Data sheet CPU 314ST/DPM (314-6CF02)

Similar documents
Data sheet CPU 313SC (313-5BF13)

Data sheet VIPA CPU 314SC DPM (314-6CG23)

Data sheet CPU 013C (013-CCF0R00)

2A (recommended) Power loss

General information. Supply voltage

Product type designation. General information. Supply voltage

6ES7314-6BH04-0AB0. STEP7 as of V5.5 + SP1 or STEP 7 V5.3 + SP2 or higher with HSP 204

Product type designation. General information. Hardware product version 01. Firmware version V2.6. Engineering with. update.

CPU 314C-2 PTP. Function

Order number 031-1BB BB BB BD30 Figure. SM 031, AI 2x12Bit I. Note - - Coming soon - Features. 2 inputs, Current 0(4)...

CPU 221, CPU 222, CPU 224, CPU 224 XP, CPU 224 XPsi, CPU 226

6ES7214-1AG31-0XB0. General information Engineering with. Supply voltage 24 V DC Yes permissible range, upper limit (DC)

100 h; (min. 70 h at 40 C); 200 days (typ.) with optional battery module Memory Number of memory modules (optional)

SIMATIC S7-1200, CPU 1212C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 8 DI 24V DC; 6 DO 24 V DC; 2 AI 0-10V DC, POWER SUPPLY: DC

Programming restrictions when operating SM 331; AI 8 x RTD with PROFIBUS masters which only support DPV0.

FM 355 CONTROLLER MODULE

6ES BE30-0XB0 6ES AE30-0XB0 6ES HE30-0XB0

FM COUNTER MODULE

General specifications and features

SIMATIC S7-300 Function modules

FM COUNTER MODULE

FM HIGH-SPEED BOOLEAN PROCESSOR

6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0)

XIOC technology and networking modules

Product type designation. General information. CiR - Configuration in RUN. Supply voltage. Input current

General information. CiR - Configuration in RUN

8V General information. 2 Order data 8V

General information. CiR - Configuration in RUN

SM 1223 DIGITAL INPUT/OUTPUT MODULE

FM POSITIONING MODULE

SIPLUS SM 1234 ANALOG INPUT/OUTPUT MODULE

This data sheet is only valid in association with the IL SYS INST UM E user manual.

EXM INPUT/OUTPUT EXPANSION

FM COUNTER MODULE

CPU. BM40, BM40PB, BM40IE Industrial amplifier. Special features. Data sheet. Block diagram

PLC-K506 Series FEATURES DESCRIPTION FEATURES

Product Information. Release 3 4 SIMATIC ET 200S. 4DI UC V High Feature Digital Electronic Module

Zentralbaugruppen CPU 222

8V General information. 2 Order data 8V

KNC-PLC-K506 Series FEATURES DESCRIPTION FEATURES

Highlights Very compact EtherCAT I/O system in IP 20 for plug-in into a circuit board (signal distribution board)

Q.raxx A slimline RS / EC Universal Measurement System

SM 1222 DIGITAL OUTPUT MODULE

Q.raxx A101-8 slimline RS / EC

EP-5111, EP-5112, EP-5212, EP-5261, EP-5311, EP-5422, EP-5442

Q.raxx A slimline RS / EC

Digital electronic module 4DO DC24V/2A HF (6ES7132-4BD30-0AB0) SIMATIC

Analog Inputs and Outputs

Q.raxx A slimline RS / EC Multi Channel System for Thermocouples

Industrial Modbus I/O Modules

MULTIFUNCTION GRAPHICAL UNIT MGU 800

NEW! Transient Data Acquisition. Stand alone. Compact. Powerful.

DEA 115, Digital Input/Output Modules

AIO and DIO PFXLM4B01DAK:Sink Output Type PFXLM401DAC:Source Output Type Virtual Resolution (pixels)

Data Acquisition Modules/ Distributed IO Modules

USB-TEMP and TC Series USB-Based Temperature Measurement Devices

NetBiter I/O Extender 4RO 6RTD 8DIO - DAIO User Manual Revision 1.00

CAN-IO Custom IO remote module

USB4. Encoder Data Acquisition USB Device Page 1 of 8. Description. Features

PFXLM4B01 D * * (1) (2) (3) (4)

PHOENIX CONTACT

Temperature Input Module for Zone 1 Series 9482/32

Advanced Ladder Logic Full IEC Languages 25A for <1 24 VDC DC Switched

VersaMax Mixed Discrete / High-Speed Counter Module

imc C-SERIES: CS-1016-N, CL-1032-N

Arbitrary power supplies. 160 W to 5200 W

CompactLogix 5370 L3 Control System

Isolation (ISO), Special Overvoltage functions protection (OP) Voltage measurement PAD-V8-P 8 Voltage, up to ±50 V BW: 6 Hz ISO: 350 V DC

UniStream Built-in. Technical Specifications US7-B5-RA28, US7-B10-RA28 US7-B5-TA30, US7-B10-TA30

MX440A. Data Sheet. Universal amplifier. Special features. Block diagram Digital platform. B en

Positioning drives DC motor, brushless Absolute multiturn position detection, Profibus-DP

PQM4000RGW Class A DIN 192x144 power quality analyzer with Rogowski coils

The DO8332 module is equipped with eight outputs for 1-wire connections. The rated output current is 2 A.

Let`s get SIRIUS! SIRIUS Overview. SIRIUS from Dewesoft. SIRIUS Overview. The new hardware generation makes your measurement more precise!

UniStream Uni-I/O Modules

SIMATIC S5. ET 100U Distributed I/Os. Manual. EWA 4NEB a

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

VersaMax Mixed Discrete / High-Speed Counter Module

imc C-SERIES: CS-3008-N, CL-3016-N

Let`s get SIRIUS! SIRIUS Overview. SIRIUS from Dewesoft. SIRIUS Overview. The new hardware generation makes your measurement more precise!

PHOENIX CONTACT - 09/2009

imc C-SERIES: CS-5008-FD

UniStream 5" Technical Specifications US5-B5-RA28, US5-B10-RA28

Instruction manual. art Installation manual

USB Multifunction Arbitrary Waveform Generator AWG2300. User Guide

Intelligent Drive Systems, Worldwide Services SK 700E F 3070 GB

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

The AT4222 module is equipped with four inputs for PT100/PT1000 resistance temperature measurement.

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide

MGCplus. Measuring amplifier system. Special features. Data sheet

MX840B R. Data sheet. Ultra-rugged universal amplifier CAN. Special features. Block diagram. B en

SHF Communication Technologies AG,

High Stability Voltage Source

DS1621. Digital Thermometer and Thermostat FEATURES PIN ASSIGNMENT

S7-200 SMART Programmable controller Answers for industry.

Ethernet-Based Temperature, Voltage and Strain Measurement Modules

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

GFT1504 4/8/10 channel Delay Generator

Outputs U8 I1. Protection class IP64 (IP67) WB25

Transcription:

Data sheet CPU 314ST/DPM (314-6CF02) Technical data Order no. Type 314-6CF02 CPU 314ST/DPM General information Note - Features SPEED-Bus SPEED7 technology, SPEED-Bus 8 x DI, 8 x DIO, 4 x AI, 2 x AO, 1 x AI Pt100 512 kb work memory Memory extension (max. 2 MB) PROFIBUS-DP master / PtP (switchable) Technical data power supply Power supply (rated value) Power supply (permitted range) DC 20.4...28.8 V Reverse polarity protection Current consumption (no-load operation) 300 ma Current consumption (rated value) 1 A Inrush current 5 A I²t 0.5 A²s Max. current drain at backplane bus 2.5 A Max. current drain load supply - Power loss 14 W Technical data digital inputs Number of inputs 8 Cable length, shielded Cable length, unshielded Rated load voltage Reverse polarity protection of rated load voltage Current consumption from load voltage L+ (without load) Rated value Input voltage for signal "0" Input voltage for signal "1" Input voltage hysteresis - Frequency range - Input resistance - Input current for signal "1" Connection of Two-Wire-BEROs possible Max. permissible BERO quiescent current Input delay of "0" to "1" Input delay of "1" to "0" Number of simultaneously utilizable inputs horizontal configuration Number of simultaneously utilizable inputs vertical configuration 8 1000 m 600 m 70 ma DC 0...5 V DC 15...28.8 V 6 ma 1.5 ma parameterizable 2.56µs - 40ms parameterizable 2.56µs - 40ms 8 Input characteristic curve IEC 61131-2, type 1 Page 1/9

Initial data size 34 Byte Technical data digital outputs Number of outputs 8 Cable length, shielded 1000 m Cable length, unshielded 600 m Rated load voltage Reverse polarity protection of rated load voltage - Current consumption from load voltage L+ (without load) 30 ma Total current per group, horizontal configuration, 40 C 4 A Total current per group, horizontal configuration, 60 C 3 A Total current per group, vertical configuration 3 A Output voltage signal "1" at min. current L+ (-0.8 V) Output voltage signal "1" at max. current L+ (-0.8 V) Output current at signal "1", rated value 0.5 A Output current, permitted range to 40 C 5 ma to 0.6 A Output current, permitted range to 60 C 5 ma to 0.6 A Output current at signal "0" max. (residual current) 100 µa Output delay of "0" to "1" 100 µs Output delay of "1" to "0" 100 µs Minimum load current - Lamp load 5 W Parallel switching of outputs for redundant control of a load possible Parallel switching of outputs for increased power not possible Actuation of digital input Switching frequency with resistive load max. 2.5 khz Switching frequency with inductive load max. 0.5 Hz Switching frequency on lamp load max. 2.5 khz Internal limitation of inductive shut-off voltage L+ (-52 V) Short-circuit protection of output, electronic Trigger level 1 A Number of operating cycle of relay outputs - Switching capacity of contacts - Output data size 18 Byte Technical data analog inputs Number of inputs 5 Cable length, shielded Rated load voltage Reverse polarity protection of rated load voltage Current consumption from load voltage L+ (without load) Voltage inputs Min. input resistance (voltage range) Input voltage ranges 200 m 85 ma 120 kohm -10 V... +10 V 0 V... +10 V Operational limit of voltage ranges +/-0.3% Operational limit of voltage ranges with SFU - Basic error limit voltage ranges +/-0.3% Basic error limit voltage ranges with SFU - Destruction limit voltage Page 2/9

Current inputs Max. input resistance (current range) Input current ranges 85 Ohm Operational limit of current ranges +/-0.3% Operational limit of current ranges with SFU - Basic error limit current ranges +/-0.2% Radical error limit current ranges with SFU - Destruction limit current inputs (electrical current) Destruction limit current inputs (voltage) Resistance inputs Resistance ranges -20 ma... +20 ma 0 ma... +20 ma +4 ma... +20 ma max. 50mA 0... 600 Ohm Operational limit of resistor ranges +/-0.4% Operational limit of resistor ranges with SFU - Basic error limit +/-0.2% Basic error limit with SFU - Destruction limit resistance inputs Resistance thermometer inputs Resistance thermometer ranges Pt100 Pt1000 Ni100 Ni1000 Operational limit of resistance thermometer ranges +/-0.6% Operational limit of resistance thermometer ranges with SFU - Basic error limit thermoresistor ranges +/-0.4% Basic error limit thermoresistor ranges with SFU - Destruction limit resistance thermometer inputs Thermocouple inputs - Thermocouple ranges - Operational limit of thermocouple ranges - Operational limit of thermocouple ranges with SFU - Basic error limit thermoelement ranges - Basic error limit thermoelement ranges with SFU - Destruction limit thermocouple inputs - Programmable temperature compensation - External temperature compensation - Internal temperature compensation - Technical unit of temperature measurement C Resolution in bit 12 Measurement principle Basic conversion time Noise suppression for frequency Initial data size Sigma-Delta 6 ms 80 db 10 Byte Technical data analog outputs Number of outputs 2 Cable length, shielded 200 m Rated load voltage Reverse polarity protection of rated load voltage Current consumption from load voltage L+ (without load) - Page 3/9

Voltage output short-circuit protection - Voltage outputs Min. load resistance (voltage range) 1 kohm Max. capacitive load (current range) 1 µf Max. inductive load (current range) Output voltage ranges 30 ma -10 V... +10 V 0 V... +10 V Operational limit of voltage ranges +/-0.4% Basic error limit voltage ranges with SFU +/-0.3% Destruction limit against external applied voltage Current outputs Max. in load resistance (current range) Max. inductive load (current range) Typ. open circuit voltage current output Output current ranges 500 Ohm 10 mh 16 V Operational limit of current ranges +/-0.4% Radical error limit current ranges with SFU +/-0.3% Destruction limit against external applied voltage Settling time for ohmic load Settling time for capacitive load Settling time for inductive load Resolution in bit 12 Conversion time Substitute value can be applied Output data size -20 ma... +20 ma 0 ma... +20 ma +4 ma... +20 ma 0.2 ms 0.5 ms 0.75 ms 1 ms 4 Byte Technical data counters Number of counters 4 Counter width 32 Bit Maximum input frequency 100 khz Maximum count frequency 100 khz Mode incremental encoder Mode pulse / direction Mode pulse Mode frequency counter - Mode period measurement - Gate input available Latch input available Reset input available Counter output available Load and working memory Load memory, integrated Load memory, maximum Work memory, integrated Work memory, maximal Memory divided in 50% program / 50% data Memory card slot 2 MB 2 MB 512 KB 2 MB MMC-Card with max. 1 GB Page 4/9

Hardware configuration Racks, max. 4 Modules per rack, max. 8 in multiple-, 32 in a single-rack configuration Number of integrated DP master 1 Number of DP master via CP 4 Operable function modules 8 Operable communication modules PtP 8 Operable communication modules LAN 8 Status information, alarms, diagnostics Status display Interrupts Process alarm Diagnostic interrupt Diagnostic functions Diagnostics information read-out Supply voltage display Group error display Channel error display, parameterizable, parameterizable possible green LED red SF LED red LED per group Isolation Between channels Between channels of groups to 8 Between channels and backplane bus Between channels and power supply - Max. potential difference between circuits DC 75 V/ AC 50 V Max. potential difference between inputs (Ucm) - Max. potential difference between Mana and Mintern (Uiso) - Max. potential difference between inputs and Mana (Ucm) - Max. potential difference between inputs and Mintern (Uiso) - Max. potential difference between Mintern and outputs - Insulation tested with DC 500 V Command processing times Bit instructions, min. 0.01 µs Word instruction, min. 0.01 µs Double integer arithmetic, min. 0.01 µs Floating-point arithmetic, min. 0.06 µs Timers/Counters and their retentive characteristics Number of S7 counters 512 S7 counter remanence 0.. 512 S7 counter remanence adjustable C0.. C7 Number of S7 times 512 S7 times remanence 0.. 512 S7 times remanence adjustable not retentive Data range and retentive characteristic Number of flags 8192 Byte Page 5/9

Bit memories retentive characteristic adjustable 0.. 8192 Bit memories retentive characteristic preset MB0.. MB15 Number of data blocks 4095 Max. data blocks size 64 KB Max. local data size per execution level 510 Byte Blocks Number of OBs 24 Number of FBs 2048 Number of FCs 2048 Maximum nesting depth per priority class 8 Maximum nesting depth additional within an error OB 4 Time Real-time clock buffered Clock buffered period (min.) 6 w Accuracy (max. deviation per day) 10 s Number of operating hours counter 8 Clock synchronization Synchronization via MPI Master/Slave Synchronization via Ethernet (NTP) no Address areas (I/O) Input I/O address area 8192 Byte Output I/O address area 8192 Byte Input process image maximal 2048 Byte Output process image maximal 2048 Byte Digital inputs 65536 Digital outputs 65536 Digital inputs central 1032 Digital outputs central 1032 Integrated digital inputs 8 Integrated digital outputs 8 Analog inputs 1024 Analog outputs 1024 Analog inputs, central 261 Analog outputs, central 258 Integrated analog inputs 5 Integrated analog outputs 2 Communication functions Global data communication Number of GD circuits, max. 4 Size of GD packets, max. 22 Byte S7 basic communication S7 basic communication, user data per job 76 Byte S7 communication S7 communication as server S7 communication as client - Page 6/9

S7 communication, user data per job Number of connections, max. 32 160 Byte PWM data PWM channels - PWM time basis - Period length - Minimum pulse width - Type of output - Functionality Sub-D interfaces Type X2 Type of interface RS485 Connector Sub-D, 9-pin, female Electrically isolated MPI MP²I (MPI/RS232) - DP master - DP slave - Point-to-point interface - 5V DC Power supply max. 90mA, isolated 24V DC Power supply max. 100mA, non-isolated Type X3 Type of interface RS485 Connector Sub-D, 9-pin, female Electrically isolated MPI - MP²I (MPI/RS232) - DP master DP slave Point-to-point interface 5V DC Power supply max. 90mA, isolated 24V DC Power supply max. 100mA, non-isolated Functionality MPI Number of connections, max. 32 Routing Global data communication S7 basic communication S7 communication S7 communication as server S7 communication as client - Transmission speed, min. 19.2 kbit/s Transmission speed, max. 12 Mbit/s Functionality PROFIBUS master Page 7/9

Routing S7 basic communication S7 communication S7 communication as server S7 communication as client - Activation/deactivation of DP slaves Direct data exchange (slave-to-slave communication) - DPV1 Transmission speed, min. 9.6 kbit/s Transmission speed, max. 12 Mbit/s Number of DP slaves, max. 124 Address range inputs, max. 1 KB Address range outputs, max. 1 KB User data inputs per slave, max. 244 Byte User data outputs per slave, max. 244 Byte Functionality PROFIBUS slave Routing S7 communication S7 communication as server S7 communication as client - Direct data exchange (slave-to-slave communication) - DPV1 Transmission speed, min. 9.6 kbit/s Transmission speed, max. 12 Mbit/s Automatic detection of transmission speed - Transfer memory inputs, max. 244 Byte Transfer memory outputs, max. 244 Byte Address areas, max. 32 User data per address area, max. 32 Byte Point-to-point communication PtP communication Interface isolated RS232 interface - RS422 interface - RS485 interface Connector Sub-D, 9-pin, female Transmission speed, min. 150 bit/s Transmission speed, max. 115.5 kbit/s Cable length, max. 500 m Point-to-point protocol ASCII protocol STX/ETX protocol 3964(R) protocol RK512 protocol - USS master protocol Modbus master protocol Page 8/9

Modbus slave protocol - Special protocols - Functionality RJ45 interfaces Type X5 Type of interface Ethernet 10/100 MBit Connector RJ45 Electrically isolated Number of connections, max. 4 Productive connections - Housing Material PPE Mounting Rail System 300 Mechanical data Dimensions (WxHxD) 80 mm x 125 mm x 120 mm Net weight 480 g Weight including accessories - Gross weight - Environmental conditions Operating temperature 0 C to 60 C Storage temperature -25 C to 70 C Certifications UL certification KC certification - Page 9/9