Circuit design for reproducible on-site measurements of transfer function on large power transformers using the SFRA method

Similar documents
Performing reliable and reproducible frequency response measurements on power transformers

INTERPRETATION METHODOLOGY TO IDENTIFY FAULT LOCATION IN A POWER TRANSFORMER

Chapter 7 Conclusion 7.1 General

FRAX Series Sweep Frequency Response Analyzers

Investigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA)

Vallabh Vidyanagar, Anand, INDIA

Matz Ohlen Director Transformer Test Systems. Megger Sweden

متلب سایت MatlabSite.com

FRAX Series Sweep Frequency Response Analyzers

How to overcome undesirable effects ABSTRACT KEYWORDS. 1. Introduction

Variation in SFRA plot due to design and external parameter

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

EFFECT OF RADIAL AND AXIAL MOVEMENT OF WINDING ON COHERENCE FUNCTION IN A 220/132 KV, 100 MVA, AUTO TRANSFORMER

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Research Article Diagnosing Integrity of Transformer Windings by Applying Statistical Tools to Frequency Response Analysis Data Obtained at Site

Shunt Capacitance Influences on Single-Phase Transformer FRA Spectrum

Benefits of SFRA - Case Studies

A Literature Survey on Frequency Response Analysis for Detection of Transformer Winding Fault

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Analysis of Frequency Response measurement results with end-to-end/interwinding test setup correlation

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

FRANEO 800. The next generation for a reliable core and winding diagnosis of power transformers

Efficient HF Modeling and Model Parameterization of Induction Machines for Time and Frequency Domain Simulations

Effective maintenance test techniques for power transformers

FRAnalyzer. Reliable core and winding diagnosis for power transformers

P a g e 1 ST985. TDR Cable Analyzer Instruction Manual. Analog Arts Inc.

Demagnetization of Power Transformers Following a DC Resistance Testing

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Transformers handling and transport

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

TMS 580. Transformer Loss Measuring System FEATURES BENEFITS APPLICATIONS

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Diagnostic testing of cast resin transformers

FAULT IDENTIFICATION IN TRANSFORMER WINDING

Measurements of the Distorted No-load Current of a 60/20 kv, 6 MVA Power Transformer Søgaard, Kim; Bak, Claus Leth; Wiechowski, Wojciech Tomasz

Field Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques

Importance of Transformer Demagnetization

FRAX Series Sweep Frequency Response Analyzers

Unit 27 Three-Phase Circuits

Advanced Test Equipment Rentals ATEC (2832)

Test Report CESI A6/ Approved Page 1. MF Trasformatori s.r.l. - Calcinato (BS) Italy

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Impact Assessment Generator Form

TECHNIQUES AND STANDARD

Correlation between time and frequency domain polarisation measurements for transformer moisture assessment

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

HV AC TESTING OF SUPER-LONG CABLES

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

New Method for Transformer Winding Fault Detection

Transformer Factory Testing

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

OMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates

FRAX 101 Sweep Frequency Response Analyzer

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

Mitigating Murphy s Law While Test. Frédéric Dollinger

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

MECHANICAL faults in transformers can pose a great threat to electric power system. There are many

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

Improved Method for Winding Deformation Detection Sensitivity in Transformer

150Hz to 1MHz magnetic field coupling to a typical shielded cable above a ground plane configuration

MIDAS Mobile Insulation Diagnosis & Analysing System. Features. Benefits. Applications

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

86 chapter 2 Transformers

Progress Report on Failures of High Voltage Bushings with Draw Leads By Jim McBride and Larry Coffeen, JMX Services / NEETRAC 7/26/2010

Recommendations for Harmonic and Power Measurements in Electrical Networks

Transformer condition assessment with an integrated test van

Commissioning Manual Distribution Transformers - Three-phase Oil Filled

Rarely used, problems with unbalanced loads.

Automatic Transformer Winding Analyser

IVE(TY) Department of Engineering. Electrical Machines 1. Electrical Machines 1. Hour 13. slide 1

148 Electric Machines

TD-100. HAEFELY HIPOTRONICS Technical Document

KIT-ENERGY CENTRE. KIT The research University in the Helmholtz Association

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

MODEL 5002 PHASE VERIFICATION BRIDGE SET

How the Braid Impedance of Instrumentation Cables Impact PI and SI Measurements

Optimization of power transformers based on operative service conditions for improved performance

Research Article Transformer Winding Deformation Profile using Modified Electrical Equivalent Circuit

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Transient Recovery Voltage at Transformer Limited Fault Clearing

VFRA-25 transformer frequency response analyzer

Probing Techniques for Signal Performance Measurements in High Data Rate Testing

Dielectric analysis of high-voltage power transformers DIAGNOSIS ABSTRACT KEYWORDS. 1. Introduction

Current sensor by IZM

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Embedded Generation Connection Application Form

TTR2796. Fully Automated Three Phase 250V Transformer Turns Ratio Meter FEATURES AND BENEFITS APPLICATIONS

Core Technology Group Application Note 6 AN-6

Effects of Transformer Connection on Voltage Sag Characterization

Fully automated three phase 250V Transformer Turns Ratio Meter

Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation

Transcription:

Circuit design for reproducible on-site measurements of transfer function on large power transformers using the SFRA method C. Homagk 1*, T. Leibfried 1, K. Mössner 1 and R. Fischer 1 Institute of Electric Energy Systems and High-Voltage Technology, University of Karlsruhe, Germany Haefely Test AG, Basel, Switzerland *Email: homagk@ieh.uni-karlsruhe.de Abstract: By the analysis of transfer function mechanical deformations or displacements of transformer windings can be detected. For on site measurements on large power transformers essential attention has to be put on accurate cabling and handling of grounding conductors. Of further concern is the selection of a meaningful upper frequency limit, from where beyond measurements of frequency responses are not practicable on site. A set-up concept for reproducible measurements that has been developed by the authors shows satisfying results. Investigations on the transfer function of power transformers identical in construction have been carried out: Depending on the type, size and winding construction the transfer function of a winding system of identical transformers is well comparable to frequencies above 1 MHz. A mathematical approach to evaluate the quality of different comparison methods using the coherence function is presented. 1 INTRODUCTION The evaluation of the transfer function is a sensitive diagnostic method to detect mechanical variation of the active part of a power transformer. Deformations caused by short circuit currents or transportation result in variation of the transfer function. Some authors of technical publications (e.g. [1]) propose to extend the frequency range in which the transfer function is evaluated to at least 1 MHz and prove deviations in the transfer function from 1 MHz up to high frequency ranges by artificial mechanical deformation of a transformer winding. THE SFRA METHOD To acquire the TF (transfer function) with the SFRA method (Sweep Frequency Response Analysis) presented in this paper, a frequency variable sinusoid signal with known voltage is applied on one terminal of an off-line power transformer. On a second terminal the signal of the same frequency is picked up by a sensor. With this procedure the transfer function U ( f) H( f) = (1) U ( f) 1 between two terminals of a power transformer can be acquired in frequency domain with magnitude and phase. Through variation of signal frequency the transfer function can be evaluated in the desired frequency range []. Fig. 1 shows the equivalent circuit of a measurement between 1U and 1N on a typical delta-wye distribution transformer. Fig. shows the practical realisation of the circuit on a test specimen with complex, frequency variable impedances. The main difference between ideal and real circuitry is the distributed grounding system and non-zero length of the measuring leads. U 1 1U 1V 1W OS 1N 5 Ω Fig. 1: SFRA measurement principle U US.1. On site acquisition of transfer function As the measurement principle is based on the comparison of frequency plots, the greatest challenge for on site acquisitions is a good reproducibility of measurements that are repeated after a certain time. The measurement circuit itself and the grounding system has a certain physical dimension and has an impact on the acquired transfer function, especially in the high frequency range starting at a few 1 khz. Another fundamental requirement is that the measurement instrumentation for transfer function must be independent from local grounding conditions, e.g. for power transformer transport. To ensure repeatability of FRA measurements also after long time with a measuring set-up as identical as possible, focus has to be put on accurate documentation. The tap changer position, all used connection and grounding points at the transformer have to be clearly recorded. Taking detail photographs has proven to be very helpful. The type and length of grounding connectors have to be remarked in the report. x y z

Analyzer l variations of transfer characteristics of other parts in the signal path, like bushings or tap changer contacts Z M ~ Z 1 (f) U 1 U Z (f) Z 3 (f) Z M Fig. : Realisation of measurement circuitry All measurements presented in this paper have been performed with the Tettex FRA 531 measurement system manufactured by Haefely Test AG... Handling of Terminals Particularly on transformers with high nominal voltages and large power rating cabling work takes significant time and because of the large dimensions it determines the overall measurement duration. In principle it is possible to ground or short circuit unused winding systems, although perfect grounding or short circuit of windings is impossible to realise especially at higher frequencies. If the measurement is repeated, identical cabling set-up must be used. On reproduction measurements with several cabling steps small deviations in the set-up will accumulate and possibly affect deviations of the transfer function. Under the aspect of good reproducibility the authors did not ground or short circuit unused terminals at their measurements and tried to keep number and length of used measuring wires as small as possible. Fig. 3 shows the typical connection of the measurement clamps and ground connectors to the transformer s neutral point equipped with a 4 kv bushing. l 1 DUT As transformer high voltage bushings are connected to the terminal lead by a flexible conductor, the position of the conductor may vary between transformers identical in construction or after maintenance. This might be source of high frequency deviations. The effect of variations on tap changer and bushings on the transfer function has not been investigated yet but cannot be ruled out in principal..3. Influence of Measurement Voltage The transformer s magnetic core shows variant behaviour not only after magnetization [6] but also on variation of measurement voltage, as shown in Fig. 4 on a /.4 kv 8 kva distribution transformer. There was no influence of measurement voltage in higher frequencies. When a measurement is repeated on the same test specimen, it must be ensured that the same measurement voltage is used. Otherwise there will be deviations in the low frequency range that might be accidentally detected as fault. 5-5 -1-15 - Measurement Voltage,1 Vpp 1 Vpp 5,5 Vpp 1 Vpp 1 Vpp -5 1 1 1 1 3 1 4 1 5 Fig. 4: Influence of measurement voltage on transfer function Fig. 3: Measurement connection on bushing stem and ground connection with aluminium braid on a 4 kv bushing If deviations occur on chronological measurements on a transformer there are aspects beside an actual deformation of windings that can be held responsible for changes in the transfer function: variations caused by the measurement set-up.4. Influence of Bushings Capacitive controlled bushings with their stacked conducting layers basically show high pass behaviour between the bushing stem and the root point connected to the transformer tank. To investigate the influence of a capacitor bushing the transfer function between the low voltage terminals U and N was determined. Afterwards the measurement was repeated with identical parameters but a 13 kv bushing was put in series between the terminal and the receiver. The bushing root point was connected with a very short piece of aluminium braid to the transformer s tank; the bushing s test tap was grounded. Fig. 5 proves an influence of the capacitor bushing on the transfer function even below 1 MHz.

-5-1 -15 - Poor grounding can cause significant deviations even below 1 MHz and can therefore be tremendous source for mismeasurements that are hard to detect. Fig. 6 shows measurements on a 4 MVA 11/1 kv single phase transformer with different contact quality on the receiver arm of the measurement device. 1-5 -3 TF without bushing TF with bushing -1-35 1 4 1 5 1 6 1 7 Fig. 5: Influence of bushing on transfer function U 1 /U (db) - -3-4.5. Measurement impedance Using high impedance Z M (e.g. 1 MΩ) will result in bad matching of the 5 Ohms coaxial cable connecting transformer and measurement device and unsatisfying high frequency behaviour. This problem can be overcome if the measurement termination impedance is placed in direct proximity to the transformer s connection point, reducing cable length l to zero. Also winding end-to-end measurements with high measuring impedance can result in transfer functions without distinct resonance peaks if the winding impedance is rather low [7]..6. Ground connections The earthed transformer tank has to be connected to the grounding system of the measurement device. It has become evident that the connection between tank an measurement connector has considerable influence on the transfer function. To provide good reproducibility of FRA measurements, the specification of a grounding strategy must be an integral part of the acquisition procedure. Furthermore the set-up must be realisable also on largest power transformers. In the context of comprehensive analysis it has been realised that broad, thin-leaded aluminium braid for connection of measurement ground with the transformer tank is an acceptable compromise within cost and benefit. The fundamental difference of braid conductor and conventional wire is not only a reduced inductivity but also the noticeable reduction of the frequencydependant skin effect. The current displacement is remarkable already at measurement frequencies of 5 khz. Another vulnerability of transfer function measurements is the contact point of grounding conductor and transformer tank. As the tank is usually coated corrosion protection paint, the coating has to be removed for satisfying contact. For good high frequency behaviour the contact should not be punctual but laminar. -5 good grounding poor grounding no grounding -6 1 1 3 1 4 1 5 1 6 f (Hz) Fig. 6: Transfer function of one 4 MVA transformer, different grounding contact quality of receiver arm on bushing root point To investigate the influence of an altered ground setup on the acquired transfer function the measurement device was connected to the transformer tank with an additional ground connector (copper wire, length 1m) during measurements on a single-phase 11/13 kv 5 MVA coupling transformer. Here the transfer functions showed up identical characteristics up to about 1.6 MHz, at higher frequencies there was significant deviation in the magnitude of the transfer function but also in the position of resonance peaks, see Fig. 7. Fig. 7: Deviations of TF caused by alteration of ground connectors between transformer and measurement device

3 METHODS OF COMPARISON 3.1. Time-based comparison The most common method is the timed-based comparison of transfer functions, also called finger print measurement. These can be for example measurements on annual inspections or before and after transports of power transformers. With a careful and accurate set-up and a high frequency capable grounding concept one will get satisfying results up to several MHz. Fig. 8 shows the repetition of a measurement on a 11/1 kv 4 MVA single phase transformer after five months with almost no deviation. This proves that the chosen measurement set-up provides excellent reproducibility. The transformer was in service before and after the measurements. -1 - -3-4 -5-6 -7-8 -9 1 1 3 1 4 1 5 1 6.5.6 11.9.6 Fig. 8: Reproduction of TF after time, HV winding, 4 MVA single phase transformer 3.. Phase-to-phase comparison Depending on the size and type of construction a phase-to-phase comparison is possible up to a maximum frequency ranging widely from about 4 to 7 khz. The transfer functions of the low voltage windings of a 4/15 kv 73 MVA power transformer in Fig. 9 show good similarity up to about 35 khz. In the frequency range below 1 khz there is also the typical deviation of the middle transformer winding ( V-Mp ) that is caused by the geometry of the magnetic core. The asymmetry of the core, different stray capacitances and varying length and position of terminal leads of the windings limit the usable frequency range. -1 - -3-4 -5-6 -7-8 U-Mp -9 V-Mp W-Mp -1 1 1 3 1 4 1 5 1 6 1 7 Fig. 9: Phase-to-phase comparison, HV star winding, 73 MVA generator transformer 3.3. Sister unit comparison In large power plants or substations often power transformers can be found that are apparently identical in construction. If the transformers have sequential serial numbers it can be assumed with high likeliness that the mechanical construction is identical. Please note that even in a series of transformers with identical characteristics modifications in the mechanical and electrical design are possible [5]. -1 - -3-4 -5-6 -7-8 HV winding transformer 1 HV winding transformer -9 1 1 3 1 4 1 5 1 6 1 7 Fig. 1: Sister unit comparison, HV star winding, 11 MVA generator transformers Fig. 1 shows the transfer functions of two 4/7 kv 11 MVA transformers that are connected in parallel to a large generator and to one high voltage feeder. These transformers have been in service since 1978. Fig. 11 shows the low voltage windings transfer functions of two 4/15 kv 73 MVA sister transformers connected to separate generators in a hydro power plant.

5 4 1-5 -1-15 - -5 Error.5 Coherence -3-35 -4-45 1 1 3 1 4 1 5 1 6 1 7 LV Transformer 1 LV Transformer Fig. 11: Sister unit comparison, LV wye winding, 73 MVA generator transformers 3.4. Mathematical approach There are different ways to investigate the alikeness of two transfer functions, e.g. calculation of the difference function or the coherence function [3], [4]. The coherence function gives information on the analogy of two functions at a frequency f and is defined as: G ( f ) XY γ ( f ) = () XY G ( f ) G ( f) XX YY This function provides values between (no correlation) and 1 (full correlation of both signals). Already small deviations in magnitude and phase result in variation of the coherence function from γ ( f ) = 1. XY However the coherence function gives only information about one specific frequency f. If the coherence function is scaled from for full correlation and is summed up, a monotonic rising function is obtained, that gives information about the total deviation δ of the transfer functions up to a frequency f : 1 f1 δ( f ) = 1 γ ( k) 1 (3) XY k= f Fig. 1 shows the coherence and error function for two transfer functions with significant deviation. Under the assumption that there is no mechanical defect when comparing the transfer functions, an arbitrary level δ is defined and the corresponding frequency f is calculated up to which two transfer functions can be regarded as similar. The value of f characterizes the frequency at which the two compared transfer functions diverge more than the tolerated measure δ.this method may only be used if transfer functions with identical frequency sampling points are provided. 1 4 1 5 1 6 1 7 Fig. 1: Coherence and sum error To determine the upper frequency limit in this investigation the evaluated lowest frequency was defined to be 7 khz to mask time variant influence of the magnetic core [6]. The error level was chosen to δ = 1.5. As shown in Fig. 13, three different sizes of generator transformers were investigated. time-based HV time-based LV sister unit HV sister unit LV phase-based HV phase-based LV better similarity 4 MVA 73 MVA 11 MVA 1 3 4 5 Frequency (khz) Fig. 13: Quality of comparison, δ = 1.5 The investigations prove that the transfer functions of the same phases of transformers identical in construction are much more similar than the different phases of one transformer compared to each other. Obviously, constructive tolerances have less influence on the transfer function than the different length and position of terminal leads and the general asymmetry of the winding arrangement in the transformer tank. The phase-based comparison is limited to a much smaller frequency range. Compared to the 4 MVA transformer, the large 73 MVA and 11 MVA transformers are comparable in a larger frequency range, especially for the high voltage windings. Constructive tolerances cause slight deviation in the transfer function in the region of 1 MHz and above. From the experience of the authors, at most power transformers transfer functions of low voltage windings identical in construction are similar up to higher

frequencies than transfer functions of high voltage windings. This is due to the more complex construction of the winding, longer terminal leads (e.g. tap changer) and larger bushings, but the individual influence has not been investigated yet. Please note that the authors do not recommend the coherence function as solely tool for interpretation on transfer functions. Deviations in magnitude that are sometimes caused by poor set-up will also be detected by the coherence function and may lead to misinterpretation. 4 CONCLUSIONS Reproducible on site FRA measurements above 1 MHz are possible, but full attention has to be put on the quality of the measurement set-up. Grounding strategies with low inductance and little skin effect are essential for congruent measurements. FRA measurements on power transformer sister units show up a much better correlation than a comparison of different phases of one power transformer. The experience shows that usually identity of transfer functions of low voltage windings can be obtained to higher frequencies than on high voltage windings. Constructive tolerances manifest in slight deviation of the transfer function above 1 MHz. As the measurement set-up has a certain dimension and high frequency deviations are easily caused by grounding issues, practical on-site measurements of transfer function should be reasonable limited to an absolute maximum of 5 MHz. If set-up quality and accuracy is poor a much lower maximum usable frequency will be achieved. 6 REFERENCES [1] Wang, M., Vandermaar A.J., Srivastava K. D.: Improved Detection of Power Transformer Winding Movement by Extending the FRA High Frequency Range. IEEE Transactions on power delivery, Vol., No. 3, July 5 [] Feser K., Christian J., Neumann C., Sundermann U., Liebfried T., Kachler A., Loppacher M., The Transfer Function Method for Detection of Winding Displacements on Power Transformers After Transport, Short Circuit or 3 Years of Service, CIGRE Paris, paper no. 1/33-4, [3] Rickmann J., Britton J., Gockenbach E., Coffeen L., A New Technique to Detect Winding Displacements in Power Transformers Using Frequency Response Analysis, presented at the IEEE Powertech Conference, Bologna, 3 [4] Leibfried T., Die Analyse der Übertragungsfunktion als Methode zur Überwachung des Isolationszustandes von Großtransformatoren, Dissertation, University of Stuttgart, 1996, German language [5] Christian J., Erkennung mechanischer Wicklungsschäden in Transformatoren mit der Übertragungsfunktion, Dissertation, University of Stuttgart,, German language [6] Nothaft M., Untersuchung der Resonanzvorgänge in Wicklungen von Hochspannungsleistungstransformatoren mittels eines detaillierten Modells, Dissertation, University of Karlsruhe, 1994, German language [7] Homagk C., Mössner K., Leibfried T., Reproducible on-site measurements of transfer function on power transformers in frequency domain, presented at the NORD-IS Conference, Kgs. Lyngby, 7 5 ACKNOWLEDGMENTS The authors would like to acknowledge the kind support from Deutsche Forschungsgemeinschaft (DFG) and from various power utilities for making measurements possible.