CSA Hazardous Area Approvals Fisher FIELDVUE DVC6005 Series Remote Mount Digital Valve Controllers

Similar documents
CSA Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers

FM Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers

IECEx Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers

CERTIFICATE OF COMPLIANCE

Thie. Automation Products Rev. Chang Date Name Supersedes Dwg. : Part Class:

Fisher 646 Electro Pneumatic Transducer

Fisher LCP100 Local Control Panel

Fisher 646 Electro-Pneumatic Transducers

IP26 Series Current to Pneumatic Converter

JM Enclosure Dimensions (in mm)

Fisher 4200 Series Electronic Position Transmitters

2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER

Range Spring, Bias Spring, and Spring Retainer/ Spacer Selection for Fisher 3570 Pneumatic Valve Positioners

Intrinsic Safety Control Drawing

EJX and EJA-E Series Differential Pressure and Pressure Transmitters Installation Manual. Contents 1. Introduction. 3. Installation. 5.

EN Series Installation Manual

Power supply. Calibration. Surface finishing. Seal. Process connection

Product manual wire programmable RTD transmitter

ESSENTIAL INSTRUCTIONS Read this page before proceeding!

Certificate of Compliance

MCR-FL-TS-LP-I-EX SIL IEC Programmable Intrinsically Safe Loop-Powered Temperature Measuring Transducer With HART Protocol

Title: INTRINSIC SAFETY MADE EASY

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

AH71, AH72, and AH73 FM Approved Humidity Transmitter Assemblies Installation and Operating Instructions

User s Manual. Manual Change No V-E. Please use the attached sheets for the pages listed below in IM 01F06F00-01EN (7th).

HT880 and HT885 FM Approved Humidity Transmitter Assemblies Installation and Operating Instructions

Specifications. Specifications. Transfer Characteristics Accuracy at 20 C (68 F) Temperature Drift

Certificate of Conformity

Customer Drawings Product Selection

ControlWave INTRINSICALLY SAFE PROXIMITY SENSOR INTF. BOARD

Loop Powered Indicator

LIQ_MAN_ABR_5081P-FF-FI/Rev. D January 2015

DPharp Differential Pressure and Pressure Transmitters

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

Annex 1 to Certificate of Conformity IECEx KEM X Issue No. 8 Rota Yokogawa Rotamass 3 Series Coriolis Mass Flowmeter

LIQ_MAN_ABR_5081T-HT/Rev. L January 2015

INSTRUCTION MANUAL. SIL 3 - SIL 2 Digital Output Loop/Bus Powered DIN-Rail Models D1040Q, D1041Q, D1042Q, D1043Q, D1040Q - D1041Q - D1042Q - D1043Q

INTRINSICALLY SAFE DUPLEXER

YVP110 Advanced Valve Positioner

ATEX Installation Drawings and Instructions

White Paper. Requirements for fieldbus equipment installed in a Zone 2 and Division 2 hazardous area environment. March 24, 2005

D1061S INSTRUCTION MANUAL. RS422/RS485 Fieldbus Isolating Repeater Din-Rail Model D1061S. D RS422 / RS485 Fieldbus Isolating Repeater

D1035S INSTRUCTION MANUAL. Frequency-Pulse Isolating Repeater DIN Rail Model D1035S. D Frequency-Pulse Isolating Repeater

Installation Instructions P/N MMI , Rev. AA July ATEX Installation Instructions for Micro Motion Model 3500 Transmitters

INSTRUCTION MANUAL. SIL 3 - SIL 2 Digital Output Loop/Bus Powered DIN-Rail Models D1040Q, D1041Q, D1042Q, D1043Q, D1040Q - D1041Q - D1042Q - D1043Q

QN5O, QXBO, QNBO, QX7O, QN7O, QXCO, QNCO

ATEX Installation Instructions for Micro Motion CMF400 Sensors with Booster Amplifier

Description. Annexe to: IECEx CML X Issue 1. Isolating Amplifier D461

ORIGINAL SIZE SYSTEM CONTROL DWG. FILE. ROSEMOUNT 2410 OrCADl. o o

Model DY Vortex Flowmeter Model DYA Vortex Flow Converter Fieldbus Communication Type

TÜV NORD CERT. TÜV NORD CERT GmbH & Co. KG Am TÜV 1 D Hannover. Annexe to IECEx TUN , issue No. 0 Page 1 of 5.

Micro Motion Model 5700 Transmitter IECEx Zone 2/22 Installation Instructions EPL Gc and EPL Dc

User s Manual YOKOGAWA. Model PH202G (S) ph Transmitter. IM 12B6C3-E-E 12th Edition

CERTIFICATE OF COMPLIANCE

Certificate of Compliance

D1061S INSTRUCTION MANUAL. RS422/RS485 Fieldbus Isolating Repeater Din-Rail Model D1061S. D RS422 / RS485 Fieldbus Isolating Repeater

MODEL: B6U-B B6-UNIT. [2] LCD DISPLAY 0: Without 1: With

PROline promag 53 Division 1

Micro Motion Model 5700 Transmitter ATEX Zone 2/22 Installation Instructions II 3 G or II 3 (2) G/EPL Gc & II 3 D/EPL Dc

Product Manual wire HART transmitter

GTS High Frequency Pulser. Technical Bulletin

COMMUNICATION NETWORKS

YTA610 and YTA710 Temperature Transmitter (Hardware)

Rosemount 848L Logic Transmitter with FOUNDATION Fieldbus

Rev ECN Description Approval Date AA Release to Approvals RCS 10/9/12

Rev ECN Description Approval Date AA Release to Approvals RCS 10/9/12

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

MODEL LP35 LP SERIES LOW PROFILE INTRINSIC SAFETY INCREMENTAL ENCODER

INTRINSIC SAFETY BASIC PRINCIPLES

INSTRUCTION MANUAL. SIL 3 Switch/Proximity Detector Interface DIN-Rail Models D1034S, D1034D D1034S - D1034D

Instruction Manual LIQ_MAN_5081A-FF/rev.M January A. FouNdAtIoN Fieldbus two-wire Chlorine, dissolved oxygen, and ozone transmitter

INSTRUCTION & SAFETY MANUAL

F2xx & F2xx-XE Megablock Series

Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters

Fieldbus Solutions & Network Topologies. ISA Exhibition Toronto May 12, 2004

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5.

Electrodynamic Velocity Sensor

Instruction. MI October I/A Series Models 83.-D and -T Vortex Flowmeter Intrinsic Safety Connection Diagrams

Rosemount 148 Temperature Transmitter

Safety Instructions Proline Promag 500

Emerson (Appleton Group ATX)

Attachment to Certificate IECEx PTB X

STT 3000 Smart Temperature Transmitter Series STT170 Specifications

IECEx Certificate of Conformity Annexe

General Specifications

User's Manual. ROTAMASS Total Insight Coriolis Mass Flow and Density Meter Explosion Proof Type Manual IECEx IM 01U10X02-00EN-R

DPharp Fieldbus Communication Type (EJX A, EJA E)

F2xx & F2xx-XE megablock range

User s Manual Diaphragm Sealed Differential Pressure and Pressure Transmitters EJ 118 and EJ 438

The T6000 Series Electro-Pneumatic Transducer converts a DC current or voltage input signal to a directly proportional pneumatic output.

User s Manual Flange Mounted Differential Pressure Transmitters EJX210A and EJA210E

Binary Output Series 9175

User s Manual EJX118A and EJX438A Diaphragm Sealed Differential Pressure and Pressure Transmitters

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents

Rosemount 148 Temperature Transmitter

Armstrong Intelligent Monitoring Installation and Operation Manual

1-830 SERIES DISPLACEMENT TRANSMITTER

Level Lance Model 5100

Product Manual wire HART transmitter

R88000 T (including ATEX)

Transcription:

Instruction Manual Supplement DVC6005 Digital Valve Controllers CSA Hazardous Area Approvals Fisher FIELDVUE DVC6005 Series Remote Mount Digital Valve Controllers Hazardous Area Approvals and Special Instructions for Safe Use and Installations in Hazardous Locations Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of safe use. These special instructions for safe use are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval type. Note This information supplements the nameplate markings affixed to the product and the DVC6005 Series Remote Mount quick start guide (D103784X012), available from your Emerson sales office, Local Business Partner or at Fisher.com. Approval information is for both aluminum and stainless steel constructions. Always refer to the nameplate itself to identify the appropriate certification. WARNING Failure to follow these conditions of safe use could result in personal injury or property damage from fire or explosion and area re classification. Ordinary Locations Approval Complies with general electrical safety CAN/CSA C22.2 No. 61010 1 2004 SELV, conduit connected, Enclosure Type 4X, IP66, Installation Category I, Pollution Degree 4 DVC6005 Series (HART HW1, FOUNDATION fieldbus) Rated Input 9-30 VDC, 4-20 ma Outputs 0-9.6 VDC, 0-3.5 ma -52 C Ambient +80 C Rated Input 10 VDC max, 3.5 ma max -60 C Ambient 125 C www.fisher.com

DVC6005 Digital Valve Controllers Instruction Manual Supplement Explosion-proof and Dust Ignition-proof Class I, Division 1, Groups B,C,D ; Class I, Division 2, Groups A,B,C,D Class II, Division 1, Groups E,F,G ; Class II, Division 2, Groups F,G Class III, Division 1 Ex d IIC Ex nc IIC (DVC6005 Series) Ex na IIC () Type 4X, IP66 Single Seal Device (HART HW2 with I/O Package pending) DVC6005 Series (HART HW1 & HW2, FOUNDATION FIELDBUS) Rated input 30 Vmax, 20 ma - 52 C Ambient + 80 C Max inlet pressure 10 bar (145 psig) (air or natural gas) Temperature Code: (Tamb 75 C), (Tamb ) Rated input 10 Vmax, 5 ma - 60 C Ambient + 125 C Temperature Code: (Tamb ), (Tamb 95 C), (Tamb 125 C) Intrinsically Safe Class I, Division 1, Groups A,B,C,D Class II, Division 1, Groups E,F,G Class III, Division 1 Ex ia IIC Type 4X, IP66 Single Seal Device (HART HW2 with I/O Package pending) DVC6005 Series (HART HW1 & HW2, FOUNDATION FIELDBUS) Rated input 30 V DC max, 20 ma - 52 C Ambient + 80 C Max inlet pressure 10 bar (145 psig) (air or natural gas) Rated input 10 Vmax, 5 ma - 60 C Ambient + 125 C Intrinsically safe when connected per installation drawing GE42818, as shown in the following figures DVC6005 HW1 and... figure 1 and 4 DVC6005 HW2 and... figure 2 and 4 DVC6005f and... figure 3 and 4 2

Instruction Manual Supplement DVC6005 Digital Valve Controllers Figure 1. CSA Loop Schematics FIELDVUE DVC6005 HW1 and HAZARDOUS LOCATION NON HAZARDOUS LOCATION Ci = 0 uf Pi = 160 mw NOTE 1 1 Voc = 30 VDC Isc = 12 ma Ca = 66 nf La = 246 mh Po = 86 mw DVC6005 Imax = 226 ma Ci = 5 nf Li = 0.55 mh Pi = 1.4 W NOTE 7 CSA APPROVED BARRIER NOTE 1, 3, 4, 5, 6 1 1 125 C 95 C 75 C 1 SEE NOTES IN FIGURE 4 GE42818 Sheet 5, Rev. F 3

DVC6005 Digital Valve Controllers Instruction Manual Supplement Figure 2. CSA Loop Schematics FIELDVUE DVC6005 HW2 and HAZARDOUS LOCATION NON HAZARDOUS LOCATION HW2 - WITH OR WITHOUT I/O PACKAGE DVC6005 REMOTE FIELD WIRING TERMINAL BOX FIELD WIRING TERMINAL BOX Ci = 0 uf Pi = 160 mw NOTE 1, 3 1 Voc = 30 VDC Isc = 21.2 ma Ca = 55 nf La = 78 mh Po = 160 mw LOOP TERMINALS Imax = 130 ma Ci = 15 nf Li = 0.55 mh Pi = 1.0 W OUTPUT TERMINALS Vmax = 28 VDC Ci = 15 nf Li = 0.5 mh Pi = 1.0 W NOTE 7 1 CSA APPROVED BARRIER NOTE 1, 3, 4, 5, 6 1 CSA APPROVED BARRIER 125 C 95 C NOTE 1, 3, 4, 5, 6 1 WITH I/O PACKAGE WITHOUT I/O PACKAGE POWER MAY BE APPLIED TO EITHER THE LOOP TERMINALS OR OUTPUT TERMINALS OR TO BOTH SETS OF TERMINALS AT THE SAME TIME UNITS WITHOUT THE I/O PACKAGE WILL NOT HAVE OUTPUT TERMINALS AVAILABLE FOR CONNECTION 1 SEE NOTES IN FIGURE 4 61 C 74 C GE42818 Sheet 13, Rev. C 4

Instruction Manual Supplement DVC6005 Digital Valve Controllers Figure 3. CSA Loop Schematics FIELDVUE DVC6005f and CSA APPROVED ENTITY DEVICE NOTE 1, 3 1 DVC6015, DVC6025, DVC6035 Ci = 0 uf Pi = 160 mw NOTE 1 1 HAZARDOUS LOCATION Voc = 24 VDC Isc = 17.5 ma Ca = 121 nf La = 100 mh Po = 105 mw DVC6005f Vmax = 24 VDC Imax = 380 ma Ci = 5 nf Pi = 1.4 W NON HAZARDOUS LOCATION CSA APPROVED BARRIER NOTE 7 1 125 C 95 C 77 C 62 C 1 NOTE 1, 3, 4, 5, 6 GE42818 Sheet 6, Rev. F ENTITY FIELDBUS LOOP HAZARDOUS LOCATION NON HAZARDOUS LOCATION CSA APPROVED FISCO DEVICE NOTE 2, 3 1 DVC6015, DVC6025, DVC6035 Ci = 0 uf Pi = 160 mw NOTE 2 1 DVC6005f Voc = 17.5 VDC Isc = 17.5 ma Ca = 121 nf La = 100 mh Po = 105 mw Vmax = 17.5 VDC Imax = 380 ma Ci = 5 nf Pi = 5.32 W CSA APPROVED FISCO BARRIER CSA APPROVED FISCO TERMINATOR 125 C 95 C 77 C 62 C 1 NOTE 2, 3, 4, 5, 6 GE42818 Sheet 7, Rev. F FISCO LOOP 1 SEE NOTES IN FIGURE 4 5

DVC6005 Digital Valve Controllers Instruction Manual Supplement Figure 4. Notes for CSA Loop Schematics THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Vmax or Ui), THE CURRENT (Imax or Ii), AND THE POWER (Pmax or Pi) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Voc or Uo), AND THE CURRENT (Isc or Io), AND THE POWER(Po) DEFINED BY THE ASSOCIATED APPARATUS. IN ADDITION, THE SUM OF THE MAX UNPROTECTED CAPACITANCE (Ci) AND MAX UNPROTECTED INDUCTANCE (Li), INCLUDING THE INTERCONNECTING CABLING CAPACITANCE (Ccable) AND CABLING INDUCTANCE (Lcable) MUST BE LESS THAN THE ALLOWABLE CAPACITANCE (Ca) AND INDUCTANCE (La) DEFINED BY THE ASSOCIATED APPARATUS. IF THE ABOVE CRITERIA IS MET, THEN THE COMBINATION MAY BE CONNECTED. Vmax or Ui Voc or Uo Imax or Ii Isc or Io Pmax or Pi Po Ci + Ccable Ca Li + Lcable La THE FISCO CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR THE INTERCONNECTION IS THAT THE VOLTAGE (Vmax or Ui), CURRENT (Imax or Ii), AND POWER (Pmax or Pi), WHICH AN INTRINSICALLY SAFE APPARATUS CAN RECEIVE AND REMAIN INTRINSICALLY SAFE, CONSIDERING FAULTS, MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Voc or Uo), CURRENT (Isc or Io), AND POWER (Po) LEVELS WHICH CAN BE DELIVERED BY THE ASSOCIATED APPARATUS, CONSIDERING FAULTS AND APPLICABLE FACTORS. IN ADDITION THE MAXIMUM UNPROTECTED CAPACITANCE (Ci) AND INDUCTANCE (Li) OF EACH APPARATUS (OTHER THAN THE TERMINATION) CONNECTED TO THE FIELDBUS MUST BE LESS THAN OR EQUAL TO 5 nf AND 10 uh RESPECTIVELY. IN EACH SEGMENT ONLY ONE ACTIVE DEVICE, NORMALLY THE ASSOCIATED APPARATUS, IS ALLOWED TO PROVIDE THE NECESSARY ENERGY FOR THE FIELDBUS SYSTEM. THE VOLTAGE (Uo or Voc or Vt) OF THE ASSOCIATED APPARATUS HAS TO BE LIMITED TO THE RANGE OF 9 V TO 17.5 VDC. ALL OTHER EQUIPMENT CONNECTED TO THE BUS CABLE HAS TO BE PASSIVE, MEANING THAT THEY ARE NOT ALLOWED TO PROVIDE ENERGY TO THE SYSTEM, EXCEPT FOR A LEAKAGE CURRENT OF 50 ua FOR EACH CONNECTED DEVICE. SEPARATELY POWERED EQUIPMENT NEEDS A GALVANIC ISOLATION TO ASSURE THAT THE INTRINSICALLY SAFE FIELDBUS CIRCUIT REMAINS PASSIVE. THE CABLE USED TO CONNECT THE DEVICES NEEDS TO HAVE THE PARAMETERS IN THE FOLLOWING RANGE: LOOP RESISTANCE R': 15 TO 150 ohms/km INDUCTANCE PER UNIT LENGTH L: 0.4 TO 1 mh/km CAPACITANCE PER UNIT LENGTH C': 80 TO 200 nf/km C' = C' LINE/LINE + 0.5' LINE/SCREEN, IF BOTH LINES ARE FLOATING OR C' = C' LINE/LINE + C' LINE/SCREEN, IF THE SCREEN IS CONNECTED TO ONE LINE. LENGTH OF SPLICE: < 1 m (T BOX MUST ONLY CONTAIN TERMINAL CONNECTIONS WITH NO ENERGY STORAGE CAPABILITY) LENGTH OF SPUR CABLE: < 30 M LENGTH OF TRUNK CABLE: < 1 km AT EACH END OF THE TRUNK CABLE AN APPROVED INFALLIBLE TERMINATION WITH THE FOLLOWING PARAMETERS IS SUITABLE: R = 90 TO 100 ohms AND C = 0 TO 2.2 uf NOTE, A BUILT IN TERMINATOR IS INCLUDED IN THE FIELD SIDE AND A SELECTABLE TERMINATOR IS AVAILABLE ON THE HOST SIDE. THE NUMBER OF PASSIVE DEVICES CONNECTED TO THE BUS SEGMENT IS NOT LIMITED IN THE FISCO CONCEPT FOR INTRINSICALLY SAFE REASONS. IF THE ABOVE RULES ARE RESPECTED, UP TO A TOTAL LENGTH OF 1000 m (SUM OF THE LENGTH OF THE TRUNK CABLE AND ALL SPUR CABLES), THE INDUCTANCE AND CAPACITANCE OF THE CABLE WILL NOT IMPAIR THE INTRINSIC SAFETY OF THE INSTALLATION. INSTALLATION MUST BE IN ACCORDANCE WITH THE CANADIAN ELECTRICAL CODE (CEC) AND ANSI/ISA RP12.6. MAXIMUM SAFE AREA VOLTAGE SHOULD NOT EXCEED 250 Vrms. RESISTANCE BETWEEN INTRINSICALLY SAFE GROUND AND EARTH GROUND MUST BE LESS THAN ONE OHM LOOPS MUST BE CONNECTED ACCORDING TO THE BARRIER MANUFACTURER'S INSTRUCTIONS. IF HAND HELD COMMUNICATOR OR MULTIPLEXER IS USED, IT MUST BE CSA APPROVED WITH ENTITY PARAMETERS AND INSTALLED PER THE MANUFACTURER'S CONTROL DRAWINGS. GE42818 Sheet 8, Rev. E 6

Instruction Manual Supplement DVC6005 Digital Valve Controllers 7

DVC6005 Digital Valve Controllers Instruction Manual Supplement Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Fisher and FIELDVUE are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice. Emerson Automation Solutions Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore www.fisher.com 8 2016, 2017 Fisher Controls International LLC. All rights reserved.