1/5A CT, 80A Multifunction three-phase meter 4 DIN modules compact version Fully bi-directional four quadrants measurements for all energies and powers Main electrical parameters measured and displayed for a costeffective consumption analysis Version for 1 or 5A CT, for direct connection up to 6A or 80A Possibility to connect by PT Up to 8 MB for data recording (ENH version) Possibility to record all energy counters (ENH version) Up to 24 parameters selectable among real time measurements for MIN/AVG/MAX recording (ENH version) MODBUS RTU/ASCII communication by RS485 port or MODBUS TCP communication by Ethernet port Possibility to manage the instrument in remote mode by WintoolNET software or by Web server interface Network Analyzers» General features is an innovative instrument for measurement and recording of the electrical parameters. It is particularly suitable for consumption analysis and control, with an excellent quality/price ratio. is the ideal instrument to establish the measurement points on the plant. The instrument can communicate through the RS485 serial port by MODBUS RTU/ASCII protocol or through Ethernet port by MODBUS TCP protocol. Furthermore, it is available the WintoolNET software for the instrument remote management. Web server interface is also available in case of instrument with Ethernet port: a very useful function that gives the possibility to manage the instrument by any PC connected on the network.» Benefits provides fully and accurate information on the load in the measurement point and it allows to calculate the costs of the energy consumption. Data sent to PC allows to generate consumption profiles, recorded values trend, alarms/events report and costs calculation as well as critical values identification. Available the remote firmware upgrade of the instrument.» Applications Energy audit. Monitoring system and energy control. Individual machine load monitoring. Power peak control. Switchboards, gensets, motor control centers, etc. Remote metering and cost allocation.» Related Products WintoolNET 1
» Available configurations CURRENT INPUTS For 1/5A CT Direct connection up to 80A BASIC ENH AUXILIARY POWER SUPPLY 85...265 VAC COMMUNICATION PORT RS485 for MODBUS RTU/ASCII communication Ethernet for HTTP, MODBUS TCP communication INSTRUMENT REMOTE MANAGEMENT WintoolNET Web server (only for instrument with Ethernet port) SIGN REPRESENTATION IN MODBUS PROTOCOL Sign bit 2 s complement DIGITAL OUTPUT (only for instrument with RS485 port) For alarm events or pulse emissions DMD VALUE CALCULATION MODE Fixed window Fixed or Sliding window MEMORY 1 MB 8 MB Active and reactive power AVG values RECORDINGS Real time params MIN/AVG/MAX values (up to 24 params programmable) Energy counters Three phase, 4 wires, 3 currents (3.4.3) WIRING MODES Three phase, 3 wires, 2 currents (3.3.2) Single phase (1ph) THD & HARMONICS Voltage and current THD values Voltage and current harmonics up to 15 th APPARENT ENERGY COUNTERS Total counters Separated Inductive&Capacitive counters» Technical drawing 90 45 72 44 64 2
» Measurements & recordings INSTANTANEOUS VALUES BASIC ENH VOLTAGE V L1-N - V L2-N - V L3-N - V L1-L2 - V L2-L3 - V L3-L1 - V [V] MAM CURRENT (+/-) I L1 - I L2 - I L3 - I N - I MAM ACTIVE POWER (+/-) P L1 - P L2 - P L3 - P AVG MAM REACTIVE POWER (+/-) Q L1 - Q L2 - Q L3 - Q AVG MAM APPARENT POWER (+/-) S L1 - S L2 - S L3 - S MAM POWER FACTOR (ind&cap) PF L1 - PF L2 - PF L3 - PF MAM DPF (+/-) DPF L1 - DPF L2 - DPF L3 MAM TANGENT Ø (+/-) TANØ L1 - TANØ L2 - TANØ L3 - TANØ MAM VOLTAGE THD THDV L1 - THDV L2 - THDV L3 - THDV L1-L2 - THDV L2-L3 - THDV L3-L1 [V] MAM CURRENT THD THDA L1 - THDA L2 - THDA L3 - THDA N MAM FREQUENCY f [Hz] MAM PHASE ORDER DEMAND VALUES (DMD) DMD CURRENT (abs) I L1DMD - I L2DMD - I L3DMD - I NDMD - I DMD DMD ACTIVE POWER (imp&exp) P L1DMD - P L2DMD - P L3DMD - P DMD BALANCE OF DMD SYSTEM ACTIVE POWER (+/-) P DMDBAL DMD REACTIVE POWER (imp&exp) Q L1DMD - Q L2DMD - Q L3DMD - Q DMD BALANCE OF DMD SYSTEM REACTIVE POWER (+/-) Q DMDBAL DMD APPARENT POWER (imp&exp) S L1DMD - S L2DMD - S L3DMD - S DMD BALANCE OF DMD SYSTEM APPARENT POWER (+/-) S DMDBAL DMD POWER FACTOR (imp&exp) PF L1DMD - PF L2DMD - PF L3DMD - PF DMD MAX VALUES MAX VOLTAGE V L1-NMAX - V L2-NMAX - V L3-NMAX - V L1-L2MAX - V L2-L3MAX - V L3-L1MAX - V MAX [V] MAX CURRENT (abs) I L1MAX - I L2MAX - I L3MAX - I NMAX - I MAX MAX ACTIVE POWER (imp&exp) P L1MAX - P L2MAX - P L3MAX - P MAX MAX REACTIVE POWER (imp&exp) Q L1MAX - Q L2MAX - Q L3MAX - Q MAX MAX APPARENT POWER (imp&exp) S L1MAX - S L2MAX - S L3MAX - S MAX MAX POWER FACTOR (imp&exp) PF L1MAX - PF L2MAX - PF L3MAX - PF MAX MAX TANGENT Ø (imp&exp) TANØ L1MAX - TANØ L2MAX - TANØ L3MAX - TANØ MAX MAX VOLTAGE THD THDV L1MAX - THDV L2MAX - THDV L3MAX - THDV L1-L2MAX - THDV L2-L3MAX - THDV L3-L1MAX [V] MAX CURRENT THD THDA L1MAX - THDA L2MAX - THDA L3MAX - THDA NMAX MAX DMD CURRENT I L1MAXDMD - I L2MAXDMD - I L3MAXDMD - I MAXDMD MAX DMD ACTIVE POWER (imp&exp) P L1MAXDMD - P L2MAXDMD - P L3MAXDMD - P MAXDMD MAX DMD REACTIVE POWER (imp&exp) Q L1MAXDMD - Q L2MAXDMD - Q L3MAXDMD - Q MAXDMD MAX DMD APPARENT POWER (imp&exp) S L1MAXDMD - S L2MAXDMD - S L3MAXDMD - S MAXDMD MIN VALUES MIN SYSTEM ACTIVE POWER P MIN MIN SYSTEM REACTIVE POWER Q MIN MIN SYSTEM APPARENT POWER S MIN COUNTERS ACTIVE ENERGY (imp&exp) kwh L1 - kwh L2 - kwh L3 - kwh [Wh] EC BALANCE OF SYSTEM ACTIVE ENERGY kwh BAL [Wh] EC REACTIVE ENERGY (imp&exp) (ind&cap) kvarh L1 - kvarh L2 - kvarh L3 - kvarh [varh] EC BALANCE OF SYSTEM REACTIVE ENERGY (ind&cap) kvarh BAL [varh] EC APPARENT ENERGY (imp&exp) (ind&cap on request) kvah L1 - kvah L2 - kvah L3 - kvah [VAh] EC BALANCE OF SYSTEM APPARENT ENERGY (ind&cap on request) kvah BAL [VAh] EC INSTALLATION HOUR COUNTER HRCNTi [h] MEASUREMENT HOUR COUNTER HRCNTm [h] HARMONIC ANALYSIS UP TO 15 th VOLTAGE HARMONICS V L1-N - V L2-N - V L3-N - V L1-L2 - V L2-L3 - V L3-L1 [V] MAM CURRENT HARMONICS I L1 - I L2 - I L3 - I N MAM LEGEND = Standard AVG = Parameters for AVG recording (fixed) MAM = Parameters for MIN/AVG/MAX recording (up to 24 params programmable) EC = Parameters for Energy counter recording (fixed) +/- = Signed value imp&exp = Values splitted in imported and exported abs = Absolute value ind&cap = Values splitted in inductive and capacitive DMDBAL = Difference between the positive and negative demand value: [DMD+] - [DMD-] BAL = Difference between the imported and exported value: [imp] - [exp] Ph 3
» Specifications POWER SUPPLY Voltage range: Maximum consumption: Frequency: VOLTAGE INPUTS Voltage range: Minimum voltage value for FFT calculation: CURRENT INPUTS Maximum value: Starting current (I st ) CT burden: Minimum current value for FFT calculation: 85... 265 VAC, Cat II Instrument with RS485 port: 1.6 VA - 1 W Instrument with Ethernet port: 4.5 VA - 1.6 W 50/60 Hz 3x10/17... 3x285/495 VAC, Cat III 300 V 20/35 VAC (multiplied by PT ratio in case of PT use) with direct connection 1/5A CT model: 6A 80A model: 80A 1/5A CT model: 2 ma 80A model: 20 ma 1/5A CT model: 0.04 VA 1/5A CT model: 100 ma * CT ratio 80A model: 200 ma TYPICAL ACCURACY Voltage: ±0.2% reading in 10% FS...FS range (FS=Full Scale value) Current: ±0.4% reading in 5% FS...FS range Power: ±0.5% reading ±0.1% FS (PF=1) Frequency: ±0.1% reading ±1 digit in 45...65 Hz range Active energy: Class 1 according to IEC/EN 62053-21 Reactive energy: Class 2 according to IEC/EN 62053-23 Display & KEYBOARD Display: Keyboard: COMMUNICATION PORT Type: Protocols: Baud rate: DIGITAL OUTPUT (DO) Type: Maximum values (according to IEC/EN 62053-31): Energy pulse length (only for DO in pulse mode): Maximum output reaction time (only for DO in alarm mode): SIZE & WEIGHT LxHxP, W: Backlighted LCD, 43x29 mm 3 rows, 4 digits + symbols 3 front buttons + 1 protected button RS485 optoisolated or Ethernet MODBUS RTU/ASCII in case of RS485 port HTTP, NTP, DHCP, MODBUS TCP in case of Ethernet port 300... 57600 bps in case of RS485 port 10/100 Mbps in case of Ethernet port Passive optoisolated 27 VDC - 27 ma 50 ±2ms ON time 1 s WIRE DIAMETER FOR TERMINALS Measuring terminals (A & V): 1/5A CT model: 1.5... 6 mm 2 80A model: 1.5... 35 mm 2 Terminals for digital output, AUX input, RS485 port: 0.14... 2.5 mm 2 72x90x65 mm, max 436 g ENVIRONMENTAL CONDITIONS Operating temperature: -25 C... +55 C (3K6) Storage temperature: -25 C... +75 C (2K3) Max humidity (without condensation): 80% Sinusoidal vibration amplitude: 50 Hz ±0.075 mm Protection degree - frontal part: IP51 (granted only in case of installation in a cabinet with at least IP51 protection degree) Protection degree - terminals: IP20 Pollution degree: 2 Installation and use: Internal STANDARD COMPLIANCE (for the parts applicable for the instrument) Directives: 2006/95/EC, 2004/108/EC Safety: EN 61010-1, EN 61010-2-030 EMC: EN 61326-1, EN 55011, EN 61000-4-2, EN61000-4-3, EN61000-4-4, EN61000-4-5, EN61000-4-6, EN61000-4-11, EN61000-6-2 4
15 DIGIT ORDER CODE APR Labelling A = Algodue C = Custom (instrument name on display, label, manual, Web server if present) User instructions M = Multilingual guide M Auxiliary power supply A = 85...265 VAC A Current inputs 6 = For 1/5A CT 8 = 80A direct connection Communication port 5 = RS485 for MODBUS RTU/ASCII communication W = Ethernet for HTTP, MODBUS TCP communication Sign representation in Modbus protocol 1 = Sign bit 2 = 2 s complement X Version B = Basic - reduced parameter set and functions H = ENH - extended parameter set and functions Memory 1 = 1 MB (only with Basic version) 8 = 8 MB (only with ENH version) Voltage and current THD & Harmonics 2 = THD values (only with Basic version) 3 = THD values + Harmonics up to 15 th (only with ENH version) Apparent energy counter S = Separated Inductive&Capacitive counters T = Total counters (Ind+Cap) X AVAILABLE FEATURES RS485 Ethernet DO - Digital output WintoolNET for instrument remote management Web server for instrument remote management 5
LEGEND: AVG=1MB memory, active&reactive power AVG recording MAM+EC=8MB memory, real time params MIN/AVG/MAX recording (up to 24 params programmable), energy counter recording DO=1 digital output DEFAULT CONFIGURATION BASIC 6A RS485 BASIC 80A RS485 BASIC 6A ETHERNET BASIC 80A ETHERNET ENH 6A RS485 ENH 80A RS485 ENH 6A ETHERNET ENH 80A ETHERNET ORDER CODE VERSION CURRENT INPUTS COMMUNICATION (Sign Bit in Modbus) MEMORY BASIC ENH 1/5A 80A RS485 ETH AVG MAM+EC VAh COUNTER Sep. Ind&Cap APRAMA651XB12SX APRAMA851XB12SX APRAMA6W1XB12SX APRAMA8W1XB12SX APRAMA651XH83SX APRAMA851XH83SX APRAMA6W1XH83SX APRAMA8W1XH83SX I/O DO Other order codes on request (MOQ 30 pcs) NOTE: - Subject to change without notice - The code made up of 15 digits including the X Via Passerina, 3/A - 28010 Fontaneto d Agogna (NO) - Italy - Tel.: +39 0322 89307 Fax: +39 0322 89871 sales@algodue.it - www.algodue.com 72PG01_2_201510_5