Capacitor protection relay

Similar documents
Single Phase Rectifier Bridge, 1.2 A

Single Phase Bridge Rectifier, 2 A

Single Phase Rectifier Bridge, 1.9 A

Surface Mount Ceramic Chip Antennas for 2.4 GHz

Thin Film Bar MOS Capacitors

Single Phase Rectifier Bridge, 2 A

Single Phase Rectifier Bridge, 3 A, 6 A

Power Resistors Cooled by Auxiliary Heatsink (Not Supplied) Thick Film Technology

Lower Voltage Ceramic Singlelayer DC Disc Capacitors 1 kv DC to 3 kv DC Low Dissipation Factor

Versatile Planar Transformer

Ceramic Disc Capacitors Class 2, 500 V DC, 1 kv DC, General Purpose

Aluminum Electrolytic Capacitors Power Ultra High Ripple Current Snap-In for Solar

Single Phase Rectifier Bridge, 1.2 A

Single Turn Servo Mount Hall Effect Sensor in Size 05 (12.7 mm)

AC Line Rated Ceramic Disc Capacitors Class X1, 400 V AC / Class Y2, 300 V AC / 250 V AC

Standard Recovery Diodes, 400 A

Rotational Position Sensor, Kit Type, Hall Effect Technology

Single phase bridge. (Power Modules), 25 A / 35 A

Single Phase Rectifier Bridge, 1.9 A

Single Phase Rectifier Bridge, 2 A

Throttle Position Sensor in Hall Effect Technology Hollow and D-Shaft Versions

Single phase bridge. (Power Modules), 25 A/35 A

Single-Line ESD Protection in SOT-23

Power Rectifier Diodes (T-Modules), 2200 V, 20 A

Aluminum Electrolytic Capacitors Power Ultra Miniature Snap-In

Dual Common Cathode Ultrafast Rectifier

INT-A-PAK Half Bridge IGBT (Standard Speed IGBT), 200 A

Surface Mount Multilayer Ceramic Chip Capacitors for High Frequency Applications

Aluminum Electrolytic Capacitors Radial, High Temperature, Low Impedance, High Vibration Capability

FEATURES. Package. PARAMETER SYMBOL PB3506 PB3508 PB3510 UNIT Maximum repetitive peak reverse voltage V RRM V 35 T A = 25 C (2) 4.

VS-1N1183, VS-1N3765, VS-1N1183A, VS-1N2128A Series Power Silicon Rectifier Diodes, (Stud Version), 35 A, 40 A, 60 A

Insulated Ultrafast Rectifier Module, 230 A

Enhanced isocink+ Bridge Rectifiers

Small Signal Switching Diode, Dual

Thick Film Resistor Networks, Dual-In-Line, Molded DIP

Molding Type Module IGBT, 2 in 1 Package, 1200 V, 100 A

HEXFRED Ultrafast Diodes, 300 A (INT-A-PAK Power Modules)

Thick Film Resistor Networks, Military, MIL-PRF Qualified, Type RZ010 and RZ020 Dual-In-Line, Molded DIP

Silicon PIN Photodiode

Single phase bridge. (Power Modules), 25 A, 35 A

Small Signal Switching Diode

Bicolor Symbol LED in 2.5 mm x 5 mm Untinted Top-Diffused Package

AC Line Rated Disc Capacitors Class X1, 400 V AC /Class Y2, 300 V AC

FEATURES ± [0.64 ± 0.05] dia. (no. 22 AWG) tinned nickel leads solderable and weldable

Low Current LED in Ø 5 mm Tinted Diffused Package

Aluminum Electrolytic Capacitors Power Miniaturized General Purpose - Snap-In

Half Bridge IGBT Power Module, 600 V, 100 A

Three Phase Bridge, 160 A (Power Modules)

Standard Recovery Diodes (Stud Version), 12 A

3-Channel EMI-Filter with ESD-Protection

Bidirectional Symmetrical (BiSy) Low Capacitance, Dual-Line ESD-Protection Diode in SOT-323

Power Resistor, for Mounting onto a Heatsink Thick Film Technology

Analog Rectilinear Displacement Sensor

High Intensity Red Low Current 7-Segment Display

Dual INT-A-PAK Low Profile Half Bridge (Standard Speed IGBT), 300 A

Fully Sealed Container 12 mm Square or Round Single-Turn Cermet Trimmer

Knob Potentiometer FEATURES. P16NP P16NM Panel Cutout. Thickness nut 2 mm washer 1.5 mm. Panel sealing ring 12 wrench Thread M10 x

Automotive Dual P-Channel 30 V (D-S) 175 C MOSFET

Insulated Single Phase Hyperfast Bridge (Power Modules), 60 A

Molding Type Module IGBT, 1-in-1 Package, 1200 V and 300 A

Molding Type Module IGBT, 2-in-1 Package, 1200 V and 300 A

Dual INT-A-PAK Low Profile Half Bridge (Standard Speed IGBT), 400 A

Insulated Ultrafast Rectifier Module, 280 A

Standard Recovery Diodes, (Hockey PUK Version), 800 A

Three Phase Bridge, 300 A (Power Modules)

FRED Pt Gen 4 Single Ultrafast Diode, 500 A (INT-A-PAK Power Modules)

Universal LED in Ø 5 mm Tinted Diffused Package

Wirewound Resistors, Military, MIL-PRF Qualified, Type RE, Aluminum Housed, Chassis Mount

HEXFRED Ultrafast Soft Recovery Diode, 220 A

Dual Common Cathode Ultrafast Plastic Rectifier

Schottky Rectifier Surface-Mount

Small Signal Fast Switching Diode

VS-1N1183, VS-1N3765, VS-1N1183A, VS-1N2128A Series Power Silicon Rectifier Diodes, (Stud Version), 35 A, 40 A, 60 A

P-Channel 30-V (D-S), MOSFET

Knob Potentiometer with Switch

Standard Diodes (Super MAGN-A-PAK Power Modules), 600 A

Bidirectional Symmetrical (BiSy) Low Capacitance, Dual-Line ESD Protection Diode in SOT-23

HEXFRED Ultrafast Diodes, 100 A (INT-A-PAK Power Modules)

High Intensity LED in Ø 3 mm Tinted Diffused Package

FEATURES. Package. PARAMETER SYMBOL PB4006 PB4008 PB4010 UNIT Maximum repetitive peak reverse voltage V RRM V

Standard Recovery Diodes, (Hockey PUK Version), 2100 A

Silicon PIN Photodiode

Single Phase Bridge Rectifier, 2 A

Standard Recovery Diodes Generation 2 DO-5 (DO-203AB) (Stud Version), 95 A

Insulated Ultrafast Rectifier Module, 280 A

N-Channel 60-V (D-S) MOSFET

Fully Sealed Container Cermet Potentiometer Professional Grade

High Voltage, Input Rectifier Diode, 20 A

Phase Control Thyristor RMS SCRs, 25 A, 35 A

Aluminum Electrolytic Capacitors Axial High Temperature, High Ripple Current

1 Form A Solid-State Relay

Standard Recovery Diodes, (Stud Version), 400 A

HEXFRED Ultrafast Soft Recovery Diode, 140 A

N-Channel 2.5-V (G-S) Battery Switch, ESD Protection

Low Capacitance ESD Protection Diodes for High-Speed Data Interfaces FEATURES

Insulated Ultrafast Rectifier Module, 210 A

Surface Mount Multilayer Ceramic Chip Capacitors DSCC Qualified Type 03028

6-Channel EMI-Filter with ESD-Protection FEATURES VEMI65AC-HCI VEMI65AC-HCI-GS MOLDING COMPOUND FLAMMABILITY RATING

High Efficiency Blue LED in Ø 3 mm Tinted Diffused Package

P-Channel 1.8 V (G-S) MOSFET

Transcription:

Capacitor Protection Relay FEATURES Capacitor unbalance protection Line current unbalance protection Overvoltage protection Overheating protection Ground fault protection Overcurrent protection Undercurrent protection Capacitor bank discharge timer APPLICATIONS Protection of capacitor bank in double star or bridge connection. QUICK REFERENCE DATA Type Description Rated data Current data Protecting level Capacitor protection relay Capacitor bank protection relay: unbalance, line current unbalance, overvoltage, overcurrent, undercurrent, overheating, ground fault, discharge timer Supply voltages: 100 V AC to 240 V AC, 50 Hz to 60 Hz / 100 V DC to 375 V DC / 18 V DC to 75 V DC 4 current inputs: 1 A or 5 A IP54 TECHNICAL DATA Thermal current withstand 15 A continuous / 100 A, 1 s Power consumption 1 VA per measuring circuit Measurement accuracy Class 1 Rated frequency 50 Hz / 60 Hz Galvanic separation Via current voltage transformer, dielectric strength of 2 kv Signal outputs Interfaces Note Complete mounting instructions / manual available at www.vishay.com/doc?13173 Potential-free change-over switch contacts for alarm and switch-off Position of relay can be selected, picked up, or released Contact rating 8 A / 265 V AC or 0.3 A / 300 V DC or 8 A / 30 V DC Front: RS232 (9600 Bd) Rear: RS485 and RS232 Temperature Operation: -10 C to +60 C Storage: -20 C to +70 C Dimensions 135 mm x 135 mm x 121 mm Standards EN 50178 class 2, EN 61010-1, EN 50081-1, EN 50082-2 Revision: 28-Mar-17 1 Document Number: 13177

APPLICATION The double star circuit generates a sum current the size and phase of which result from the three unbalance currents. Using the reference current, the can analyze the sum current into the three unbalanced currents. Each change of the sum current can take place only in the same phase of the capacitor current. Thus the can reveal the partial path in which the defective capacitor unit is located. This means that only 1/6 of the capacitors need to be checked. L1 L2 L3 Within the bridge circuit, the phase position of the unbalance current L1, L2, and L3 in relation to the reference current is 0, +120, or +240 degrees. The can reveal the fault phase and the bridge circuit branch in which the faulty capacitor unit is located. It is possible to configure the four current inputs of the for different applications. For a YY- or bridge connection, inputs 1-3 will be the three line currents, and the fourth input would be the unbalance current. It is also possible to use the first input to measure the line current and inputs 2-4 can be used for the unbalance measurements. Thus it is possible to control three individual YY or bridge connections with different unbalance settings for each bank. CHARACTERISTICS The microprocessor-based capacitor protection relay uses a versatile integrated current measuring multifunction relay design to enable the protection of medium and high voltage capacitor banks. Using FFT techniques, the calculates the fundamental and harmonic currents from measured line and unbalance currents, and uses these values to implement individual protection functions. The capacitor protection relay is particularly appropriate for capacitor banks connected in double star and bridge circuit configurations. The following protective functions are provided by the : Capacitor unbalance protection Line current unbalance protection Overvoltage protection Overheating protection Ground fault protection Overcurrent protection Undercurrent protection Capacitor bank discharge timer CAPACITOR UNBALANCE PROTECTION The relay measures the circuit s natural unbalance at its fundamental frequency and compensates for both amplitude and phase to zero shifts, to enable detection of further changes in both amplitude and phase angle. The phase current input I L1 is used as the synchronizing input for the compensation. The phase angle indicates the leg in which the change in capacitance has occurred. The protection has two stages, warning and tripping, both with an adjustable definite timer. A trip signal is initiated if the associated threshold is exceeded for the definite time setting. The trip values obtained mathematically relate to the nominal voltage of the capacitor equipment. Therefore, accurate protection is not maintained in case of voltage fluctuation - especially with decreased voltage. Revision: 28-Mar-17 2 Document Number: 13177

LINE CURRENT UNBALANCE PROTECTION The relay calculates the fundamental frequency line current unbalance due to faults or failures within the capacitor bank. The line current unbalance is calculated from three-phase line currents. The protection includes two stages, warning and tripping, both with an adjustable definite timer. A trip signal is initiated if the value of the line unbalance current exceeds the selected setpoint value for the definite time. OVERVOLTAGE PROTECTION The purpose of the overvoltage protection is to protect the capacitor bank against overload due to fundamental and harmonics currents, which may lead to dielectric breakdown, i.e. short-circuit in a capacitor element. The capacitor bank voltage is calculated from the three-phase line fundamental frequency component current and from the harmonic currents. The overvoltage factor is calculated and continuously compared with a variable threshold. The user may select between a definite time characteristic and an inverse time characteristic according to the ANSI curve. A trip signal is output if the setpoint value is exceeded for the definite time. OVERHEATING PROTECTION The overheating protection function is intended to be used for the protection of series reactance coils used within capacitor banks. This protection works by measuring the RMS three-phase line currents and comparing them with an adjustable threshold. The protection feature has two stage options, warning and tripping, both with adjustable definite-time delay, or the user can select the tripping time depending on the ratio of the actual current to the nominal current. The warning time is half of the tripping time. If the current exceeds the relevant setpoint value for the definite-time delay, a tripping or warning signal is initiated. GROUND FAULT PROTECTION The protection calculates the fundamental frequency ground fault current, as the value of the vector sum of the three-phase line currents. The protection has two stages, warning and tripping, both with adjustable definite time. A trip signal is initiated if the amplitude of the ground fault current exceeds the selected setpoint value for the definite time. OVERCURRENT PROTECTION The protection stage measures the fundamental frequency of three-phase currents and compares them with an adjustable threshold. This function may be used for short-circuit protection. A trip signal is initiated if the value of the line current exceeds the selected setpoint value for the definite time. UNDERCURRENT PROTECTION The undercurrent protection function is intended for the detection of capacitor bank disconnection. In case of voltage loss in the feeding bus, the capacitor bank has to be disconnected from the system to prevent reapplication of the voltage on the capacitors before they are fully discharged. The stage starts if all the three-phase currents fall below the set level. If the undercurrent condition persists for an interval longer than the set operating time, the trip signal is initiated. CAPACITOR BANK DISCHARGE TIMER The relay includes an adjustable timer, started by the circuit breaker auxiliary contacts, which stops the breaker from reclosing until the capacitor bank is discharged to an acceptable voltage level for switching in. Revision: 28-Mar-17 3 Document Number: 13177

PC SOFTWARE The PC software provided with allows all settings to be made easily. All setting data is stored in a setup file. DATA STORAGE The stores all data, including date and time information, in a report file. The included PC software provides you with convenient access to this data. FFT ANALYSIS AND REALTIME MEASURING The PC software allows users to see the actual current values of the four measuring inputs up to the thirteenth harmonic. Revision: 28-Mar-17 4 Document Number: 13177

Legal Disclaimer Notice Vishay Disclaimer ALL PRODUCT, PRODUCT SPECIFICATIONS AND DATA ARE SUBJECT TO CHANGE WITHOUT NOTICE TO IMPROVE RELIABILITY, FUNCTION OR DESIGN OR OTHERWISE. Vishay Intertechnology, Inc., its affiliates, agents, and employees, and all persons acting on its or their behalf (collectively, Vishay ), disclaim any and all liability for any errors, inaccuracies or incompleteness contained in any datasheet or in any other disclosure relating to any product. Vishay makes no warranty, representation or guarantee regarding the suitability of the products for any particular purpose or the continuing production of any product. To the maximum extent permitted by applicable law, Vishay disclaims (i) any and all liability arising out of the application or use of any product, (ii) any and all liability, including without limitation special, consequential or incidental damages, and (iii) any and all implied warranties, including warranties of fitness for particular purpose, non-infringement and merchantability. Statements regarding the suitability of products for certain types of applications are based on Vishay s knowledge of typical requirements that are often placed on Vishay products in generic applications. Such statements are not binding statements about the suitability of products for a particular application. It is the customer s responsibility to validate that a particular product with the properties described in the product specification is suitable for use in a particular application. Parameters provided in datasheets and / or specifications may vary in different applications and performance may vary over time. All operating parameters, including typical parameters, must be validated for each customer application by the customer s technical experts. Product specifications do not expand or otherwise modify Vishay s terms and conditions of purchase, including but not limited to the warranty expressed therein. Except as expressly indicated in writing, Vishay products are not designed for use in medical, life-saving, or life-sustaining applications or for any other application in which the failure of the Vishay product could result in personal injury or death. Customers using or selling Vishay products not expressly indicated for use in such applications do so at their own risk. Please contact authorized Vishay personnel to obtain written terms and conditions regarding products designed for such applications. No license, express or implied, by estoppel or otherwise, to any intellectual property rights is granted by this document or by any conduct of Vishay. Product names and markings noted herein may be trademarks of their respective owners. 2017 VISHAY INTERTECHNOLOGY, INC. ALL RIGHTS RESERVED Revision: 08-Feb-17 1 Document Number: 91000