head Universal Temperature Transmitter INDEX SECTION CONTENTS PAGE NO.

Rosemount 248 Wireless Temperature Transmitter

User s Manual. Manual Change No V-E. Please use the attached sheets for the pages listed below in IM 01F06F00-01EN (7th).

Safety Instructions Proline Promass 300

Proline Promass 40. Safety Instructions. NEPSI Zone 1, Zone 21

Temperature Input Module for Zone 1 Series 9482/32

Product manual wire HART 7 temperature transmitter

Rosemount 148 Temperature Transmitter

Rosemount 148 Temperature Transmitter

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex

General Specifications

Thie. Automation Products Rev. Chang Date Name Supersedes Dwg. : Part Class:

Isolators A3/1.

OPTIWAVE 7300 C Supplementary instructions

MODEL: B3HU. Space-saving Two-wire Signal Conditioners B3-UNIT

Rosemount 148 Temperature Transmitter

Precision Junction Boxes

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500

Alphaline Temperature Transmitters

Transcription:

ATEX Installation Instructions EB-20025742 Rev. AC December 2015 Micro Motion Model 5700 Transmitter ATEX Zone 2/22 Installation Instructions II 3 G or II 3 (2) G/EPL Gc & II 3 D/EPL Dc

5700 ATEX Installation Instructions EB-20025742 Rev. AC December 2015 Manufactured and submitted for examination Address Basis for examination Micro Motion, Inc. Boulder, Co. 80301, USA Annex II of Directive 2014/34/EU Subject: Equipment type Transmitter type 5700I1***VA*** Standard basis Code for type of protection Type Examination Certificate EN 60079-0:2012+A11:2013 General requirements EN 60079-11:2012 Type of protection i EN 60079-15:2010 Type of protection n EN 60079-31:2014 Dust Enclosure t II 3 G Ex na nc IIB + H2 T4/T5 Gc or II 3 G Ex na nc IIC T4/T5 Gc and II 3 D Ex tc IIIC T75 C Dc IP66/IP67 OR II 3 G Ex na nc IIB + H2 T4 Gc or II 3 G Ex na nc IIC T4 Gc IP66 OR II 3 G Ex na IIB + H2 T4 Gc or II 3 G Ex na IIC T4 Gc and II 3 D Ex tc IIIC T75 C Dc IP66/67 OR Ex na [ic] IIB + H2 T4 Gc or Ex na [ic] IIC T4 Gc and Ex tc [ib Db] IIIC T75 C Dc IP66/IP67 BVS 14 ATEX E 055 X Subject: Equipment type Transmitter type 5700(C or R)1***VA*** Standard basis Code for type of protection EC Type Examination Certificate EN 60079-0:2012 + A11:2013 General requirements EN 60079-11:2012 Type of protection i EN 60079-15:2010 Type of protection n EN 60079-31:2014 Dust Enclosure t II 3 (2) G Ex na nc [ib Gb] IIB + H2 T4/T5 Gc or II 3 (2) G Ex na nc [ib Gb] IIC T4/T5 Gc and II 3 (2) D Ex tc [ib Db] IIIC T75 C Dc IP66/IP67 OR II 3 (2) G Ex na nc [ib Gb] IIB + H2 T4 Gc or II 3 (2) G Ex na nc [ib Gb] IIC T4 Gc IP66 OR II 3 (2) G Ex na [ic] [ib Gb] IIB + H2 T4 Gc or II 3 (2) G Ex na [ic] [ib Gb] IIC T4 Gc and II 3 (2) D Ex tc [ib Db] IIIC T75 C Dc IP66/IP67 OR Ex na [ic] IIB + H2 T4 Gc or Ex na [ic] IIC T4 Gc and Ex tc [ib Db] IIIC T75 C Dc IP66/IP67 BVS 14 ATEX E 175 X THIS COMPONENT MUST COMPLY WITH REGULATORY AGENCY REQUIREMENTS. NO CHANGES ARE ALLOWED WITHOUT PRIOR AUTHORIZATION FROM MICRO MOTION APPROVALS ENGINEERING 2 of 12

December 2015 5700 ATEX Installation Instructions EB-20025742 Rev. AC Model Designation 1) Transmitter type 5700*1******** Instead of the *** in the complete denomination letters and numerals will be inserted which characterize the following variations: Type 5 7 0 0 * 1 * * * * * * * * Options without influence on explosion protection Approval VA = 5700I = II 3 G Ex na nc ** Gc II 3 D Ex tc ** Dc VA = 5700(C,R) = II 3 (2) G Ex na nc [ib Gb]** Gc II 3 (2) D Ex tc [ib Db]** Dc Letter for conduits Output Options A = Configurable Outputs: Ex na nc C = Ethernet Output :Ex na nc E = Intrinsically Safe Foundation Fieldbus H1: Ex na [ic] N = Non-I.S. Foundation Fieldbus H1: Ex na Display Options 2 = Backlit dual line Display = Ex *** IIB + H 2 T6 Gc 3 = No Display = Ex *** IIC T6 Gc 5 = Backlit dual line Display = Ex *** IIC T6 Gc Letter for mounting I = Integral Mount Transmitter R = 4-wire remote mount transmitter C = 9-wire remote mount transmitter Transmitter Model 3 of 12

5700 ATEX Installation Instructions EB-20025742 Rev. AC December 2015 2) Description The transmitter is, in combination with a sensor, used for measurement of mass flow and data transmission. The electrical circuitry of the transmitters is mounted inside a metal enclosure which is divided into three compartments. In one compartment (electronic compartment) the EMI Terminal Board, Power Supply Board, Feature Board, Core Board and Backplane Board are mounted. When executed with display, there is a window cover available, either marked (for gas application) as IIB + H 2 (type 5700*12**VA***) or IIC (type 5700*15**VA***). The other compartment (terminal compartment) is equipped with terminals for the connection of I/O signals and power. The enclosure can be constructed with a terminal compartment (compartment for sensor connection) for the connection of remotely operating intrinsically safe sensors, type 5700C1***VA*** for a 9 wire connection, or type 5700R1***VA*** for a 4 wire connection. Alternatively, the enclosure can be mounted directly to the sensor via a transition compartment (type 5700I1***VA****). This type of mounting has to be certified separately. The enclosures (electronic compartment, terminal compartment and compartment for sensor connection) also fulfil the requirements for type of protection Protection by enclosures. The transmitter is intended to be used in a hazardous dust environment without change to any of the electronics aspects of the design. Supplement 1 to BVS 14 ATEX E 055 X covers: o Only 5700I (= integral version) o Added SMART Wireless THUM, Model 775, Type Examination Certificate Baseefa 09ATEX0131. Supplement 2 to BVS 14 ATEX E 055 X adds: o Ethernet Output o Fieldbus Output (Intrinsically Safe as well as Non-Intrinsically Safe) Issue 0 to BVS 14 ATEX E 175 X covers: o 5700 C (= 9 wire remote) and 5700R (= 4 wire remote) with [ib] output marking for connection to intrinsically safe sensors. Supplement 1 to BVS 14 ATEX E 175 X covers: o Ethernet Output o Fieldbus Output (Intrinsically Safe ic as well as Non-Intrinsically Safe na ) 4 of 12

December 2015 5700 ATEX Installation Instructions EB-20025742 Rev. AC 3) Parameters 3.1 Mains circuits: 3.1.1 for type 5700*1*(A,E,N)******(J1, terminal 1-2) voltage AC/DC 18-240 V + 10 % max. voltage Um AC/DC 265 V 3.1.2 for type 5700*1*C******(J6, terminal 1-2) voltage AC/DC 18-240 V + 10 % max. voltage Um AC/DC 265 V 3.2 Non intrinsically safe input/output circuits: 3.2.1 For all types(j2, USB) voltage Um AC/DC 10 V 3.2.2 for type 5700*1*A******(J3,terminals 1-10) voltage Um AC/DC 30 V 3.2.3 for type 5700*1*N******(J3,terminals 1-2, FF) voltage Um DC 33 V 3.2.4 for type 5700*1*N******(J3,terminals 3-4, ma) voltage Um DC 30 V 3.2.5 for type 5700*1*N******(J3,terminals 5-6, FO/DO) voltage Um DC 30 V 3.2.6 for type 5700*1*C******(J5,terminals 1-2) voltage Um AC/DC 30 V 3.2.7 for type 5700*1*C******(J7/J8,ETHERNET RJ-45) voltage Un DC 2,4 V 3.3 Intrinsically safe circuits ic : 3.3.1 for type 5700*1*E******(J3,terminals 1-2 FF) voltage Ui DC 30 V current Ii 300 ma power Pi 1,3 W effective internal inductance Li 5 μh effective internal capacitance Ci 0,27 nf 5 of 12

5700 ATEX Installation Instructions EB-20025742 Rev. AC December 2015 3) Parameters (continued) 3.3.1.1 for type 5700*1*E******(J3,terminals 1-2 FF) for the connection of a FIELDBUS circuit in accordance with FISCO model, Annex G of EN 60079-11:2012 voltage Ui DC 33 V current Ii 380 ma power Pi 5,32 W effective internal inductance Li 5 μh effective internal capacitance Ci 0,27 nf 3.3.2 for type 5700*1*E******(J3,terminals 3-4, ma) voltage Ui DC 30 V current Ii 484 ma power Pi 2,05 W effective internal inductance Li 5 μh effective internal capacitance Ci 0,27 nf 3.3.3 for type 5700*1*E******(J3,terminals 5-6, FO/DO) voltage Ui DC 30 V current Ii 484 ma power Pi 2,05 W effective internal inductance Li 5 μh effective internal capacitance Ci 11,27 nf 3.4 Sensor circuits for type 5700R1******** (J1 in J-box, VDC+ RED; VDC- BLK; COM A WHT; COM B GRN); ib voltage Uo DC 17,2 V current; instantaneous Io 0,479 A current; steady state Io 0,272 A power Po 2,06 W type of protection Ex ib IIC max. external inductance Lo 154,9 H max. external capacitance Co 333 nf max. induct/resistance ratio Lo/Ro 17,26 H/ type of protection Ex ib IIB and IIIC max. external inductance Lo 619,8 H max. external capacitance Co 2,04 μf max. induct/resistance ratio Lo/Ro 69,0 H/ 6 of 12

December 2015 5700 ATEX Installation Instructions EB-20025742 Rev. AC 3) Parameters (continued) 3.5 Sensor circuits for type 5700(C or I)1********; ib 3.5.1 Drive circuit; (J2 in J-box, DR+ BRN; DR- RED) voltage Uo DC 10,5 V current; instantaneous Io 1,06 A current; steady state Io 0,272 A power Po 2,13 W internal resistance Ri 9,9 for group IIC max. external capacitance Co 2,41 F max. external inductance Lo 31,6 H max. external induct/resist Lo/Ro 12,77 H/ for group IIB and IIIC max. external capacitance Co 16,8 F max. external inductance Lo 126,6 H max. external induct/resist Lo/Ro 51,1 H/ The maximum external inductance L (sensor coil) can be calculated with the following term: Ri Ro L 2 E 1.5Uo 2 whereby E = 40 μj for group IIC and E = 160 μj for group IIB & IIIC will be inserted. 3.5.2 Pick-off circuits (J1 in J-box, LPO+ GRN; LPO- WHT; RPO+ BLU; RPO- GRY) voltage Uo DC 17,3 V current Io 6,92 ma power Po 30 mw for group IIC max. external capacitance Co 353 nf max. external inductance Lo 742 mh max. external induct/resist Lo/Ro 1,19 mh/ for group IIB and IIIC max. external capacitance Co 2,06 F max. external inductance Lo 2,97 H max. external induct/resist Lo/Ro 4,75 mh/ 7 of 12

5700 ATEX Installation Instructions EB-20025742 Rev. AC December 2015 3) Parameters (continued) 3.5.3 Temperature circuit (J1 in J-box, RTD+ VIO; RTD- ORA; RTD-SIG YEL) voltage Uo DC 17,3 V current Io 19,26 ma power Po 83,3 mw for group IIC max. external capacitance Co 353 nf max. external inductance Lo 95,8 mh max. external induct/resist Lo/Ro 0,42 mh/ for group IIB and IIIC max. external capacitance Co 2,06 F max. external inductance Lo 383 mh max. external induct/resist Lo/Ro 1,68 mh/ 3.6 Sensor circuits for type 5700I1********; na : 3.6.1 Drive circuit; (J2 in J-box, DR+ BRN; DR- RED) Rated voltage DC 10,5 V Rated current 80 ma 3.6.2 Pick-off circuits (J1 in J-box, LPO-WHT, LPO+ GRN; RPO+ BLU; RPO- GRY) Rated voltage DC 17,3 V Rated current 6,92 ma 3.6.3 Temperature circuit(j1 in J-box, RTD+ VIO; RTD- ORA; RTD-SIG YEL) Rated voltage DC 17,3 V Rated current 19,26 ma 3.7 Ambient temperature range Type 5700*1***VA*** Ta -40 C to +65 C 8 of 12

December 2015 5700 ATEX Installation Instructions EB-20025742 Rev. AC 4) Marking type Type 5700*1******** Ta -40 C to +65 C For BVS 14 ATEX E 055 X: type of protection Model 5700I12A*VA*** Model 5700I1(3,5)A*VA*** Model 5700I12C*VA*** Model 5700I1(3,5)C*VA*** Model 5700I12N*VA*** (Ex na) Model 5700I1(3,5)N*VA*** (Ex na) Model 5700I12E*VA*** (Ex na) Model 5700I1(3,5)E*VA*** (Ex na) Model 5700I12**VA*** with THUM 775 Model 5700I1(3,5)**VA*** with THUM 775 II 3G Ex na nc IIB+H 2 T5 Gc II 3G Ex na nc IIC T5 Gc II 3G Ex na nc IIB+H 2 T4 Gc II 3G Ex na nc IIC T4 Gc II 3G Ex na IIB+H 2 T4 Gc II 3G Ex na IIC T4 Gc II 3G Ex na [ic] IIB+H 2 T4 Gc II 3G Ex na [ic] IIC T4 Gc II 3G Ex na nc IIB+H 2 T4 Gc IP66 II 3G Ex na nc IIC T4 Gc IP66 5 min delay time after switch off 9 of 12

5700 ATEX Installation Instructions EB-20025742 Rev. AC December 2015 4) Marking (Continued) type For BVS 14 ATEX E 175 X: type of protection Model 5700(R,C)12A*VA*** Model 5700(R,C)1(3,5)A*VA*** Model 5700(R,C)12C*VA*** Model 5700(R,C)1(3,5)C*VA*** Model 5700(R,C)12N*VA*** (Ex na) Model 5700(R,C)1(3,5)N*VA*** (Ex na) Model 5700(R,C)12E*VA*** (Ex na ic) Model 5700(R,C)1(3,5)E*VA*** (Ex na ic) Model 5700(R,C)12**VA*** with THUM 775 Model 5700(R,C)1(3,5)**VA*** with THUM 775 II 3 (2)G Ex na nc [ib Gb]IIB+H 2 T5 Gc II 3 (2)D Ex tc [ib Db] IIIC T75 C Dc IP66/IP67 II 3 (2)G Ex na nc [ib Gb]IIC T5 Gc II 3 (2)D Ex tc [ib Db] IIIC T75 C Dc IP66/IP67 II 3 (2)G Ex na nc [ib Gb]IIB+H 2 T4 Gc II 3 (2)D Ex tc [ib Db] IIIC T75 C Dc IP66/IP67 II 3 (2)G Ex na nc [ib Gb]IIC T4 Gc II 3 (2)D Ex tc [ib Db] IIIC T75 C Dc IP66/IP67 II 3(2)G Ex na [ib Gb] IIB+H 2 T4 Gc II 3(2)D Ex tc [ib Db] IIIC T75 C Dc IP66/IP67 II 3(2)G Ex na [ib Gb] IIC T4 Gc II 3(2)D Ex tc [ib Db] IIIC T75 C Dc IP66/IP67 II 3(2)G Ex na [ic][ib Gb]IIB+H 2 T4 Gc II 3(2)D Ex tc [ib Db] IIIC T75 C Dc IP66/IP67 II 3(2)G Ex na [ic][ib Gb]IIC T4 Gc II 3(2)D Ex tc [ib Db] IIIC T75 C Dc IP66/IP67 II 3 (2) G Ex na nc [ib Gb] IIB+H 2 T4 Gc IP66 II 3 (2) G Ex na nc [ib Gb] IIC T4 Gc IP66 5 min delay time after switch off 10 of 12

December 2015 5700 ATEX Installation Instructions EB-20025742 Rev. AC 5) Special conditions for safe use / Installation instructions 5.1 For the application of the transmitter in an ambient temperature of less than - 20 C suitable cable and cable entries or conduit entries certified for this condition shall be used. 5.2 For use in explosive atmosphere caused by combustible dust, suitable cables and for that purpose certified cable entries res. blanking plugs shall be used. 5.3 The user interface module shall not be disconnected from the electronic module unless the unit has been de-energized. 5.4 The Rotary and DIP switches on the user interface shall not be switched unless the unit has been de-energized. 5.5 The USB connection in the terminal compartment is only for service facilities and shall only be used when there is no explosive gas or dust atmosphere present. Making connection to this port is only allowed when the equipment is de-energized. 5.6 The windows cover forms one unit and cannot be taken apart without destroying the cover parts. If a cover is damaged it must be replaced by a new cover. 5.7 The transmitter 5700I is intended to be used only in the combination with Micro Motion sensors. The integral combination with sensors must be certified separately. 11 of 12

EB-20025742 Rev AC 2015 Emerson Process Management Micro Motion Inc. USA Worldwide Headquarters 7070 Winchester Circle Boulder, Colorado 80301 T +1 303-527-5200 T +1 800-522-6277 F +1 303-530-8459 www.micromotion.com Emerson Process Management Micro Motion Europe Neonstraat 1 6718 WX Ede The Netherlands T +31 (0) 318 495 555 F +31 (0) 318 495 556 www.micromotion.nl Emerson Process Management Micro Motion Asia 1 Pandan Crescent Singapore 128461 Republic of Singapore T +65 6777-8211 F +65 6770-8003 Emerson Process Management Ltd. Micro Motion United Kingdom Horsfield Way Bredbury Industrial Estate Stockport SK6 2SU U.K. T +44 0870 240 1978 F +44 0800 966 181 Emerson Process Management Micro Motion Japan 1-2-5, Higashi Shinagawa Shinagawa-ku Tokyo 140-0002 Japan T +81 3 5769-6803 F +81 3 5769-6844 2015 Micro Motion, Inc. All rights reserved. The Emerson logo is a trademark and service mark of Emerson Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct Connect marks are marks of one of the Emerson Process Management family of companies. All other marks are property of their respective owners.