Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Similar documents
Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Effective Elimination Factors to the Generated Lightning Flashover in High Voltage Transmission Network

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Computation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission Lines

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Lightning transient analysis in wind turbine blades

Study of Tower Grounding Resistance Effected Back Flashover to 500 kv Transmission Line in Thailand by using ATP/EMTP

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Lightning performance of a HV/MV substation

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise

Back-flashover Investigation of HV Transmission Lines Using Transient Modeling of the Grounding Systems

Analyzing and Modeling the Lightning Transient Effects of 400 KV Single Circuit Transmission Lines

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

The Influences of Soil Ionization in the Grounding System and Corona Phenomena on the Injection Lightning Current of 1000 KV UHV Transmission Line

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

Lightning Overvoltage Performance of 110 kv Air-Insulated Substation

Modeling insulation in high-voltage substations

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Accuracy of Lightning Surge Analysis of Tower Surge Response

ABSTRACT 1 INTRODUCTION

The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line.

SCIENCE & TECHNOLOGY

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines

The Many Uses of Transmission Line Arresters

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

ABSTRACTS of SESSION 6

Substation Insulation Coordination Study

Lightning overvoltage and protection of power substations

Including Surge Arresters in the Lightning Performance Analysis of 132kV Transmission Line

Lightning Performance of Transmission Lines with Tall Sections

Investigation on the Performance of Different Lightning Protection System Designs

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS

Sensitivity Analysis of Maximum Overvoltage on Cables with Considering Forward and Backward Waves

GIS Disconnector Switching Operation VFTO Study

Electric Power Systems Research

X International Symposium on Lightning Protection

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations

The Use of a Special Grounding Arrangement to Improve the Lightning Performance of Transmission Line

Simulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP

Comparison between Different InstallationLocations of Surge Arresters at Transmission Line Using EMTP-RV

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT

Experimental Study on Lightning Surge Response of 500kV Transmission Tower with Overhead Lines

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Mitigation of Back-Flashovers for 110-kV Lines at Multi-Circuit Overhead Line Towers

ATP SIMULATION OF FARADAY CAGE FOR THE ANALYSIS OF LIGHTNING SURGES

Fig.1. Railway signal system

ACCURATE SIMULATION OF AC INTERFERENCE CAUSED BY ELECTRICAL POWER LINES: A PARAMETRIC ANALYSIS

Power Quality and Reliablity Centre

Utility System Lightning Protection

Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

EVALUATION OF LIGHTNING-INDUCED VOLTAGES ON LOW-VOLTAGE DISTRIBUTION NETWORKS

High Voltage Induced By Transmission Lines Due To Lightning Case Study

Analysis of the Electromagnetic Interferences between Overhead Power Lines and Buried Pipelines

Transmission of Electrical Energy

Earthing of Electrical Devices and Safety

Research on Lightning Over-voltage and Lightning Protection of 500kV. HGIS Substation

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

The line-lightning performance and mitigation studies of shielded steelstructure

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

The Simulation Experiments on Impulse Characteristics of Tower Grounding Devices in Layered Soil

Estimating BFOR on HV Transmission Lines Using EMTP and Curve of Limiting Parameters

Lightning current waves measured at short instrumented towers: The influence of sensor position

EXPLOTING THE IMPULSE RESPONSE OF GROUNDING SYSTEMS FOR AUTOMATIC CLASSIFICATION OF GROUNDING TOPOLOGIES

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Investigation of Transmission Line Overvoltages and their Deduction Approach

Towards an Accurate Modeling of Frequency-dependent Wind Farm Components under Transient Conditions

A Study of Lightning Surge on Underground Cables in a Cable Connection Station

OVERVOLTAGE PROTECTION OF POLE MOUNTED DISTRIBUTION TRANSFORMERS

DEPARTMENT OF EEE QUESTION BANK

APPLICATION OF THE ELECTROMAGNETIC FIELD METHOD TO STUDY A COMMUNICATION SATELLITE SITE DAMAGED BY LIGHTNING

Modeling of substation grounding for fast front overvoltage studies

MAHALAKSHMI ENGINEERING COLLEGE

Traveling Wave Fault Location Experience at Bonneville Power Administration

An Approximate Formula for Estimating the Peak Value of Lightning-Induced Overvoltage Considering the Stratified Conducting Ground

SURGES TRANSFERRED TO THE LOW-VOLTAGE NETWORK VIA TRANSFORMER THE INFLUENCE OF THE LOAD CONNECTED TO THE SECONDARY

Industrial and Commercial Power Systems Topic 7 EARTHING

Insulation Co-ordination For HVDC Station

Grounding for Power Quality

High voltage engineering

B2-301 IMPROVING DOUBLE CIRCUIT TRANSMISSION LINE RELIABILITY THROUGH LIGHTNING DESIGN

IEEE Power Engineering Society 2001 Winter Meeting Columbus, OH. Panel Session. Data for Modeling System Transients

The impact of recent advances on lightning measurement and detection on the protection of transmission and distribution lines

Mitigation Methods to Improve the Lightning Performance of Hybrid Transmission Line

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

Protection against unacceptable voltages in railway systems

INTEGRATED METHOD IN ELECTROMAGNETIC INTERFERENCE STUDIES

Transcription:

Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 10), Cairo University, Egypt, December 19-21, 2010, Paper ID 111. Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning Ossama E. Gouda Adel Z. El Dein Ghada M. Amer Department of Electric Engineering Department of Electric Engineering Department of Electric Engineering Faculty of Engineering High Institute of Energy High Institute of Technology Cairo University, Giza, Egypt South Valley University, Aswan, Egypt Benha University, Benha, Egypt d_gouda@yahoo.com azeinm2001@hotmail.com dr_ghada11@hotmail.com Abstract This paper describes analysis study on some factors, which affecting the back flashover across the insulator in a transmission system. Parameters of this study include the modeling of transmission line tower, the modeling of tower footing ground system, magnitude of lightning stroke, front and tail times of lightning stroke impulse, and striking distance. All components of the system, which is under study, are simulated by using ATP program. Index Terms ATP, Back Flashover, Induced Voltage, Overhead Transmission Line. I I. INTRODUCTION N this paper, the lightning overvoltage in 500 kv transmission line is described. The lightning overvoltage is one of an important factors causing flashover and damage the insulators in the transmission line. A lightning flash generally consists of several strokes which are charges, negative or positive from the cloud to the ground. The first stroke is most often more severe than the subsequent stroke [1]. In stroked location a current impulse is injected into the transmission line. Voltage and current waves propagate from this stroked location to both sides of line, which reflect in every place where there is a change in surge impedance. Probability of direct lightning strike to phase conductor is decreased by using of ground wires. If ground wire is stroked by lightning, reflections appear in places of connection with tower or on earthing of tower. As the lightning current propagates on ground wire to both sides from stroked place, the value of overvoltage in this place can be determined as voltage drop caused by lightning current flow through parallel combination of line surge impedance and tower where steel tower bears as surge impedance approximately of hundreds ohm depended on tower configuration and dimensions. When lightning strikes a tower, a traveling voltage is generated which travels back and forth along the tower, being reflected at the tower footing and at the tower top, thus raising the voltage at the cross-arms and stressing the insulators. The insulator will flashover if their transient voltage exceed its withstand level (backflash). II. MODELING OF THE SYSTEM UNDER STUDY A. Single-Circuit 500 kv Transmission Line The 500 kv transmission line has three sub-conductors per phase and two ground wires. The span length is equal to 400 m. The tower is of flat configuration as shown in Fig. 1, and the distance between two adjacent phases is equal to 13.2 m. Modeling of transmission line tower is an essential part of the travelling-wave analysis of lightning surges in overhead transmission lines. Tower equivalent circuit is shown in Fig. 2, and Fig. 3 shows the transmission line tower model, which is simulated by ATP program. The model consists of main legs and cross-arms. The surge impedance of each part is expressed by the functions of their dimensions and geometry [2]. The surge impedance in ohm, propagation velocity in mega meter per second and length in meter of each tower s part are indicated in Fig. 2. Fig. 1 500 kv transmission line tower 44

[4-5] (3) where is permittivity of the soil in farad per meter. Fig.2 Simplified representation of 500 kv tower Fig. 4 High Frequency lumped RLC circuit simulates the grounding electrode. Finally, the inductance (in Henries) for both vertical and horizontal electrode is given by: Fig. 3 ATP Model of 500kV transmission line tower B. Tower Footing Ground System In order to simulate behavior of different tower footing ground system during lightning transient, a vertical or horizontal electrode is used at each leg of the transmission line tower and simulated by ATP program as shown in Fig. 3. A simple lumped circuit high frequency mode suggested by Rudenberg [3-4] is illustrated in Fig. 4. For the vertical electrode, according to Dwight [4-5], the resistance (in Ohms) is calculated as: where is permeability of the soil in henries per meter. C. Lightning strike The lightning stroke is modeled by a current source and a parallel resistance, which represents the lightning-path impedance. Lightning-path impedance is selected as 400 Ω according to [7]. Figure 5 shows the lightning stroke model that simulated by ATP program. Typical stroke impulse current waveform is shown in Fig. 6. (4) (1) and for the horizontal electrode, according to Sunde [6], the resistance is calculated as: where is resistivity of the earth in ohm. meter, is ground electrode length in meter, is its radius in meter, and is depth of burial of horizontal electrode in meter. and the grounding capacitance (in Farad) for both vertical and horizontal electrode is computed based on the relationship (2) Fig. 5 Simulation of lightning stroke model D. Back flashover Model The transient-voltage withstands level of a power apparatus is not a unique number. An apparatus may withstand a high transient voltage which has a short duration even it has failed to withstand a lower transient voltage with longer duration. This characteristic of the insulator is known as the volt-time characteristic of the insulation. However, a simplified 45

expression for the insulator voltage withstands capability can be calculated as [8] (5) where t is elapsed time after lightning stroke, µs. The back flashover mechanism of the insulators can be represented by volt-time curves. When a back flashover might occur, a parallel switch is applied. If the voltage across the insulator exceeds the insulator voltage withstand capability, the back flashover occurs. The back flashover is simulated by closing the parallel switch. Once the back flashover occurs, the voltage across insulator goes down to zero. L Fig. 6. Lightning current waveform is a flashover voltage (kv), is 400*L, is 710*L, is insulator length, (meter), III. SIMULATION RESULTS In this section, the 500 kv overhead transmission line has been modeled using ATP program as shown in Fig. 7. In order to take into account the effect of the AC steady-state voltage of the line on a lightning surge, the transmission line is connected to AC voltage source via multiphase matching impedance (surge impedance matrix). As the transmission line is terminated with multiphase matching impedance, there is no reflected traveling wave from the far end of the transmission line, and thus, the transmission line is regarded as an infinite line. The parameters of the transmission line used in this study are shown in Table I. Fig. 7 ATP simulation of the system under study. TABLE I CHARACTERISTICS OF 500 KV LINE CONDUCTORS Conductor number Radius (mm) X- Coordinate (m) Y- Coordinate (m) R dc at 20 C (Ω/km) A1 15.3-13.425 22.13 511 A2 15.3-12.975 22.13 511 A3 15.3-13.2 21.74 511 B1 15.3-0.225 24.48 511 B2 15.3 0.225 24.48 511 B3 15.3 0 24.09 511 C1 15.3 12.975 22.13 511 C2 15.3 13.425 22.13 511 C3 15.3 13.2 21.74 511 G1 5.6-8 30 64 G2 5.6 8 30 64 A. Striking Distance In this section, a lightning stroke, of which a current is 20 ka, hits one of the two ground wires (G1). Figure 8 shows the induced voltage wave forms on phase A, which is the nearest phase to stroke point, at various striking distances; d=0, 400, 800, 1200, 1600 m (towers 1, 2, 3, 4 and 5). It is noticed that the induced voltage magnitude decreases with increasing striking distance, and they almost have the same wave form. Also it is noticed that there is a delay introduced in the induced voltage waveforms. The time delay seen in the induced voltage waveforms corresponds to the time taken for the electromagnetic field produced by the lightning current to travel to the respective observation points. Figure 9 shows the induced voltage wave forms on the three 46

phases A, B and C of tower 1. It is noticed that, due to asymmetry, the induced voltages are not the same in the three phases, but it is highest at phase A as it is nearest to the lightning strike point (G1), and it is smallest at phase C as it is farther to the lightning strike point. Backflash voltages are generated by multiple reflections along the struck tower and also along the ground. The backflash voltage across insulator for the struck tower is not a straightforward. The peak voltage will be directly proportional to the peak current as shown in Fig. 11. From Fig. 11 it is noticed that the transient-voltage withstands level of the insulator is not a unique number. The insulator withstands a high transient voltage for a short duration and it withstands a low transient voltage for relatively longer duration. *10 6 1.6 - - (file Lightning.pl4; x-var t) v:twr1a v:twr2a v:twr3a v:twr4a v:twr5a Fig. 8 Induced voltage at phase A for various striking distances 3.0 3.5 [us] 4.0 lightning_v_amp_10.pl4: m:u lightning_v_amp_20.pl4: m:u lightning_v_amp_30.pl4: m:u lightning_v_amp_40.pl4: m:u Fig. 11Backflash over clearance at insulator of phase A with various peaks of lightning current - - (file Lightning.pl4; x-var t) v:twr1a v:twr1b v:twr1c Fig. 9 Induced voltage at phase A for various striking distances B. Peak of the Lightning Current Figure 10 shows the induced voltage wave forms on the top of tower 1 with a various peaks of lightning current. It is noticed that the magnitude of the induced voltage increases with increasing the peak of the lightning current. 3.0 C. Front Time of Lightning Stroke Figure 13 compares induced voltage wave form on the top of tower 1 with various front time of lightning strokes;, 4, 6µs, with magnitude 40 ka, as shown in Fig. 12. It is noticed that the shorter front wave time increases the induced voltage. Figure 14 compares the time for clearing the overvoltage (backflash over) at insulator of tower1 with various front time of lightning strokes, also it is noticed that as the front wave time increases the induced overvoltage decreases and in turn the time to clear the overvoltage increases. D. Tail Time of Lightning Stroke Figure 16 compares induced voltage wave form on the top of tower 1 with various tail time of lightning strokes; 20, 30, 40 µs, with magnitude 40 ka, as shown in Fig. 15. It is noticed that the shorter tail wave time decreases the induced voltage. Figure 17 compares the time for clearing the overvoltage (backflash over) at insulator of tower1 with various tail time of lightning strokes, also it is noticed that as the tail wave time increases the induced overvoltage increases and in turn the time to clear the overvoltage decreases. - - Lightning_V_Amp_40.pl4: v:gr1 lightning_v_amp_30.pl4: v:gr1 lightning_v_amp_20.pl4: v:gr1 lightning_v_amp_10.pl4: v:gr1 Fig. 10 Induced voltage at top of tower 1 with various peaks of lightning current 47

50 [ka] 40 30 3.0 20 10 0 Lightning_V_Front_6.pl4: c:xx0227-gr1 lightning_v_front_4.pl4: c:xx0227-gr1 lightning_v_front_.pl4: c:xx0227-gr1 Fig. 12 Lightning source wave shape with various front time 3.5 - - Lightning_V_Tail_20.pl4: v:gr2 lightning_v_tail_30.pl4: v:gr2 lightning_v_tail_40.pl4: v:gr2 Fig. 16 Induced voltage at top of tower 1 with various front time of lightning current *10 6 1.6 - - - Lightning_V_Front_6.pl4: v:gr1 lightning_v_front_4.pl4: v:gr1 lightning_v_front_.pl4: v:gr1 Fig. 13 Induced voltage at top of tower 1 with various front time of lightning current 3.0 *10 6 3.0 3.5 [us] 4.0 Lightning_V_Tail_20.pl4: m:u lightning_v_tail_30.pl4: m:u lightning_v_tail_40.pl4: m:u Fig. 17Backflash over clearance at insulator of phase A with various front time of lightning current E. Parameters of the Ground System Vertical and horizontal electrodes which are used at each leg of the transmission line tower as footing ground system during lightning transient, have many parameters such as: 3.0 3.5 [us] 4.0 lightning_v_front_.pl4: m:u lightning_v_front_4.pl4: m:u lightning_v_front_6.pl4: m:u Fig. 14 Backflash over clearance at insulator of phase A with various front time of lightning current 40 [ka] 35 30 25 20 15 resistivity of the earth in ohm. meter, ; permittivity of the soil in farad per meter, ; permeability of the soil in henries per meter, ; electrode length in meter, ; electrode radius in meter, ; depth of burial of horizontal electrode in meter,. Among these parameters, the length of the electrode has the major effect. Figures 18 and 19 show the induced voltage wave forms on the top of tower 1 with a various lengths of vertical and horizontal electrodes respectively. It is noticed that the magnitude of the induced voltage increases with increasing the length of vertical or horizontal electrode. 10 5 0 Lightning_V_Tail_20.pl4: c:xx0227-gr1 lightning_v_tail_30.pl4: c:xx0227-gr1 lightning_v_tail_40.pl4: c:xx0227-gr1 Fig. 15 Lightning source wave shape with various front time 48

1.6 - - lightning_v_l_30.pl4: v:gr1 lightning_v_l_5.pl4: v:gr1 lightning_v_l_3.pl4: v:gr1 lightning_v_l_1.pl4: v:gr1 Fig.18 Induced voltage at top of tower 1 with various lengths vertical electrode 1.6 [3] Leonid Grcev, Modeling of Grounding Electrodes under Lightning Currents IEEE Transaction on Electromagnetic Compatibility, Vol. 51, No. 3, Aug. 2009, pp. 559-571. [4] R. Rudenberg, Electrical Shock Waves in Power System. Cambridge, MA: Harvard Univ. Press, 1968. [5] H. B. Dwight, "Calculation of the resistances to ground", Electr. Eng., vol. 55, pp. 1319-1328, Dec. 1936. [6] E. D. Sunde, Earth Conduction Effects in Transmission Systems, 2 nd ed. New York: Dover, 1968. [7] Ametani, A.; Kawamura, T., A Method of a Lightning Surge Analysis Recommended in Japan Using EMTP, IEEE Trans. on Power Delivery, Vol. 20, No. 2, pp. 867-875, April 2005. [8] P. Yadee and S. Premrudeepreechacharn, Analysis of Tower Footing Resistance Effected Back Flashover Across Insulator in a Transmission System the International Conference on Power Systems Transients (IPST 07) in Lyon, France on June 4-7, 2007. - - lightning_h_l_30.pl4: v:gr1 lightning_h_l_5.pl4: v:gr1 lightning_h_l_3.pl4: v:gr1 lightning_h_l_1.pl4: v:gr1 Fig.19 Induced voltage at top of tower 1 with various lengths horizontal electrode IV. CONCLUSION This paper has described an analysis of parameters effected the backflash voltage across insulator in a transmission system. Parameters of this study include the modeling of transmission line tower, the modeling of tower footing ground system, magnitude of lightning stroke, front and tail times of lightning stroke impulse and striking distance. All components of the system, under study, are simulated by using ATP program. As seen from simulation results, the larger striking distance will decrease the induced voltage magnitude and will increase the time delay seen in the induced voltage waveforms. Also, it is noticed that, all of the increase in the peak, the shorter front time and the longer tail time of lightning current will increase the induced voltage magnitude and in turn will reduce the clearance time of beckfash over. Finally, among the parameters of the tower footing ground system, the length of the electrode has the major effect. Where the longer vertical or horizontal electrode will increase the induced voltage magnitude REFERENCES [1] P. Chowdhuri, Parameters of lightning strokes and their effects on power systems, IEEE Transmission and Distribution Conference and Exposition, Nov. 2001, pp. 1047-1051. [2] J. A. Gutierrez R., P. Moreno, L. Guardado, L Naredo, Comparison of Transmission line models for Evaluating Lightning Performance IEEE Bologna Power Tech. Conference, June 23-26, Bologna, Italy 2003. 49