ESO 210 Introduction to Electrical Engineering

Similar documents
Polyphase Systems. Dr Gamal Sowilam

Chapter Objectives: Payam zarbakhsh EElE301 Circuit Theory II Department of Electrical and Electronic Engineering Cyprus International university

ESO 210 Introduction to Electrical Engineering

Chapter 11 Thre r e e e P has a e e C i C rc r u c its t

Chapter 12 Three Phase Circuits. Chapter Objectives:

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

EE 221 CIRCUITS II. Chapter 12 Three-Phase Circuit

Three-Phase Induction Motors. By Sintayehu Challa ECEg332:-Electrical Machine I

Bakiss Hiyana binti Abu Bakar JKE, POLISAS BHAB

Module 9. DC Machines. Version 2 EE IIT, Kharagpur

Bahram Amin. Induction Motors. Analysis and Torque Control. With 41 Figures and 50 diagrams (simulation plots) Springer

3.1.Introduction. Synchronous Machines

CHAPTER 11. Balanced Three-Phase Circuits

Actuators. EECS461, Lecture 5, updated September 16,

Circuit Analysis-II. Circuit Analysis-II Lecture # 2 Wednesday 28 th Mar, 18

Phasor. Phasor Diagram of a Sinusoidal Waveform

ESO 210 Introduction to Electrical Engineering

THE SINUSOIDAL WAVEFORM

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

Study Guide for Chapter 11

EE 221 CIRCUITS II. Chapter 12 Three-Phase Circuit

LECTURE NOTES ON ELECTRICAL MACHINE-II. Subject Code-PCEL4302

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.

DISCUSSION OF FUNDAMENTALS

Code No: R Set No. 1

CHAPTER 3 EQUIVALENT CIRCUIT AND TWO AXIS MODEL OF DOUBLE WINDING INDUCTION MOTOR

Generator Advanced Concepts

Electric Circuits II Three-Phase Circuits. Dr. Firas Obeidat

1. Explain in detail the constructional details and working of DC motor.

CHAPTER 6 THREE-LEVEL INVERTER WITH LC FILTER

AC Machinery. Revised October 6, Fundamentals of AC Machinery 1

Module 1. Introduction. Version 2 EE IIT, Kharagpur

Unit 27 Three-Phase Circuits

Electric Power Systems 2: Generators, Three-phase Power, and Power Electronics

5.0 THREE PHASE SYSTEM

Design and Performance of Brushless Doubly-fed Machine Based on Wound Rotor with Star-polygon Structure

Power systems 2: Transformation

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

CHAPTER-III MODELING AND IMPLEMENTATION OF PMBLDC MOTOR DRIVE

Question Paper Profile

Sample Question Paper

EEE3410 Microcontroller Applications Department of Electrical Engineering Lecture 11 Motor Control

SYNCHRONOUS MACHINES

Code No: R Set No. 1

A Comparative Study of Sinusoidal PWM and Space Vector PWM of a Vector Controlled BLDC Motor

CHAPTER 2 STATE SPACE MODEL OF BLDC MOTOR

Analysis of Indirect Temperature-Rise Tests of Induction Machines Using Time Stepping Finite Element Method

A Practical Guide to Free Energy Devices

Experiment 3. Performance of an induction motor drive under V/f and rotor flux oriented controllers.

6. List two possible arrangements of a Yconnection and give one application

AC Power Instructor Notes

3. What is hysteresis loss? Also mention a method to minimize the loss. (N-11, N-12)

Chapter 33. Alternating Current Circuits

DC Machine Construction. Figure 1 General arrangement of a dc machine

Electrical Circuits and Systems

University of North Carolina-Charlotte Department of Electrical and Computer Engineering ECGR 4143/5195 Electrical Machinery Fall 2009

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

Contents. Core information about Unit

GRAAD 12 NATIONAL SENIOR CERTIFICATE GRADE 12

THE UNIVERSITY OF BRITISH COLUMBIA. Department of Electrical and Computer Engineering. EECE 365: Applied Electronics and Electromechanics

PREDICTIVE CONTROL OF INDUCTION MOTOR DRIVE USING DSPACE

VALLIAMMAI ENGINEERING COLLEGE

CHAPTER 5 SYNCHRONOUS GENERATORS

Reg. No. : BASIC ELECTRICAL TECHNOLOGY (ELE 101)

A COMPARISON STUDY OF THE COMMUTATION METHODS FOR THE THREE-PHASE PERMANENT MAGNET BRUSHLESS DC MOTOR

Module 7. Electrical Machine Drives. Version 2 EE IIT, Kharagpur 1

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1

Conventional Paper-II-2011 Part-1A

PHYS 1444 Section 003 Lecture #19

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage

AC generator theory. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

Thermal Imaging, Power Quality and Harmonics

MILWAUKEE SCHOOL OF ENGINEERING LABORATORY SESSION 4 THREE PHASE TRANSFORMERS

Electrical Theory 2 Lessons for Fall Semester:

Exercise 3. Phase Sequence EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Phase sequence fundamentals

Space Vector PWM and Model Predictive Control for Voltage Source Inverter Control

Look over Chapter 31 sections 1-4, 6, 8, 9, 10, 11 Examples 1-8. Look over Chapter 21 sections Examples PHYS 2212 PHYS 1112

PHYS 1442 Section 004 Lecture #15

Design of A Closed Loop Speed Control For BLDC Motor

INSTITUTE OF AERONAUTICAL ENGINEERING (AUTONOMOUS) Dundigal, Hyderabad

UEE11 Electrotechnology. Training Package

2015 ELECTRICAL SCIENCE

Goals. Introduction. To understand the use of root mean square (rms) voltages and currents.

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY

UNIT 1 CIRCUIT ANALYSIS 1 What is a graph of a network? When all the elements in a network is replaced by lines with circles or dots at both ends.

Goals. Introduction. To understand the use of root mean square (rms) voltages and currents.

VOLTAGE AND CURRENT RELATIONS AND POWER PART1: THREE PHASE VOLTAGE AND CURRENT RELATIONSHIPS

UNIT-III STATOR SIDE CONTROLLED INDUCTION MOTOR DRIVE

PART 2 - ACTUATORS. 6.0 Stepper Motors. 6.1 Principle of Operation

An Induction Motor Control by Space Vector PWM Technique

ELECTROMAGNETIC INDUCTION AND ALTERNATING CURRENT (Assignment)

Dr.Arkan A.Hussein Power Electronics Fourth Class. 3-Phase Voltage Source Inverter With Square Wave Output

Space Vector PWM Voltage Source Inverter Fed to Permanent Magnet Synchronous Motor

EE 340L EXPERIMENT # 3 SYNCHRONOUS GENERATORS

Transformer & Induction M/C

IOCL Electrical Engineering Technical Paper

Chapter 33. Alternating Current Circuits

Electrical Motor Power Measurement & Analysis

Voltage-Versus-Speed Characteristic of a Wind Turbine Generator

El-Hawary, M.E. The Transformer Electrical Energy Systems. Series Ed. Leo Grigsby Boca Raton: CRC Press LLC, 2000

Transcription:

ESO 210 Introduction to Electrical Engineering Lecture-12 Three Phase AC Circuits

Three Phase AC Supply 2

3 In general, three-phase systems are preferred over single-phase systems for the transmission of power for many reasons, including the following: 1. Thinner conductors can be used to transmit the same kva at the same voltage, which reduces the amount of copper required (typically about 25% less) and in turn reduces construction and maintenance costs. 2. The lighter lines are easier to install, and the supporting structures can be less massive and farther apart. 3. Three-phase equipment and motors have preferred running and starting characteristics compared to single-phase systems because of a more even flow of power to the transducer than can be delivered with a single-phase supply. 4. In general, most larger motors are three phase because they are essentially self-starting and do not require a special design or additional starting circuitry.

4 Generation of Three-phase Balanced Voltages: To obtain a balanced three-phase voltage, the windings are to be placed at an electrical angle of 120 0 with each other, such that the voltages in each phase are also at an angle of 120 0 with each other. The waveforms in each of the three windings (R, Y & B), are also shown in Fig. 18.1b. The windings are in the stator, with the poles shown in the rotor, which is rotating at a synchronous speed of N s rpm

5

For clockwise rotation of rotor 6

7 THE THREE-PHASE GENERATOR The three-phase generator of Fig. (a) on the previous slide has three induction coils placed 120 apart on the stator, as shown symbolically by Fig. (b). Since the three coils have an equal number of turns, and each coil rotates with the same angular velocity, the voltage induced across each coil will have the same peak value, shape, and frequency. As the shaft of the generator is turned by some external means, the induced voltages e AN, e BN, and e CN will be generated simultaneously, as shown in Fig. below. Note the 120 phase shift between waveforms and the similarities in appearance of the three sinusoidal functions.

8

The sinusoidal expression for each of the induced voltages: 9

the vector sum of any number of vectors drawn such that the head of one is connected to the tail of the next, and that the head of the last vector is connected to the tail of the first is zero, we can conclude that the phasor sum of the phase voltages in a three-phase system is zero. That is, 10

11 The number of phase voltages that can be produced by a polyphase generator is not limited to three. Any number of phases can be obtained by spacing the windings for each phase at the proper angular position around the stator. Some electrical systems operate more efficiently if more than three phases are used. One such system involves the process of rectification, which is used to convert an alternating output to one having an average, or dc, value. The greater the number of phases, the smoother the dc output of the system.

12 THE Y or Star CONNECTED GENERATOR If the three terminals denoted N in Fig. are connected together, the generator is referred to as a Y-connected three-phase generator As indicated in Fig., the Y is inverted for ease of notation and for clarity. The point at which all the terminals are connected is called the neutral point. If a conductor is not attached from this point (N) to the load, the system is called a Y- connected, three-phase, three-wire generator. If the neutral is connected, the system is a Y- connected, three-phase, four-wire generator. The function of the neutral will be discussed in detail when we consider the load circuit.

THE Y-CONNECTED GENERATOR 13 The three conductors connected from A, B, and C to the load are called lines. For the Y-connected system, it is obvious from Fig. that the line current equals the phase current for each phase; that is

14

the phasor drawn from the end of one phase to another in the counterclockwise direction. Applying Kirchhoff s voltage law around the indicated loop of Fig. we obtain 15

16

The phase angle between any line voltage and the nearest phase voltage at 30 17

Therefore, we can conclude that the sum of the line voltages is also zero; that is, 18

19 PHASE SEQUENCE (Y-CONNECTED GENERATOR) The phase sequence can be determined by the order in which the phasors representing the phase voltages pass through a fixed point on the phasor diagram if the phasors are rotated in a counterclockwise direction. For example, in Following Fig. the phase sequence is ABC (or RYB). However, since the fixed point can be chosen anywhere on the phasor diagram, the sequence can also be written as BCA or CAB. The phase sequence is quite important in the three-phase distribution of power. In a three phase motor, for example, if two phase voltages are interchanged, the sequence will change, and the direction of rotation of the motor will be reversed. Other effects will be described when we consider the loaded three-phase system.

PHASE SEQUENCE (Y-CONNECTED GENERATOR) 20

21 THE Y (Star)-CONNECTED GENERATOR WITH A Y(Star)-CONNECTED LOAD Loads connected to three-phase supplies are of two types: the Y and the. If a Y- connected load is connected to a Y-connected generator, the system is symbolically represented by Y-Y. The physical setup of such a system is shown in following Fig.

22 If the load is balanced, the neutral connection can be removed without affecting the circuit in any manner; that is, if then I N will be zero. Note that in order to have a balanced load, the phase angle must also be the same for each impedance. In practice, if a factory, for example, had only balanced, three-phase loads, the absence of the neutral would have no effect since, ideally, the system would always be balanced. The cost would therefore be less since the number of required conductors would be reduced. However, lighting and most other electrical equipment will use only one of the phase voltages, and even if the loading is designed to be balanced (as it should be), there will never be perfect continuous balancing since lights and other electrical equipment will be turned on and off, upsetting the balanced condition. The neutral is therefore necessary to carry the resulting current away from the load and back to they-connected generator. This will be demonstrated when we consider unbalanced Y- connected systems.

Four wire Y-Y Connected system 23 We shall now examine the four-wire Y-Y-connected system. The current passing through each phase of the generator is the same as its corresponding line current, which in turn for a Y-connected load is equal to the current in the phase of the load to which it is attached: For a balanced or an unbalanced load, since the generator and load have a common neutral point, then In addition, since the magnitude of the current in each phase will be equal for a balanced load and unequal for an unbalanced load.

24 You will recall that for the Y-connected generator, the magnitude of the line voltage is equal to 3 times the phase voltage. This same relationship can be applied to a balanced or an unbalanced four-wire Y-connected load: For a voltage drop across a load element, the first subscript refers to that terminal through which the current enters the load element, and the second subscript refers to the terminal from which the current leaves. In other words, the first subscript is, by definition, positive with respect to the second for a voltage drop.

EXAMPLE: The phase sequence of the Y-connected generator in the following is ABC. a. Find the phase angles θ 2 and θ 3. b. Find the magnitude of the line voltages. c. Find the line currents. d. Verify that, since the load is balanced, I N =0. 25

Solutions: a. For an ABC phase sequence, θ 2 = -120 and θ 3 = 120 26

27

28 THE Y- SYSTEM There is no neutral connection for the Y- as shown in the figure below. Any variation in the impedance of a phase that produces an unbalanced system will simply vary the line and phase currents of the system.

29 For a balanced load, The voltage across each phase of the load is equal to the line voltage of the generator for a balanced or an unbalanced load: The relationship between the line currents and phase currents of a balanced load can be found using an approach very similar to find the relationship between the line voltages and phase voltages of a Y-connected generator. For this case, however, Kirchhoff s current law is employed instead of Kirchhoff s voltage law. The results obtained are and the phase angle between a line current and the nearest phase current is 30. For a balanced load, the line currents will be equal in magnitude, as will the phase currents.

EXAMPLE: For the three-phase system of following Fig. a. Find the phase angles θ 2 and θ 3. b. Find the current in each phase of the load. c. Find the magnitude of the line currents. 30

Solutions: a. For an ABC sequence, θ 2 =-120 0 and θ 3 =+120 0 31

32 THE -CONNECTED GENERATOR If we rearrange the coils of the generator as shown in Fig. below the system is referred to as a three-phase, three-wire, -connected ac generator. Generator coils

33 In this system, the phase and line voltages are equivalent and equal to the voltage induced across each coil of the generator; that is, Note that only one voltage (magnitude) is available instead of the two available in the Y-connected system. Unlike the line current for the Y-connected generator, the line current for the - connected system is not equal to the phase current. The relationship between the two can be found by applying Kirchhoff s current law at one of the nodes and solving for the line current in terms of the phase currents; that is, at node A,

The phasor diagram for a balanced load 34

35

36 with the phase angle between a line current and the nearest phase current at 30. The phasor diagram of the currents is shown as below It can be shown in the same manner employed for the voltages of a Y-connected generator that the phasor sum of the line currents or phase currents for -connected systems with balanced loads is zero.

PHASE SEQUENCE ( -CONNECTED GENERATOR) 37

38 The basic equations necessary to analyze either of the two systems ( -, -Y) have been presented. We will therefore proceed directly to two descriptive examples, one with a -connected load and one with a Y-connected load. EXAMPLE : For the - system shown in Fig.: a. Find the phase angles θ 2 and θ 3 for the specified phase sequence. b. Find the current in each phase of the load. c. Find the magnitude of the line currents.

39 EXAMPLE : For the - system shown in Fig.: a. Find the phase angles θ 2 and θ 3 for the specified phase sequence. b. Find the current in each phase of the load. c. Find the magnitude of the line currents.

40

EXAMPLE: For the -Y system shown in Fig. below: a. Find the voltage across each phase of the load. b. Find the magnitude of the line voltages. 41

42

43

44

45