Relay. Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay

Similar documents
Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay

Technical Datasheet. True RMS Digital Protection Relay. Voltage Protection Relay

Digital Multifunction Instrument - Rish Master 3440

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features:

RS Pro ENGLISH. Datasheet

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

Technical Data Sheet. x1000. kwh R Y B

RISH Master Digital Multifunction Instrument with onsite pluggable output options. Application : Product Features:

Jewell DPM Power / Power Factor Size 96/96 BEST IN CLASS

Data Sheet. RISH Master Record %THD

Technical Data Sheet

RS Pro ENGLISH. Datasheet

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)

Application: Product Features: On site programmable PT/CT ratios: User selectable CT Secondary 5A/1A. User selectable PT Secondary

Data Sheet. Earth Leakage Relay RISH ELR/ELR+/ELR VI/ELR VI(NE) A V RISH ELR VI. Record. Digital Protection Relay RESET TEST ENTER

Jewell DPM EINE BEST IN CLASS

RISH ELR Earth Leakage Relay Preliminary Datasheet True RMS Measurement Trip relay cum DPM CBCT Open Detection 4 digit 7 segment LED display

Technical Data Sheet AMIK 300 / 301

AMIK 200 / 201 Technical Data Sheet

RISH Master 3430 DIGITAL MULTI-FUNCTION TRANSDUCER. Electro-Meters

AMIK Three Phase Digital Panel Meters

ALPHA 20 MULTIFUNCTION METER (ALPHA SERIES)

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics

RISH Delta Energy / Demand (Multifunction instrument) Data Sheet

Theta 20A / 20V. Technical Data Sheet. Special Features

Alpha 50. Technical Data Sheet. Special Features

Programmable DPM RISH EINE

OPERATING MANUAL Rish Eine. Size: 48 x 96 Size: 96 x 96

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

Application: Salient Features: Products Features:

Theta Hz. Technical Data Sheet. Special Features

n True RMS measurement n Fully onsite programmable input voltage range (for CIP-V)

Analog Digital Multimeter with Insulation Resistance Measurement

RISH MIT 30 Analog Digital Multimeter with Insulation Resistance Measurement

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID

1 INTRODUCTION ORDER CODE / INFORMATION

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

VEO. V2PF480Y/277VS01 Art.Nr.: B TECHNICAL DATA

V2IM10AL10 Art.Nr.: V2IM10AL10P Art.Nr.: Control element. Tripping delay. Function selector. Status indication 24...

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

V2UM230V10 Art.Nr.: V2UM230V10P Art.Nr.: Control elements. Tripping delay. Function selector. Status indication 230 V AC/DC

Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16

SPECIFICATION FOR OVERCURRENT RELAYS

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Energy Management. Type WM14 DIN Advanced version. Product Description 3-phase advanced power analyzer with integrated programming

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

OPERATING MANUAL PROGRAMMABLE DPM. Size: 48 x 96 Size: 96 x 96

Electronic measuring and monitoring relays CM-range

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

RISH Master 3440i/3440iDL 0.2S

Technical Datasheet. Delta Power 1000A / 400A AC-DC

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

Measuring Transducer MT4xx series Programmable AC Current Transducer MT418

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

MID. Energy Management Energy Analyzer Type EM11 DIN. Product Description. How to order EM11 DIN AV8 1 X O1 PF. Type Selection EM11 DIN

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)

Thermistor motor protection relays

TD 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

Energy Management. Type WM14-DIN Basic Version. How to order WM14-DIN AV5 3 D PGX. Type Selection. Input specifications. CptBSoft

Voltage Relays. Ensuring Reliable Protection for Electrical Systems against Voltage Faults. ISO 9001:2008 Certified.

T 1000 PLUS Secondary Injection Relay Test Set

Integra 1560 and 1580 Digital Transducer Systems

PQube 3 Specifications

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

Energy Management. Type WM14-96 Basic Version. Product Description. How to order WM14-96 AV5 3 D PGX. Type Selection. Input specifications.

GAMMA 20 DIGITAL MULTIMETER

EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1. Three phase multifunction din rail energy meter

ASHIDA Numerical OC/EF Protection Relay

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring

INTELLIGENT DIGITAL MULTI POWER METER [DIC-MPM]

27/04/2015

ENGLISH 3 Phase Multi-function Power Meter 1/5A MID MID

PRELIMINARY DATA SHEET. RI-F400 Series. easywire Single and Three Phase Multifunction Energy Meter

N. TEST TEST DESCRIPTION

APPENDIX APPENDIX A 1

Centrale de mesure Power Meter PM500 Merlin Gerin

N. TEST TEST DESCRIPTION

Zelio Control Measurement Relays

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

PRELIMINARY DATA SHEET. RI-F300 Series. easywire Single and Three Phase Multifunction Energy Meter (MID Certified) MID

D I G I T A L V O L T A G E R E G U L A T O R

XUA1 - AC Voltage and phase balance relay

Power Regenerative Converter, THYFREC CV240S

Instantaneous Overcurrent Relay

POWER \ PHASE ANGLE \ POWER FACTOR TRANSDUCER RISH

Fluke 1740 Series. Three-Phase Power Quality Loggers Memobox. Assess power quality and conduct long-term studies with ease

PD300. Transformer, generator and motor protection Data sheet

Programmable AC Current Transducer MT418

ZITARES CCD 2 nd Generation SELV constant current control gear, 1-channel, dimm- and adjustable

Energy Management Energy Meter GM3D

Control module CP-A CM

Model Range code System Power supply Option. variables. Housing for panel mounting, (front) protection degree IP50 and optional RS485 serial output.

PROGRAMMABLE DIGITAL TIMER ELIRO (33 Functions): V7DFTS3

1587/1577. Insulation Multimeters. Technical Data. Two powerful tools in one.

Ziegler EM 1320/30/40

Transcription:

Line Monitoring Technical Datasheet RISH RELAY-1 RELAY-2 RISHABH k V Hz True RMS Digital Protection RISH V/Hz is used to protect against Over Voltage, Under Voltage, Phase Unbalance, Phase Sequence detection, Phase Failure detection, Under and Over Frequency conditions. RESET TEST ENTER True RMS Measurement Trip relay cum DPM with Class 0.5 4 digit 7 segment LED display 7 different parameters on site selection Stores last 15 faults Con guration via USB-based PRKAB Dual color LED for fault indication Detection of fault with display of parameter value Page 1 of 8

Line Monitoring RISH RELAY-1 RELAY-2 RESET TEST ENTER RISHABH k V Hz Applications: Over voltage Under voltage Start up standby generators Operation of mains failure units Switching standby hybrid supplies Protecting computer supplies Close control of equipment Gensets - to monitor correct operation of the AVR (Automatic voltage regulator) and excitation system Motors-Some electric motors are voltage sensitive, and can overheat and burn out when operated at low voltage UPS supplies - When the main A. C. supply falls outside the acceptable operating voltage window the relay can initiate a change over to an alternate or standby supply Motors - Single Phasing Incorrect sequence connection. Product Features: Over voltage protection Under voltage protection Single phasing protection Phase unbalance protection Phase incorrect sequence protection Over frequency protection Under frequency protection 4 Digits ultra bright 7 Segment LED Display Trip cum DPM with Class 0.5 True RMS measurement The instrument measures distorted waveform up to 15th harmonic. Previous fault Storage Instrument memorizes the last 15 fault occurred. LED Indication - LED indication for relay-1 and relay-2 status. - Trip indication are displayed on 4 Digit display. - Dual color LED for per phase indication green color for normal condition and Red color for faulty condition. User selectable 3 phase 3W or 4W User can on site program the network connection as either 1P2W / 3P4W / 3P3W network using front panel keys. User selectable System Sequence User can program System Phase sequence as 123 or 321. Adjustable set point for - Over voltage. - Under voltage. - Phase failure. - Phase Unbalance. - Over frequency. - Under frequency. Adjustable time delay for - Over voltage. - Under voltage. - Phase failure. - Phase Unbalance. - Over frequency. - Under frequency. AND function User can use ANDing function to set trip on any two fault condition. Con guration via USB-based PRKAB User can con gure the Meter using USB-based PRKAB. Trip or Buzzer mode can be used to protect the system or simply to control the buzzer. Trip mode is for protection purpose and Buzz mode is for buzzer control. Page 2 of 8

Line Monitoring Auto / Manual reset In auto mode instrument automatically clears itself. If the device set into manual mode, the device must be manually reset by push button through display if it goes into fault. User selectable PT primary The Primary of Potential transformer can be programmed on site from 100 VL-L to 1200 kvl-l for Voltage trip relay. User selectable PT Secondary The input rated voltage can be programmed on site as 100-600VL-L using front panel keys. Onsite selection of Auto scroll / Fixed Screen User can set the display in auto scrolling mode or xed screen mode using front panel keys. Compliance to International Safety standards Compliance to International Safety standard IEC 61010-1- 2010. EMC Compatibility Compliance to International standard IEC 61326-1. Technical Speci cations: Dimensions Details: Input Voltage Nominal Input Voltage (AC RMS) 600VL-L (346.42VL-N) Max Continuous Input Voltage 127% of PT Secondary System PT Secondary Values 100VL-L to 600 VL-L programmable on site System PT Primary Values 100VL-L to 1200 kvl-l programmable on site Nominal Frequency 50 / 60 Hz ( programmable on site) Input Voltage Burden < 0.6VA approx. Auxiliary Supply External Higher Aux 60 V 300 V AC/DC Higher Aux Nominal value 230 V AC/DC 50/60 Hz for AC Aux OR External Lower Aux 20 V 60 VDC / 20 V 40 VAC Lower Aux Nominal value 48 VDC / 24 VAC 50/60 Hz for AC Aux Aux Supply Frequency 45 to 66 Hz range Aux Supply Burden < 4VA approx. Overload Withstand Voltage 2 x rated value for 1 second, repeated 10 times at 10 seconds Operating Measuring Ranges Voltage Range 20...125% of PT Secondary Frequency 40...70Hz Reference condition for Accuracy Reference Condition 23 C +/- 2 C Input waveform Sinusoidal (distortion factor 0.005) Input Frequency 50 or 60 Hz ±2% Auxiliary supply voltage Nominal Value ±1% Auxiliary supply frequency Nominal Value ±1% Page 3 of 8

Line Monitoring Electrical Connection: N 3 Phase 4 wire Unbalanced load NC 11 12 14 1 2 3 4 7 8 1 Phase 2 Wire 1 2 COM COM NO L N AUX SUPPLY L O A D 3 Phase 3 wire Unbalanced load N 1 2 3 7 8 L N AUX SUPPLY 1 4 7 8 NC 1 2 3 4 5 6 L O A D L N AUX SUPPLY L O A D 21 22 24 Note- Contacts are shown in power off condition NO Technical Speci cations: Accuracy Voltage ±0.5% of nominal value - Frequency ±0.2 Hz - Power ON, Trip, Reset Delays ±140 msec or ±5% of Set Delay, Whichever is Greater (WIG) In uence of Variations Temperature coef cient : Applicable Standards 0.025%/ C for Voltage EMC IEC 61326-1 - Immunity IEC 61000-4-3. 10V/m min Level 3 industrial Low level - Safety IEC 61010-1-2010, Permanently connected use - IP for water & dust IEC60529 - Pollution degree: 2 - Installation category: 300V CAT III / 600V CAT II - High Voltage Test 2.2 kv AC, 50Hz for 1 minute between all Environmental Electrical circuits. Operating temperature -10 to +55 C - Storage temperature -25 to +70 C - Relative humidity 0... 90% non condensing - Shock 15g in 3 planes - Vibration 10... 55 Hz, 0.15mm amplitude - Enclosure IP20 (front face only) Contacts Types of output 1CO, 2CO, 1CO+1CO - Contact Ratings (Res. Load) 5A/250VAC/30VDC - Mechanical Endurance 1x10^7 OPS Electrical Endurance NC- 1x10^4 OPS 1x10^5 OPS NO- 3x10^4 OPS for 1CO / 1CO+1CO relay for 2CO relay Mechanical Attributes 7 8 9 11 12 14 21 22 24 Weight 300g Approx. - Page 4 of 8

Line Monitoring Characteristics: Over set (%) Over (OV) and Under (UV) voltage / -2 Under set (%) Over set (%) / -3 Under set (%) Over set (%) / -1 Under set (%) 1 - OV: 11-14 (Energized) 2 - UV: 21-24 (De-Energized) Phase -LED Phase -LED Phase -LED Pd Td Rd Td Rd Differential (hysteresis) -1 LED (OV) -2 LED (UV) Aux Supply Time States - Energized De-Energized / -2 Phase fail set(%) / -3 Phase fail set(%) Phase Failure (Ph.F) and Phase Unbalance (Ph.un) Unbalance Unbalance Phase LED Indications - Red blinking - Trip Delay (only Phase LEDs) Green blinking - Reset Delay (only Phase LEDs) RED ON - fault condition Green ON - healthy condition Input Absent LED Indications - RED ON - fault condition / -1 Green ON - healthy condition Phase fail set(%) 1 - Ph.F: 11-14 (Energized) 2 - Ph.un: 21-24 (De-Energized) Phase -LED Pd Td Rd Td Rd Note: 1] Pd- Power ON delay 2] Td- Trip delay 3] Rd- Reset delay 4] Both relay can be con gured to energize or de-energize mode 5] Any relay can be assigned to any fault condition Phase -LED Phase -LED -1 LED (Ph.F) -2 LED (Ph.Un) Aux Supply Time Page 5 of 8

Line Monitoring Over (OF) and Under (UF) Frequency Over set (%) F sys F rated Under set (%) 1-OF: 11-14 (Energized) 2-UF: 21-24 (De-Energized) Phase -LED Pd Td Rd Td Rd Phase -LED Phase -LED -1 LED (OF) -2 LED (UF) Aux Supply States - Phase sequence (Ph.r) Time Energized De-Energized Incorrect phase sequence correct phase sequence Phase LED Indications - Red blinking - Trip Delay (only Phase LEDs) Green blinking - Reset Delay (only Phase LEDs) RED ON - fault condition Green ON - healthy condition Input Absent LED Indications - RED ON - fault condition 1: 11-14 (Energized) 2: 21-24 (De-Energized) Phase -LED Phase -LED Phase -LED -1 LED (Ph.r) -2 LED (Ph.r) Aux Supply Pd Rd Note: 1] Pd- Power ON delay 2] Td- Trip delay 3] Rd- Reset delay 4] Both relay can be con gured to energize or de-energize mode 5] Any relay can be assigned to any fault condition Time Green ON - healthy condition ANSI Numbers: ANSI Number 47 Acronyms 27 Under Voltage Phase-Sequence or Phase-Unbalance Voltage 59 Over Voltage 81 Over / Under Frequency Page 6 of 8

Line Monitoring 4 6 5 RISH RISHABH RISHABH Operating elements: 1 - - LED : Indicates status of V1 (in 3P4W) and V1-2 in 3P3W. It Lights green when input voltage is healthy, red in fault condition, red blinking in trip delay and green blinking in reset delay. 2 - -LED : Indicates status of V2 (in 3P4W) and V2-3 in 3P3W. It Lights green when input voltage is healthy, red in fault condition, red blinking in trip delay and green blinking in reset delay. 1 2 3 RELAY-1 RELAY-2 k v Hz 7 3 - - LED : Indicates status of V3 (in 3P4W) and V3-1 in 3P3W. It Lights green when input voltage is healthy, red in fault condition, red blinking in trip delay and green blinking in reset delay. RESET TEST ENTER 11 4/5 - -1 and -2 status LED : Indicates status of relay-1and relay-2 respectively. It lights green for relay in healthy condition and red for relay in trip condition. 10 9 8 6-4 Digit ultra bright 7 seg LED Display. 7 - K LED : It is used to show value in KV. 8 - Enter Key : Con rms changes of parameter setting. When on the measurement screen, holding for 3 sec enters in setup menu. Parameter Settings : Parameters 9- Test Key : Increments setting value, move upwards in the menu or change parameter. It is also used to test operation of relay. Continuous holding of test key changes relay position and when released, it resets the relay position (Only in healthy condition). 10- Reset Key : Decrements setting value, move downwards in the menu or change parameter. It is also used to reset relay when manual reset mode is selected. 11- Configuration via USB-based PRKAB. RISH -V/Hz Trip setting for phase failure 20-85% Trip setting for Voltage Unbalance Trip setting for over voltage Trip setting for under voltage 70-99% Trip setting for Max Frequency 101-110% Trip setting for Min Frequency 90-99% Setting for Differential / hysteresis Nominal Frequency settable Individual Faults can be deactivated as per system requirement Reset option control mode Reset Delay Programmable trip Delay for over voltage, Under Voltage, Over Frequency, Under Frequency, Phase failure, Phase Unbalance 2-20% 101-125% 1-15%* 50 / 60 Hz Yes ( Phase failure can not be deactivated) Auto / Manual De-energize/energize 0.2-30s 0-30s PT primary Voltage(V L-L) 100-1200KV L-L Power ON Delay 0.5-30s NOTE : Regenerate voltage may get produced in open phase due to blown fuse for some loads. In such a case, set the trip point for Phase. Failure (20-85%) as per requirement considering the possibility of a higher regenerated voltage * Differential setting range for voltage unbalance is limited as per its setting of trip point. Page 7 of 8

Line Monitoring Hysteresis Calculation Method: Example: - For OV (Over Voltage) PT Secondary = 100 V L-L. Trip point = 105% of PT Secondary = 105 V L-L Hysteresis = 2% of PT Secondary = 2 V L-L Reset point = Trip point - Hysteresis = 105-2 = 103 V L-L. Example: - For Ph.un (Phase Unbalance) PT Secondary = 100 V L-L. Trip point = 10% of PT Secondary = 10 V L-L Hysteresis = 2% of PT Secondary = 2 V L-L. Reset point = Trip point - Hysteresis = 10-2 = 8 V L-L. Page 8 of 8