Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Similar documents
The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

FERRORESONANCE SIMULATION STUDIES USING EMTP

A Study on Ferroresonance Mitigation Techniques for Power Transformer

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

Solving Customer Power Quality Problems Due to Voltage Magnification

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

TECHNICAL BULLETIN 004a Ferroresonance

Effects of Harmonic Distortion I

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Harmonic Distortion Evaluations

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Impact Assessment Generator Form

Long lasting transients in power filter circuits

Tab 2 Voltage Stresses Switching Transients

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

Power Quality Basics. Presented by. Scott Peele PE

Do Capacitor Switching Transients Still Cause Problems?

A SPECIAL CASE OF FERRORESONANCE INVOLVING A SERIES COMPENSATED LINE

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Three-Phase/Six-Phase Conversion Autotransformers

Harmonic control devices

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Power Factor & Harmonics

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

Design and Simulation of Passive Filter

Harmonic filter design for electrified railways

GIS Disconnector Switching Operation VFTO Study

Evaluating the Response of Surge Arresters

Improving the Power Factor Correction in the Presence of Harmonics by Reducing the Effect of Resonance and Harmonics

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

ELECTRICAL POWER TRANSMISSION TRAINER

Performance of Indirectly Controlled STATCOM with IEEE 30-bus System

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Connection Impact Assessment Application Form

Modeling Ferroresonance Phenomena on Voltage Transformer (VT)

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Spectral analysis of voltages and currents during different modes of ferroresonance in switchgear

Embedded Generation Connection Application Form

VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

Transients under energizing multiple power filter circuits

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

of the improved scheme is presented. Index Terms Inrush current, power quality, transformer.

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

Ferroresonance Experience in UK: Simulations and Measurements

Compensation of Reactive Power Case Study

Conventional Paper-II-2013

Ferroresonance on Transformer 13-kV Ungrounded Tertiary at Arab

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW

Harmonic Design Considerations for Wind Farms

Voltage and Current Waveforms Enhancement using Harmonic Filters

(2) New Standard IEEE P (3) Core : (4) Windings :

Volume I Issue VI 2012 September-2012 ISSN

DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS

Energization of a no-load transformer for power restoration purposes: Impact of the sensitivity to parameters.

Power Quality Analysis in Power System with Non Linear Load

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

Transients impact on power filter circuit sizing

2. Current interruption transients

Analysis of a 405 km transmission line with series compensation

Connection Impact Assessment Application

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Assessment of Saturable Reactor Replacement Options

Embedded Generation Connection Application Form

PART 1 OWNER/APPLICANT INFORMATION

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor

Thyristorised Automatic Power Factor

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

22.0 Harmonics in Industrial Power Systems

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:

Overvoltages While Switching Off a HV- Transformer with Arc-Suppression Coil at No-Load

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

In power system, transients have bad impact on its

Power Quality enhancement of a distribution line with DSTATCOM

Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits

Frequency Domain Analysis of Capacitor Transient Overvoltages

Study of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T.

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC)

Transcription:

Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit with a voltage regulator connected under back-feed conditions, where high overvoltages developed causing the failure of distribution class surge arresters. Key parameters of equipment and circuit conditions are described that lead to zero sequence, i.e., 3 rd harmonic, resonance conditions where the only path for the magnetizing current of a voltage regulator to flow is through the capacitance of connected cable circuits, isolated from the rest of the system by delta-wye connected network transformers. The results of the study provide guidance for the identification of potential ferroresonance circuits in distribution systems and potential means of mitigation through the application of grounding transformers, modification to protective relaying strategies, and consideration to circuit connectivity. Keywords: ferroresonance, distribution, back-feed, voltage regulator, network transformers, resonance, grounding transformer, protective relaying F I. INTRODUCTION ERRORESONANCE conditions are described for a feeder circuit where a voltage regulator is left connected to cables under back-feed conditions. System conditions, key equipment parameters, and means of overvoltage mitigation are described to avoid high overvoltages that could cause the failure of distribution class surge arresters. The focus is on zero sequence, i.e., 3 rd harmonic, resonance conditions, where the only path for the magnetizing current of a voltage regulator to flow is through the capacitance of connected cable circuits, isolated from the rest of the system by deltawye connected network transformers. The study provides guidance for the identification of potential ferroresonance circuits in distribution systems, recognition of key equipment parameters, and potential means of mitigation through the application of grounding transformers, modification to protective relaying strategies, and consideration to circuit connectivity. II. SYSTEM TOPOLOGY REPRESENTATION Fig. 1 shows the representation of the distribution system, where the system is of focus. The 23 kv system is represented by its positive and zero short-circuit strength on D. Shoup and J. Paserba are with Mitsubishi Electric Power Products, Inc. (MEPPI), Warrendale, PA 186, USA (E-mail: don.shoup@meppi.com). A. Mannarino is with Public Service Gas and Electric (PSE&G), Newark, NJ 712, USA. Presented at the International Conference on Power Systems Transients (IPST 7) in Lyon, France on June 4-7, 27. the high-side of a 23/13.2 kv Delta-Wye step-down transformer. On the low-side of the transformer three radial feeder circuits are represented in both positive and zero sequence, each consisting of the following: Station breaker of mostly overhead wire circuit with ~4 ft of underground cable 1.2 (3-4 kvar) Mvar capacitor bank Voltage regulator capable of carrying load of 1 MVA (3-333 MVA) Sectionalizer at load-side of regulators 1.2 miles of cable circuit 1 MVA of Delta-Wye connected network transformers Network protectors at low-side of network transformers Two different circuit configurations for the station breaker were examined. One was examined with the breaker on the source-side of the voltage regulator near its terminals as shown in Fig. 1 for the far right feeder circuit. A second configuration, with the station breaker before the 4 miles of overhead wire and underground cable circuit, as shown for the two other feeder circuits, was also examined. Ferroresonance conditions were observed for either configuration under back-feed conditions. The back-feed conditions of interest here were based on an actual system condition where the station breaker was open and a network protector stuck closed at the low-side of a network protector, with the sectionalizers closed. For this system condition, the 1.2 miles of cable circuit and voltage regulator is back-fed through the network transformer adjacent to the stuck network protector. Note that the load at the low-side of the network transformers is not included here since it does not impact the floating back-feed circuit of interest here. The focus of the analysis described here is on the interaction that occurs between the 1.2 miles of cable circuit and voltage regulator, and potential means of mitigation for all potential overvoltage conditions. III. KEY EQUIPMENT REPRESENTATION The following describes the representation of key equipment of Fig. 1 for the Electromagnetic Transients Program (EMTP) for the ferroresonance back-feed analysis. EMTP representation of the following equipment is described: voltage regulator, grounding transformer, surge arresters, cables, overhead wire, and network transformers.

S-C Equivalent +/ Sequence D Y 23 kv 13.2 kv Station Breaker +/ sequence 4 kvar/ph Station Breaker +/ sequence Breaker Open 4 kvar/ph F14SW +/ sequence Location of distribution class surge arrester. Regulator Pit 3-333 kva Voltage Regulator Sectionalizer F14RG F14RL Simulations to mitigate ferroresonance have wye-delta transformer connected line-to-ground. Note that and 1 kva (3-phase) sizes were analyzed. Sectionalizers closed. Total of 1.2 miles of underground cable circuit. 1 ft overhead 1 1 1 7 kva 7 kva Network protectors back-fed by feeder-1 and feeder-2. 1 kva 1 kva All network transformers delta on source-side and wye-g on low-side. A. Voltage Regulator The voltage regulator with a through-put capability of 1 MVA, rated as 1 MVA based on series winding, was represented with the following characteristics: Magnetizing reactance of 3.2 H Saturated reactance of 14 mh An EMTP type 98 nonlinear reactor was used to represent the excitation characteristics of the voltage regulator, shown in Fig. 2a and 2b. [1-] Network protector stuck closed Fig. 1. One-line diagram of back-feed circuit under analysis. Peak Flux (V-s) 4 3 3 2 2 1 1 4 Peak Flux (V-s) 3 3 2 2 1 1 1 1 2 2 3 Peak Current (Amps) Fig. 2a. Voltage regulator saturation characteristics. 1 2 3 4 Peak Current (Amps) Fig. 2b. Zoom of voltage regulator saturation characteristics. B. Grounding Transformer The EMTP classical transformer representation was used to represent the grounding transformer, based on its MVA size, winding voltages, winding connectivity, and leakage impedance. The grounding transformer was specified as a wye-delta connected transformer with 3-phase MVA ratings of kva and 1 kva examined, each based on a leakage impedance of 1%. For the wye-connected winding, the leakage impedance is 338 Ω or.9 H for the kva transformer and 113 Ω or.3 H for the 1 kva transformer. [1, 6-8]

C. Distribution Class Surge Arrester The class distribution class surge arresters were modeled using an EMTP type 92 piece-wise linear representation [1, ]. The arresters were specified with a 1 kv rated duty cycle, 8.4 kv rated maximum continuous operating voltage (MCOV), and energy duty absorption capability of 4.9 kj/kv based on the MCOV, or 4.9 kj/kv x 8.4 kv = 41 kj. Surge arresters were modeled based on manufacturer s minimum characteristics for a slow wave front appropriate for estimating peak energy duty for screening purposes. Simulations where significant energy duty applied was imposed on arresters were flagged. TABLE 1 DISTRIBUTION CLASS SURGE ARRESTER CHARACTERISTICS Voltage Where Arrester Applied: Rated Duty 1 Cycle (kv): Rated MCOV (kv): 8.4 Base for V-I Characteristics (kv) : Energy Duty Absorption (kj/kv of MCOV): Current (A, pk) 26.8 4.9 Voltage For Energy Duty Model (P.U. on 26.8 kv) Total kj: 4.9 x 8.4 = 41 kj Surge Arrester V-I Characteristics for Peak Energy Duty Voltage For Energy Duty Model (kv, pk) 1.96 1.973 1.631 16.911 1.676 18.117.738 19.778 1.769 2.69 2.87 21.628 D. Cables, Overhead Wire, and Network Transformers The 1.2 mile of cable circuit was composed of cables of the following averaged characteristics: Length: 62 ft 3-phase kvar/1 ft: 7.7 kvar Surge impedance: 36 Ω Resistance:. Ω/mi Inductance: 7 µh/mi The total capacitance for the feeder-3 back-fed circuit was.777 µf for the 1.2 mi section, which is the capacitance that interacted with the saturation characteristics of the voltage regulator under analysis here. The overhead sections were composed of the following average characteristics: length of 3 ft sections, resistance of.4 Ω/1 ft, reactance of.1 Ω/1 ft, and charging of.2 kvar/1 ft (3-phase). The network transformers were all delta-connected on the side and wye-grounded connected on the low voltage side, with voltages of 48 V and 216 V, and leakage impedances of % to 7%. The 3-phase MVA rating of the transformers ranged from. MVA to 2. MVA. IV. BACK-FEED ANALYSIS Simulations were performed for the back-feed case shown in Fig. 1 with no grounding transformer or surge arresters modeled. Fig. 3 shows the line-to-ground voltage at the regulator for the back-feed conditions where the magnetizing current of the regulator flows through the cable circuit, as energy is exchanged between the voltage regulator (saturating nonlinear inductance) and cable circuit (capacitance based on Mvar charging. High voltages, primarily composed of the 3 rd harmonic (i.e., 18 Hz), between 3. to 4. P.U. on a system peak line-to-ground voltage base of 1614. V. Voltage (V pu) 6 4 2-2 -4 Pre-Event Voltage = 1.4 P.U. _ ( yp ) Line-to-neutral voltage at source-side of voltage regulator terminals. Back-feed circuit isolated from rest of system at t = 2+ ms. Peak Voltage = 4.17 P.U. Overvoltage caused by magnetizing current of voltage regulator flowing through cable circuit. -6 1 1 2 2 3 Fig. 3. Line-to-ground voltage at regulator under back-feed conditions without mitigation. Fig. 4 shows a zoom-in of the saturated current flowing through the voltage regulator for the back-feed circuit under the conditions described for Fig. 3. Current (A) 1 1 - -1 _ ( yp ) Peak Current = 14 A Saturated current through voltage regulator. -1 2 4 6 8 1 Fig. 4. Saturated current through regulator under back-feed conditions without mitigation. Tables 2 and 3 list the harmonic summary of the voltage shown in Fig. 3. and the current shown in Fig. 4., respectively. Tables 2 and 3 show that the voltage and current are largely dominated by the 3 rd harmonic. [9]

TABLE 2 HARMONIC SUMMARY OF LINE-TO-GROUND VOLTAGE AT REGULATOR Name Freq Fund % THD % RMS RMSh RMS ASUM H3 H H7 H9 H11 H13 H1 F14RGA 6 7322 22 231 1482 16924 99262 13779 8 172 263 19 182 138 F14RGB 6 742 196 22 14777 16989 11231 13744 36 8 22 66 39 296 F14RGC 6 7447 198 227 1471 16898 16411 1373 976 12 66 98 348 213 % THD = Percent Total Harmonic Distortion = RMSh/Fund x 1 % RMS = Percent of Root Mean Square Value = RMS/Fund x1 RMSh = Root Mean Square Value of Harmonic Content RMS = Root Mean Square Value ASUM = Arithmetic Sum of All Harmonics H3-H1 = Magnitude content of each odd harmonic TABLE 3 HARMONIC SUMMARY OF SATURATED CURRENT THROUGH REGULATOR Name Freq Fund % THD % RMS RMSh RMS ASUM H3 H H7 H9 H11 H13 H1 F14RGA 6 1.6 169 26 17.9 21.8 263 12. 4..9.31.19.11.23 F14RGB 6 11.2 164 2 18.3 23. 269 12.4 4.6.1.46.23.27.64 F14RGC 6 1.7 168 24 18. 21.8 222 12.2 3.8.3.23.2.36.4 % THD = Percent Total Harmonic Distortion = RMSh/Fund x 1 % RMS = Percent of Root Mean Square Value = RMS/Fund x1 RMSh = Root Mean Square Value of Harmonic Content RMS = Root Mean Square Value ASUM = Arithmetic Sum of All Harmonics H3-H2 = Magnitude content of each odd harmonic Simulations were repeated with a distribution class surge arrester modeled at the source-side of the voltage regulator terminals. The impact of the voltage shown in Fig. 3 on the surge arrester is quantified in Fig., which shows the total accumulated energy duty for the surge arrester as a function of time. Fig.. indicates that within approximately 1. seconds the accumulated surge arrester energy would exceed its energy duty absorption capability. 6 Accumulated energy duty imposed on surge arrester. Voltage (V pu) 2 1-1 Line-to-neutral voltage at source-side of voltage regulator Pre-Event Voltage = 1.4 P.U. with 1 kva wye-delta grounding transformer in the circuit. Peak Voltage = 1.8 P.U. Back-feed circuit isolated from rest of system at t = 2+ ms. Energy (kj) 4 3 2 Estimated surge arrester energy duty capability of distribution class surge arrester located at sourceside of voltage regulator (no prior event). Energy duty imposed at a rate of 26.7 kj/s. -2 1 1 2 2 3 Fig. 6. Line-to-ground voltage at regulator under back-feed conditions with 1 kva grounding transformer. 1 Saturated current through voltage regulator. 1 Peak Current = 4. A.. 1. 1. 2. Time ( s) Fig.. Accumulated energy duty imposed on distribution class surge arrester. A 1 kva wye-delta grounding transformer was then connected to the source-side terminals of the voltage regulator and the simulations repeated once again. Fig. 6 and Fig. 7 show the voltage across the regulator and saturated current through the regulator, respectively, with the grounding transformer connected. When the surge arrester was inserted back into service, negligible energy duty was imposed on it. With the grounding transformer connected to the circuit, the ferroresonance conditions were no longer present because the magnetizing current no longer had a series path with the cable capacitance in a radial, floating circuit. Current (A) - Back-feed circuit isolated from rest of system at t = 2+ ms. -1 1 1 2 2 3 Fig. 7. Saturated current through regulator under back-feed conditions with 1 kva grounding transformer. V. RECOMMENDATIONS The recommendations for the analysis were as follows: To mitigate potential ferroresonance conditions and excessive energy duty applied to existing surge arresters caused by the back-feed circuit, (1) one

solution is to have the breaker that disconnects the 13 kv system from the source-side of the regulator located between the regulator and the capacitor bank and connect a wye-delta transformer line-to-ground in the regulator/cable back-fed circuit. (2) Another potential solution is to insert a switching device on the load-side of the voltage regulator capable of detecting the back-feed conditions (such as through relaying) and opening within. s. Such a device would limit peak energy duty imposed on existing surge arresters to below their rated absorption capability. o Breaker for solution (1) avoids ferroresonance caused by interaction of voltage regulator and capacitor bank, which is not mitigated by wyedelta grounding transformer. o Wye-delta grounding transformer of solution (1) mitigates ferroresonance caused by interaction of magnetizing characteristics of voltage regulator and connected cable circuit. kva wye-delta transformer limits voltage to 1.2 P.U. and energy duty applied to rate of.38 kj/s. 1 kva wye-delta transformer limits voltage to 1.8 P.U. and energy duty applied to rate of.37 kj/s. Solution (2) does not avoid ferroresonance conditions; rather it limits the duration of the event to where excessive energy duty would not be applied to existing surge arresters. Note that after opening of the switching device for solution (2), a trapped charge on the capacitor drains/oscillates through the saturation characteristics of the regulator, where the magnitude of the overvoltage is not a cause for concern. VI. OVERALL SUMMARY OF FINDINGS For radial distribution feeders fed by a voltage regulator, ferroresonance conditions can develop when the station breaker is open and a network protector at the low-side of a distribution transformer sticks closed. A sustained overvoltage dominated by the 3 rd harmonic, i.e., zero sequence, occurs as the magnetizing current of the voltage regulator flows through the cable capacitance, based on the total Mvar charging of cable circuits. Ferroresonance can also occur when a voltage regulator is left connected to a distribution capacitor bank part of a radial back-fed circuit. To avoid these conditions, a breaker can be placed between the distribution capacitor bank and voltage regulator, avoiding capacitor bank-regulator interaction; and a grounding transformer can be inserted in the regulator-cable back-fed circuit, eliminating the series path of the regulator with the cable capacitance for the regulator s magnetizing current to flow. Alternately, a switching device can be inserted on the load-side of the voltage regulator capable of detecting (such as through relaying) the back-feed conditions and open in sufficient time to limit the peak energy duty imposed on the surge arresters to within their rated energy duty absorption capabilities, for either the capacitor bank-regulator or cableregulator ferroresonance conditions. Based on the outcomes of the analysis, PSE&G is planning to install relay protection to sense the harmonic current that occurs under the back-feed conditions and trip the station-side switching device to eliminate the back-feed circuit. VII. REFERENCES [1] T. A. Short, Electric Power Distribution Handbook, CRC Press LLC, 1 st edition, 23, pp. 24+. [2] J. Vernieri, B. Barbieri, P. Arnera, "Influence of the Representation of the Distribution Transformer Core Configuration on Voltages Developed During Unbalanced Operations," presented at the International Conference on Power Systems Transients (IPST 1), Rio de Janeiro, Brazil, June 24-28, 21. [3] R. Iravani et al., Modeling Guidelines for Low Frequency Transients, IEEE PES Special Publication Modeling and Analysis of System Transients, 99TP133-, 1998, pp.3-1/3-29. [4] P. Ferracci, Ferroresonance, Cahier Technique Schneider nº19, March 1998. [] Bonneville Power Administration, Electromagnetic Transients Program Rule Book, Portland, Oregon, April 1982. [6] S. Santoso, R. C. Dugan, T. E. Grebe, Modeling Ferroresonance Phenomena in an Underground Distribution System, presented at the International Conference on Power Systems Transients (IPST 1), Rio de Janeiro, Brazil, June 24-28, 21. [7] R. C. Dugan, Examples of Ferroresonance in Distribution Systems, IEEE PES 23 General Meeting, Vol. 2, pp. 1212-121, July 13-17, 23. [8] R. A. Walling, Ferroresonance in Low Loss Distribution Transformers, IEEE PES 23 General Meeting, Vol. 2, pp. 122-1222, July 13-17, 23. [9] J. A. M. Neto, N. C. Jesus, L. L. Piesanti, Impact of the Reactive Power Compensation on Harmonic Distortion Level, presented at the International Conference on Power Systems Transients (IPST 1), Rio de Janeiro, Brazil, June 24-28, 21. VIII. BIOGRAPHIES Donald J. Shoup joined the Mitsubishi Electric Power Products Inc., Warrendale, PA in July 2. Prior to joining MEPPI, Mr. Shoup was with Robicon s Research and Development Department in Pittsburgh, PA, where he worked during the summers as an engineering assistant, beginning in 1998. In 2, he earned a MS in Electric Power Engineering from Rensselaer Polytechnic Institute in Troy, NY. Prior to this, he earned his BEE from Gannon University in Erie, PA in 1999. Donald Shoup is a registered professional engineer in the state of Pennsylvania. He is also an active member of IEEE and CIGRE WG A3.19 on short-line faults. John J. Paserba earned his BEE ( 87) from Gannon University, Erie, PA, and his ME ( 88) from Rensselaer Polytechnic Institute, Troy, NY. Mr. Paserba joined Mitsubishi Electric Power Products Inc. in 1998 after working for over 1 years at General Electric. He is currently the Chair of the IEEE Power Systems Dynamic Performance Committee and is a Fellow Member of IEEE. Antonio Mannarino earned his BSEE from New Jersey Institute of Technology in 198 and successfully completed the General Electric Power System Engineering Course in 198. Mr. Mannarino joined Public Service Electric and Gas, Newark, NJ in 1981 and held various engineering positions in the Electrical Engineering Department and currently working in Electric Delivery Asset Reliability Group. He is also a registered professional engineer in the state of New Jersey and an active member of IEEE.