Open Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer

Similar documents
Open Access Partial Discharge Fault Decision and Location of 24kV Composite Porcelain Insulator based on Power Spectrum Density Algorithm

Open Access Partial Discharge Fault Decision and Location of 24kV Multi-layer Porcelain Insulator based on Power Spectrum Density Algorithm

PD Solutions. On-Line PD Measurement Devices

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

Design of Meander Antenna for UHF Partial Discharge Detection of Transformers

Partial Discharge Monitoring and Diagnosis of Power Generator

A Compiler Design Technique for EMS Test CS115

Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and Waveform Characteristics

Open Access Parallel Resonant DC Link Inverter for Thermoacoustic Power Generation

Open Access Research of Dielectric Loss Measurement with Sparse Representation

C I R E D 21 st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011

Open Access Pulse-Width Modulated Amplifier for DC Servo System and Its Matlab Simulation

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

Diagnostic testing of cast resin transformers

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

Open Access Design of Diesel Engine Adaptive Active Disturbance Rejection Speed Controller

PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS

Open Access Research on Fast Response Characteristic of Magnetic Control Reactor

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

PARTIAL DISCHARGE DETECTION - AN OVERVIEW

The R Portable Device for Partial Discharge Measurement and Analysis in High Voltage Equipment Insulation

UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES

APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS

Partial Discharge Monitoring of Power Transformers by UHF Sensors

Research Article Design of a UHF Antenna for Partial Discharge Detection of Power Equipment

Application of High-Voltage Power Supply on Electrostatic Precipitator

TECHIMP Power Transformer Monitoring

PARTIAL DISCHARGE MEASUREMENT

Research Article Study on Noise Prediction Model and Control Schemes for Substation

Study on the Technology of Leakage Protection

Research Article A New Kind of Circular Polarization Leaky-Wave Antenna Based on Substrate Integrated Waveguide

Software System for Finding the Incipient Faults in Power Transformers

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

SAMPLE. Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs.

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Hybrid Simulation of ±500 kv HVDC Power Transmission Project Based on Advanced Digital Power System Simulator

Research on Transformer On-line Monitoring System of 500 kv Transformer Substation based on Vibration Method

Diagnosis of Water Tree Aging in XLPE Cable by the Loss Current Harmonic Component Under Variable Frequency Power

Insulation Level and Test Technology of. 1000kV Power Transformer

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS

DEVELOPMENT OF HIGH-POWER, HIGH-FREQUENCY AND HIGH- VOLTAGE POWER SUPPLY SYSTEM FOR ELECTROSTATIC PRECIPITATOR

HV AC TESTING OF SUPER-LONG CABLES

Research Article Modified Dual-Band Stacked Circularly Polarized Microstrip Antenna

The Open Automation and Control Systems Journal, 2015, 7, Application of Fuzzy PID Control in the Level Process Control

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

Partial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor

process has few stages and is highly repeatable. Excellent mechanic properties and electro-magnetic compatibility. Planar design gives the height lowe

How to Analyze and Test the Location of Partial. Discharge of Single-winding Transformer Model

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

The Occurrence of Faults in Permanent Magnet Synchronous Motor Drives and its Effects on the Power Supply Quality

The importance of partial discharge testing throughout the development and operation of power transformers

PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics

FAULT DIAGNOSIS AND PERFORMANCE ASSESSMENT FOR A ROTARY ACTUATOR BASED ON NEURAL NETWORK OBSERVER

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

OMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon

Fault Detection in Transformer Using Frequency (Sweep) Response Analysis

ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS

Research on State Estimation and Information Processing Method for Intelligent Substation

HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL. Huazheng Electric Manufacturing(Baoding) Co.,Ltd

PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Influence of Impurity Concentration on Insulation Strength of Insulating Oil under Different Voltage Types

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Why partial discharge testing makes good sense

MONTRANO. Continuous monitoring system for power transformers

Comparison of capacitive and inductive sensors designed for partial discharges measurements in electrical power apparatus

Fushun Power Supply Company, Liaoning Electric Power Company Limited, State Grid, China

PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM

IGBT Induction Heater Profiles

VARIABLE FREQUENCY RESONANT TEST SYSTEM

IEEE Transactions on Power Delivery. 15(2) P.467-P

Transient calibration of electric field sensors

OMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates

Investigation of PD Detection on XLPE Cables

Field Test and Analysis of Partial Discharge. on GIS Under Impulse Voltage

Research on the Effect of High Power Microwave on Low Noise Amplifier and Limiter Based on the Injection Method

A New TEM Horn Antenna Designing Based on Plexiglass Antenna Cap

Open Access Sparse Representation Based Dielectric Loss Angle Measurement

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

Open Access On Improving the Time Synchronization Precision in the Electric Power System. Qiang Song * and Weifeng Jia

Autotransformer Condition Monitoring Systems

High Voltage DC Transmission 2

Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid

A Broadband High-Efficiency Rectifier Based on Two-Level Impedance Match Network

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Sources of transient electromagnetic disturbance in medium voltage switchgear

Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission

J.-H. Ryu Agency for Defense Development Yuseong, P. O. Box 35-5, Daejeon , Korea

Research Article CPW-Fed Wideband Circular Polarized Antenna for UHF RFID Applications

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements

Research Article Miniaturized Circularly Polarized Microstrip RFID Antenna Using Fractal Metamaterial

Research on Bamboo Hat ATC Control Design and Adjustment

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Research Article A Rectangular Planar Spiral Antenna for GIS Partial Discharge Detection

Coherence and time-frequency analysis of impulse voltage and current measurements

Transcription:

Send Orders for Reprints to reprints@benthamscience.ae 784 The Open Automation and Control Systems Journal, 2015, 7, 784-791 Open Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer He Ninhui 1,*, Wang Bo 1,2, Zhang Tao 1,2 and Guo Fei 1 1 Power Science Research Institute of State Grid Ningxia Power Co., Yingchuan Ningxia 750011, China 2 School of Electrical Engineering Wuhan University, Hubei Wuhan 430072, China Abstract: The partial discharge detection technology (UHF) is specially used in YD-B Phase of ± 660kV converter transformer pole I system, in connection with overheating failure problems. Through analysis by PRPD map to strengthen the monitoring for partial discharge defective of converter transformer, the continuous tracking for the running state of converter transformer can be achieved. Application results show that: the signal of partial discharge characteristics can be effectively found inside the converter transformer through UHF Online Monitoring techniques, which has good sensitivity and Interference capability, providing guarantee for safe and stable running of power equipment. Keywords: UHF, On-line Monitor, Partial Discharge, PRPD Map. 1. INTRODUCTION With the increasing of voltage grade of DC transmission, the insulator for ultra high voltage direct current (UHVDC) equipments is becoming more and more outstanding. As the most important electrical equipment in DC system, the convert transformer will influence the whole system directly. Turn-on and cut-off of the rectifying valve will produce impulse voltage with high amplitude and steep waveform. When the impulse voltage superimposed on the winding voltage, it will form a kind of compound voltage that is similar to sinusoidal AC waveform, which is composed by direct voltage and alternating voltage (exists many harmonic waves) with heavy distortion. At the same time, the valve side winding have to endure the lighting impulse and voltage operation. What's more, the short circuit impedance and loss of converter transformer will make the equipment heat up more than ordinary transformer. And the internal temperature of converter transformer is 20% higher than the ordinary transformer s. Therefore, the insulator failure rate of converter transformer coil is higher than the ordinary transformer. As the research shows, too hot insulator medium caused by partial discharge is the main factor that causes insulator failure.in this way, observing the partial discharge of converter transformer by installing Ultra High Frequency (UHF) partial discharge equipment will have high significance of improving the safe operation level of converter transformer., 2. HF PARTIAL DISCHARGE DETECTION TECH- NOLOGY 2.1. The Principle of UHF Partial Discharge Detection Technology Insulator strength and breakdown field strength of electronic equipment s insulator are relatively high. When the partial discharge happens within a tight trading range, the breakdown process is fast, and it will produce very steep pulse current whose rise time will be less than 1ns and radiate a kind of electromagnetic wave with a frequency up to GHz. The method of UHF partial discharge detection was put forward by Central Electricity Generating Board Laboratory in the early 1980s. Its basic principle is to use UHF sensor to detect the signal of UHF electromagnetic wave (300MHz f 3GHz) produced by the partial discharge (PD) of power equipment. This method can detect the signals of PD, and realize PD monitoring. According to different field devices, we can apply Built-in UHF sensor and external UFH sensor. Built-in UFH senor detects signals generally by oil drain valve, flange plate and standardized medium window into the transformer from inside, which can provide high detection sensitivity and strong anti-interference capacity. External UHF senor detects signals generally by Coupling with small amount of electromagnetic leaking from outlet port and seams, which can be easy to install and doesn't influence transformer s internal electric field. As the corona interference is focused on the frequency band below 300MHz, the method of UHF can have a good ability of avoiding the corona interference effectively, and realize PD on-line detection, positioning and flaw detection [1]. 1874-4443/15 2015 Bentham Open

Application of Partial Discharge Online Monitoring Technology The Open Automation and Control Systems Journal, 2015, Volume 7 785 Fig. (1). The monitoring system of UHF partial discharge. 2.2. The Contrast of UHF Detection Methods and Traditional PD Methods Comparing with other PD online techniques, UHF detection methods have many prominent advantages: 1) High detection sensitivity The signals of UHF electromagnetic waves generated by PD will fade out in the process of converter transmission. If ignoring the influence of the insulator, the signal of UHF electromagnetic waves with 1GHz can only be reduced to 3~5dB/km. And when electromagnetic waves reflect on the inner discontinuity of converter transformer, it will cause resonance in the shell of converter transformer to make the oscillation time of PD signals longer and easier to be detected. Therefore, UHF detection methods have high sensitivity. Furthermore, comparing to ultra-sonic detection, UHF detection methods can detect more effective range and need less necessary sensor data to detect converter transformer online [2]. 2) Strong anti-interference capacity As there is a large number of electric interference when the convert transformer works, it will bring some difficulties to partial discharge detection. The corona interference between high voltage transmission line and equipment is the most common field interference. The frequency of discharge energy is mainly below 200MHz. Detection frequency band of UHF method is usually 300MHz~3GHz. So it effectively avoids the field corona interference, and has strong anti interference ability. 3) Benefit for insulation defect recognition For different types of insulation defect, their UHF signals, produced by PD, have different frequency spectra. So, the time domain signal distribution of conventional method can be utilized. Also, it can be combined with Frequency distribution characteristics of UHF signal for PD type recognition, and realize diagnosis of insulation defect types. According to the propagation property of UHF electromagnetic waves, we know that applying Built-in UHF sensor to detect signals has higher sensitivity and stronger antiinterference ability than external UFH sensor, by extending the sensor into transformer through the oil discharge valve, flange and the standardization of dielectric window. 3. ANALYSIS OF UHF PD ONLINE MONITORING FOR CONVERTER TRANSFORMER APPLICATION EFFECT 3.1. Case In 2014.07.13, oil chromatography online monitoring system found that YD-B occur the phenomenon of excessive acetylene. Subsequently, hydrogen, acetylene and hydrocarbon components rapidly grew. Through theoretical analysis, it was confirmed that B-phase of the equipment exists inner overheat Fault. When shifting from converter to running state, the monitoring is too simple. In order to guarantee the safety and stable operation of convert transformer, we use UHF PD monitoring technology and install SIM3-PD portable PD online monitoring device. UHF signal sensor is installed on the oil valve at the top of converter transformer, and it is used to monitoring PD of B-phase whose oil chromatography is abnormal [3]. The date of intelligent monitoring unit in field is uploaded to the integrated processing unit by CAN2.0B Field Bus. Integrated processing unit deals with the date. Then the field monitoring unit uploads to station CAC (Status information of the access controller) by the way of MMS, through the LAN based on IEC61850 Communication Protocol. It can also upload to the backstage diagnosis center. The system structure of UHF PD monitoring is shown in Fig. (1). 3.2. Analysis of Application Effect By analyzing monitoring data from July 3 to July 25, during this time, continuous typical PD signals related with power frequency voltage were basically not found. But there had been short continuous time (2-3 hours), during which B- phase happened, and had typical PD signals as shown in

786 The Open Automation and Control Systems Journal, 2015, Volume 7 Ninhui et al. Fig. (2). The persistence abnormal PD signal in the B phase during 18:00 on July 4 th to 11:00 on July 5 th. Fig. (3). Only three hours abnormal PD signal in the B-phase during 14:00 to 15:00 on July 14 th. Fig. (2). At the same time, B-phase monitored unnormal signal that is unrelated with power frequency voltage. It often occurred between 18:00-11:00 the next day as shown in Fig. (3). But it did not occurred every day. 1) The effect of switch position on Partial discharge signal From July 25 th to July 30 th, pole I operate reducing power to 1200MW, meanwhile the swich will be changed from by

Application of Partial Discharge Online Monitoring Technology The Open Automation and Control Systems Journal, 2015, Volume 7 787 Fig. (4). Similar characteristics PRPD map during 20:00 on July 26 th to 5:00 on July 27. Fig. (5). The PRPD map of pole system YD-B phase at 15:00 on August 25. the previous automatic regulating state to manually adjusting state, so that the switch operate in "22, 23, 24" gear for two days. During this period, there is Partial discharge characteristic signal shown in PRPD maps through UHF on-line monitoring device from from 8 p.m to 7 a.m every day, and presents the obvious characteristics of the phase, the discharge intensity of peak and average less than -65 dbm, taking the PRPD maps at 20:00 on the 26 th - at 5:00 on the 27 th for example, as shown in Fig. (4). The high frequency signal strength keep up -80dBm in PRPD map during other period, only occasional signal pulse is weak, but there is no correlation with the frequency of the voltage, not having obvious characteristics of the discharge phase [4]. 2) The effect of current load on Partial discharge signal At 1:00 on August 25, the system will run for three days with raising the power to 1600MW (80% load), at 1:00 on August 28, the power will be raised to 2000MW (100% load). After six days of following observation, no continued and fundamental typical PD signal associated with frequency voltage be found, but the daily 19:00 to 6:00 the next day, a signal with typical characteristic of PD appeared, which had been confirmed that the signal caused by Highvoltage Sodium lamp in firewall of Converter transformer indoor. From 8:00 on August 25 to 18:00 on August 25 th, it has similar PRPD map features during this period, shown in Fig. (5). From 19:00 on August 25 to 6:00 on August 26, it has similar PRPD map features during this period, as shown in Table 1 and Fig. (6). From 0:00 on August 28 to 6:00 on August 28, it has similar PRPD map features during this period, as shown in Fig. (7).

788 The Open Automation and Control Systems Journal, 2015, Volume 7 Ninhui et al. Fig. (6). The PRPD map of pole system YD-B phase at 19:00 on August 25. Fig. (7). The PRPD map of pole system YD-B phase at 0:00 on August 28. Table 1. PD parameters of pole system as the power raised to 1600MW (80% load). Time Peak Discharge (dbm) Mean Discharge (dbm) Pulses Number ( / ) Phase Features (%) 08 25 16-78 -78 0 0 08 25 17-78 -78 0 0 08 25 18-78 -78 0 0 08 25 19-78 -78 0 0 08 25 20-72.024-73.793 56.6 11.269 08 25 21-72.366-74.098 39.1 2.463 08 25 22-72.099-73.857 45 4.805 08 25 23-72.148-73.978 41.2 1.543 08 26 00-71.959-73.668 48.3 2.637

Application of Partial Discharge Online Monitoring Technology The Open Automation and Control Systems Journal, 2015, Volume 7 789 Table 1. contd Time Peak Discharge (dbm) Mean Discharge (dbm) Pulses Number ( / ) Phase Features (%) 08 26 01-71.424-73.248 57.2 11.018 08 26 02-71.769-73.596 49.7 6.604 08 26 03-72.038-73.867 44.3 0.075 08 26 04-72.057-73.834 44.9 0.787 08 26 05-71.885-73.743 46.3 3.927 08 26 06-76.792-77.154 9.2 0.48 08 26 07-78 -78 0 0 08 26 08-78 -78 0 0 08 26 09-78 -78 0 0 Table 2. PD parameters of pole system as the power raised to 2000MW (100% load). Time Peak Discharge (dbm) Mean Discharge (dbm) Pulses Number ( / ) Phase Features (%) 08 28 16-78 -78 0 0 08 28 17-78 -78 0 0 08 28 18-78 -78 0 0 08 28 19-74.161-75.03 46.3 17.169 08 28 20-69.472-71.569 82.9 42.471 08 28 21-69.783-71.799 80.8 34.674 08 28 22-69.978-71.973 75.8 33.098 08 28 23-70.166-72.159 74.9 23.537 08 29 00-69.766-71.758 78.9 34.864 08 29 01-69.714-71.728 78.5 36.909 08 29 02-69.799-71.712 81.4 28.183 08 29 03-70.014-72.003 77.6 21.907 08 29 04-70.276-72.273 72.1 29.321 08 29 05-71.124-73.037 59.9 19.408 08 29 06-76.379-76.831 14.1 3.617 08 29 07-78 -78 0 0 08 29 08-78 -78 0 0 08 29 09-78 -78 0 0

790 The Open Automation and Control Systems Journal, 2015, Volume 7 Ninhui et al. Fig. (8). The PRPD map of pole system YD-B phase at 18:00 on August 28. From 7:00 on August 28 to 18:00 on August 28, it has similar PRPD map features during this period, as shown in Table 2 and Fig. (8). 4. ANALYSIS OF PARTIAL DISCHARGE DATA After PRPD maps and dates acquired from July 13th to August 30th were analyzed, it s determined as the following: For the abnormal signal of B-phase not related to frequency voltage during July 13 to July 25 (usually appear between 18:00-11:00 the next day, but there will not be everyday), due to the abnormal signals are not appear in the C- phase and B-phase as the same time, the interference from external space of Converter transformers can be ruled out; due to the abnormal signal is not synchronized with the power frequency voltage, and no interference caused by commutated and rectifier of thyristor, the interference generated by SCR can be exclude; whether that be caused by load change of Converter transformers, it need for further analysis. The signal with the typical features of partial discharge appear at 19:00 to 6:00 every night from July 25 to July 30 and August 25 to August 30, which have significant phase characteristics, the peak discharge and mean discharge are less than -65 dbm (the equivalent discharge amount not exceed hundreds of pc, will not affect the insulating properties of the transformer). Because the load of conversion transformer remained unchanged during this period, the impact of load changes can be excluded; Secondly, the impact of bad contact of tap changer can be excluded for tap-free operation. Although the signal appear in the C-phase and B-phase meantime, and keep synchronous with the frequency voltage, only in a fixed period of time, the interference of the SCR commutated rectifier outside converter transformer can be excluded. After analysis test, it s determined that the signal comes from the influence of high-voltage sodium lamps of converter transformer interior. The PRPD from the July 25 to July 30 and August 25 to August 30, UHF signal strength keep stable of -78dBm and there is not obvious pulse signal during other period daily. Since August 28 the power of poleⅠrose to 2000MW, the online monitoring discharge PRPD maps and discharge intensity, phase data and power YD-B phase of polo Ⅰ system compared to 1600MW, the amplitude of the partial discharge signal increased 2 ~ 3dBm, but the peak discharge and mean discharge less than -65 dbm, will not affect the performance of the transformer insulation. CONCLUSION After the conversion transformer in fault of overheating, there is no significant partial discharge and UHF signal strength are lower than -65 dbm, only occasional weak partial discharge characteristics appear in PRPD map, it suggest that monitoring system have strong anti-interfere capability. UHF partial discharge monitoring combined with a variety of oil chromatography effectively ensure security of conversion transformer in fault operation. CONFLICT OF INTEREST The authors confirm that this article content has no conflict of interest. ACKNOWLEDGEMENTS Declared none. REFERENCES [1] R. Zhang, X. Wu, and P. Ding, UHF partial discharge monitoring of 750kV main transformer, Ningxia Electric Power, vol. 25, no. 7, pp. 18-22, 2010. [2] P. Wang, The Research of Partial Discharge UHF Characteristics in Converter Transformer and Monitoring Sensors, MS thesis, Chongqing University, China, 2013.

Application of Partial Discharge Online Monitoring Technology The Open Automation and Control Systems Journal, 2015, Volume 7 791 [3] J. Li, P. Wang, T. Jiang, L. Bao, and Z. He, UHF stacked hilbert antenna array for partial discharge detection, IEEE Transactions on Antennas and Propagation, vol. 16, no. 3, pp. 299-304, 2013. [4] L. Liang, The Corresponding Relation Between Typical Partial Discharge Defects of Transformer and Dissolved Gas in Oil, Chongqing University, Chongqing, 2009. Received: September 16, 2014 Revised: December 23, 2014 Accepted: December 31, 2014 Ninhui et al.; Licensee Bentham Open. This is an open access article licensed under the terms of the Creative Commons Attribution Non-Commercial License (http://creativecommons.org/licenses/bync/3.0/) which permits unrestricted, non-commercial use, distribution and reproduction in any medium, provided the work is properly cited.