Micro Motion Model 2700 Transmitters with Configurable Input/Outputs 2700***B 2700***C. Configuration and Use Manual Supplement

Similar documents
Micro Motion Model 1700 Transmitters with Analog Outputs 1700***A. Configuration and Use Manual Supplement. Configuration Operation Maintenance

Micro Motion Filling Mass Transmitters with Modbus

Micro Motion Model 2500 Transmitters with Configurable Input/Outputs

Micro Motion Model 2500 Transmitters with Configurable Input/Outputs

The MFT B-Series Flow Controller.

Micro Motion Model 5700 Transmitters with FOUNDATION Fieldbus

HART Mode. Users Guide. July Fluke Corporation. All rights reserved. All product names are trademarks of their respective companies.

Model RFT9709 Transmitter Instruction Manual

Micro Motion Model 1700 Transmitters with Intrinsically Safe Outputs

Calibration Instruction Manual Emerson 475 Field Communicator. Manual Revision FC.2

Instruction Manual TRICOR TCE HART Communication TCM COHA_S_EN_161220_E002

Micro Motion Model 2700 Transmitters with Intrinsically Safe Outputs

RTT20 I/A Series Temperature Transmitter

Mass and Volume Flow Transmitter

815LT Submersible Smart Level Transmitter

Micro Motion Model 2400S Transmitters with MVD Technology

Technical Bulletin, Communicating with Honeywell TM ST3000/STT3000 Smart Transmitters

Modbus Mapping Assignments for Micro Motion Transmitters

ROC800-Series HART Module

Micro Motion Fork Viscosity Meters

ControlMaster CM10, CM30, CM50 Universal process controllers, 1 /8, 1 /4 and 1 /2 DIN

815PT Smart Pressure Transmitter

NetBiter I/O Extender 4RO 6RTD 8DIO - DAIO User Manual Revision 1.00

Micro Motion LF-Series Low Flow Flowmeter

FLXA402 4-Wire Converter HART Communication. FLEXA, FLXA, SENCOM and FieldMate are registered trademarks of Yokogawa Electric Corporation.

Installation, Operation and Maintenance Manual

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

Micro Motion Fork Density Meters

8510 AC Spindle Drive System

Sarasota CM200 Sarasota HME900 Density Converter Electronics

Series 1000 and 2000 Transmitters with MVD TM Technology

Micro Motion LF-Series Low Flow Sensor and Transmitter

DeltaV SIS Logic Solver

GS1 Parameter Summary Detailed Parameter Listings...4 9

HC900 Hybrid Controller

The wireless alternative to expensive cabling...

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents

The keypad is used to set the flowmeter. The function of the keys are as follows: This key selects the figures to be changed.

Inductive Loop Detector

Installation, Operation and Maintenance Manual

Mass Flow and Density Transmitter with FOUNDATION fieldbus

Mass Flow and Density Transmitter

OVEN INDUSTRIES, INC. Model 5C7-362

Rosemount 333 HART Tri-Loop

905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use

The wireless alternative to expensive cabling...

GE Intelligent Platforms. PAC8000 Modular I/O

The wireless alternative to expensive cabling...

F4 08DA 2 8-Channel Analog Voltage Output

Liquid Level Transmitter Model MC420 Analog Output

F4 04DAS 1 4-Channel Isolated 4 20mA Output

Micro Motion Gas Specific Gravity Meters

HC-220 PID Controller

Micro Motion Model RFT9739 Flow and Density Transmitter

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class

BATCHMATE 1500 Batch Control Computer Technical Bulletin

MI June Instruction. I/A Series Intelligent Pressure Transmitters. Operation, Configuration, and Calibration Using a HART Communicator

USER MANUAL. EPP Intelligent Positioner Control Unit 1/22.

PACSystems* RX3i IC695MDL664-BB

Relay Driver Overview and Applications

Jaguar Motor Controller (Stellaris Brushed DC Motor Control Module with CAN)

ACT-3X Tachometer / Totalizer / Ratemeter User Manual and Reference Guide

Micro Motion Model 1500 Transmitter with the Filling and Dosing Application

SERIES PM172 POWERMETERS COMMUNICATIONS. DNP Communications Protocol REFERENCE GUIDE

F4-08RTD 8-Channel RTD Input

F4-04DA-1 4-Channel Analog Current Output

Table of Contents. HWIO-Gateway User Manual

The wireless alternative to expensive cabling...

USER S MANUAL PULSE INPUTS MODULE WITH PROVER SUPPORT

PumpSmart Commissioning Process

ADAM-4022T Serial Base Dual Loops PID Controller User s Manual

Temperature Monitoring and Fan Control with Platform Manager 2

KMS101W. ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products. Electromagnetic Wafer Flowmeters with S100 display

Micro Motion Series 1000 and 2000 Transmitters

MicroManager. Velocity Mode PID Dancer/Loadcell Control. Instruction Manual MM3000-PID

ATEX Installation Instructions for Micro Motion CMF400 Sensors with Booster Amplifier

AI Analogue Input Module (open < 2.8 ma)

Micro Motion Model RFT9739

F4 16DA 2 16-Channel Analog Voltage Output

Characteristics and functioning

PC10 Intelligent Transmitter Configurator Version 4.0

NWS300 Field Type Smart Meter

Micro Motion Series 1000 and Series 2000 Transmitters with MVD Technology

Model FLSC-C1-LIQ. Microprocessor Based Loop Powered Transmitter

SRC-110 Series Zone Controllers with Modbus RTU

TECHNICAL DATASHEET #TDAX ISOLATED DUAL CHANNEL UNIVERSAL SIGNAL CONVERTER

Micro Motion Specific Gravity Meters (SGM)

T6+ Analog I/O Section. Installation booklet for part numbers: 5/4-80A-115 5/4-90A-115 5/4-80A /4-90A-1224

Milliamp Calibrator. Model 434. General description. Calibrate with laboratory accuracy. All 4 to 20 ma loop functions

Contents. Introduction and description Package contents Device identification PM Options... 80

CX105 Conductivity/Resistivity Transmitter

53U MULTI POWER MONITOR OPERATING MANUAL MODEL 53U CONTENTS. (4 digital displays)

This Errata Sheet contains corrections or changes made after the publication of this manual.

vacon 100 flow ac drives application manual

Micro Motion Series 1000 and 2000 Transmitters

Temperature Monitoring and Fan Control with Platform Manager 2

PROCESS & TEMPERATURE CONTROLLERS

DS1621. Digital Thermometer and Thermostat FEATURES PIN ASSIGNMENT

Absolute Process Instruments

Single Channel Loop Detector

Transcription:

P/N MMI-20015781, Rev. AA September 2009 Micro Motion Model 2700 Transmitters with Configurable Input/Outputs Configuration and Use Manual Supplement 2700***B 2700***C Configuration Operation Maintenance

Micro Motion customer service Location Telephone Number U.S.A. 800-522-MASS (800-522-6277) (toll free) Canada and Latin America +1 303-527-5200 (U.S.A.) Asia Japan 3 5769-6803 All other locations +65 6777-8211 (Singapore) Europe U.K. 0870 240 1978 (toll-free) All other locations +31 (0) 318 495 555 (The Netherlands) Customers outside the U.S.A. can also send an email to flow.support@emerson.com. Copyrights and trademarks 2009 Micro Motion, Inc. All rights reserved. The Micro Motion and Emerson logos are trademarks and service marks of Emerson Electric Co. Micro Motion, ELITE, MVD, ProLink, MVD Direct Connect, and PlantWeb are marks of one of the Emerson Process Management family of companies. All other trademarks are property of their respective owners.

Contents Chapter 1 Configure device options and preferences... 1 1.1 Configure Variables and Precision... 1 Chapter 2 Integrate the meter with the control system... 3 2.1 Configure Channels B and C... 3 2.2 Configure the ma output(s)... 4 2.3 Configure the frequency output...11 2.4 Configure the discrete output(s)...18 2.5 Configure the discrete input...23 2.6 Configure digital communications...25 2.7 Configure events...31 Chapter 3 Set up the Weights & Measures application...35 3.1 Locale-specific commissioning...35 Chapter 4 Appendix A Operate the transmitter...37 4.1 View process data...37 codes and abbreviations...39 A.1 codes for process variables...39 A.2 Codes and abbreviations used in display menus...40 Configuration and Use Manual Supplement i

ii Micro Motion Model 2700 Transmitters with Configurable Input/Outputs

About this supplement This supplement is designed for use with the following manual: Micro Motion Series 1000 and Series 2000 Transmitters: Configuration and Use Manual. It replaces sections of the manual with sections that are new or modified for v6.0 of the Model 2700 transmitter with configurable input/outputs. See the following table for section replacement guidelines. Section replacement guidelines Section in Micro Motion Series 1000 and Series 2000 Transmitters: Configuration and Use Manual 6.3.1 Channels B and C Section 2.1 6.5 Configuring the ma output(s) Section 2.2 6.6 Configuring the frequency output Section 2.3 6.7 Configuring the discrete output Section 2.4 6.8 Configuring the discrete input Section 2.5 7.4.1 Viewing process variables with the display Section 4.1.1 8.11 Configuring events Section 2.7 8.14.6 Configuring the display variables and display precision Replace with the following section from this supplement Section 1.1 8.15 Configuring digital communications Section 2.6 11.2 Locale-specific commissioning Section 3.1 Table H-1 codes used for process variables Section A.1 Table H-2 codes used in off-line menu Section A.2 Communications tools and versions Information in this supplement assumes that you are using one of the following to configure your transmitter: The transmitter display v2.9 375 Field Communicator with the following device description: 2000CMass flo, Dev v6, DD v1 If you are using an earlier version of or the Communicator device description, some features described in this supplement may not be available. Configuration and Use Manual Supplement iii

iv Micro Motion Model 2700 Transmitters with Configurable Input/Outputs

Chapter 1 Configure device options and preferences Topics covered in this chapter Configure Variables and Precision 1.1 Configure Variables and Precision Not available ProLink Configuration Communicator 6,7,3 Detailed Setup Setup Variables 6,7,4 Detailed Setup Setup Precision The display can scroll through up to 15 process variables in any order. You can configure the process variables to be displayed and the order in which they will appear. You can repeat variables, and you can leave slots empty. You can also configure Precision for each process variable. Precision controls the number of digits to the right of the decimal place that are shown on the display when the process variable is selected as a display variable. Precision can be set to any value from 0 to 5. The lower the precision, the larger a process change must be in order to be reflected in the displayed value. Precision does not affect the value of the process variable reported via other methods or used in calculations. Restrictions Note You cannot set Variable 1 to None. Variable 1 must always be set to a process variable. If you have fixed Variable 1 to the primary ma output, you cannot change the setting of Variable 1 using this method. To change the setting of Variable 1, you must change the configuration of ma Output Process Variable for the primary ma output. If you have configured a volume process variable as a display variable, and you subsequently change the setting of Volume Flow Type, the display variable is automatically changed to the equivalent process variable. For example, if Variable 2 was set to Volume Flow Rate, it will be changed to Gas Standard Volume Flow Rate. Configuration and Use Manual Supplement 1

Configure device options and preferences Example: variable configuration variable Variable 1 Variable 2 Variable 3 Variable 4 Variable 5 Variable 6 Variable 7 Variable 8 Variable 9 Variable 10 Variable 11 Variable 12 Variable 13 Variable 14 Variable 15 Process variable assignment Mass flow Mass totalizer Volume flow Volume totalizer Density Temperature External pressure Mass flow None None None None None None None 1.1.1 Configure Variable 1 from the display menu OFF-LINE MAINT OFF-LINE CONFG DSPLY VAR 1 Communicator Not available Not available If desired, you can configure Variable 1 from the display menu by fixing it to the process variable assigned to the primary ma output, which is also the HART Primary Variable. If you do this, Variable 1 will always be the process variable assigned to the primary ma output. This is the only way to configure a display variable from the display menus. If Variable 1 is fixed to the primary ma output, the only way to set Variable 1 to a different process variable is to change the ma output assignment. If you do not fix Variable 1 to the primary ma output, you must use a communications tool such as or the Communicator to change Variable 1. Even if Variable 1 is fixed, you can still set its precision. To set its precision, you must use a communications tool. Note This option applies only to Variable 1. To change any other display variable, you still need a communications tool. 2 Micro Motion Model 2700 Transmitters with Configurable Input/Outputs

Chapter 2 Integrate the meter with the control system Topics covered in this chapter Configure Channels B and C Configure the ma output(s) Configure the frequency output Configure the discrete output(s) Configure the discrete input Configure digital communications Configure events 2.1 Configure Channels B and C OFF-LINE MAINT OFF-LINE CONFG IO CH B SET FO/SET MAO/SET DO OFF-LINE MAINT OFF-LINE CONFG IO CH B SET FO/SET DO POWER OFF-LINE MAINT OFF-LINE CONFG IO CH C SET FO/SET DO/SET DI OFF-LINE MAINT OFF-LINE CONFG IO CH C SET FO/SET DO/SET DI POWER ProLink Configuration Channel Communicator 6,3,1,3 Detailed Setup Config Outputs Channel Setup Channel B Setup 6,3,1,4 Detailed Setup Config Outputs Channel Setup Channel C Setup The I/O terminal pairs on the transmitter are called channels, and are identified as Channel A, Channel B, and Channel C. You can configure Channels B and C to operate in several different ways. The channel configuration must match the wiring. Channel configuration parameters include: Channel Type Power Type Always verify the output configuration after changing channel configuration. When the configuration of a channel is changed, the channel s behavior will be controlled by the configuration that is stored for the selected output type, which may or may not be appropriate for the process. To avoid causing process error: Configure the channels before configuring the outputs. When changing channel configuration, be sure that all control loops affected by this channel are under manual control. Before returning the loop to automatic control, ensure that the output is correctly configured for your process. Configuration and Use Manual Supplement 3

Before configuring a channel to operate as a discrete input, check the status of the remote input device and the actions assigned to the discrete input. If the discrete input is ON, all actions assigned to the discrete input will be performed when the new channel configuration is implemented. If this is not acceptable, change the state of the remote device or wait to configure the channel as a discrete input until an appropriate time. 2.1.1 Options for Channels B and C Table 2-1 Options for Channels B and C Channel Operation Power Channel B ma output 2 (default) Internal only Frequency output (FO) Internal or external (1) Discrete output 1 (DO1) (2) Internal or external (1) Channel C Frequency output (default) (2) (3) Internal or external (1) Discrete output 2 (DO2) Internal or external (1) Discrete input (DI) Internal or external (1) 2.2 Configure the ma output(s) OFF-LINE MAINT OFF-LINE CONFG IO CH A OFF-LINE MAINT OFF-LINE CONFG IO CH B ProLink Configuration Analog Output Communicator 6,3,1,5 Detailed Setup Config Outputs Channel Setup AO Setup The ma output is used to report a process variable. The ma output parameters control how the process variable is reported. Your transmitter may have one or two ma outputs: Channel A is always an ma output (the primary ma output) and Channel B may be configured as an ma output (the secondary ma output). The ma output parameters include: ma Output Process Variable Lower Range Value (LRV) and Upper Range Value (URV) AO Cutoff Added Damping AO Fault Action and AO Fault Value Prerequisites If you plan to configure an ma output to report volume flow, ensure that you have set Volume Flow Type as desired: Liquid or Gas Standard Volume. (1) If set to external power, you must provide power to the output. (2) Because DO1 uses the same circuitry as the frequency output, it is not possible to configure both FO and DO1. If both a frequency output and a discrete output are required, configure Channel B as the FO and Channel C as DO2. (3) When configured for two FOs (dual-pulse mode), FO2 is generated from the same signal as FO1. FO2 is electrically isolated but not independent. 4 Micro Motion Model 2700 Transmitters with Configurable Input/Outputs

If you plan to configure an ma output to report a concentration measurement process variable, ensure that the concentration measurement application is configured so that the desired variable is available. Postrequisites Important Whenever you change an ma output parameter, verify all other ma output parameters before returning the flowmeter to service. In some situations, the transmitter automatically loads a set of stored values, and these values may not be appropriate for your application. 2.2.1 Configure ma Output Process Variable OFF-LINE MAINT OFF-LINE CONFG IO CH A AO 1 SRC OFF-LINE MAINT OFF-LINE CONFG IO CH B AO 2 SRC ProLink Configuration Analog Output Primary Output PV Is ProLink Configuration Analog Output Secondary Output SV Is Communicator 6,3,1,5,3 Detailed Setup Config Outputs Channel Setup AO Setup PV Is 6,3,1,5,8 Detailed Setup Config Outputs Channel Setup AO Setup SV Is ma Output Process Variable controls the variable that is reported over the ma output. Prerequisites If you are using the HART variables, be aware that changing the configuration of ma Output Process Variable will change the configuration of the HART Primary Variable (PV) and/or the HART Secondary Variable (SV). Options for ma Output Process Variable Table 2-2 Options for ma Output Process Variable Process variable code code Communicator code Mass flow rate MFLOW Mass Flow Rate Mass flo Volume flow rate VFLOW Volume Flow Rate Vol flo Gas standard volume GSV F Gas Std Vol Flow Rate Gas vol flo flow rate (4) Temperature TEMP Temp Temp Density DENS Density Dens External pressure (4) EXT P External Pressure External pres External temperature (4) EXT T External Temperature External temp Temperature-corrected TCDEN API: Temp Corrected Density TC Dens density (5) Temperature-corrected (standard) volume flow rate (5) TCVOL API: Temp Corrected Volume Flow TC Vol (4) Requires transmitter software v5.0 or later. (5) Available only if the petroleum measurement application is enabled on your transmitter. Configuration and Use Manual Supplement 5

Table 2-2 Options for ma Output Process Variable continued Process variable code code Communicator code Drive gain DGAIN Drive Gain Driv signl Average corrected AVE D API: Avg Density TC Avg Dens density (5) (6) Average temperature (5) (6) AVE T API: Avg Temperature TC Avg Temp Density at reference RDENS CM: Density @ Reference ED Dens at Ref temperature (7) Specific gravity (7) SGU CM: Density (Fixed SG units) ED Dens (SGU) Standard volume flow STD V CM: Std Vol Flow Rate ED Std Vol flo rate (7) Net mass flow rate (7) NET M CM: Net Mass Flow Rate ED Net Mass flo Net volume flow rate (7) NET V CM: Net Vol Flow Rate ED Net Vol flo Concentration (7) CONC CM: Concentration ED Concentration Baume (7) BAUME CM: Density (Fixed Baume Units) ED Dens (Baume) 2.2.2 Configure Lower Range Value (LRV) and Upper Range Value (URV) OFF-LINE MAINT OFF-LINE CONFG CH A AO 1 4 ma OFF-LINE MAINT OFF-LINE CONFG CH A AO 1 20 ma OFF-LINE MAINT OFF-LINE CONFG IO CH B AO 2 4 MA OFF-LINE MAINT OFF-LINE CONFG IO CH B AO 2 20 MA ProLink Configuration Analog Output Primary Output Lower Range Value ProLink Configuration Analog Output Primary Output Upper Range Value ProLink Configuration Analog Output Secondary Output Lower Range Value ProLink Configuration Analog Output Secondary Output Upper Range Value Communicator 6,3,1,5,4 Detailed Setup Config Outputs Channel Setup AO Setup Range Values 6,3,1,5,9 Detailed Setup Config Outputs Channel Setup AO Setup Range Values The Lower Range Value (LRV) and Upper Range Value (URV) are used to scale the ma output, i.e., to define the relationship between ma Output Process Variable and the ma output level. (6) Requires transmitter software v3.3 or later. Can be assigned only via the display or v1.2 or later. (7) Available only if the concentration measurement application is enabled on your transmitter. 6 Micro Motion Model 2700 Transmitters with Configurable Input/Outputs

The ma output uses a range of 4 20 ma to represent ma Output Process Variable: LRV specifies the value of ma Output Process Variable to be represented by an output of 4 ma. URV specifies the value of ma Output Process Variable to be represented by an output of 20 ma. Between LRV and URV, the ma output is linear with the process variable. If the process variable drops below LRV or rises above URV, the transmitter posts an output saturation alarm. Enter values for LRV and URV in the measurement units that are configured for ma Output Process Variable. Notes You can set URV below LRV. For example, you can set URV to 50 and LRV to 100. For transmitter software v5.0 and later, if you change LRV and URV from factory default values, and you later change ma Output Process Variable, LRV and URV will not be reset to the default values. For example, if you configure ma Output Process Variable as mass flow and change the LRV and URV for mass flow, then you configure ma Output Process Variable as density, and finally you change ma Output Process Variable back to mass flow, LRV and URV for mass flow are reset to the configured values. In earlier versions of the transmitter software, LRV and URV were reset to factory default values. Default values for Lower Range Value (LRV) and Upper Range Value (URV) Each option for ma Output Process Variable has its own LRV and URV. If you change the configuration of ma Output Process Variable, the corresponding LRV and URV are loaded and used. Default LRV and URV settings are listed in Table 2-3. Table 2-3 Default values for Lower Range Value (LRV) and Upper Range Value (URV) Process variable LRV URV All mass flow variables 200.000 g/sec 200.000 g/sec All liquid volume flow variables 0.200 l/sec 0.200 l/sec All density variables 0.000 g/cm 3 10.000 g/cm 3 All temperature variables 240.000 C 450.000 C Drive gain 0.00% 100.00% Gas standard volume flow 423.78 SCFM 423.78 SCFM External temperature 240.000 C 450.000 C External pressure 0.000 bar 100.000 bar Concentration 0% 100% Density Baume 0 10 Specific gravity 0 10 Configuration and Use Manual Supplement 7

2.2.3 Configure AO Cutoff Not available ProLink Configuration Analog Output Primary Output AO Cutoff ProLink Configuration Analog Output Secondary Output AO Cutoff Communicator 6,3,1,5,5 Detailed Setup Config Outputs Channel Setup AO Setup PV AO Cutoff 6,3,1,5,SV AO2 Cutoff Detailed Setup Config Outputs Channel Setup AO Setup SV AO2 Cutoff AO Cutoff (Analog Output Cutoff) specifies the lowest mass flow rate, volume flow rate, or Gas Standard Volume flow rate that will be reported through the ma output. Any flow rates below the AO Cutoff will be reported as 0. Restriction AO Cutoff is applied only if ma Output Process Variable is set to Mass Flow Rate, Volume Flow Rate, or Gas Standard Volume Flow Rate. If ma Output Process Variable is set to a different process variable, AO Cutoff is not configurable, and the transmitter does not implement the AO cutoff function. Tip For most applications, the default value of AO Cutoff should be used. Contact Micro Motion customer service before changing AO Cutoff. Cutoff interaction When ma Output Process Variable is set to a flow variable (mass flow, volume flow, or gas standard volume flow), AO Cutoff interacts with Mass Flow Cutoff, Volume Flow Cutoff, or Gas Standard Volume Flow Cutoff. The transmitter puts the cutoff into effect at the highest flow rate at which a cutoff is applicable. Example: Cutoff interaction Configuration: ma Output Process Variable = Mass Flow Rate Frequency Output Process Variable = Mass Flow Rate AO Cutoff = 10 g/s Mass Flow Cutoff = 15 g/s Result: If the mass flow rate drops below 15 g/s, all outputs representing mass flow will report zero flow. 8 Micro Motion Model 2700 Transmitters with Configurable Input/Outputs

Example: Cutoff interaction Configuration: Result: ma Output Process Variable =Mass Flow Rate Frequency Output Process Variable = Mass Flow Rate AO Cutoff = 15 g/s Mass Flow Cutoff = 10 g/s If the mass flow rate drops below 15 g/s but not below 10 g/s: The ma output will report zero flow. The frequency output will report the actual flow rate. If the mass flow rate drops below 10 g/s, both outputs will report zero flow. 2.2.4 Configure Added Damping Not available ProLink Configuration Analog Output Primary Output AO Added Damp ProLink Configuration Analog Output Secondary Output AO Added Damp Communicator 6,3,1,5,6 Detailed Setup Config Outputs Channel Setup AO Setup PV AO Added Damp 6,3,1,5,SV AO Added Damp Detailed Setup Config Outputs Channel Setup AO Setup SV AO Added Damp Added Damping controls the amount of damping that will be applied to the ma output. It affects the reporting of ma Output Process Variable through the ma output only. It does not affect the reporting of that process variable via any other method (e.g., the frequency output or digital communications), or the value of the process variable used in calculations. Note Added Damping is not applied if the ma output is fixed (for example, during loop testing) or if the ma output is reporting a fault. Added Damping is applied while sensor simulation is active. Options for Added Damping When you set the value for Added Damping, the transmitter automatically rounds the value down to the nearest valid value. Valid values are listed in Table 2-4. Note Added Damping values are affected by the setting of Update Rate and 100 Hz Variable. Configuration and Use Manual Supplement 9

Table 2-4 Valid values for Added Damping Update Rate setting Process variable Update rate in effect Valid values for Added Damping Normal All 20 Hz 0.0, 0.1, 0.3, 0.75, 1.6, 3.3, 6.5, 13.5, 27.5, 55.0, 110, 220, 440 Special 100 Hz variable (if assigned to the ma output) 100 Hz variable (if not assigned to the ma output) 100 Hz 0.0, 0.04, 0.12, 0.30, 0.64, 1.32, 2.6, 5.4, 11.0, 22.0, 44, 88, 176, 350 6.25 Hz 0.0, 0.32, 0.96, 2.40, 5.12, 10.56, 20.8, 43.2, 88.0, 176.0, 352 All other process variables 6.25 Hz 0.0, 0.32, 0.96, 2.40, 5.12, 10.56, 20.8, 43.2, 88.0, 176.0, 352 Interaction of damping parameters When ma Output Process Variable is set to a flow variable, density, or temperature, Added Damping interacts with Flow Damping, Density Damping, or Temperature Damping. If multiple damping parameters are applicable, the effect of damping the process variable is calculated first, and the added damping calculation is applied to the result of that calculation. Example: Damping interaction Configuration: Flow Damping = 1 sec ma Output Process Variable = Mass Flow Rate Added Damping = 2 sec Result: A change in the mass flow rate will be reflected in the ma output over a time period that is greater than 3 seconds. The exact time period is calculated by the transmitter according to internal algorithms which are not configurable. 2.2.5 Configure ma Output Fault Action and ma Output Fault Level Not available ProLink Configuration Analog Output Primary Output AO Fault Action ProLink Configuration Analog Output Primary Output AO Fault Level ProLink Configuration Analog Output Secondary Output AO Fault Action ProLink Configuration Analog Output Secondary Output AO Fault Level Communicator 6,3,1,5,7 Detailed Setup Config Outputs Channel Setup AO Setup AO1 Fault Setup 6,3,1,5,AO2 Fault Setup Detailed Setup Config Outputs Channel Setup AO Setup AO2 Fault Setup ma Output Fault Action controls the behavior of the ma output if the transmitter encounters an internal fault condition. Note If Last Measured Value Timeout is set to a non-zero value, the transmitter will not implement the fault action until the timeout has elapsed. 10 Micro Motion Model 2700 Transmitters with Configurable Input/Outputs

Options for ma Output Fault Action and ma Output Fault Level Table 2-5 Options for ma Output Fault Action and ma Output Fault Level code Communicator code ma Output Fault Level ma output behavior Upscale (8) Upscale (8) Default: 22 ma Range: 21 24 ma Downscale (default) (8) Downscale (default) (8) Default: 2.0 ma Range: 1.0 3.6 ma Goes to the configured fault level Goes to the configured fault level Internal Zero Intrnl Zero Not applicable Goes to the ma output level associated with a process variable value of 0 (zero), as determined by Lower Range Value and Upper Range Value settings None None Not applicable Tracks data for the assigned process variable; no fault action If you set ma Output Fault Action or Frequency Output Fault Action to None, be sure to set Digital Communications Fault Action to None. If you do not, the output will not report actual process data, and this may result in measurement error or unintended consequences for your process. If you set Digital Communications Fault Action to NAN, you cannot set ma Output Fault Action or Frequency Output Fault Action to None. If you try to do this, the transmitter will not accept the configuration. 2.3 Configure the frequency output OFF-LINE MAINT OFF-LINE CONFG IO CH B SET FO OFF-LINE MAINT OFF-LINE CONFG IO CH C SET FO ProLink Configuration Frequency Communicator 6,3,1,6 Detailed Setup Config Outputs Channel Setup FO Setup The frequency output is used to report a process variable. The frequency output parameters control how the process variable is reported. Your transmitter may have zero, one, or two frequency outputs, depending on the configuration of Channels B and C. If both Channels B and C are configured as frequency outputs, they are electrically isolated but not independent. You cannot configure them separately. (8) If you select Upscale or Downscale, you must also configure Fault Level. Configuration and Use Manual Supplement 11

The frequency output parameters include: Frequency Output Process Variable Frequency Output Scaling Method Frequency Output Maximum Pulse Width Frequency Output Polarity Frequency Output Mode Frequency Output Fault Action and Frequency Output Fault Value Postrequisites Important Whenever you change a frequency output parameter, verify all other frequency output parameters before returning the flowmeter to service. In some situations, the transmitter automatically loads a set of stored values, and these values may not be appropriate for your application. 2.3.1 Configure Frequency Output Process Variable OFF-LINE MAINT OFF-LINE CONFG IO CH B SET FO FO SRC OFF-LINE MAINT OFF-LINE CONFG IO CH C SET FO FO SRC ProLink Configuration Frequency Tertiary Variable Communicator 6,3,1,6,3 Detailed Setup Config Outputs Channel Setup FO Setup TV Is Frequency Output Process Variable controls the variable that is reported over the frequency output. Prerequisites If you are using the HART variables, be aware that changing the configuration of Frequency Output Process Variable will change the configuration of the HART Tertiary Variable (TV). Options for Frequency Output Process Variable Table 2-6 Options for Frequency Output Process Variable Process variable code code Communicator code Mass flow rate MFLOW Mass Flow Rate Mass flo Volume flow rate VFLOW Volume Flow Rate Vol flo Gas standard volume flow rate (9) GSV F Gas Std Vol Flow Rate Gas vol flo Temperature-corrected (standard) volume flow rate (10) TCVOL API: Temp Corrected Volume Flow TC Vol Standard volume flow rate (11) STD V CM: Std Vol Flow Rate ED Std Vol flo Net mass flow rate (11) NET M CM: Net Mass Flow Rate ED Net Mass flo Net volume flow rate (11) NET V CM: Net Vol Flow Rate ED Net Vol flo (9) Requires transmitter software v5.0 or later. (10) Available only if the petroleum measurement application is enabled on your transmitter. (11) Available only if the concentration measurement application is enabled on your transmitter. 12 Micro Motion Model 2700 Transmitters with Configurable Input/Outputs

2.3.2 Configure Frequency Output Scaling Method OFF-LINE MAINT OFF-LINE CONFG IO CH B SET FO FO SCALE OFF-LINE MAINT OFF-LINE CONFG IO CH C SET FO FO SCALE ProLink Configuration Frequency Scaling Method Communicator 6,3,1,6,4 Detailed Setup Config Outputs Channel Setup FO Setup FO Scale Method Frequency Output Scaling Method defines the relationship between output pulse and flow units. Set Frequency Output Scaling Method as required by your frequency receiving device. Procedure 1. Set the channel to operate as a frequency output, if you have not already done so. 2. Set Frequency Output Scaling Method. Frequency=Flow Pulses/Unit Units/Pulse Frequency calculated from flowrate A user-specified number of pulses represents one flow unit A pulse represents a user-specified number of flow units 3. Set additional required parameters. If you set Frequency Output Scaling Method to Frequency=Flow, set Rate Factor and Frequency Factor. If you set Frequency Output Scaling Method to Pulses/Unit, define the number of pulses that will represent one flow unit. If you set Frequency Output Scaling Method to Units/Pulse, define the number of units that each pulse will indicate. Frequency=Flow The Frequency=Flow option is used to customize the frequency output for your application when you do not know appropriate values for Units/Pulse or Pulses/Unit. If you select Frequency=Flow, you must provide values for Rate Factor and Frequency Factor: Rate Factor Frequency Factor The maximum flow rate that you want the frequency output to report. Above this rate, the transmitter will report A110: Frequency Output Saturated. A value calculated as follows: where: T N Factor to convert selected time base to seconds Number of pulses per flow unit, as configured in the receiving device Configuration and Use Manual Supplement 13

The resulting Frequency Factor must be within the range of the frequency output (0 to 10,000 Hz): Tip If Frequency Factor is less than 1 Hz, reconfigure the receiving device for a higher pulses/unit setting. If Frequency Factor is greater than 10,000 Hz, reconfigure the receiving device for a lower pulses/unit setting. If Frequency Output Scale Method is set to Frequency=Flow, and Frequency Output Maximum Pulse Width is set to a non-zero value, Micro Motion recommends setting Frequency Factor to a value less than 200 Hz. Example: Configure Frequency=Flow You want the frequency output to report all flow rates up to 2000 kg/min. The frequency receiving device is configured for 10 pulses/kg. Solution: Set parameters as follows: Rate Factor: 2000 Frequency Factor: 333.33 2.3.3 Configure Frequency Output Maximum Pulse Width Not available ProLink Configuration Frequency Freq Pulse Width Communicator 6,3,1,6,6/7 Detailed Setup Config Outputs Channel Setup FO Setup Max Pulse Width Frequency Output Maximum Pulse Width is used to ensure that the duration of the ON signal is great enough for your frequency receiving device to detect. Restriction If the transmitter is configured for two frequency outputs, Frequency Output Maximum Pulse Width is not implemented. The outputs always operate with a 50% duty cycle. The ON signal may be the high voltage or 0.0 V, depending on Frequency Output Polarity, as shown in Table 2-7. 14 Micro Motion Model 2700 Transmitters with Configurable Input/Outputs

Table 2-7 Polarity Active High Interaction of Frequency Output Maximum Pulse Width and Frequency Output Polarity Pulse width Active Low Tips For typical applications, the default value (0) is appropriate for Frequency Output Maximum Pulse Width. The default value produces a frequency signal with a 50% duty cycle. High-frequency counters such as frequency-to-voltage converters, frequency-to-current converters, and Micro Motion peripherals usually require a duty cycle of approximately 50%. Electromechanical counters and PLCs that have low-scan cycle rates generally use an input with a fixed non-zero state duration and a varying zero state duration. Most low-frequency counters have a specified requirement for Frequency Output Maximum Pulse Width. Frequency Output Maximum Pulse Width You can set Frequency Output Maximum Pulse Width to 0, or to values between 0.5 milliseconds and 277.5 milliseconds. The user-entered value is adjusted automatically to the nearest valid value. Figure 2-1 If you set Frequency Output Maximum Pulse Width is set to 0 (the default), the output will have a 50% duty cycle, independent of the output frequency. See Figure 2-1. 50% Duty cycle If you set Frequency Output Maximum Pulse Width to a non-zero value, the duty cycle is controlled by the crossover frequency. The crossover frequency is calculated as follows: Configuration and Use Manual Supplement 15

At frequencies below the crossover frequency, the duty cycle is determined by the pulse width and the frequency. At frequencies above the crossover frequency, the output changes to a 50% duty cycle. Example: Frequency Output Maximum Pulse Width with specific PLC requirements The frequency receiving device is a PLC with a specified pulse width requirement of 50 milliseconds. The crossover frequency is 10 Hz. Solution: Set Frequency Output Maximum Pulse Width to 50 milliseconds. Result: For frequencies lower than 10 Hz, the frequency output will have a 50 millisecond ON state, and the OFF state will be adjusted as required. For frequencies higher than 10 Hz, the frequency output will be a square wave with a 50% duty cycle. 2.3.4 Configure Frequency Output Polarity OFF-LINE MAINT OFF-LINE CONFG IO CH B SET FO FO POLAR OFF-LINE MAINT OFF-LINE CONFG IO CH C SET FO FO POLAR ProLink Configuration Frequency Freq Output Polarity Communicator 6,3,1,6,7/8 Detailed Setup Config Outputs Channel Setup FO Setup Polarity Frequency Output Polarity controls how the output indicates the ON (active) state. The default value, Active High, is appropriate for most applications. Active Low may be required by applications that use low-frequency signals. Options for Frequency Output Polarity Table 2-8 Options for Frequency Output Polarity Polarity Reference voltage (OFF) Pulse voltage (ON) Active High 0 As determined by power supply, pull-up resistor, and load (see the installation manual for your transmitter) Active Low As determined by power supply, pull-up resistor, and load (see the installation manual for your transmitter) 0 2.3.5 Configure Frequency Output Mode OFF-LINE MAINT OFF-LINE CONFG IO CH B SET FO MODE OFF-LINE MAINT OFF-LINE CONFG IO CH C SET FO MODE ProLink Configuration Frequency Freq Output Mode Communicator 6,3,1,6,8/9 Detailed Setup Config Outputs Channel Setup FO Setup Mode 16 Micro Motion Model 2700 Transmitters with Configurable Input/Outputs

Frequency Output Mode defines the relationship between the two frequency outputs (dual-pulse mode). Prerequisites Before configuring Frequency Output Mode, ensure that both Channel B and Channel C are configured to operate as frequency outputs. If you do not have two frequency outputs on your transmitter, Frequency Output Mode is set to Single and cannot be changed. Options for Frequency Output Mode Table 2-9 Options for Frequency Output Mode Option Channel behavior Process condition In-Phase 50% duty cycle 90 Phase Shift 50% duty cycle 90 Phase Shift 50% duty cycle 180 Phase Shift 50% duty cycle Quadrature (12) 50% duty cycle Channel B Channel C Channel B Channel C Channel B Channel C Channel B Channel C Channel B Channel C Channel B Channel C Channel B Channel C Forward flow Channel C lags Channel B by 90 Reverse flow Channel C leads Channel B by 90 Fault condition Channel C is driven to 0 2.3.6 Configure Frequency Output Fault Action and Frequency Output Fault Level Communicator Not available ProLink Configuration Frequency Freq Fault Action ProLink Configuration Frequency Freq Fault Level 6,3,1,6,FO Fault Indicator Detailed Setup Config Outputs Channel Setup FO Setup FO Fault Indicator 6,3,1,6,FO Fault Value Detailed Setup Config Outputs Channel Setup FO Setup FO Fault Value Frequency Output Fault Action controls the behavior of the frequency output if the transmitter encounters an internal fault condition. (12) Quadrature mode is used only for specific Weights & Measures applications where required by law. Configuration and Use Manual Supplement 17

Note If Last Measured Value Timeout is set to a non-zero value, the transmitter will not implement the fault action until the timeout has elapsed. Options for Frequency Output Fault Action Table 2-10 Options for Frequency Output Fault Action code Frequency output behavior Communicator code All modes except Quadrature (13) Quadrature mode Upscale (14) Upscale (14) Configured Upscale value: Range: 10 15000 Hz Default: 15000 Hz Channel B: Configured Upscale value: Range: 10 15000 Hz Default: 15000 Hz Channel C: 0 Hz Downscale Downscale 0 Hz Channel B: Configured Upscale value: Range: 10 15000 Hz Default: 15000 Hz Channel C: 0 Hz Internal Zero Intrnl Zero 0 Hz Channel B: Configured Upscale value: Range: 10 15000 Hz Default: 15000 Hz Channel C: 0 Hz None (default) None (default) Tracks data for the assigned process variable Channel B: Tracks data for the assigned process variable Channel C: Tracks data for the assigned process variable If you set ma Output Fault Action or Frequency Output Fault Action to None, be sure to set Digital Communications Fault Action to None. If you do not, the output will not report actual process data, and this may result in measurement error or unintended consequences for your process. If you set Digital Communications Fault Action to NAN, you cannot set ma Output Fault Action or Frequency Output Fault Action to None. If you try to do this, the transmitter will not accept the configuration. 2.4 Configure the discrete output(s) OFF-LINE MAINT OFF-LINE CONFG IO CH B SET DO OFF-LINE MAINT OFF-LINE CONFG IO CH C SET DO ProLink Configuration Discrete Output Communicator 6,3,1,7 Detailed Setup Config Outputs Channel Setup DI/DO Setup (13) Applies to both Channel B and Channel C. (14) If you select Upscale, you must also configure the Upscale value. 18 Micro Motion Model 2700 Transmitters with Configurable Input/Outputs

The discrete output is used to report specific flowmeter or process conditions. The discrete output parameters control which condition is reported and how it is reported. Your transmitter may have zero, one, or two discrete outputs, depending on the configuration of Channels B and C. If both Channels B and C are configured as discrete outputs, they operate independently and you can configure them separately. The discrete output parameters include: Discrete Output Source Discrete Output Polarity Discrete Output Fault Action Restriction Before you can configure the discrete output, you must configure a channel to operate as a discrete output. Postrequisites Important Whenever you change a discrete output parameter, verify all other discrete output parameters before returning the flowmeter to service. In some situations, the transmitter automatically loads a set of stored values, and these values may not be appropriate for your application. 2.4.1 Configure Discrete Output Source OFF-LINE MAINT OFF-LINE CONFG IO CH B SET DO DO 1 SRC OFF-LINE MAINT OFF-LINE CONFG IO CH C SET DO DO 2 SRC ProLink Configuration Discrete Output Discrete Output 1 DO1 Assignment ProLink Configuration Discrete Output Discrete Output 2 DO2 Assignment Communicator 6,3,1,7,4 Detailed Setup Config Outputs Channel Setup DI/DO Setup DO 1 Is 6,3,1,7,7 Detailed Setup Config Outputs Channel Setup DI/DO Setup DO 2 Is Discrete Output Source controls which flowmeter condition or process condition is reported via the discrete output. Options for Discrete Output Source Table 2-11 Options for Discrete Output Source Option code code Communicator code Condition Discrete output voltage (15) Discrete Event D EV x Discrete Event x Discrete Event x 1 5 (16) ON OFF Site-specific 0 V (15) Assumes that Discrete Output Polarity is set to Active High. If Discrete Output Polarity is set to Active Low, reverse the voltage values. (16) Events configured using the enhanced event model. Configuration and Use Manual Supplement 19

Table 2-11 Options for Discrete Output Source continued Option code code Communicator code Condition Discrete output voltage (15) Event 1 2 (17) EVNT1 EVNT2 E1OR2 Event 1 Event 2 Event 1 or Event 2 Event 1 Event 2 Event 1 or Event 2 ON OFF Site-specific 0 V Flow Switch (18) (19) FL SW Flow Switch Indication Flow Switch ON OFF Site-specific 0 V Flow Direction FLDIR Forward/Reverse Indication Forward/Reverse Forward flow Reverse flow 0 V Site-specific Calibration in Progress ZERO Calibration in Progress Calibration in Progress ON OFF Site-specific 0 V Fault FAULT Fault Condition Indication Fault ON OFF Site-specific 0 V Meter Verification Fault Not available Meter Verification Fault Not available ON OFF Site-specific 0 V Note If your transmitter has two discrete outputs: You can configure them independently. For example, you can assign one to Flow Switch and one to Fault. If you assign both to Flow Switch, the same settings for Flow Switch Variable, Flow Switch Setpoint, and Flow Switch Hysteresis will be implemented for both discrete outputs. Configure Flow Switch parameters Communicator OFF-LINE MAINT OFF-LINE CONFG IO CH B SET DO CONFIG FL SW OFF-LINE MAINT OFF-LINE CONFG IO CH B SET DO CONFIG FL SW ProLink Configuration Flow Flow Switch Setpoint ProLink Configuration Flow Flow Switch Variable ProLink Configuration Flow Flow Switch Hysteresis 6,3,1,7,Flow Switch Setpoint Detailed Setup Config Outputs Channel Setup DI/DO Setup Flow Switch Setpoint 6,3,1,7,Flow Switch Variable Detailed Setup Config Outputs Channel Setup DI/DO Setup Flow Switch Variable 6,3,1,7,Hysteresis Detailed Setup Config Outputs Channel Setup DI/DO Setup Hysteresis Flow Switch is used to indicate that the flow rate (measured by the configured flow variable) has dropped below the configured setpoint. The flow switch is implemented with a user-configurable hysteresis. (17) Events configured using the basic event model. (18) If you set Discrete Output Source to Flow Switch, you must also configure Flow Switch Variable, Flow Switch Setpoint, and Hysteresis. (19) If your transmitter is configured with two discrete outputs, you can set both of them to Flow Switch Variable. However, they will share the settings for Flow Switch Variable, Flow Switch Setpoint, and Hysteresis. 20 Micro Motion Model 2700 Transmitters with Configurable Input/Outputs

Procedure 1. Set Discrete Output Source to Flow Switch, if you have not already done so. 2. Set Flow Switch Variable to the flow variable that will be used to control the flow switch. 3. Set Flow Switch Setpoint to the flow rate below which you want the flow switch to turn on. 4. Set Hysteresis to the percentage of variation above and below the setpoint that will operate as a deadband. Hysteresis defines a range around the setpoint within which the flow switch will not change. The default value is 5%. The range is 0.1% to 10%. For example, if Flow Switch Setpoint = 100 g/sec and Hysteresis = 5%, and the flow rate drops below 95 g/sec, the discrete output will turn ON. It will stay ON until the flow rate rises above 105 g/sec. At this point it turns OFF and will remain OFF until the flow rate drops below 95 g/sec. 2.4.2 Configure Discrete Output Polarity OFF-LINE MAINT OFF-LINE CONFG IO CH B SET DO DO 1 POLAR OFF-LINE MAINT OFF-LINE CONFG IO CH C SET DO DO 2 POLAR ProLink Configuration Discrete Output Discrete Output 1 DO Polarity ProLink Configuration Discrete Output Discrete Output 2 DO Polarity Communicator 6,3,1,7,5 Detailed Setup Config Outputs Channel Setup DI/DO Setup DO 1 Polarity 6,3,1,7,8 Detailed Setup Config Outputs Channel Setup DI/DO Setup DO 2 Polarity Discrete outputs have two states: ON (active) and OFF (inactive). Two different voltage levels are used to represent these states. Discrete Output Polarity controls which voltage level represents which state. Options for Discrete Output Polarity Table 2-12 Polarity Active High Options for Discrete Output Polarity Discrete output power supply Internal External Description When asserted (condition tied to DO is true), the circuit provides a pull-up to 15 V. When not asserted (condition tied to DO is false), the circuit provides 0 V. When asserted (condition tied to DO is true), the circuit provides a pull-up to a site-specific voltage, maximum 30 V. When not asserted (condition tied to DO is false), the circuit provides 0 V. Configuration and Use Manual Supplement 21

Table 2-12 Options for Discrete Output Polarity continued Polarity Active Low Discrete output power supply Internal External Description When asserted (condition tied to DO is true), the circuit provides 0 V. When not asserted (condition tied to DO is false), the circuit provides a pull-up to 15 V. When asserted (condition tied to DO is true), the circuit provides 0 V. When not asserted (condition tied to DO is false), the circuit provides a pull-up to a site-specific voltage, to a maximum of 30 V. Figure 2-2 Typical discrete output circuit (internal power) A B C D 15 V (Nom) 3.2 KΩ Out+ Out 2.4.3 Configure Discrete Output Fault Action Not available ProLink Configuration Discrete Output Discrete Output 1 DO1 Fault Action ProLink Configuration Discrete Output Discrete Output 2 DO2 Fault Action Communicator 6,3,1,7,6 Detailed Setup Config Outputs Channel Setup DI/DO Setup DO 1 Fault Indication 6,3,1,7,9 Detailed Setup Config Outputs Channel Setup DI/DO Setup DO 2 Fault Indication 22 Micro Motion Model 2700 Transmitters with Configurable Input/Outputs

Discrete Output Fault Action controls the behavior of the discrete output if the transmitter encounters an internal fault condition. Note If Last Measured Value Timeout is set to a non-zero value, the transmitter will not implement the fault action until the timeout has elapsed. Do not use Discrete Output Fault Action as a fault indicator. Because the discrete output is always ON or OFF, you may not be able to distinguish its fault action from its normal operating state. To use the discrete output as a fault indicator, see Section 2.4.4. Options for Discrete Output Fault Action Table 2-13 Options for Discrete Output Fault Action code Upscale Downscale Communicator code Upscale Downscale Fault state Polarity=Active High Discrete output voltage Fault Site-specific voltage 0 V No fault Polarity=Active Low Discrete output is controlled by Discrete Output Source Fault 0 V Site-specific voltage No fault Discrete output is controlled by Discrete Output Source None (default) None (default) Not applicable Discrete output is controlled by Discrete Output Source 2.4.4 Fault indication with the discrete output To indicate faults via the discrete output, set parameters as follows: Discrete Output Source = Fault Discrete Output Fault Action = None Note If Discrete Output Source is set to Fault and a fault occurs, the discrete output is always ON. The setting of Discrete Output Fault Action is ignored. 2.5 Configure the discrete input OFF-LINE MAINT OFF-LINE CONFG IO CH C SET DI ProLink Configuration Discrete Input Communicator 6,3,1,7 Detailed Setup Config Outputs Channel Setup DI/DO Setup The discrete input is used to initiate one or more transmitter actions from a remote input device. Your transmitter may have zero or one discrete input, depending on the configuration of Channel C. Configuration and Use Manual Supplement 23

The discrete input parameters include: Discrete Input Action Discrete Input Polarity 2.5.1 Configure Discrete Input Action OFF-LINE MAINT OFF-LINE CONFG IO CH C SET DI DI ACT ProLink Configuration Discrete Input Action Communicator 6,8,1 Detailed Setup Discrete Actions Assign Discretes Discrete Input Action controls the action or actions that the transmitter will perform when the discrete input transitions from OFF to ON. Before assigning actions to an enhanced event or discrete input, check the status of the event or the remote input device. If it is ON, all assigned actions will be performed when the new configuration is implemented. If this is not acceptable, wait until an appropriate time to assign actions to the event or discrete input. Options for Discrete Input Action Table 2-14 Options for Discrete Input Action or Enhanced Event Action Action code code Communicator code None (default) NONE None None Start sensor zero START ZERO Start Sensor Zero Start Sensor Zero Start/stop all totalizers START STOP Start/Stop All Totalization Start/Stop Totals Reset mass total RESET MASS Reset Mass Total Reset Mass Total Reset volume total RESET VOL Reset Volume Total Reset Volume Total Reset gas standard volume total RESET GSVT Reset Gas Std Volume Total Reset Gas Standard Volume Total Reset all totals RESET ALL Reset All Totals Reset All Totals Reset temperature-corrected volume total TCVOL Reset API Ref Vol Total Reset Corrected Volume Total Reset reference volume total RESET STD V Reset CM Ref Vol Total Not available Reset net mass total RESET NET M Reset CM Net Mass Total Not available Reset net volume total RESET NET V Reset CM Net Vol Total Not available Increment curve INCr CURVE Increment Current CM Curve Not available Start meter verification test START VERFY Start Meter Verification Not available Before assigning actions to an enhanced event or discrete input, check the status of the event or the remote input device. If it is ON, all assigned actions will be performed when the new configuration is implemented. If this is not acceptable, wait until an appropriate time to assign actions to the event or discrete input. 24 Micro Motion Model 2700 Transmitters with Configurable Input/Outputs

2.5.2 Configure Discrete Input Polarity OFF-LINE MAINT OFF-LINE CONFG IO CH C SET DI DI POLAR ProLink Configuration Discrete Input Polarity Communicator 6,3,1,7,3 Detailed Setup Config Outputs Channel Setup DI/DO Setup DI 1 Polarity The discrete input has two states: ON and OFF. Discrete Input Polarity controls how the transmitter maps the incoming voltage level to the ON and OFF states. Options for Discrete Input Polarity Table 2-15 Options for Discrete Input Polarity Polarity Discrete input power supply Description State of discrete input Active High Internal Voltage across terminals is high ON Voltage across terminals is 0 VDC OFF External Voltage applied across terminals is 3 30 VDC ON Voltage applied across terminals is <0.8 VDC OFF Active Low Internal Voltage across terminals is 0 VDC ON Voltage across terminals is high OFF External Voltage applied across terminals is <0.8 VDC ON Voltage applied across terminals is 3 30 VDC OFF 2.6 Configure digital communications OFF-LINE MAINT OFF-LINE CONFG COMM ProLink Configuration Device Communicator 6,3,2 Detailed Setup Config Outputs HART Output The digital communications parameters control how the transmitter will communicate using digital communications. The Model 2700 transmitter with configurable input/outputs supports the following types of digital communications: HART/Bell 202 over the primary ma terminals Modbus/RS-485 via the service port Digital Communications Fault Action applies to all types of digital communications. Configuration and Use Manual Supplement 25

Note The service port responds automatically to a wide range of connection requests. It is not configurable. 2.6.1 Configure HART/Bell 202 communications OFF-LINE MAINT OFF-LINE CONFG COMM ProLink Configuration Device Digital Comm Settings Communicator 6,3,2 Detailed Setup Config Outputs HART Output HART/Bell 202 communications parameters support HART communication with the transmitter's primary ma terminals over a HART/Bell 202 network. The HART/Bell 202 communications parameters include: HART Address (Polling Address) Loop Current Mode () or ma Output Action (Communicator) Burst Parameters (optional) HART Variables (optional) Procedure 1. Set Protocol to HART/Bell 202. Parity, Stop Bits, and Baud Rate are set automatically. 2. Set HART Address to a value between 0 and 15. HART Address must be unique on the network. The default address (0) is typically used unless you are in a multidrop environment. Tip Devices using HART protocol to communicate with the transmitter may use either HART Address or HART Tag (Software Tag) to identify the transmitter. You may configure either or both, as required by your other HART devices. 3. Check the setting of Loop Current Mode (ma Output Action) and change it if required. Enabled Disabled The primary ma output reports process data as configured. The primary ma output is fixed at 4 ma and does not report process data. Tip Whenever you use to set HART Address to 0, also enables Loop Current Mode. Whenever you use to set HART Address to any other value, also disables Loop Current Mode. This is designed to make it easier to configure the transmitter for legacy behavior. Be sure to verify Loop Current Mode after setting HART Address. 4. (Optional) Enable and configure Burst Parameters. 26 Micro Motion Model 2700 Transmitters with Configurable Input/Outputs