Three-Phase, Step-Wave Inverter Circuits

Similar documents
Unit-3-A. AC to AC Voltage Converters

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

Dr.Arkan A.Hussein Power Electronics Fourth Class. 3-Phase Voltage Source Inverter With Square Wave Output

Lecture Note. DC-AC PWM Inverters. Prepared by Dr. Oday A Ahmed Website:

Dr.Arkan A.Hussein Power Electronics Fourth Class. Operation and Analysis of the Three Phase Fully Controlled Bridge Converter

13. DC to AC Converters

6. Explain control characteristics of GTO, MCT, SITH with the help of waveforms and circuit diagrams.

14. DC to AC Converters

High Voltage DC Transmission 2

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

Lecture 19 - Single-phase square-wave inverter

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM

Introduction to Rectifiers and their Performance Parameters

Lecture 4 - Three-phase circuits, transformer and transient analysis of RLC circuits. Figure 4.1

2.0 AC CIRCUITS 2.1 AC VOLTAGE AND CURRENT CALCULATIONS. ECE 4501 Power Systems Laboratory Manual Rev OBJECTIVE

CHAPTER - 3 CONVENTIONAL SOURCE INVERTER FED INDUCTION MOTOR DRIVE. output voltage could be fixed or variable at a fixed or variable frequency.

Module 4. AC to AC Voltage Converters. Version 2 EE IIT, Kharagpur 1

CHAPTER 11. Balanced Three-Phase Circuits

Power Electronics Single Phase Uncontrolled Half Wave Rectifiers. Dr. Firas Obeidat

DOWNLOAD PDF POWER ELECTRONICS DEVICES DRIVERS AND APPLICATIONS

CHAPTER 9. Sinusoidal Steady-State Analysis

Unit-II----Analysis of HVDC Converters

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

LECTURE.3 : AC-DC CONVERSION

Chapter 2 Shunt Active Power Filter

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1

ELEC4240/ELEC9240 POWER ELECTRONICS

Chapter 31 Alternating Current

ECE 2006 University of Minnesota Duluth Lab 11. AC Circuits

VALLIAMMAI ENGINEERING COLLEGE

Experiment 4: Three-Phase DC-AC Inverter

11. Define the term pinch off voltage of MOSFET. (May/June 2012)

ELEC387 Power electronics

Chapter 33. Alternating Current Circuits

Thermal Imaging, Power Quality and Harmonics

Module 4. AC to AC Voltage Converters. Version 2 EE IIT, Kharagpur 1

Lecture Note. Uncontrolled and Controlled Rectifiers

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1

Chapter 6: Alternating Current. An alternating current is an current that reverses its direction at regular intervals.

Nicolò Antonante Kristian Bergaplass Mumba Collins

( ) ON s inductance of 10 mh. The motor draws an average current of 20A at a constant back emf of 80 V, under steady state.

Switching and Semiconductor Switches

AC Power Instructor Notes

Exercise 9: inductor-resistor-capacitor (LRC) circuits

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Switching Angles and DC Link Voltages Optimization for. Multilevel Cascade Inverters

SINGLE-STAGE HIGH-POWER-FACTOR SELF-OSCILLATING ELECTRONIC BALLAST FOR FLUORESCENT LAMPS WITH SOFT START

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

UNIVERSITY QUESTIONS. Unit-1 Introduction to Power Electronics

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

SHUNT ACTIVE POWER FILTER

POWER ELECTRONICS PO POST GRAD POS UATE 2010 AC Ch AC o Ch p o per Prepare Prep d are by: d Dr. Gamal Gam SOwilam SOwila 11 December 2016 ١

Phasor. Phasor Diagram of a Sinusoidal Waveform

Single-Phase Half-Wave Rectifiers

UNIT-III STATOR SIDE CONTROLLED INDUCTION MOTOR DRIVE

Third Harmonics Injection Applied To Three Phase/Three Level/Three Switch Unidirectional PWM Rectifier

CHAPTER 3 H BRIDGE BASED DVR SYSTEM

Electromagnetic Oscillations and Currents. March 23, 2014 Chapter 30 1

3 PHASE INVERTER WITH 180 AND 120 CONDUCTION MODE

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL

International Journal of Advance Engineering and Research Development

Ac fundamentals and AC CIRCUITS. Q1. Explain and derive an expression for generation of AC quantity.

12 Three-phase Controlled Rectifiers

ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

CHAPTER-III MODELING AND IMPLEMENTATION OF PMBLDC MOTOR DRIVE

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

CHAPTER 4 FULL WAVE RECTIFIER. AC DC Conversion

Analysis of Advanced Techniques to Eliminate Harmonics in AC Drives

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

22.0 Harmonics in Industrial Power Systems

Power Electronics. Exercise: Block Operation

Spring 2000 EE361: MIDTERM EXAM 1

POWER ELECTRONICS LAB MANUAL

Electric Circuits II Three-Phase Circuits. Dr. Firas Obeidat

Chapter 6: Alternating Current

Harmonics Elimination Using Shunt Active Filter

Hysteresis Controller and Delta Modulator- Two Viable Schemes for Current Controlled Voltage Source Inverter

Sascha Stegen School of Electrical Engineering, Griffith University, Australia

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

Study Guide for Chapter 11

EE POWER ELECTRONICS UNIT IV INVERTERS

The typical ratio of latching current to holding current in a 20 A thyristor is (A) 5.0 (B) 2.0 (C) 1.0 (D) 0.5

CHAPTER 6 THREE-LEVEL INVERTER WITH LC FILTER

Space Vector PWM and Model Predictive Control for Voltage Source Inverter Control

UNIT 2. Q.1) Describe the functioning of standard signal generator. Ans. Electronic Measurements & Instrumentation

Experiment 1 LRC Transients

Space Vector PWM Voltage Source Inverter Fed to Permanent Magnet Synchronous Motor

Chapter 4. Hybrid series active filter. 4.1 Introduction

DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLY Mamallapuram chennai

Downloaded from / 1

v o v an i L v bn V d Load L v cn D 1 D 3 D 5 i a i b i c D 4 D 6 D 2 Lecture 7 - Uncontrolled Rectifier Circuits III

CHAPTER 4 HARMONICS AND POWER FACTOR

Power Electronics (Sample Questions) Module-1

Power Quality improvement of a three phase four wire system using UPQC

CHAPTER 4 4-PHASE INTERLEAVED BOOST CONVERTER FOR RIPPLE REDUCTION IN THE HPS

8/4/2011. Electric Machines & Drives. Chapter 21 Example of gating pulses on SCR condition

CHAPTER 5 CONTROL SYSTEM DESIGN FOR UPFC

Experiment 9 AC Circuits

Transcription:

0 Three-Phase, Step-Wave Inverter Circuits 0. SKELETON INVERTER CIRCUIT The form of voltage-source inverter (VSI) most commonly used consists of a three-phase, naturally commutated, controlled rectifier providing adjustable direct voltage V as input to a three-phase, force-commutated inverter (Fig. 0.). The rectifier output inverter input section is known as the link. In addition to a shunt capacitor to aid direct voltage stiffness the link usually contains series inductance to limit any transient current that may arise. Figure 0.a shows the skeleton inverter in which the semiconductor rectifier devices are shown as generalized switches S. The notation of the switching devices in Fig. 0. is exactly the same as for the controlled rectifier in Fig. 7. and the naturally commutated inverter of Fig. 9.. In high-power applications the switches are most likely to be SCRs, in which case they must be switched off by forced quenching of the anode voltages. This adds greatly to the complexity and cost of the inverter design and reduces the reliability of its operation. If the inverter devices are GTOs (Fig. 0.b), they can be extinguished using negative gate current. Various forms of transistor switches such as BJTs (Fig. 0.c), and IGBTs (Fig. 0.d) can be extinguished by control of their base currents, as briefly discussed in Chapter. In Fig. 0. the commutating circuitry is not shown. It is assumed in the following analysis that each switch can be opened or closed freely. Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

FIG. Basic form of voltage-source inverter (VSI) [0]. From the power circuit point of view all versions of the skeleton inverter of Fig. 0. are identical. In each case the frequency of the generated voltages depends on the frequency of gating of the switches and the waveforms of the generated voltages depend on the inverter switching mode.the waveforms of the associated circuit currents depend on the load impedances. Many different voltage waveforms can be generated by the use of appropriate switching patterns in the circuit of Fig. 0.. An invariable requirement in threephase systems is that the three-phase output voltages be identical in form but phase displaced by 0 electrical from each other. This does not necessarily create a balanced set of load voltages, in the sinusoidal sense of summing to zero at every instant of the cycle, but it reduces the possibility of gross voltage unbalance. A voltage source inverter is best suited to loads that have a high impedance to harmonic currents, such as a series tuned circuit or an induction motor. The series inductance of such loads often results in operation at low power factors. 0. STEP-WAVE INVERTER VOLTAGE WAVEFORMS For the purpose of voltage waveform fabrication it is convenient to switch the devices of Fig. 0. sequentially at intervals of 60 electrical or one-sixth of a period. The use of a supply having equal positive and negative voltage values V is common. The zero point of the supply is known as the supply zero pole but is not grounded. 0.. Two Simultaneously Conducting Switches If two switches conduct at any instant, a suitable switching pattern is defined in Fig. 0. for no-load operation. The devices are switched in numerical order, and each remains in conduction for 0 electrical. Phase voltages v AN, v BC, and v CN Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

FIG. Skeleton switching circuit of voltage source inverter: (a) general switches, (b) GTO switches, (c) BJT switches, and (d) IGBT switches [0]. Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

Load voltage waveforms with two simultaneously conducting switches. No load and resistive load [0]. FIG. Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

consist of rectangular pulses of height V. If equal resistors R are now connected in star to the load terminals A, B, and C of Fig. 0., the conduction pattern of Fig. 0.4 ensues for the first half period. In interval 0 t /, V van = ILR = = R R V vbn = 0 V vcn = ILR = =+ R R V v = v + v = v v = V AN NB AN BN (0.) In the interval / t /, v = 0 v = I R =+ V v = I R =+ V v AN BN L CN L =+ V In the interval / t, v = I R =+ V v = I R = V v v AN L BN L CN = 0 = V For each interval it is seen that the load current during conduction is (0.) (0.) V V IL = ± =± R R (0.4) The results of Eqs. (0.) (0.4) are seen to be represented by the waveforms of Fig. 0.. For this particular mode of switching the load voltage and current waveforms with star-connected resistive load are therefore identical with the pattern of the open-circuit voltages. The potential of load neutral point N is always midway between V and V and therefore coincides with the potential of the supply midpoint 0. Phase voltage waveform v AN in Fig. 0. is given by an expression 40 60, 60 AN = ( ωt) = V V 0 0, 00 v (0.5) Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

FIG. 4 Current conduction pattern for the case of two simultaneously conducting switches: (a) 0 t 60, (b) 60 t 0, and (c) 0 t 80 [0]. This has the rms value V = v ( ωt) dωt = V = 086. V 0 AN AN The fundamental Fourier coefficients of waveform v AN ( t) are found to be a = AN t t d t = V v ( ω )cos ω ω 0 b = AN t t d t = 0 v ( ω )sin ω ω 0 (0.6) (0.7) (0.8) c a b = + = a = V (0.9) a = tan = tan ( ) = 90 b ψ (0.0) Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

It is seen from Eqs. (0.9) and (0.0) that the fundamental (supply frequency) component of the phase voltages has a peak value ( / ) V,or.V with its origin delayed by 90. This ( / )V fundamental component waveform is sketched in Fig. 0.. The distortion factor of the phase voltage is given by VAN c Distortion factor / = = = V V AN AN (0.) Line voltage v ( t) in Fig. 0. is defined by the relation v ( ωt) = 0, 40, V V V, 60 00, + 80 60 80 0 40 0 60 V (0.) 00 This is found to have fundamental frequency Fourier coefficients of value a = V b =+ V 6 Therefore, c = V ψ = tan = 60 (0.) The fundamental component of v ( t) is therefore given by v 6 ( ωt) = V sin( ωt 60 ) (0.4) It is seen in Fig. 0. that v ( t) leads v AN ( t)by0, as in a balanced threephase system, and comparing Eqs. (0.9) and (0.), the magnitude V is times the magnitude V AN. With a firing pattern of two simultaneously conducting switches the load voltages of Fig. 0. are not retained with inductive load. Instead, the load voltages become irregular with dwell periods that differ with load phase-angle. Because of this, the pattern of two simultaneously conducting switches has only limited application. 0.. Three Simultaneously Conducting Switches A different load voltage waveform is generated if a mode of switching is used whereby three switches conduct at any instant. Once again the switching devices conduct in numerical sequence but now each with a conduction angle of 80 Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

electrical. At any instant of the cycle three switches with consecutive numbering are in conduction simultaneously. The pattern of waveforms obtained on no load is shown in Fig. 0.5. With equal star-connected resistors the current conduction patterns of Fig. 0.6 are true for the first three 60 intervals of the cycle, if the load neutral N is isolated. For each interval, V 4V I = = R+ R/ R (0.5) FIG. 5 Output voltage waveforms with three simultaneously conducting switches. No load [0]. Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

FIG. 6 Current conduction pattern for the case of three simultaneously conducting switches. Star-connected R load: (a) 0 t 60, (b) 60 t 0, and (c) 0 t 80 [0]. In the interval 0 t /, I v = v = R = V 4 vbn = IR = V v = v v = V AN CN AN BN (0.6) Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

In the interval / t, van = vbn = R = V 4 vcn = IR = V v = V In the interval / t, van = vbn = R = V 4 vcn = IR = V v = 0 (0.7) (0.8) The load voltage waveforms obtained with star-connected resistive load are plotted in Fig. 0.7. The phase voltages are seen to be different from the corresponding no-load values (shown as dashed lines), but the line voltages remain unchanged. Although the no-load phase voltages do not sum to zero, the load currents, with three-wire star connection, must sum to zero at every instant of the cycle. In Fig. 0.7 the phase voltage v AN is given by van ( ωt) = 60, 80, V V, 40 60, + 4 0 4 00 V V 0 0 80 00 60 40 (0.9) It can be seen by inspection in Fig. 0.7 that the fundamental frequency component of v AN ( t) is in time phase with it, so that α = 0 α ψ = tan = 0 b (0.0) Fundamental frequency Fourier coefficient b for the load peak phase voltage is found to be 4 b = c = V (0.) The corresponding fundamental (supply) frequency Fourier coefficients for line voltage v ( t) are given by a = V 6 b = V Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

Output voltage waveforms with three simultaneously conducting switches. Starconnected R load, isolated neutral. No-load waveforms [0]. FIG. 7 4 c = V = the phase value ψ = tan = 0 (0.) The positive value 0 for implies that its origin lies to the left of the zero on the scale of Fig. 0.7. Line voltage component ( t) is plotted in Fig. 0.7, consistent with Eq. (0.). Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

The fundamental components of the load voltages, plotted in Fig. 0.7 show that, as with a three-phase sinusoidal system, the line voltage leads its corresponding phase voltage by 0. The rms value of phase voltage v AN ( t) is found to be V = v ( ωt) dωt = V = 094. V 0 AN AN (0.) Combining Eqs. (0.) and (0.) gives the distortion factor of the phase voltage, c VAN = = Distortion factor = V V AN AN (0.4) This is seen to be identical to the value obtained in Eq. (0.) for the phase voltage waveform of Fig. 0. obtained with two simultaneously conducting switches. Although the distortion factors are identical, waveform AN ( t)offig. 0.7 has a slightly greater fundamental value (4/ )V than the corresponding value ( / )V for AN ( t) of Fig. 0., given by Eq. (0.7). The switching mode that utilizes three simultaneously conducting switches is therefore potentially more useful for motor speed control applications. The properties of relevant step waves and square waves are summarized in Table 0.. It can be deduced from the waveforms of Fig. 0.7 that load neutral point N is not at the same potential as the supply neutral point 0. While these points remain isolated, a difference voltage V NO exists that is square wave in form, with amplitude V / and of frequency three times the inverter switching frequency. If the two neutral points are joined, a neutral current will flow that is square wave in form, of amplitude V /R, and of three times the inverter switching frequency. 0. MEASUREMENT OF HARMONIC DISTORTION The extent of waveform distortion for an alternating waveform can be defined in a number of different ways. The best known of the these, the distortion factor defined by Eq. (0.4), was used in connection with the rectifier circuits of Chapters 9. An alternative measure of the amount of distortion is by means of a property known as the total harmonic distortion (THD), which is defined as THD = V AN VAN V ANh = V V AN AN (0.5) Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

Copyright 004 by Marcel Dekker, Inc. All Rights Reserved. TLE 0. Properties of Step Waves [0] Properties of the phase voltage waveform Phase voltage Total Distortion Corresponding line wave form Peak RMS rms factor THD voltage waveform V V V V V υ AN υ AN υ AN ωt ωt ωt 4 V V 6 V =. 7 V =. V = 9. V 4 V 6 V 6 V = = 078. V V = 5. V V V V 09 =. 0955 =. 0955 =. 8 9 9 = 048. = 0. = 0. V V V V V V V υ υ υ ωt ωt ωt V s υ AN ωt V V V 067 =. 4 =. V V υ ωt

For a pure sinusoid V AN V AN, and the THD then has the ideal value of zero. The numerator of Eq. (0.5) is seen to represent the effective sum of the nonfundamental or higher harmonic components V ANh. A comparison of Eqs. (0.4) and (0.5) shows that for any wave, VAN Distortion factor = = V AN + ( THD) (0.6) 0.4 HARMONIC PROPERTIES OF THE SIX-STEP VOLTAGE WAVE The six-step phase voltage waveforms of Fig. 0.7 are defined by the Fourier series v AN 4 ( ωt)= V sin ωt+ sin 5ωt+ sin 7ωt 5 7 + sinωt + sinωt + (0.7) It is seen from Eq. (0.7) that the waveform v AN ( t) of Fig. 0.7 contains no triplen harmonics and its lowest higher harmonic is of order five with an amplitude equal to 0% of the fundamental. The rms value of the function in Eq. (0.7) is given by V AN 4V = + + + + + 5 7 7 4 = V 079. + = 0. 95V + (0.8) which confirms the value obtained by integration in Eq. (0.). For the step wave of Fig. 0.7, substituting Eqs. (0.) and (0.) into Eq. (0.5) gives V THD = ( / ) ( 4/ ) V ( ) 4/ / = = 0. 9 (0.9) Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

From Eq. (0.5) harmonic voltage V ANh is therefore.% of the rms value of the fundamental component and 9.7% of the total rms value. Values of THD for other waveforms are given in Table 0.. In general, if there are N steps/ cycle, each occupying /N radians, the only harmonics present are of the order h nn, where n,,, For a six-step waveform Fig. 0.7, for example, N 6sothath 5, 7,,, etc., as depicted in Eq. (0.7). 0.5 HARMONIC PROPERTIES OF THE OPTIMUM -STEP WAVEFORM A reduction of the harmonic content can be realized by increase of the number of steps in the phase voltage wave. If a -step waveform is used, N and h,,, 5, Example 0.4 gives some detail of a certain -step waveform calculation. It is found that the optimum -step waveform, shown in Fig. 0.8, is represented by the Fourier expression v( ωt) = V(sin ωt+ sinωt+ sinωt+ sin ωt + ) (0.0) In each interval of the optimum waveform of Fig. 0.8 the step height corresponds to the average value of the sinusoidal segment. For 0 t /6, for example, the average value is FIG. 8 Twelve-step voltage waveform [0]. Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

V 6 / 6 Step height = sin ωtdωt= 068. V 0 (0.) A -step waveform can be fabricated by the use of two six-step inverters with their outputs displaced by 0 or by the series addition of square-wave or PWM voltages. 0.6 SIX-STEP VOLTAGE INVERTER WITH SERIES R-L LOAD When a reactive load is connected to a step-wave inverter, it becomes necessary to include a set of reverse-connected diodes in the circuit to carry return current (Fig. 0.9). The presence of the diodes immediately identifies the circuit as a VSI rather than a current-source inverter (CSI) for which return diodes are unnecessary. In the presence of load inductance with rectifier supply, a shunt capacitor must be connected in the link to absorb the reactive voltamperes because there is no path for reverse current in the supply. 0.6. Star-Connected Load In the switching mode where three switches conduct simultaneously, the no-load voltages are given by Fig. 0.5. Let these voltages now be applied to the starconnected R-L loads, as in Fig. 0.9. The resulting current undergoes an exponential increase of value. Consider the instant t 0 in the typical steady-state FIG. 9 Voltage-source transistor inverter incorporating return current diodes [0]. Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

cycle shown in Fig. 0.0. Transistor T has been in conduction for 80 and has just switched off. Transistor T has been in conduction for 0 passing positive current I c. Transistor T is 60 into its conduction cycle resulting in current i B that is increasing negatively. Transistor T 4 has just switched on, connecting terminal A to V, which will attempt to create positive I A. The negative current i A (0) at t 0 is diverted from its previous path through T and passes through diode D 4 to circulate through capacitor C. As soon as i A 0, diode D 4 switches off, at point t in Fig. 0.0 and T 4 takes up the positive current I A. For each interval in Fig. 0.0 the current can be described mathematically by a constant term plus a decaying exponential component. Even if the load is highly inductive the load phase voltages and line voltages largely retain the forms of Fig. 0.7. For example, the diagram of Fig. 0. is reproduced from oscillograms of waveforms when a three-phase induction motor is driven from a stepwave, voltage-source inverter. The motor phase voltage is the classical six-step FIG. 0 Current waveforms for voltage-source six-step inverter with star-connected series R-L load [0]. Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

FIG. Waveforms with six-step VSI applied to an induction motor load [0]. waveform. At each switching there is an abrupt change of current slope. A motor input impedance is much more complex than the passive R-L load of Fig. 0.9 since the resistance value is speed related and there are magnetically induced voltages in the windings. It can be seen in Fig. 0. that the fundamental component of the very spiky current lags the voltage by about 60 of phase angle, which is typical of low-speed operation of an induction motor. Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

0.6. Delta-Connected Load Let the voltages of Fig. 0.7, for the case of three simultaneously conducting switches be applied to a balanced, three-phase, delta-connected load, as in Fig. 0.. Since the star-connected load of Fig. 0.9 can be replaced by an equivalent delta-connected load, the line current waveforms of Fig. 0.0 remain true. The phase current waveforms can be deduced by the application of classical mathematical analysis or transform methods. In the interval 0 t 0 of Fig. 0.0 a voltage V is impressed across terminals so that, with cot R/ L, i V cot φωt ( ωt) ( ) i( 0) 0 < ωt < 0 = R + cot φωt (0.) In the interval 0 t 80 of Fig. 0.0 terminals A and B are coincident and load branch is short-circuited so that V cot φ/ i( ωt) = ( ) 0 < ωt < 80 R cot φ/ + i( 0) cot φω ( t / ) (0.) Since the current wave possesses half-wave inverse symmetry, i (0) i ( ) i ( ). Putting t in Eq. (0.) and utilizing the inverse-symmetry identity give i V ( 0) = R cot φ / cot φ + φ (0.4) cot FIG. Delta-connected series R-L load [0]. Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

Combining Eq. (0.4) with Eqs. (0.) and (0.), respectively, gives i ( ωt) V 0 < ωt < 0 = R + + cot φ / cot φ cotφωt (0.5) i ( ωt) V 0 < ωt < 80 = R + cot φ/ cot φ cot φω ( t / ) (0.6) Current i CA ( t) in Fig. 0. is given by expressions corresponding to those of Eqs. (0.5) and (0.6) but with the time delayed by 4 / radians. The rms value of the branch current is defined by the expression I = i( ωt) dωt 0 In elucidating Eq. (0.7) it is convenient to use the substitutions (0.7) K = + + cot φ / cotφ K = + cot φ/ cot φ (0.8) An examination of K and K above shows that K K cot / (0.9) Substituting Eqs. (0.5) and (0.6) into Eq. (0.7) gives I 4V 0 cotφωt = K ( ) R 0 + 80 0 cot φω ( t / ) ( K ) dωt 4V K t K = ωt + R φ cot φω cot K + φ ω cot ( t / ) cot φ dωt cot φωt 80 0 cotφ 0 0 4V K K = + R cotφ cot φ / cot / ( ) ( ) cot φ φ4 K cot φ/ ( ) cot φ (0.40) Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

Eliminating the explicit exponential terms between Eqs. (0.8) and (0.40) gives I 4V K K ( ) = + K K + K R cot φ K (0.4) Line current i A ( t) in Fig. 0. changes in each 60 interval of conduction. In general, i A ( t) i ( t), so that cot φ / cot φ / V ( )( ) ia( ωt) 0 < ωt < 60 = R + cot φωt cotφ + (0.4) i i A ( ωt) ( ωt) cot φ / V ( ) 60 < ωt < 0 = R cot φ ++ cot φω ( t / ) cot φ/ cot φ / V ( )( ) 0 < ωt < 80 = R + + cotφ + (0.4) cot φω ( t / ) (0.44) A typical pattern of waves consistent with Eqs. (0.4) to (0.44) is shown in Fig. 0.. At any instant the current i A ( t) must be flowing through one of the devices T, T 4, D,orD 4 in the inverter of Fig. 0.9. In the interval 0 t 60, the negative part of i A ( t), up to t, is conducted via transistor T 4. For t 80, the positive current i A ( t) reduces to zero through diode D and then goes negative via T. The properties of both the transistor and the diode currents can be calculated by use of the appropriate parts of Eqs. (0.5) (0.44). The oscillating unidirectional current in the link (Fig. 0.) consists of a repetition of the current i A ( t) in the interval 60 t 0. For the interval, 0 t 60, i ( t) is defined by where i ( ) V cotφωt ( ωt) = K R (0.45) cot φ/ ( + ) K = cot + φ (0.46) This link current will become negative for part of the cycle if the load is sufficiently inductive. The boundary condition for the start of negative link current is i ( t) 0at t 0, which occurs when K. This happens for loads Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

FIG. Current waveforms for six-step VSI with delta-connected, series R-L load [0]. with a power factor smaller than 0.55 lagging. The average value of I ( t) in the interval 0 t 60 and therefore in all the intervals is given by I cotφωt ( ) 60 V = K 0 R V K = ωt + R cot φ cot φωt dωt 60 0 V K = + R cotφ cot φ / ( ) (0.47) 0.7 WORKED EXAMPLES Example 0. An ideal supply of constant voltage V supplies power to a three-phase force-commutated inverter consisting of six ideal transistor Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

switches. Power is thence transferred to a delta-connected resistive load of R per branch. The mode of inverter switching is such that two transistors are in conduction at any instant of the cycle. Deduce and sketch waveforms of the phase and line currents. The load is connected so that the system currents have the notation shown in Fig. 0.. The triggering sequence is given at the top of Fig. 0.5. At any instant of the cycle two of the three terminals A, B, and C will be connected to the supply, which has a positive rail V while the other rail is zero potential. The load effectively consists of two resistors R in series shunted by another resistor R. In the interval 0 t /, for example, transistors T and T are conducting so that V ic = ia = = R / ib = 0 V ica = ic = R ibc = i = ic = V R V R In the interval t /, transistors T and T are conducting, resulting in the isolation of terminal A so that i C = i = B V R ia = 0 V ibc = R V ica = i =+ R In the interval / t, transistors T and T 4 are in conduction so that terminal B has the negative rail potential of zero while terminal A is connected to the V rail, so that i = 0 i i i C A CA = i = B V R V = R V = ibc = R Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

The pattern of waveforms so produced (Fig. 0.4) is that of a six-step phase (i.e., branch) current but a square-wave line current. In fact, the pattern of waveforms is identical in form, but with different amplitude scaling, to that obtained with a star-connected load of R /phase in Fig. 0.7 when three transistors conduct simultaneously. FIG. 4 Voltage waveforms of VSI with delta-connected R load (Example 0.) [0]. Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

Example 0. The voltage waveform of a certain type of -step inverter is given in Fig. 0.5. For this waveform calculate the fundamental value, the total rms value, and the distortion factor. The waveform of Fig. 0.5 is defined by the relation, 5 / 5, 4 /5 Em Em e( ωt) = + + E 0, 4/ 5 / 5, / 5 m / 5 / 5 For the interval 0 t the rms value E is given by E = e ( ωt) dωt 0 E Em 5 4Em 5 4 5 =, t + /, / / 5 ω ωt E 9 04, / 5 9 mωt / 5, / 5 / 5 Em 9 5 0 4 = + 45 + 9 5 5 + 4 5 5 + 5 5 Em 4 = + + 9 5 9 5 5 8 9 = Em + + = 9 Em 45 45 45 45 = 06.5E m + ( ) FIG. 5 Voltage waveform of -step VSI in Example 0. [0]. Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

It is obvious that the fundamental component of waveform e( t) in Fig. 0.5 is symmetrical with respect to the waveform itself. Therefore, In this case b = e ( ωt )sin ωt dωt 0 = e( ω t)sin ω t d ω t 0 b, 5 / 5, 4 /5 Em Em = cosωt E 4/ 5 0, / 5, / 5 E m 4 = cos cos 0 + cos cos 5 5 4 + + cos cos cos cos cos cos 5 5 5 5 5 5 E = m 4 + + cos cos + cos cos 5 5 5 5 Em = ( + + 0. 809 + 0. 809 + 0. 09 + 0. 09) Em 8. Em = ( 44. ) = = 09. Em E 09. Distortion factor = = = 098. E 065. m / 5 cosωt / 5 Example 0. A six-step voltage source inverter is supplied with power from an ideal battery of constant voltage V 50 V. The inverter has a deltaconnected series R-L load, where R 5, X L 5 at 50 Hz. Calculate the rms current in the load, the power transferred, and the average value of the supply current at 50 Hz. In this example an inverter of the form of Fig. 0.9 supplies power to a load with the connection of Fig. 0.. The pattern of phase or branch currents i ( t), i BC ( t), i CA ( t) is similar in form to the load currents with star-connected load shown in Fig. 0.0. The line currents have the typical form i A ( t) given Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

in Fig. 0.. The branch current i ( t) is defined by Eqs. (0.5) and (0.6), where the voltage is now V (rather than V ) ωl φ = tan = tan 67. = 59. R cot φ = cot 59. = 0. 6 cot φ / 06. = = 05. cot φ/ 6. = = 0. 85 cot φ 88. = = 05. cot φ4/ 5. = = 008. Now in Eq. (0.8) K K = + + = + cot φ / cot φ cot φ/ cot φ 5. = =. 5. 075. = = 06. 5. Substituting into Eq. (0.4) gives I 50 094 67 5 0 6 66 77. 0. 86 0. 79 =. +.... + 5.66 I 0 = 094 67 0 95 = 4 04 (... ). A The total power dissipation is P I R (4.04) 5 75 W The average value of the link current may be obtained by integrating Eq. (0.45) between the limits 0 and /: ( ) V K I = R + φ cot φ / cot In this case, from Eq. (0.8), ( ) cot φ/ + K = cot φ + (. 5) = = 04.. 5 Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

Therefore, 50 04. I =. 094 + ( ) 5 06 0.. 5 0 = (. 094. 588 ) = 4.8A The power entering the inverter through the link is P in VI 50 4.8 75 W which agrees with the value of the load power. PROBLEMS 0. Sketch the circuit diagram of a three-phase, force-commutated inverter incorporating six SCRs and six diodes. The commutation system should not be shown. Two SCRs only conduct at any instant, and power is transferred from the source voltage V into a balanced three-phase resistive load. Explain the sequence of SCR firing over a complete cycle and sketch a resulting per-phase load voltage waveform consistent with your firing pattern. 0. Sketch the skeleton circuit of the basic six-switch, force-commutated inverter with direct supply voltage V. The switching mode to be used is that where three switches conduct simultaneously at every instant of the cycle. Deduce and sketch consistent waveforms of the output phase voltages v AN, v BN, v CN (assuming phase sequence C) and the line voltage v on open circuit over a complete time cycle, indicating which switches are conducting through each 60 interval. What is the phase difference between the fundamental component v of the line voltage v and the fundamental component v AN of the phase voltage v AN?In what ways would a phasor diagram of the fundamental, open-circuit phase voltages give a misleading impression of the actual operation? 0. The basic circuit of a six-switch, force-commutated inverter with supply voltage V is shown in Fig. 0.. The triggering mode to be used is where three switches conduct simultaneously. Deduce and sketch waveforms of the instantaneous phase voltages v AN, v BN, v CN and the instantaneous line voltage v for open-circuit operation with phase sequence C. Indicate which of the six switches are conducting during each 60 interval of the cyclic period. If equal resistors R are connected to terminals A, B, C as a star-connected load, deduce and sketch the waveform of phase current i AN. Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

0.4 In the inverter circuit of Fig. 0. the triggering mode to be used is where three switches conduct simultaneously. The load consists of three identical resistors R connected in wye (star).. If the load neutral point N is electrically isolated from the supply neutral point O, deduce the magnitude, frequency, and waveform of the neutral neutral voltage V NO.. If the two neutral points N and O are joined, deduce the magnitude, frequency, and waveform of the neutral current. 0.5 The stepped waveform of Fig. 0.6 is typical of the phase voltage waveform of a certain type of inverter. Use Fourier analysis to calculate the magnitude and phase angle of the fundamental component of this waveform. Sketch in correct proportion, the waveform and its fundamental component. What is the half-wave average value of the stepped wave compared with the half-wave average value of its fundamental component? 0.6 A set of no-load, phase voltage waveforms v AN, v BN, v CN produced by a certain type of inverter is given in Fig. 0.5. Sketch, on squared paper, the corresponding no-load line voltages v AN, v BN, v CA. Calculate the magnitude and phase-angle of the fundamental component v AN of the line voltage v AN and sketch v AN in correct proportion to v AN. What is the half-wave average value of v AN compared with the corresponding halfwave average value of v AN? The set of voltages in Fig. 0.5 is applied to a set of equal star-connected resistors of resistance r. Deduce and FIG. 6 Motor phase voltage waveform in Problem 0.5 [0]. Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

sketch the waveform of the current in phase A with respect to the opencircuit voltage v AN. 0.7 An ideal supply of constant voltage V supplies power to a three-phase, force-commutated inverter consisting of six ideal transistors. Power is then transferred to a delta-connected resistive load of R per branch (Fig. 0.7). The mode of inverter switching is such that three transistors are conducting simultaneously at every instant of the cycle. Show that the line current waveforms are of six-step form with a peak height of V/R. Further show that the phase (branch) currents are square waves of height V/R. 0.8 For the periodic voltage waveform of Fig. 0.8 calculate the fundamental component, the total rms value, the distortion factor, and the displacement factor. 0.9 For the -step waveform of Fig. 0.8 show that the step height for the interval /6 t / is given by 0.7 V. Also show that the fundamental component of this waveform has a peak height of / V and a displacement angle 0. 0.0 For the -step voltage waveform of Fig. 0.8 calculate the rms value and hence the distortion factor. 0. A six-step voltage source inverter is supplied from an ideal battery with terminal voltage V 00 V. The inverter supplies a delta-connected load with a series R-L impedance in each leg consisting of R 0, FIG. 7 Inverter circuit connection in Problem 0.7 [0]. Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.

FIG. 8 Voltage waveform of Problem 0.0 [0]. X L 0 at the generated frequency. Calculate the rms load current and the average value of the supply current. Check that, within calculation error, the input power is equal to the load power. 0. Repeat Problem 0. if the load inductance is removed. 0. For the inverter operation of Problem 0. calculate the maximum and minimum values of the time-varying link current. Copyright 004 by Marcel Dekker, Inc. All Rights Reserved.