Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

Similar documents
VariSTAR Type AZL heavy-duty distribution-class MOV arrester

VariSTAR Type AZU heavy-duty distribution-class under-oil MOV surge arrester

Tab 8 Surge Arresters

Surge Arresters. VariSTAR Type AZS Normal Duty Distribution Class MOV Arrester

COOPER POWER. UltraSIL Polymer-Housed VariSTAR Type U2Surge Arrester for Systems through 275 kv IEC 10-kA; Line Discharge Class 2 SERIES

EE 1402 HIGH VOLTAGE ENGINEERING

35 kv Class M.O.V.E. DirectConnect elbow arrester

UltraSIL Polymer-Housed Evolution Distribution Class Surge Arrester Certified Test Report

POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

SURGE ARRESTERS AND TESTING. Keith Hill Doble Engineering Company

Energy Division. Bowthorpe LV/MV Surge Arresters

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

Substation Design Volume VII

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

Figure 1. Two- and Three-phase MagneX Interrupter.

Our experience. Our products

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

UltraSIL Polymer-Housed VariSTAR Normal-Duty, Heavy-Duty and Riser Pole Distribution-Class Arresters

Effective February 2017 Supersedes January 2012 (CP1122)

Eaton s Cooper Power Series DEADFRONT ARRESTERS

Single Line Diagram of Substations

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

3EK8 distribution class surge arresters. Catalogue HP-AR Version siemens.com/arresters

Two- and three-phase MagneX interrupter

Section 2 Outdoor Voltage Transformers

IMP/007/011 - Code of Practice for the Application of Lightning Protection

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

Distribution/Substation Transformer

Howard Smart Transformer Specification Guide

Unit 2. Single Line Diagram of Substations

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

TECHNICAL SPECIFICATION

CLU Arrester. Certified Test Report. IEEE Standard C

High voltage engineering

Overvoltage Protection

R Distribution Transformers. Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections. Reference Data

The Variable Threshold Neutral Isolator (VTNI)

ABSTRACTS of SESSION 6

TECHNICAL DATA TYPE CMD OIL-IMMERSED ON-LOAD TAP CHANGER

SUBJECT CODE : EE6702 SUBJECT NAME: Protection & switchgear STAFF NAME : Ms.J.C.Vinitha

Substation Preventive Maintenance

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

Insulation Co-ordination For HVDC Station

ANSI DESIGN TEST REPORT Report No. EU1295-H-00 Type PVN Station Class Surge Arrester

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

VI 3 - i TABLE OF CONTENTS

Outdoor Installation 2: Lightning Protection and Grounding

Medium voltage circuit breaker technical guide

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Coordination of surge arresters in DC 3 kv railway traction system field tests

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

GAS DISCHARGE TUBES GAS DISCHARGE TUBES

60Hz Ratings. Typical Applications. Features & Characteristics. Ratings

In-Service Testing and Diagnosis of Gapless Metal Oxide Surge Arresters According to IEC

Electromechanical Power Products

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

High Voltage Generation

7P Series - Surge Protection Device (SPD) Features 7P P P

OUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description:

CEYLON ELECTRICITY BOARD SRI LANKA. Procurement of Plant

4. Classification E: High capacity. 3. Terminal Form Blank: Tab terminals (#250 terminals) Tab terminals #250 SPST-NO

Construction zglass passivated collar zaluminum termination for pressure contact

Capacitive voltage transformers

Spark Gap Surge Protectors For Lv Mains

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

Isolating Spark Gaps. Isolating spark gaps at an additional earth ring conductor. Isolating spark gaps for Ex zones

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

Great Northern Transmission Line: Behind the (Electrical) Design

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

Tab 2 Voltage Stresses Switching Transients

High Voltage Engineering

Protection against unacceptable voltages in railway systems

VBS TBS KTS BSS LFS UFS

7. INSPECTION AND TEST PROCEDURES

Under-Oil ARRESTERS Page 1 July 2016

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

G5NB. A Miniature Relay with 1-pole 3A/5A Switching Capability and 10 kv Impulse Withstand Voltage. Application Examples. Model Number Legend

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

EE High Voltage Engineering UNIT IV - MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS PART-A 1. Mention the techniques used in impulse current

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

The Isolator/Surge Protector (ISP)

I -limiter The world s fastest switching device

S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv)

CONTINUING EDUC ATION

The Isolator/Surge Protector (ISP)

TS RES - OUTSTANDING ISSUES

Capacitive voltage transformers

Pomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017

Degradation Characteristics on MOV of Surge Arrester used for 6.6kV Power Distribution Line

OIL-IMMERSED ARC-SUPPRESSION COILS

Transcription:

Surge Arresters Secondary Arresters and Protective Gaps Electrical Apparatus 235-10 GENERAL INFORMATION The necessity of providing surge arrester protection on low-voltage circuits is fundamentally the same as for primary system protection. While secondary lines usually are shorter than primary lines, they still are subject to surges which can cause stresses beyond the insulation withstand strength of connected equipment. TABLE 1 Recommended Applications of Surge Arresters System Voltage Type Rating* 120 volts 120/240 volts L 175 volts 120/240 volts Y 240 volts 480 volts S4 650 volts 600 volts 2.4 kvs 6 kv 4.16Y/2.4 kv 11 kv 4.8 kvs 11 kv 8.32Y/4.8 kv Protective gap 15 kv 6.9 kvs 15 kv 12.47Y/7.2 kv 15 kv 13.2 kvs 15 kv 14.4 kvs 15 kv *Note: An arrester rating represents the maximum line-to-ground voltage to which the arrester should be subjected. Since surge arresters are inherently sensitive to overvoltages, they should never be subjected to 60 Hz voltages above their rated voltage, even during momentary abnormal conditions. If such a condition is likely, a special system study may be necessary, and a higher rated arrester may be required. Secondary Arresters Type L secondary arresters protect street-lighting controls, low-voltage relays, railroad-signal circuits and circuits used for fire alarms, remote metering and airport lighting. They are applicable for voltages up to 175 Vac, or 125 Vdc and are designed for indoor mounting. For general circuit applications refer to Table 1. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc. TYPE S4 Type S4 secondary arresters are designed to provide protection of low-voltage equipment, secondary distribution circuits, control circuits and signal circuits up to 650 Vac. These arresters are designed for both indoor and outdoor use and a typical application would be to protect long and exposed secondary systems in oil fields or rural areas. Protective Gaps Protective gaps are auxiliary devices which serve two purposes: (1) they isolate electrical equipment during normal service conditions, and (2) they provide a path to ground for surge current during arrester operations. Protective gaps used for interconnection of arrester ground, secondary neutral, and transformer tank provide additional protection to distribution transformers and improve continuity of service to customers. Protective gaps provide effective and inexpensive surge protection for the primary neutral of a system (grounded only at the substation) if the potential of the primary neutral is less than 350 volts (rms) above ground. Transformer tanks can be isolated from ground under normal conditions by connecting the transformer to ground through a protective gap. Figure 3. Protective gap rated 6, 11, and 15 kv. Figure 2. Type S4 secondary surge arrester rated 650 Vac. Cooper Power Systems January 1996 Supersedes 1/90 1996 Cooper Power Systems, Inc. 1

Features and Detailed Description HOUSING High strength thermoplastic provides protection to internal components. AC 175 V DC 125 V SECONDARY McGRAW-EDISON POWER SYSTEMS DIVISION 1992 SPARK GAP Single spark gap designed to give uniform and consistent sparkover. VALVE ELEMENT Metal-Oxide valve element provides exceptional surge protection. SEAL A gasket between the housing and base keeps interior of arrester clean and free of contamination. TERMINALS Plated brass straps, extending from the underside of the base, are slotted for easy mounting on standard terminal blocks. BASE Molded phenolic provides both strength and insulation. Figure 4. Cutaway illustration of Type L (175 Vac, 125 Vdc) secondary arrester. SECONDARY Operation Type L arresters protect low-voltage circuits and equipment against surges by providing a low-impedance path to ground, and quickly draining off surge voltages. The arrester promptly restores the circuit to normal by interrupting the 60 Hz current which follows the surge current. Examples of applications of Type L secondary arresters are shown in Figures 5 and 6. Standards Type L arresters meet all requirements for the Association of American Railroads (AAR) Signal Section Specification 52.51. 440- OR 550-VOLT LINE TYPE S4 TO ADJOINING BLOCK TRANSFORMER & BATTERIES RELAYS INSULATED TRACK SECTIONS ø N TO ADJOINING BLOCK Figure 5. Railway application diagram showing an automatic railway block signal control with Cooper Power Systems Type L secondary arresters. One arrester is used on each outgoing line. 120/240 VOLT LINE CONTROL STATION (RELAY) LAMP CIRCUIT Figure 6. A typical multiple street lighting control circuit showing Type L secondary arresters protecting the relay coil. 2

Impulse Sparkover Uniform sparkover characteristics and a long life are assured by the design of the spark gap of Type L arresters. 1.56" 60 Hz Sparkover Each Type L arrester is factory tested to assure a minimum 60 Hz sparkover of 1100 volts. This sparkover value allows circuits to be field tested with a 1000-volt megohmmeter without removing the arrester from the circuits. 1" 1.81" 1.88" Discharge Capacity AAR Specifications require a discharge capacity of 10,000 A on a 4 x 10 - microsecond wave. Type L arresters have passed certification tests which require discharging two of these surges without damage and complete recovery of all protective characteristics. Discharge Voltage Low-voltage signal circuit apparatus is designed to withstand a 60 Hz voltage of 4200 volts crest for one minute. Table 2 shows how Type L arresters offer extra protection with very low discharge voltages. TABLE 2 Maximum Discharge Voltage (Crest kv) 8/20 µs Current Wave Arrester Rating 175 Vac 125 Vdc 1.5 ka 3 ka 5 ka 10 ka 1.1 1.2 1.4 1.7.25" 1.69".5" 1" GROUNDING LINK Figure 7. Type L secondary arrester dimensional information. 2.38" 3".63" TYPE S4 SECONDARY Operation Type S4 secondary arresters incorporate a gapless MOV design that under steady state conditions maintains the line-to-ground voltage across the arrester s terminals. When overvoltages occur the Type S4 arrester quickly goes into conduction, limiting the overvoltage to required protection levels. Upon passage of the overvoltage condition, the S4 Duty Cycle Type L arresters subjected to dutycycle tests of 22 successive impulses of a 1500 A, 8 x 20 µs current wave show remarkably consistent characteristics. Follow current is quickly and effectively interrupted. HOUSING High-strength, wet-process, glazed porcelain. SEALS Arresters are positively and permanently sealed by synthetic rubber gaskets. CONNECTIONS Flexilble, 18-inch lead is provided with most models for connection to line. Connection to ground lead is made with clamp-type terminal. VALVE ELEMENT Metal oxide varistor (MOV) provides exceptional surge protection. Figure 8. Cutaway illustration Type S4, 650 V secondary arrester. Cooper Power Systems 3

235-10 arrester returns to a highly non-linear steady state condition that conducts very minimal 60 Hz power current. A typical application is shown in Figure 9. Dimensional information is shown in Figure 10. 1.31" 4.58" 1.94".44" x.63" MOUNTING SLOTS DISTRIBUTION CLASS 3" SIDE VIEW SINGLE POLE OR DOUBLE POLE 0.59" 2.94" 4.13" FRONT VIEW SINGLE POLE LONG & EXPOSED SECONDARY CIRCUIT TYPE S4 Figure 9. Typical application of Type S4 arresters protecting long and exposed secondary lines in oil field or rural areas. 0.59" 8.19" 9.38" 5.31" FRONT VIEW DOUBLE POLE Figure 10. Type S4 secondary arresters dimensional information. Discharge Voltage Table 3 shows the discharge-voltage characteristics of the Type S4 arrester. TABLE 3 Maximum Discharge Voltage 8/20 µs Current Wave (kv crest) Rating 1.5 ka 3 ka 5 ka 10 ka 650 V 2.1 2.4 2.7 3.0 PROTECTIVE GAPS For Interconnection Of Arrester Ground, Secondary Neutral, and Transformer Tank Interconnection provides additional protection to distribution transformers and improves continuity of service to customers. Advantages are particularly evident in areas subjected to extremely heavy lightning surges and/or where soil conditions result in high ground resistance values. Without interconnection, surge voltage may build up high enough to puncture the transformer insulation. Interconnection limits the potential difference between primary and secondary windings and between the primary winding and the transformer tank to the discharge voltage (IR drop) of the primary arrester, plus the impedance drop in the arrester leads. Many local electrical codes require that interconnection of this type be made through gaps. For Primary Neutral Protection If the potential of the primary neutral of a system, grounded only at the substation, is less than 360 rms volts above ground, Cooper Power Systems protective gaps provide effective and inexpensive lighting protection. Gaps should be installed between primary neutral and ground at each distribution transformer. 4

235-10 For Isolation Of Transformer Tanks From Ground A transformer tank connected to ground through a protective gap is isolated from ground under normal conditions. The gap will spark over and limit the voltage between the transformer tank and windings during high-current lightning discharges. Sparkover Protective gaps are permanently adjusted at the factory to spark over at voltages of 6, 11, or 15 kv rms. Arcing surfaces of both electrodes are designed to assure consistent sparkover characteristics. TABLE 4 Sparkover Characteristics 60-Hertz Impulse Sparkover Sparkover System Voltage (kv) (kv rms) Crest (kv) 2.4 s 6 11 4.16Y/2.4, 4.8 s 11 17.5 8.32Y/4.8, 6.9 s 12.4Y/7.2 15 25 13.2 s,14.4 s MOUNTINGS Mounting bracket (not shown) has a 0.56" hole for attachment to transformer tanks, secondary neutral terminals, or metal structures. Caps can also be suspended from a line conductor by the top clamp-type terminal. PROTECTIVE SEALS Gaps are permanently sealed with heavy synthetic rubber gaskets. SPARK GAP Large, solid electrodes handle high currents without damage and quickly dissipate heat from the arcing surfaces. HOUSING High-strength, wet-process, glazed porcelain. 1.56 ".56" DIA. MTG. HOLE Figure 12. Cutaway illustration of protective gap. 6" AG1A22 AG1A23 AG1A24 Figure 11. Dimensional Information of protective Gaps. NOT OVER 350 VOLTS DISTRIBUTION PROTECTIVE GAPS Figure 13. Typical application of protective gaps. 5

Secondary Arresters and Protective Gaps ORDERING INFORMATION Secondary Arresters TABLE 5 Type L Rated 175 Vac, 125 Vdc Standard Package Wt. of Catalog Package Description Number Qty. (lb.) Arrester with 1 grounding link AS1B1 5 5 Arrester only AS1B2 5 5 TABLE 6 Protective Gaps Rated 6, 11, and 15 kv Standard Package Description Wt. of (60 Hz. Catalog Package Sparkover) Number Qty. (lb.) 6 kv AG1A22 1 1 11 kv AG1A23 1 1 15 kv AG1A24 1 1 TABLE 7 Type S4 Rated 650 Vac Catalog Standard Package Description Number Quantity Wt. of Package (lb.) Single unit w/o terminal cap, w/o mtg. bracket with line lead ASZ1A101 1 2 Single unit with terminal cap, w/o mtg. bracket, with line lead ASZ1A102 1 2 Single unit with terminal cap, with mtg. bracket, with line lead ASZ1A103 1 2 Double unit with terminal cap, with mtg. bracket, with line lead ASZ1A104 1 4 Single unit w/o terminal cap, w/o mtg. bracket, w/o line lead ASZ1A104 1 2 Quality from Cooper Industries P.O. Box 1640, Waukesha, WI 53187 6