Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Similar documents
Grounding for Power Quality

2 Grounding of power supply system neutral

Wisconsin Contractors Institute Continuing Education

Grounding Recommendations for On Site Power Systems

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

ECE 528 Understanding Power Quality

Education & Training

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Summary of the Impacts of Grounding on System Protection

Safety earthing. Sector Energy PTI NC. Copyright Siemens AG All rights reserved. Theodor Connor

This document covers common questions concerning the design of an effectively grounded system.

POWER SERVICE DETAILS

CONTINUING EDUC ATION

Stray Voltage and Swimming Pools

6B.6 Substation Grounding

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

Evaluating the Response of Surge Arresters

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

Three Phase Transformers

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

Wind Power Facility Technical Requirements CHANGE HISTORY

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

Ground Fault Detection using Zigzag Grounding Transformer in Ungrounded System

Industrial and Commercial Power Systems Topic 7 EARTHING

FAQ ON EARTHING STANDARDS 16/08/2018

Notes 1: Introduction to Distribution Systems

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

EPG. by Chris C. Kleronomos

American Electrical Institute

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

Electrical Description

ABSTRACT 1 INTRODUCTION

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

Earthing of Electrical Devices and Safety

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Babak Enayati National Grid Thursday, April 17

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

QUESTIONNAIRE for Wind Farm Power Stations only

Safety through proper system Grounding and Ground Fault Protection

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

Utility Interconnection and System Protection

Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC)

Article 250 Grounding & Bonding

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Industrial Electrician Level 3

Thomas Wilkins Wilkins Consulting Henderson Nevada U.S.A.

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

Connection Impact Assessment Application

Embedded Generation Connection Application Form

II Design Criteria for Electrical Facilities Connected to the PJM 765 kv, 500 kv, 345 kv, 230 kv, 138 kv, 115 kv, & 69 kv Transmission Systems

Upgrading Your Electrical Distribution System To Resistance Grounding

Modelling Parameters. Affect on DER Impact Study Results

Grounding and Bonding

Installation requirements

ECE 528 Understanding Power Quality

Single Line Diagram of Substations

PC IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

High Voltage Pylon earth Measurements. Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy

I WP Asset # I ~:2 3. I Review Annual. ~c~~ Date: 'l/j(j/! ZL>IJ,...

High Voltage Pylon Earth Measurements

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

Article 225: Outside Branch Circuits And Feeders

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

CONTENTS. 1. Introduction Generating Stations 9 40

APPLICATION FOR INTERCONNECTION & OPERATIONS OF MEMBER-OWNED GENERATION

2kVA EARTH TESTING CURRENT INJECTION SYSTEM 4046 / 4047 DATASHEET REDPHASE INSTRUMENTS

kv AC substation

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT JAGAU

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

EVALUATION OF THE EARTH RESISTANCE VALUE FOR ESE LIGHTNING ARRESTOR TECHNIQUE FOR THE SOLAR PLANTS IN INDIA

FALL-OF-POTENTIAL GROUND RESISTANCE TESTER

SWITCHING SAFETY & RELIABILITY CONFERENCE

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

HV Substation Earthing Design for Mines

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

Unit 2. Single Line Diagram of Substations

Southern Company Interconnection Requirements for Inverter-Based Generation

2012 Grid of the Future Symposium. Impacts of the Decentralized Photovoltaic Energy Resources on the Grid

High Wind Speed Shutdown / Power Available

Thailand Integrates Large-Scale Wind Farms

Power Systems Modelling and Fault Analysis

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

UNITED STATES OF DEPARTMENT OF AGRICULTURE Rural Utilities Service BULLETIN 1751F-815. Electrical Protection of Outside Plant

Guide and Requirements for Service. at 69,000 to 287,000 Volts R 0.2

Ground Fault Location. Turbo Sleuth. Instruction Manual

Our Brands. Where we are?

Transformers. 4.1 Basics

Transcription:

IEEE PES Transmission and Distribution Conference 2008 Panel Session Large Wind Plant Collector Design Wind Farm Collector System Grounding by Steven W. Saylors, P.E. Chief Electrical Engineer Vestas Americas Information contained in the following shall not be construed as detailed description of the properties or function of wind turbines manufactured by Vestas Introduction Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design Integrated with rest of wind power plant Collection System grounding design Grounding Transformers 1

Need For Adequate Grounding A well designed grounding system serves to: 1. Establish an effective reference to earth potential for normal operation of - electrical & communication equipment - controls - protective devices (circuit breakers, fuses) 2. Limit voltage differences to values that will not cause undue hazards to personnel and equipment 3. Protect the wind turbine against lightning damage 4. Limit galvanic corrosion due to dissimilar metals Codes and Standards Grounding is necessary, and required by safety codes and standards, for personnel safety and protection of equipment in electrical systems North America Europe IEEE Standards IEC 80 Substations 81 Measurements 142 Industrial/Commercial (Green Book) 1050 Instruments and Controls in Generating Stations 1100 Sensitive Electronics (Emerald Book) ANSI NFPA 780 Lightning Protection UL 96A Lightning Protection 467 Grounding/Bonding Equipment NEC, CEC, NESC 61400-24 61024-1 Lightning 62305 Lightning Protect -1 General -3 Damage -4 in Structures 61364 Buildings 61936-1 Pwr Syst > 1kV 2

Typical Wind Turbine Generator Internal Grounding Systems TN-S Considers Lightning and Power System Fault protections IEC Type B WTG Grounding Designs - Ring Conductor - Driven Rods <= 10 Ohms 3

Ground System Interconnections Foundation plus Horizontal Grounding Design Concept HORIZONTAL EARTHING CONNECTED TO NEXT TURBINE MAIN EARTH BONDING BAR HORIZONTAL EARTHING CONNECTED TO NEXT TURBINE/SUBSTATION MIN. 0,9m (3 ft) APPROX. 2m (6 ft) MIN. 40m (MIN. 44 yd) FOUNDATION EARTHING MIN. 40m (MIN. 44 yd) 4

EARTHING W IRE 13 12 11 10 14 NOTE 2 MAIN EARTH BONDING BAR NOTE 1 9 15 16 2 1 8 3 7 4 5 6 CONNECTION TERMINALS NOTE1: THIS PART OF THE EARTHING WIRE IS TO BE CONNECTED TO THE UPPER REINFORCEMENT, WHEN IN PLACE. NOTE2: SLACK OF EXCESSIVE EARTHING WIRE. Ground System Interconnections 5

Collector System Engineering & Design Soil Resistivity ranges from 10s to 1000s of ohm-meters Size of Cable Neutral/Shield 1/3, 1/2, full size Cable Insulation Rating 100%, 133%, 173% Expected Fault Duty seeing higher levels due to greater Duty from power offtaker at POI larger park ratings 100s of MW) Underground versus Overhead Constructions Collector System Engineering & Design Engineered System Drawings Trench Grounding Feeder Circuits 6

Collector System Engineering & Design Engineered System Drawings Trench Grounding Install ground in trench with Feeder Circuits Collector System Engineering & Design Engineered System Drawings Trench Grounding Feeder Circuits Counterpoise 7

Collector System Engineering & Design Engineered System Drawings Sheath Grounding Solid Bonding Collector System Engineering & Design Engineered System Drawings Sheath Grounding Solid Bonding End-Point 8

Engineering & Design Requirements Engineered System Drawings Sheath Grounding Solid Bonding Mid-Point Collector System Engineering & Design Engineered System Drawings Sheath Grounding Solid Bonding Cross Bonding 9

Collector System Engineering & Design (IEEE 575) Connecting the Collector System Grounding Transformers Provide return path for ground fault current Convert ± sequence current to zero sequence current Prevent Voltage Elevation on un-faulted phases Eliminate ferroresonance Create an effectively grounded system Winding Configuration Zig-Zag or Wye-Delta Sizing Feeder Circuits: ~5% of connected feeder load 30MVA collector circuit = 1.5MVA Grounding Transformer 10

Connecting the Collector System to the Grid Collector Circuits Feeder Grounding Transformers -Ground Current Source -Connected on the WTG Side -One Per Feeder Connecting the Collector System Grounding Transformers Zig-Zag Series connection of windings forces equal currents IA 1 = IA 2 ; IB 1 = IB 2 ; IC 1 = IC 2 Magnetic coupling of windings forces equal currents (1:1 Turns Ratio) IA 1 = IB 2 ; IB 1 = IC 2 ; IC 1 = IA 2 As a result all currents are equal IA 1 = IA 2 = IB 1 = IB 2 = IC 1 = IC 2 11

Connecting the Collector System Grounding Transformers Zig-Zag Connecting the Collector System Grounding Transformers Wye-Delta Series connection of windings forces equal currents IA 2 = IB 2 = IC 2 Magnetic coupling of windings forces equal currents related by turns ratio IA 1 = nia 2 ; IB 1 = nib 2 ; IC 1 = nic 2 As a result all primary currents are equal IA 1 = IB 1 = IC 1 12

Connecting the Collector System Grounding Transformers Wye-Delta Connecting the Collector System Current Flow Pre-Fault All voltages ~1.0pu 13

Connecting the Collector System Current Flow - L-G Fault (Ungrounded) No path for ground fault current Load current continues to flow Elevated voltages on un-faulted phases Connecting the Collector System Current Flow - L-G Fault (Grounding Transformer) Ground fault current returns through grounding transformer Metering on ground leg senses fault current 14

Connecting the Collector System Delta Connected Systems Source of ground fault current NO Difficult to detect & locate ground faults Elevated voltages (1.73pu or L-L) on un-faulted phases during fault conditions Results in damaged equipment Arrestors Power Electronics Cable Insulation SOLUTION GROUNDING TRANSFORMERS SOLUTION C-B WITH HIGH SPEED GROUND SWITCH Within ~1 cycle of breaker trip all 3 phases are grounded Connecting the Collector System Grounded-Wye Connected Systems Source of ground fault current YES (Temporarily) Source is removed as the faulted feeder circuit-breaker is tripped WTGs will continue to generate for several cycles until removed from the circuit Faulted feeder remains energized with elevated voltages on un-faulted phases SOLUTION GROUNDING TRANSFORMERS Continue to supply zero sequence fault current until the fault is cleared thus eliminating over-voltages SOLUTION C-B WITH HIGH SPEED GROUND SWITCH Within ~1 cycle of breaker trip all 3 phases are grounded 15

Questions? 16