Modeling Ferroresonance Phenomena on Voltage Transformer (VT)

Similar documents
Ferroresonance Experience in UK: Simulations and Measurements

TECHNICAL BULLETIN 004a Ferroresonance

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

Parameter Study of Ferro-Resonance with Harmonic Balance Method

FERRORESONANCE SIMULATION STUDIES USING EMTP

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Sensitivity studies on power transformer ferroresonance of a 400 kv double circuit

Simulation and Analysis of Ferroresonance in Power System

2 Grounding of power supply system neutral

Research Article Resistive Ferroresonance Limiter for Potential Transformers

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

A Study on Ferroresonance Mitigation Techniques for Power Transformer

Electrical Power and Energy Systems

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

FERRORESONANCE - its Occurrence and Control in Electricity Distribution Networks

Primary Metering. What is Primary Metering?

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

STUDY ON THE NON LINEAR CHARACTERISTIC OF POWER TRANSFORMER AND THEIR EFFECT FERRORESONANCE SALIZAWATI BT HJ. SHAMSUDDIN

The study of ferroresonance effects in electric power equipment

Effect of Circuit Breaker Shunt Resistance on Chaotic Ferroresonance in Voltage Transformer

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

DEVELOPMENT OF NUMERICAL ALGORITHMS FOR FERRORESONANCE MONITORING

GIS Disconnector Switching Operation VFTO Study

Modeling Ferroresonance Phenomena in an Underground Distribution System

ABSTRACT 1 INTRODUCTION

(2) New Standard IEEE P (3) Core : (4) Windings :

Switching Induced Transients:

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

ELECTRICAL POWER ENGINEERING

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Protection of Electrical Networks. Christophe Prévé

Spectral analysis of voltages and currents during different modes of ferroresonance in switchgear

Tab 2 Voltage Stresses Switching Transients

Solving Customer Power Quality Problems Due to Voltage Magnification

Effect of Metal Oxide Surge Arrester on Ferroresonance in Voltage Transformer Including Nonlinear Core Losses

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Electromagnetic Interference in the Substation Jose up 400/115 kv

UNDERSTANDING SUB-HARMONICS

Three-Phase/Six-Phase Conversion Autotransformers

Ferroresonances during Black Starts - Criterion for Feasibility of Scenarios

Power Quality and Reliablity Centre

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

Comprehensive Study on Magnetization Current Harmonics of Power Transformers due to GICs

Experimental Investigations and Calculations in 6-35 kv Networks with Various Neutral Conditions

Modeling insulation in high-voltage substations

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

INFLUENCE OF INSTRUMENT TRANSFORMERS ON POWER SYSTEM PROTECTION. A Thesis BOGDAN NAODOVIC

Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid

Keywords: Transformer modeling, saturation, hysteresis, MATLAB. Introduction

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

AC INTERFERENCE OF TRANSMISSION LINES ON RAILWAYS: INFLUENCE OF TRACK-CONNECTED EQUIPMENT I. ABSTRACT

Simulation of Ferroresonance Phenomena in Power Systems

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Innovative Science and Technology Publications

Long lasting transients in power filter circuits

Ferroresonance Elimination in 275kV Substation

of the improved scheme is presented. Index Terms Inrush current, power quality, transformer.

Laboratory ferroresonance measurements in power transformers

Ferroresonance on Transformer 13-kV Ungrounded Tertiary at Arab

Energization of a no-load transformer for power restoration purposes: Impact of the sensitivity to parameters.

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

FERRORESONANCE SIMULATION STUDIES OF TRANSMISSION SYSTEMS

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Grounding System Theory and Practice

DEPARTMENT OF EEE QUESTION BANK

Power Factor Insulation Diagnosis: Demystifying Standard Practices

DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

Demagnetization of Power Transformers Following a DC Resistance Testing

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

QUESTION BANK PART - A

Busbars and lines are important elements

Power System Stability. Course Notes PART-1

p. 1 p. 6 p. 22 p. 46 p. 58

ESTIMATION OF RESIDUAL FLUX FOR THE CONTROLLED SWITCHING OF TRANSFORMER

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

2. Current interruption transients

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

Power Quality Basics. Presented by. Scott Peele PE

Ironing out resonance

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System

ELECTRICAL POWER TRANSMISSION TRAINER

SERIES ACTIVE power filters have proved to be an interesting

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

Upgrading Your Electrical Distribution System To Resistance Grounding

SWITCHING OVERVOLTAGES IN A 400-KV CABLE SYSTEM

Tab 8 Surge Arresters

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

Impact of the system parameters on the ferroresonant modes

Sizing Generators for Leading Power Factor

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Performance Assessment of Advanced Digital Measurement and Protection Systems

Transcription:

Modeling Ferroresonance Phenomena on Voltage Transformer (VT) Mohammad Tolou Askari Department of Electrical Faculty of Engineering Universiti Putra Malaysia 43400 UPM Serdang, Selangor, Malaysia Abstract Ferroresonance in electromagnetic voltage transformers, fed through circuit breaker grading capacitance, is studied using nonlinear dynamics methods. The magnetising charact'eristic of a typical l00va voltage transformer is represented by a single-valued two-term polynomial of the order seven.the system exhibits three types of ferroresonance: fundamental frequency ferroresonance, subharmonic ferroresonance and chaotic fcrroresonance, similar to high capacity power transformers fed through capacitive coupling from neighbouring lines or phases. Results also show that while fundamental frequency and subharmonic ferroresonancc can occur under commonplace operating conditions, chaotic states are unlikely in practice. Keywords: Ferroresonance, Voltage Transformer, ATP, Overvoltage,Transient Analysis I. INTRODUCTION Ferroresonance is a non- linear phenomenon that can affect power network,the main feature of this phenomenon is that one stable steady state response is possible for the network parameters that are highly depond on initial conditions and circuit parameter. Ferroresonance is an important issue in transmission and distribution systems. It may result in equipment failure and service interruption that could be very costly and reduce system reliability.by diagnose ferroresonance we can manage our costs use to repair or change our facilities. Ferroresonant overvoltages on distribution systems were observed early in the history of power systems (i.e., early 1900s). Many analytical and experimental work have been carried out to understand the phenomena. One of the first analytical work was presented in [1] and [2]. A more recent paper on modeling and analysis of ferroresonant phenomena was described in [4]. In this paper, the theory of ferroresonance is briefly presented (in Section II). More theoretical description can be found in many literature. Section III describes symptoms of ferroresonance and personal accounts of engineers who witnessed the phenomena. Sections IV and V present 1

ferroresonant modeling, and a case study of an actual ferroresonance problem with its corresponding solutions. II.Ferroresonance Ferroresonance is a mysterious phenomenon that seems to occur capriciously, causing much concern among utility operating personnel. It generally occurs during a system imbalance, usually during switching, that places capacitance in series with transformer magnetizing impedance. This can result in high overvoltages that can cause failures in transformers, cables, and arresters. Any system capacitance can be involved in ferroresonance, but the major concern is about underground cable capacitance. As utilities moved cable systems into a 25-kV or 35-kV class, they found ferroresonance to be much more common than at lower voltage levels. They found they had to be more careful about how they switched the cable and how they arranged switch points to minimize the amount of cable isolated with lightly loaded transformers during switching. Ferroresonance is a greater problem at the higher voltage levels because the relative ratios of losses, magnetizing impedance and cable capacitance fall into a range more likely to produce ferroresonance. Ungrounded transformer primary connections go into ferroresonance quite easily. Therefore, many utilities no longer employ these connections and have switched to grounded-wye/grounded-wye connections for their three-phase loads fed from underground cable systems. Grounded-wye transformers comprised of three separate units are virtually immune to the common varieties of ferroresonance. Grounded-wye/grounded-wye threephase pads with 4-or 5-leg cores are less susceptible to ferroresonance than delta or ungrounded-wye connections, but they are not immune. They simply require more cable length and some different transformer characteristics. The common core configuration for the three-phase padmounts provides the necessary coupling between phases to produce ferroresonance. There are several different modes of ferroresonance possible with groundedwye 5-leg core transformers with sustained overvoltages reaching 2,0 to 2,5 per unit for some modes. Of course, if allowed to persist, these overvoltages might cause transformer failure, cable failure, and customer appliance failure. Frequent symptoms often reported are failed arresters, customer complaints of fluctuating voltage, and bubbled or charred paint on the transformer tank when the flux gets into the tank. The evaluation of ferroresonance ties in closely with the decision of applying arresters on the cable system. If surge arresters are not installed on the cable system, it has no protection against overvoltages. This could contribute to premature cable failure or transformer failure if allowed to persist. On the other hand, if arresters are applied, arrester duty during phase-by-phase switching operations is a concern, and there is the possibility that arresters might fail violently. 2

The most dangerous time is when phaseby-phase cable switching occurs during construction of a subdivision or commercial area. The transformer involved might have no load and there will be more times that the transformer is exposed to the condition with one or two open phases. However, ferroresonance can also occur accidentally due to such things as a faulty connector or splice opening, or an overhead line feeding the cable opening due to such things as an automobile collision with a pole. The no-load condition also occurs when customers install automatic relaying to disconnect from the utility at the first sign of trouble. III.FERRORESONANCE SYMPTOMS Disturbance due to ferroresonance is a common phenomenon in electric power distribution system operation. Depending on circuit conditions, its effect may be a random overvoltage that could be either a short transient for few cycle, a continuous overvoltage or even a jump resonance demonstrated by a sudden jump of voltage or current from one stable operating state to another one i.e., it is characterized by the possible existence of several stable states, besides the normal steady state, that induce dangerous over-currents and overvoltages. It causes both phase-tophase and phase-to-ground high sustained oscillating overvoltages and overcurrents with sustained levels of distortion to the current and voltage waveforms, leading to transformer heating together with excessively loud noise due to magnetostriction, electrical equipment damage, thermal or insulation breakdown and misoperation of the protective devices. In this phenomenon voltage and current relationship is dependent on: system voltage magnitude & frequency, initial magnetic flux condition of the transformer iron core i.e. extent of loading, capacitance of the circuit, feeding the transformer primary, point on wave of initial switching, the total losses in the ferroresonant circuit. IV. SYSTEM DESCRIPTION AND ATP MODELLING Current studies related to ferroresonance in electromagnetic wound voltage transformers (VT) and single-phase traction supply transformers. A Voltage Transformer Ferroresonance[5,6] During voltage transformer ferroresonance an oscillation occurs between the nonlinear inductance of the VT and the capacitance of any network remaining\ connected to the VT. In this case, energy is coupled to the nonlinear core of the voltage transformer via the open circuit breaker grading capacitance to sustain the resonance. The VT can be driven into saturation resulting in high currents at sub-harmonic or fundamental frequency. For the latter, very high voltage of up to 4 pu can theoretically arise in worst case conditions. Electromagnetic voltage transformers have a relatively low thermal capacity and overheating can result in insulation failure very quickly. Fig.1 shows the single line diagram of the most commonly encountered system arrangement that can give rise to VT 3

ferroresonance. Ferroresonance can occur upon opening of disconnector 3 with circuit breaker open and either disconnector 1 or 2 closed. Alternatively it can also occur upon closure of either disconnector 1 or 2 with circuit breaker and disconnector 3 open. The circuit of Fig.2 is modelled in ATP [7]. Transformer magnetisation characteristic supplied by the manufacturer was used in a type-93 true nonlinear inductor to simulate the magnetic core of the VT. The VT itself is a low thermal capacity, 400kV/110V, 100VA wound voltage transformer. Cseries and Cshunt were represented as lumped parameters. The resistance R was represented dynamically based on Fig. 1 System arrangement resulting to VT ferroresonance The system arrangement shown in Fig. 1 can effectively be reduced to an equivalent circuit as shown in Fig2. Fig. 2 Reduced equivalent ferroresonant circuit In Fig. 2, E is the rms supply phase voltage, Cseries is the circuit breaker grading capacitance and Cshunt is the total phase-to-earth capacitance of the arrangement. The resistor R represents voltage transformer core losses that has been found to be an important factor in the initiation of ferroresonance [4,8,9]. In (1) ROS=60W, RMS=20W, BS =1.7T and a=9.5. At every integration time-step of ATP then the value of R is recalculated depending on the value of B. B Traction Supply Transformer Ferroresonance Fig. 3 shows the single line diagram of a traction supply transformer arrangement. The single phase transformer is fed from two phases of the three-phase system. Ferroresonance occurs upon opening of circuit breakers 1 and 2 to de-energise the line and the transformer. Energy is coupled to the de-energised network from the adjacent live parallel circuit via the inter-circuit coupling capacitance, i.e. Cseries in the equivalent ferroresonant circuit. The equivalent Cshunt in the ferroresonant circuit is the phase-to-earth capacitance of the line and the transformer winding and bushing capacitance. 4

Simulation of traction supply transformer can be carried out on a complex 3-phase network. Both the measurements and simulation results are given in figure 9. Nevertheless digital computer modelling of the traction supply transformer configuration can be simplified using the single-phase ferroresonant equivalent circuit given in Fig. 2. Fig. 3 Traction supply transformer ferroresonance arrangement V. FIELD MEASUREMENTS SIMULATION RESULTS A Voltage Transformer Ferroresonance Fig. 4 (a) and (b) show the measured and simulated VT secondary voltages respectively. The measured test waveform of Fig. 4 (a) was obtained after opening disconnector 3 in Fig. 1. As it can be seen from the graphs the VT did not go into ferroresonance. Although the simulated waveform does not match the measured test waveform exactly, its general appearance is a very close fit. It can be said that the ATP model employed in this study is capable of predicting possible ferroresonance modes as long as the parameters of the system are known or can be estimated. In the study Cseries was set to 514pF and Cshunt to 1137pF to give the waveform of Fig. 4 (b). Primary current waveforms for the field measurement and the simulation study are given in Fig. 5 (a) and (b), respectively. When the same system is tested for a second time the response is totally different to the above in that it is driven into sub-harmonic ferroresonance. Prediction of this response with digital simulation proved to be hard as the system is very sensitive to parameter changes. The measured and simulated VT secondary voltage waveforms are shown in Fig. 6 (a) and (b) and the corresponding primary current waveforms are given in Fig. 7 (a) and (b), respectively. The shape of measured and simulated waveforms in Figs. 6 & 7 (a) and (b) are of a good match. The minute difference is believed was due to the numerical and actual saturation around the knee point of the magnetisation curve. The bifurcation diagram of Fig. 10 shows the sensitivity of the model to applied voltage E. Bifurcation diagrams provide information about the dynamics of the system for range of parameter values. In the diagram of Fig. 10 all system parameters except E were constant. Values of E from 0.8pu to 1.15pu result to a normal response while at 1.15pu and onwards a fundamental ferroresonant response is present. B Traction Supply Transformer Ferroresonance Figs. 8 and 9 show the results of a full scale measurement and simulation of a traction supply transformer which ferroresonated at 50Hz, the fundamental system frequency. The phase voltages and current on the de-energised transformer are presented. Clearly, the two phases feeding the transformer are in sustained fundamental frequency mode ferroresonance. 5

6

7

Fig. 10 Bifurcation diagram showing sensitivity of model to E (all other parameters kept constant) VI. CONCLUSIONS A reliable prediction of the ferroresonant voltage and current in advance can provide valuable information to planners to design the system, engineers to specify the equipment and operators to run the transmission plant within all the design and tested criteria and capabilities. This comprehensive understanding can be achieved if all the parameters of the system and plant in question are available or can be estimated with reasonable accuracy. Although the model used in this study providedcomparable result with those of field measurements, many more questions, such as the effect of magnetization hysteresis and remnance and the Point-on-Cycle switching etc are still to be examined. Boundary approach can be adopted to establish theinteraction between the system and the plant, and subsequently bringing forward an operating window with the lowest ferroresonance risk. VII. REFERENCES [1] P.H. Odessey and E. Weber, Critical conditions in ferroresonance, AIEE Trans. Vol. 57, 1938, pp. 444-452. [2] C. Kieny, Application of the bifurcation theory in studying the global behaviour of a ferroresonant electric power circuit, IEEE Trans. on Power Delivery, Vol. 6, No. 2, April 1991, pp. 866-872. [3] Z. Emin, B.A.T. Al Zahawi, D.W. Auckland and Y.K. Tong, Ferroresonance in Electromagnetic Voltage Transformers: A Study Based on Nonlinear Dynamics, IEE Proc. on Generation, Transmission, Distribution, Vol. 144, No. 4, July 1997, pp. 383-387. [4] Z. Emin, B.A.T. Al Zahawi and Y.K. Tong, Core Loss Effects on the Ferroresonant Behavior of Wound Voltage Transformers, 10th International Symposium on High Voltage Engineering, August 25-29, Montreal. [5] Tong Y K, NGC Experience on Ferroresonance in Power Transformers and Voltage Transformer on HV transmission Systems IEE Colloquium 1997. [6] NGC Technical Guidance Note TGN86, Control of Ferroresonance. [7] EMTP Rule Book and Theory Book. [8] B.A.T. Al Zahawi, Z. Emin and Y.K. Tong, Chaos in Ferroresonant Wound Voltage Transformers: Effect of Core Losses and Universal Circuit Behaviour, IEE Proc. on Science, Measurement, Technology, Vol. 145, No. 1, January 1998, pp. 39-43. [9] Z. Emin, B.A.T. Al Zahawi and Y.K. Tong, Voltage Transformer Ferroresonance in 275kV Substation, 11 th International Symposium on High Voltage Engineering, August 23-27, London 8