Analysis of Arrester Energy for 132kV Overhead Transmission Line due to Back Flashover and Shielding Failure

Similar documents
Lightning performance of a HV/MV substation

Analysis of lightning performance of 132KV transmission line by application of surge arresters

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

Lightning overvoltage and protection of power substations

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters

Electric Stresses on Surge Arrester Insulation under Standard and

Insulation Coordination Study of 275kV AIS Substation in Malaysia

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Experimental Study on Lightning Surge Response of 500kV Transmission Tower with Overhead Lines

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Computation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission Lines

Modeling insulation in high-voltage substations

Comparison between Different InstallationLocations of Surge Arresters at Transmission Line Using EMTP-RV

Parameters Affecting Lightning Backflash Over Pattern at 132kV Double Circuit Transmission Lines

Lightning Overvoltage Performance of 110 kv Air-Insulated Substation

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

A SIMPLIFIED LIGHTNING MODEL FOR METAL OXIDE SURGE ARRESTER. K. P. Mardira and T. K. Saha s: and

Research on Lightning Over-voltage and Lightning Protection of 500kV. HGIS Substation

Tab 8 Surge Arresters

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Electrical Power and Energy Systems

The line-lightning performance and mitigation studies of shielded steelstructure

GIS Disconnector Switching Operation VFTO Study

Lightning transient analysis in wind turbine blades

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation

Lightning Performance of Transmission Lines with Tall Sections

Power Quality and Reliablity Centre

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

Including Surge Arresters in the Lightning Performance Analysis of 132kV Transmission Line

Insulation Co-ordination For HVDC Station

How to Conduct the Lightning Impulse Withstand Test of. Three Gorges Right Bank Substation 550kV GIS

ABSTRACTS of SESSION 6

The impact of distributed generation to the lightning protection of modern distribution lines

Effective Elimination Factors to the Generated Lightning Flashover in High Voltage Transmission Network

INSTALLATION OF LSA ON A 400 KV DOUBLE-CIRCUIT LINE IN RUSSIA

Analysis of current distribution among long-flashover arresters for 10 kv overhead line protection against direct lightning strikes

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations

Study of Tower Grounding Resistance Effected Back Flashover to 500 kv Transmission Line in Thailand by using ATP/EMTP

Mitigation of Back-Flashovers for 110-kV Lines at Multi-Circuit Overhead Line Towers

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

Lightning Overvoltage performance of 132kV GIS Substation in Malaysia

Towards an Accurate Modeling of Frequency-dependent Wind Farm Components under Transient Conditions

Investigation of Transmission Line Overvoltages and their Deduction Approach

Transformers connected via a cable Overvoltage protection

Simulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

New Modeling of Metal Oxide Surge Arresters

High voltage engineering

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

DC current interruption tests with HV mechanical DC circuit breaker

Analyzing and Modeling the Lightning Transient Effects of 400 KV Single Circuit Transmission Lines

Substation Insulation Coordination Study

International Journal of Advance Engineering and Research Development. Analysis of Surge Arrester using FEM

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation

The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line.

TRIGGERED by energy transition towards sustainability,

X International Symposium on Lightning Protection

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

RESULTS OF EXPERIMENTAL HIGH CURRENT IMPULSE 4/10 s OF METAL OXIDE VARISTORS ZINC IN THE HIGH VOLTAGE 220KV SURGE ARRESTER

Investigation into Transient SFO, FFO, VFTO Overvoltage Characteristics for Typical Gas Insulated Substations

Accuracy of Lightning Surge Analysis of Tower Surge Response

SCIENCE & TECHNOLOGY

B2-301 IMPROVING DOUBLE CIRCUIT TRANSMISSION LINE RELIABILITY THROUGH LIGHTNING DESIGN

Estimating the Lightning Performance of a Multi- Circuit Transmission Tower

Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

Chapter 1. Overvoltage Surges and their Effects

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

A Study of Lightning Surge on Underground Cables in a Cable Connection Station

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS

Statistical Lightning Simulations for a HV "Mixed" Overhead-Cable Line: Preliminary Studies

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet

Estimating BFOR on HV Transmission Lines Using EMTP and Curve of Limiting Parameters

Research Article Survey of Induced Voltage and Current Phenomena in GIS Substation

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

Protection against unacceptable voltages in railway systems

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

Insulation Level and Test Technology of. 1000kV Power Transformer

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

AORC Technical meeting 2014

7P Series - Surge Protection Device (SPD) Features 7P P P

Computer Aided-Program for Validation of HV Impulse Measuring Systems from Unit Step Response

Transcription:

nalysis of rrester Energy for 132kV Overhead ransmission Line due to Back Flashover and Shielding Failure Nor Hidayah Nor Hassan 1,a, b. Halim bu Bakar 2,b, Hazlie Mokhlis 1, Hazlee zil Illias 1 1 Department of Electrical Engineering, Faculty of Engineering, University of Malaya, 50603 Kuala Lumpur, Malaysia 2 UM Power Energy Dedicated dvanced Center (UMPEDC), Level 4, Wisma R&D, University of Malaya, Jalan Pantai Baharu, 59990 Kuala Lumpur, Malaysia a hidayahassan@siswa.um.edu.my, b a.halim@um.edu.my bstract his paper presents the analysis of lightning arrester energy due to back flashover and shielding failure phenomena in a 132kV transmission line in Malaysia. he transmission line, towers and surge arresters were modeled using PSCD/EMDC software. he model has been used to simulate the discharged energy from lightning arresters that were installed on the tower in the event of back flashover and shielding failure. he arrester was modeled based on the IEEE frequency dependent model. Comparison between the simulation results and values calculated theoretically was performed to validate the model that has been developed. he results show that both are in reasonable agreement with each other. he maximum calculated and simulated energy discharged by the arrester is found to be less than 5.1 kj/kv, which is the rating of arresters installed in the actual 132kV transmission lines. Keywords-rrester; Back Flashover; Shielding Failure; Bergeron model; PSCD/EMDC I. INRODUCION Generally, the use of line arrester is to decrease or eliminate lightning flashover on transmission and distribution lines [1]. he purpose of line arrester installation in transmission line system is to improve the performance of overhead lines with poor shielding or with very high tower footing impedance [2]. rresters avoid lightning flashovers since transmission lines insulation voltage is higher than the residual voltage developed across the arresters, either due to back flashover or shielding failure. However, the arresters have to withstand the energy discharged by the lightning stroke. Shielding failure occurs when lightning strikes less than or equal to 20 k bypass the overhead ground wires [3]. It is always designed such that overhead ground wires are located at a position which provides the least shielding failure. hus, the majority of the lightning will terminate on the ground wires and build up a voltage across the line insulation. Back flashover will occur when these voltages exceed the line critical flashover (CFO). his paper presents the application of PSCD software to estimate the arrester energy due to shielding failure (SF) and back flashover (BFO) phenomena. he ranges of the current stroke used in the simulation, which contributes to both phenomena, are stated in [3]. he CIGRE simulation method for 132kV has been developed and the arrester was based on the frequency dependent model, which is represented with IEEE two sections of nonlinear resistance. Since the Maximum Continuous Operating Voltage (MCOV) of 132 kv transmission line is 97.2 kv, RVLQD - Class 2 type of arrester has been chosen because the rated voltage is between 3kV to 198kV as in the datasheet of porcelain type surge arrester from oshiba. II. MODELLING he overhead lines are represented by multi-phase model, which consider the distributed nature of the line parameters due to the range of frequencies involved. Phase conductors and shield wires are modeled in detail between the towers. PSCD/EMDC was used to model transmission line, towers and surge arresters. PSCD/EMDC was used because it offers real time analysis simulation. his software allows user to construct complex nonlinear power system models that combine three main components of a power system, power electronics and control circuits into one using more than 280 flexible components in the master library. Furthermore, PSCD/EMDC is suitable for simulating time domain instantaneous responses or electromagnetic transients for both electrical and control systems.. ransmission Line and ower Model ransmission line is modelled based on standard single circuit line geometry drawings and conductor data of a typical 132kV line. he transmission towers are represented geometrically similar to that of the single-storey lattice tower as shown in Figure 1. he lowest conductor from the ground is 16.45 m and the span length of the transmission line is 300m. Line geometry for the tower configuration is shown in Figure 2. he surge propagation velocity is assumed equal to 85% of the speed of light [4]. here are several formulae to calculate the surge impedance of the tower. s a basis, (1), which is for waist tower shape [5] and recommended by IEEE and CIGRE [6] is used, Z t = 60 ln [cot {0.5 tan -1 (r avg / h)}] (1) 978-1-4673-5019-8/12/$31.00 2012 IEEE 683

r avg r h + r h h r h 1 1 2 3 2 ravg + = (2) = equivalent radius of the tower represented by a truncated cone h = tower height, m h 1 = tower height from midsection to top, m h 2 = tower height from base to midsection, m r 1, r 2, r 3 = tower top, midsection and base radii, m 10 [pf] 10 [pf] 10 [pf] G1 B C 1s1 1s4 1s7 1s10 1s3 1s6 1s9 1s12 10[ohm] 1s2 G2 Figure 3. PSCD tower model Figure 1. 132 kv tower dimension B. Insulator String Model he insulator is modeled as a stray capacitor (C) connected in parallel with a voltage controlled switch (S) as shown in Figure 4. he string which consists of glass insulators, provides an equivalent capacitance used in the model. Insulator supports the conductor by providing mechanical support that depends on its normal operating and transient voltage. he voltage withstand capability of the insulator is calculated using 710 V o 0.9(400 + ) d 0.75 t = (3) V o = flashover voltage, kv t = time elapsed after lightning stroke, µs [8, 9] d = length of gap between arc horn, m Crossarm C S Conductor Figure 4 Insulator string flashover model Figure 2. 132kV tower configuration Five transmission towers were modelled as single conductor distributed parameter line (Bergeron model travelling wave) segments of transmission lines in PSCD, as shown in Figure 3. Since the line parameters are constant at the chosen frequency when the Bergeron model is used, the user may select the R, L and C values. Line termination at each side of the model is necessary to avoid any reflection that might affect the simulated overvoltages around the point of impact [7]. C. Line rrester Model he line arrester characteristics used in the simulation are shown in able 1. BLE I. RRESER CHRCERISICS Nominal voltage(kv) 120 MCOV(kV rms) 97.2 Voltage(kV) for 10 k, 8/20μs 330 Energy absorption 4.5 Length of arrester column(m) 1.485 No. of parallel column of disks 1 684

he non-linear characteristic of the line arrester is modeled as recommended by the IEEE W.G 3.4.11, which is metal oxide surge arrester [10]. IEEE line arrester model has been chosen because the oshiba surge arrester uses non linear resistor metal oxide elements as the main component. he frequency-dependent model consists of two non-linear resistors, 0 and 1, which are separated by an R-L filter, as shown in Figure 5. Figure 6 shows the V-I characteristics of 0 and 1 obtained from 8/20 µs impulse data, which is supplied by the manufacturer. III. LIGHNING he lightning source is modeled based on the IEC triangular wave shape, as shown in Figure 7 [11]. he lightning stroke is modeled by a current source in parallel with a lightning - path impedance, as shown in Figure 8. he lightning-path impedance is represented as a parallel resistance of 400 Ω [12]. peak current source of different magnitudes has been used to investigate the effects of shielding failure (SF) and back flashover (BFO) phenomena on the arrester discharge energy. able 2 shows the injected single stroke current for simulation of SF and BFO. I I peak t r = rise time t h = tail/half time I peak /2 Figure 5: IEEE frequency-dependent model line arrester Voltage, V (p.u) 2.3 2.1 1.9 1.7 1.5 1.3 1.1 0.9 0.01 1 4 8 12 16 20 Current, I (k) 0 1 t r t h t (μs) Figure 7: Recommended IEC triangular wave shape [11] 31 Istroke IME * 400[ohm] able Figure 6: V-I non-linear characteristic for 0 and 1 he initial parameters of the resistor and inductor are calculated based on the estimated height of the arrester and the number of parallel columns of metal-oxide disks using [10] L 15d / n R 65d / n L o 0.2d / n 1 = (µh) (4) 1 = (Ω) (5) = (µh) (6) R o 100d / C 100n / n d = (Ω) (7) = (pf) (8) d= estimated height of the arrester (as in data sheet), m n= number of parallel columns of metal oxide in the arrester he values of 0, 1 and L 1 have to be adjusted so that the discharge voltages between theory and experiment have a good match. Figure 8: Lightning source model consisting of a current source and lightning path impedance BLE II. INJECED CURREN FOR SIMULION Injected Current, I (k) BFO SF 35 5 80 10 100 13 150 15 180 18 200 20 ransmission shielding failure and back flashover were simulated by injecting single stroke currents to a line phase conductor or ground wire of the third tower. he time to rise, t r and time to half, t f, are chosen as 8μs and 20μs. 685

IV. RRESER ENERGY. Stroke to ower or Ground Wire he energy discharged by the line arrester, W, during back flashover can be estimated using [1] i e τ = arrester current, W = i e τ (9) = arrester discharge voltage, V = time constant, s he time constant of the arrester current, τ, is estimated by Z g R i s Z g τ = s (10) R = ground wire impedance, Ω = footing resistance, Ω i = span length divided by the velocity of light, s B. Stroke to Phase Conductor Lightning that struck at the phase conductor will give a different estimation of arrester energy discharged from lightning that struck at ground wire. he energy discharged by the surge arrester, W, during shielding failure can be expressed as an integral form of product of arrester current and discharge voltage [1]. W i = e dt 0 (11) he relation between the arrester current and discharge voltage can be represented by [13] α i = k( e ) (12) Combining both equation (11) and (12), simple arrester discharge energy equation can be express by K1Ie 1τ 1 W = (13) 1 + 1 α where E 1 are the discharge voltage for current of K I I and α is -t / τ 1. Detailed derivation of both equations is explained in [1].. Stroke to ower or Ground Wire he stroke current strikes directly to ground wire or tower, creating back flashover phenomena. Figure 9 shows the voltage across the arrester when a lightning current of 20 k, 8/20 μs was injected on the third tower. y 800 600 400 200 0-200 -400 V1-600 0.00 0.05m 0.10m 0.15m 0.20m 0.25m 0.30m Figure 9: Voltage across arrester for 20 k stroke to the ground wire he energy dissipated by the frequency dependent model, which consists of two non-linear resistors, 0 and 1 are shown in Figures 10 and 11. he total of these energies discharged by the line arrester is shown in Figure 12. Figure 10: 0 energy waveform for 20 k stroke to the ground wire Figure 11: 1 energy waveform for 20 k stroke to the ground wire V. RESULS ND DISCUSSION In practice, the 132kV transmission lines are equipped with 5.1kJ/kV energy of surge arrester. hus, comparisons between the calculation and simulation was performed for: a) back flashover for stroke current range of 20 k to 200 k b) shielding failure for stroke current range of 0 k to 20 k Over 50% of the lightning strokes contain more than one stroke, which is also known as multiple strokes lightning (MSL) [14]. However, in this work, single stroke lightning (SSL) current magnitude was only considered. Figure 12: Simulated energy discharged by the line arrester for 20 k stroke to the ground wire 686

able 3 and Figure 13 show comparison between the calculated energy values using (9) and the values obtained from simulation results of stroke currents between 20 k to 200 k. It was found that the simulated energy is slightly different than the calculated energy. his might due to the transmission line parameter used for tower models in the simulation are inaccurate. he energy discharged by the non-linear element of 0 and 1 obtained from the simulation when the peak current magnitude was injected to the conductor is shown in Figures 15 and 16. BLE III. Stroke Current (k) ENERGY OF RRESER DURING BCK FLSHOVER Calculated Energy 35 0.06 0.07 80 0.15 0.24 100 0.25 0.31 150 0.50 0.52 180 0.65 0.64 200 0.76 0.73 Simulated Energy Figure 15: 0 energy waveform for 20 k stroke to phase conductor Figure 16: 1 energy waveform for 20 k stroke to phase conductor Figure 13: Comparison of arrester energy during back flashover Both 0 and 1 do not share the discharge energy equally because of the inductance between the elements. he sum of the two energy results in the total energy absorption of the line arrester due to shielding failure is shown in Figure 17. B. Stroke to Phase Conductor direct lightning stroke to phase conductor may result in a shielding failure. his occurs when lightning currents of less than or equal to 20k bypass the overhead shield wire. For this case, only SSL current magnitudes of 5k to 20k were simulated because shielding failures tend to occur between these values. he designed line arrester was placed at the top phase 1 of the third tower and different SSL currents were injected at the top phase conductor. he waveform of the discharge voltage across the phase 1 when a 20k lightning stroke terminates at the top conductor is shown in Figure 14. Figure 14: Voltage across surge arrester for 20 k stroke to phase conductor Figure 17: Simulated energy discharged by the line arrester for shielding failures o calculate the arrester energy analytically, the stroke current is assumed to have exponential tail decay. he time to half value of the stroke current is chosen as 20μs, hence the tail time constant, τ, is 29μs. ssuming the arrester discharges the entire stroke current, the energy dissipated can be calculated from (10) and (11). Figure 18 shows comparison between the calculated and simulated results of the arrester discharge energy in kj due to SSL striking the top phase conductor. able 4 summarizes the results of the obtained total energy dissipated by the arrester in kj/kv of MCOV for different peak current magnitudes. Increase in the lightning current results in a higher energy discharged by the arrester. 687

Figure 18: Comparison of arrester energy during shielding failure BLE IV. Stroke Current (k) ENERGY OF RRESER DURING SHIELDING FILURE Calculated Energy 5 0.80 0.91 10 1.92 1.97 13 2.61 2.65 15 3.08 2.96 18 3.78 3.67 20 4.28 4.16 Simulated Energy C. Effect of footing resistance he effect of the footing impedance was analyzed by assuming a simple linear resistance for the its model. able V shows the energy discharged through the arrester installed at phase of the test line as a function of the tower footing resistance for both back flashover and shielding failure. Note that, as the footing resistance increase, energy discharged for lightning that strike to the ground wire also increase. For lightning strikes at phase conductor, arrester energy remains the same as the footing resistance increase. herefore, any changes to the footing resistance does not change the energy of arrester for shielding failure phenomena. his situation differs for back flashover phenomena as the energy discharged increase if the footing resistance increase. BLE V. ENERGY OF RRESER FOR DIFFEREN FOOING RESISNCE Energy, kj/kv Rf, Curent 200 k at ground Current 18 k at phase Ω wire (Back flashover) (Shielding Failure) 10 0.7296 3.67 20 0.7353 3.67 30 0.7390 3.67 40 0.7417 3.67 50 0.7454 3.67 60 0.7530 3.67 VI. CONCLUSION he work in this paper has investigated the capability of the arresters installed in 132 kv transmission lines in Malaysia, in withstanding single stroke lightning discharged energy caused by shielding failure and back flashover phenomena. he arrester energy discharged due to shielding failure and back flashover was calculated using analytical method and simulation using PSCD/EMDC. Comparison between the simulation results and values calculated theoretically shows that both results are within reasonable agreement to each other. he effect of footing resistance to the energy discharged also been covered in this paper. Only back flashover phenomena will increase the energy discharged as the footing resistance increase. he rating of the arresters installed in the actual 132kV transmission lines, which is 5.1 kj/kv, has been found capable of handling the maximum energy discharged by the designed arrester. Future work will consider other current impulse wave shape and multiple strokes lightning to study the behavior of arrester energy. CKNOWLEDGMEN he author thanks the University of Malaya for supporting this work through the IPPP research grant (Grant no: PS012-2012). REFERENCES [1]. R. Hillman, Insulation Coordination for Power Systems, Marcel Dekker, 1999. [2] CIGRE WG 33.11, pplication of Metal Oxide Surge rresters to Overhead Lines, Electra, October 1999. [3] C.. Nucci, Survey on Cigré and IEEE Procedures for the Estimation of the Lightning Performance of Overhead ransmission and Distribution Lines, in sia-pacific International Symposium on Electromagnetic Compatibility (PEMC), Beijing, pp. 1124-1133, 2010. [4] IEEE Working Group, Simplified Method for Estimating Lightning Performance of ransmission Lines, IEEE rans. Power pp. Syst., vol. PS-104, no. 4, pp. 919-932, pr. 1985. [5] W.. Chisholm, Y.L. Chow, K.D. Srivastava, ravel ime of ransmission owers, IEEE rans. on Power pparatus and Systems, vol. 104, no. 10, pp. 2922-2928, October 1985. [6] CIGRE WG 33.01, Guide to Procedures for Estimating the Lightning Performance of ransmission Lines, CIGRE Brochure 63, 1991. [7] Juan. Martinez-Velasco, Castro-randa; Modeling of Overhead ransmission Lines for Lightning Studies, IPS 05 in Motreal, Canada No. IPS05 190, June 19-23, 2005. [8] IEEE Standard, IEEE Guide for Improving the Lightning Performance of ransmission Lines, IEEE Std pp. 1243-199. [9] D. Caulker,. Hussein, Z.. Malek, S. Yusof, Shielding Failure nalysis of 132 kv ransmission Line Shielded by Surge rresters ssociated with Multiple Strokes Lightning, International Conference on Electrical and Computer Engineering (ICECE), 2010, vol., no., pp.298-301, 18-20 Dec. 2010. [10] IEEE WG 3.4.11, Modelling of Metal Oxide Surge rresters, IEEE rans. On Power Delivery, vol. 7, pp.302-309, Jan. 1992. [11].H.. Bakar, H. Mokhlis,.L. Lim, W.P. Hew, Lightning Over voltage performance of 132kV GIS Substation in Malaysia, International Conference on Power System echnology (POWERCON), 2010, vol., no., pp.1-7, 24-28 Oct. 2010. [12]. metani,. Kawamura, Method of a Lightning Surge nalysis Recommended in Japan Using EMP, IEEE rans. on Power Delivery, Vol. 20, No. 2, pp. 867-875, pril 2005. [13]. E. McDermott, D. E. Parrish, and D. B. Miller, Lightning Protection and Design Workstation Seminar Notes, EPRI R-000530, Sep. 1992. [14] PSCD/EMDC Manual, Introduction to PSCD/EMDC V3, Manitoba HVDC Research Centre Inc. 2001. 688